Electrical installations for lighting and beaconing of aerodromes - Constant current regulators

This International Standard specifies the requirements for a Constant Current Regulator (CCR) having a nominal output of 6,6 A for use in an aeronautical ground lighting constant current series circuit. However CCRs may be manufactured which have a different power rating (kVA) and current steps than those specified in this standard in order to be used on existing circuits. This standard shall be applied where appropriate for these CCRs.

General Information

Status
Published
Publication Date
20-Jun-2002
Current Stage
DELPUB - Deleted Publication
Completion Date
26-May-2009
Ref Project

Relations

Buy Standard

Standard
IEC 61822:2002 - Electrical installations for lighting and beaconing of aerodromes - Constant current regulators Released:6/21/2002 Isbn:2831864402
English language
22 pages
sale 15% off
Preview
sale 15% off
Preview

Standards Content (Sample)


INTERNATIONAL IEC
STANDARD
First edition
2002-06
Electrical installations for lighting
and beaconing of aerodromes –
Constant current regulators
Installations électriques pour l'éclairage
et le balisage des aérodromes –
Régulateurs du courant constant

Reference number
Publication numbering
As from 1 January 1997 all IEC publications are issued with a designation in the

60000 series. For example, IEC 34-1 is now referred to as IEC 60034-1.

Consolidated editions
The IEC is now publishing consolidated versions of its publications. For example,

edition numbers 1.0, 1.1 and 1.2 refer, respectively, to the base publication, the

base publication incorporating amendment 1 and the base publication incorporating

amendments 1 and 2.
Further information on IEC publications
The technical content of IEC publications is kept under constant review by the IEC,
thus ensuring that the content reflects current technology. Information relating to
this publication, including its validity, is available in the IEC Catalogue of
publications (see below) in addition to new editions, amendments and corrigenda.
Information on the subjects under consideration and work in progress undertaken
by the technical committee which has prepared this publication, as well as the list
of publications issued, is also available from the following:
• IEC Web Site (www.iec.ch)
• Catalogue of IEC publications
The on-line catalogue on the IEC web site (www.iec.ch/catlg-e.htm) enables
you to search by a variety of criteria including text searches, technical
committees and date of publication. On-line information is also available on
recently issued publications, withdrawn and replaced publications, as well as
corrigenda.
• IEC Just Published
This summary of recently issued publications (www.iec.ch/JP.htm) is also
available by email. Please contact the Customer Service Centre (see below) for
further information.
• Customer Service Centre
If you have any questions regarding this publication or need further assistance,
please contact the Customer Service Centre:
Email: custserv@iec.ch
Tel: +41 22 919 02 11
Fax: +41 22 919 03 00
INTERNATIONAL IEC
STANDARD
First edition
2002-06
Electrical installations for lighting
and beaconing of aerodromes –
Constant current regulators
Installations électriques pour l'éclairage
et le balisage des aérodromes –
Régulateurs de courant constant

 IEC 2002  Copyright - all rights reserved
No part of this publication may be reproduced or utilized in any form or by any means, electronic or
mechanical, including photocopying and microfilm, without permission in writing from the publisher.
International Electrotechnical Commission, 3, rue de Varembé, PO Box 131, CH-1211 Geneva 20, Switzerland
Telephone: +41 22 919 02 11 Telefax: +41 22 919 03 00 E-mail: inmail@iec.ch  Web: www.iec.ch
PRICE CODE
Commission Electrotechnique Internationale
S
International Electrotechnical Commission
Международная Электротехническая Комиссия
For price, see current catalogue

– 2 – 61822 © IEC:2002(E)
CONTENTS
FOREWORD.3

1 Scope.4

2 Normative references.4

3 Definitions .4

4 Classification .5

4.1 Output current .5

4.2 Current steps.5
4.3 Ratings.6
5 Requirements .6
5.1 General .6
5.2 Environmental requirements .6
5.3 Performance requirements.6
5.4 Electromagnetic compatibility (EMC) .10
5.5 Design requirements.10
5.6 Protection against electric shock.13
5.7 Optional accessories .13
6 Qualification and test requirements .15
6.1 Type tests .15
6.2 Routine tests .15
7 Tests description for type tests .16
7.1 Visual inspection .16
7.2 Protection against electric shock.16
7.3 Dielectric test .17
7.4 Enclosure temperature test .17
7.5 Leakage test.18
7.6 Test of protective devices .18
7.7 Operation test.18
7.8 Performance test .19
7.9 Environmental tests .21
7.10 Optional accessories .22

