Instrument transformers - Part 2: Inductive voltage transformers

Applies to new inductive voltage transformers for use with electrical measuring instruments and electrical protective devices at frequencies from 15 to 100 Hz. This standard relates basically to transformers with separate windings, but also to autotransformers. It replaces IEC 60186 (1987) plus Amendments 1 and 2 only for inductive voltage transformers. IEC 60186 remains in force for capacitive voltage transformers.

Transformateurs de mesure - Partie 2: Transformateurs inductifs de tension

S'applique aux transformateurs inductifs neufs destinées à être utilisés avec des appareils de mesure électriques et des dispositifs électriques de protection, de fréquence comprise entre 15 Hz et 100 Hz. La norme s'applique principalement aux transformateurs à enroulements séparés, mais aussi aux autotransformateurs. Elle annule et remplace la deuxième édition de la CEI 60186 (1987) et les amendements 1 et 2, pour les transformateurs inductifs de tension. La CEI 60186 reste encore en viguer pour les transformateurs condensateurs de tension.

General Information

Status
Replaced
Publication Date
31-Jan-1997
Current Stage
DELPUB - Deleted Publication
Start Date
13-Jul-2011
Completion Date
13-Feb-2026

Relations

Effective Date
05-Sep-2023
Effective Date
05-Sep-2023
Effective Date
05-Sep-2023
Standard

IEC 60044-2:1997 - Instrument transformers - Part 2: Inductive voltage transformers Released:2/14/1997 Isbn:283183712X

English and French language
75 pages
sale 15% off
Preview
sale 15% off
Preview
Standard

IEC 60044-2:1997+AMD1:2000+AMD2:2002 CSV - Instrument transformers - Part 2 : Inductive voltage transformers Released:2/13/2003 Isbn:2831868378

English and French language
97 pages
sale 15% off
Preview
sale 15% off
Preview
Standard

IEC 60044-2:1997+AMD1:2000 CSV - Instrument transformers - Part 2 : Inductive voltage transformers Released:11/15/2000 Isbn:2831855063

English and French language
89 pages
sale 15% off
Preview
sale 15% off
Preview

Get Certified

Connect with accredited certification bodies for this standard

BSMI (Bureau of Standards, Metrology and Inspection)

Taiwan's standards and inspection authority.

TAF Taiwan Verified

Sponsored listings

Frequently Asked Questions

IEC 60044-2:1997 is a standard published by the International Electrotechnical Commission (IEC). Its full title is "Instrument transformers - Part 2: Inductive voltage transformers". This standard covers: Applies to new inductive voltage transformers for use with electrical measuring instruments and electrical protective devices at frequencies from 15 to 100 Hz. This standard relates basically to transformers with separate windings, but also to autotransformers. It replaces IEC 60186 (1987) plus Amendments 1 and 2 only for inductive voltage transformers. IEC 60186 remains in force for capacitive voltage transformers.

Applies to new inductive voltage transformers for use with electrical measuring instruments and electrical protective devices at frequencies from 15 to 100 Hz. This standard relates basically to transformers with separate windings, but also to autotransformers. It replaces IEC 60186 (1987) plus Amendments 1 and 2 only for inductive voltage transformers. IEC 60186 remains in force for capacitive voltage transformers.

IEC 60044-2:1997 is classified under the following ICS (International Classification for Standards) categories: 17.220.20 - Measurement of electrical and magnetic quantities. The ICS classification helps identify the subject area and facilitates finding related standards.

IEC 60044-2:1997 has the following relationships with other standards: It is inter standard links to IEC 61869-3:2011, IEC 60044-2:1997/AMD1:2000, IEC 60044-2:1997/AMD2:2002. Understanding these relationships helps ensure you are using the most current and applicable version of the standard.

IEC 60044-2:1997 is available in PDF format for immediate download after purchase. The document can be added to your cart and obtained through the secure checkout process. Digital delivery ensures instant access to the complete standard document.

Standards Content (Sample)