61822 © IEC:2002(E) – 3 –
INTERNATIONAL ELECTROTECHNICAL COMMISSION

____________
ELECTRICAL INSTALLATIONS FOR LIGHTING

AND BEACONING OF AERODROMES –
CONSTANT CURRENT REGULATORS
FOREWORD
1) The IEC (International Electrotechnical Commission) is a worldwide organization for standardization comprising
all national electrotechnical committees (IEC National Committees). The object of the IEC is to promote
international co-operation on all questions concerning standardization in the electrical and electronic fields. To
this end and in addition to other activities, the IEC publishes International Standards. Their preparation is
entrusted to technical committees; any IEC National Committee interested in the subject dealt with may
participate in this preparatory work. International, governmental and non-governmental organizations liasing with
the IEC also participate in this preparation. The IEC collaborates closely with the International Organization for
Standardization (ISO) in accordance with conditions determined by agreement between the two organizations.
2) The formal decisions or agreements of the IEC on technical matters express, as nearly as possible, an
international consensus of opinion on the relevant subjects since each technical committee has representation
from all interested National Committees.
3) The documents produced have the form of recommendations for international use and are published in the form
of standards, technical specifications, technical reports or guides and they are accepted by the National
Committees in that sense.
4) In order to promote international unification, IEC National Committees undertake to apply IEC International
Standards transparently to the maximum extent possible in their national and regional standards. Any
divergence between the IEC Standard and the corresponding national or regional standard shall be clearly
indicated in the latter.
5) The IEC provides no marking procedure to indicate its approval and cannot be rendered responsible for any
equipment declared to be in conformity with one of its standards.
6) Attention is drawn to the possibility that some of the elements of this International Standard may be the subject
of patent rights. The IEC shall not be held responsible for identifying any or all such patent rights.
International Standard IEC 61822 has been prepared by IEC Technical Committee 97:
Electrical installations for lighting and beaconing of aerodromes.
The text of this standard is based on the following documents:
FDIS Report on voting
97/86/FDIS 97/90/RVD
Full information on the voting for the approval of this standard can be found in the report on
voting indicated in the above table.

This publication has been drafted in accordance with the ISO/IEC Directives, Part 3.
The committee has decided that the contents of this publication will remain unchanged until
2006. At this date, the publication will be
• reconfirmed;
• withdrawn;
• replaced by a revised edition, or
• amended.
– 4 – 61822 © IEC:2002(E)
ELECTRICAL INSTALLATIONS FOR LIGHTING

AND BEACONING OF AERODROMES –
CONSTANT CURRENT REGULATORS
1 Scope
This International Standard specifies the requirements for a Constant Current Regulator (CCR)

having a nominal output of 6,6 A for use in an aeronautical ground lighting constant current
series circuit. However CCRs may be manufactured which have a different power rating (kVA)
and current steps than those specified in this standard in order to be used on existing circuits.
This standard shall be applied where appropriate for these CCRs.
2 Normative references
The following referenced documents are indispensable for the application of this document. For
dated references, only the edition cited applies. For undated references, the latest edition of
the referenced document (including any amendments) applies.
IEC 60038, IEC standard voltages
IEC 60439-1:1991, Low-voltage switchgear and controlgear assemblies – Part 1: Type-tested
and partially type-tested assemblies
IEC 60529, Degrees of protection provided by enclosures (IP Code)
IEC 61000-6-2, Electromagnetic compatibility (EMC) – Part 6-2: Generic standards – Immunity
for industrial environments
IEC 61000-6-4, Electromagnetic compatibility (EMC) – Part 6: Generic standards – Section 4:
Emission standard for industrial environments
IEC/TS 61000-6-5, Electromagnetic compatibility (EMC) – Part 6-5: Generic standards –
Immunity for power station and substation environments
IEC 61140, Protection against electric shock – Common aspects for installation of equipment
CISPR 11, Industrial, scientific and medical (ISM) radio-frequency equipment – Electromagnetic
disturbance characteristics – Limits and methods of measurement
CISPR 22, Information technology equipment – Radio disturbance characteristics – Limits and
methods of measurement
3 Terms and definitions
For the purposes of this International Standard, the following definitions developed to be
included in international standards relating to airport/aerodrome visual aids apply
3.1
aeronautical ground lighting (AGL) constant current series circuit
apparatus configured as an electrical circuit designed to produce and operate with a constant
current, independent of variations in the load, in order to provide a specified light for aero-
nautical purposes
61822 © IEC:2002(E) – 5 –
3.2
constant current regulator (CCR)

apparatus which produces a current output at a constant r.m.s. value independent of variations

in the constant current series circuit load, input voltage and service conditions as specified

3.3
contractor
organisation or person(s) given a written order to provide a service or undertake specified work

3.4
earthed
connected to the ground in such a manner as to ensure at all times an immediate discharge of
electrical energy to reduce the danger of equipment damage or personnel injury
3.5
electrical equipment
anything used, intended to be used or installed for use, to generate, provide, transmit,
transform, rectify, convert, conduct, distribute, control, store, measure or use electrical energy
3.6
injury
death or personnel injury from electric shock, electric burn, electrical explosion or arcing, or
from fire or explosion initiated by electrical energy, where any such death or injury is
associated with the generation, provision, transmission, transformation, rectification,
conversion, conduction, distribution, control, storage, measurement or use of electrical energy
3.7
isolate
to disconnect and separate electrical equipment from the normal source(s) of electrical energy
in such a way that the disconnection and separation is secure
3.8
live
electrically connected to a source of electricity or having acquired a charge by other means
3.9
work/working (on electrical equipment)
installing, dismantling, assembling, maintaining or repairing of electrical equipment
4 Classification
4.1 Output current
The CCR shall produce a maximum rated r.m.s. current output of 6,6 A and a minimum rated
r.m.s. current output of 1,8 A.
4.2 Current steps
CCRs shall be classified according to the number of output current steps available, as follows:
style 1 3 current steps;
style 2 5 current steps.
Each step shall have a single adjustment over the full range specified in 4.1.
NOTE An additional low current step(s) for non-illumination purposes may be offered as an option (see5.7.6).
Each style CCR can be configured to operate with a reduced number of current steps.

– 6 – 61822 © IEC:2002(E)
4.3 Ratings
CCRs shall be manufactured in the following output power ratings:

1; 2,5; 5; 7,5; 10; 15; 20; 25; and 30 kVA.