NORME CEI
INTERNATIONALE
IEC
60044-2
INTERNATIONAL
Première édition
STANDARD
First edition
1997-02
Transformateurs de mesure –
Partie 2:
Transformateurs inductifs de tension
Instrument transformers –
Part 2:
Inductive voltage transformers
Numéro de référence
Reference number
CEI/IEC 60044-2: 1997
Validité de la présente publication Validity of this publication
Le contenu technique des publications de la CEI est cons- The technical content of IEC publications is kept under
tamment revu par la CEI afin qu'il reflète l'état actuel de constant review by the IEC, thus ensuring that the content
la technique. reflects current technology.
Des renseignements relatifs à la date de reconfirmation de Information relating to the date of the reconfirmation of the
la publication sont disponibles auprès du Bureau Central de publication is available from the IEC Central Office.
la CEI.
Les renseignements relatifs à ces révisions, à l'établis- Information on the revision work, the issue of revised
sement des éditions révisées et aux amendements peuvent editions and amendments may be obtained from IEC
être obtenus auprès des Comités nationaux de la CEI et National Committees and from the following IEC
dans les documents ci-dessous: sources:
• Bulletin de la CEI • IEC Bulletin
• Annuaire de la CEI • IEC Yearbook
Publié annuellement Published yearly
• Catalogue des publications de la CEI • Catalogue of IEC publications
Publié annuellement et mis à jour régulièrement Published yearly with regular updates
Terminologie Terminology
En ce qui concerne la terminologie générale, le lecteur se For general terminology, readers are referred to IEC 50:
reportera à la CEI 50: Vocabulaire Electrotechnique Inter- International Electrotechnical Vocabulary (IEV), which is
national (VEI), qui se présente sous forme de chapitres issued in the form of separate chapters each dealing
séparés traitant chacun d'un sujet défini. Des détails with a specific field. Full details of the IEV will be
complets sur le VEI peuvent être obtenus sur demande. supplied on request. See also the IEC Multilingual
Voir également le dictionnaire multilingue de la CEI. Dictionary.
Les termes et définitions figurant dans la présente publi- The terms and definitions contained in the present publi-
cation ont été soit tirés du VEI, soit spécifiquement cation have either been taken from the IEV or have been
approuvés aux fins de cette publication. specifically approved for the purpose of this publication.
Symboles graphiques et littéraux Graphical and letter symbols
Pour les symboles graphiques, les symboles littéraux et les For graphical symbols, and letter symbols and signs
signes d'usage général approuvés par la CEI, le lecteur approved by the IEC for general use, readers are referred to
consultera: publications:
– la CEI 27: Symboles littéraux à utiliser en – IEC 27: Letter symbols to be used in electrical
électrotechnique; technology;
– la CEI 417: Symboles graphiques utilisables – IEC 417: Graphical symbols for use on
sur le matériel. Index, relevé et compilation des equipment. Index, survey and compilation of the
feuilles individuelles; single sheets;
– la CEI 617: Symboles graphiques pour schémas; – IEC 617: Graphical symbols for diagrams;
et pour les appareils électromédicaux, and for medical electrical equipment,
– la CEI 878: Symboles graphiques pour – IEC 878: Graphical symbols for electromedical
équipements électriques en pratique médicale. equipment in medical practice.
Les symboles et signes contenus dans la présente publi- The symbols and signs contained in the present publication
cation ont été soit tirés de la CEI 27, de la CEI 417, de la have either been taken from IEC 27, IEC 417, IEC 617
CEI 617 et/ou de la CEI 878, soit spécifiquement approuvés and/or IEC 878, or have been specifically approved for the
aux fins de cette publication. purpose of this publication.
Publications de la CEI établies par le IEC publications prepared by the same
même comité d'études technical committee
L'attention du lecteur est attirée sur les listes figurant à la fin The attention of readers is drawn to the end pages of this
de cette publication, qui énumèrent les publications de la publication which list the IEC publications issued by the
CEI préparées par le comité d'études qui a établi la technical committee which has prepared the present
présente publication. publication.

NORME
CEI
INTERNATIONALE
IEC
60044-2
INTERNATIONAL
Première édition
STANDARD
First edition
1997-02
Transformateurs de mesure –
Partie 2:
Transformateurs inductifs de tension
Instrument transformers –
Part 2:
Inductive voltage transformers
 IEC 1997 Droits de reproduction réservés  Copyright - all rights reserved
Aucune partie de cette publication ne peut être reproduite ni utilisée No part of this publication may be reproduced or utilized in
sous quelque forme que ce soit et par aucun procédé, électronique any form or by any means, electronic or mechanical, including
ou mécanique, y compris la photocopie et les microfilms, sans photocopying and microfilm, without permission in writing from
l'accord écrit de l'éditeur. the publisher.
International Electrotechnical Commission 3, rue de Varembé Geneva, Switzerland
Telefax: +41 22 919 0300 e-mail: inmail@iec.ch IEC web site http: //www.iec.ch
CODE PRIX
Commission Electrotechnique Internationale
PRICE CODE W
International Electrotechnical Commission
Pour prix, voir catalogue en vigueur
For price, see current catalogue

– 2 – 60044-2 © CEI:1997
SOMMAIRE
Pages
AVANT-PROPOS. 6
Articles
1 Généralités. 8
1.1 Domaine d'application. 8
1.2 Références normatives. 8
2 Définitions. 10
2.1 Définitions générales. 10
2.2 Définitions complémentaires pour les transformateurs inductifs de tension
monophasés pour protection . 14
3 Prescriptions générales. 14
4 Conditions de service normales et spéciales . 16
4.1 Conditions de service normales. 16
4.2 Conditions de service spéciales. 18
4.3 Installations de mise à la terre . 18
5 Valeurs normales. 20
5.1 Valeurs normales des tensions assignées. 20
5.2 Valeurs normales de la puissance de précision. 20
5.3 Valeurs normales du facteur de tension assigné. 22
5.4 Limites d'échauffement. 22
6 Prescriptions relatives à la conception . 24
6.1 Prescriptions relatives à l'isolement. 24
6.2 Tenue au court-circuit . 32
6.3 Prescriptions mécaniques. 34
7 Classification des essais . 34
7.1 Essais de type. 35
7.2 Essais individuels. 36
7.3 Essais spéciaux.36
8 Essais de type . 36
8.1 Essai d'échauffement. 36
8.2 Essai de tenue au court-circuit. 38
8.3 Essai au choc sur l'enroulement primaire . 38
8.4 Essai sous pluie pour les transformateurs du type extérieur . 42
9 Essais individuels. 42
9.1 Vérification du marquage des bornes . 42
9.2 Essais de tenue à fréquence industrielle sur les enroulements primaires et mesure
des décharges partielles . 42
9.3 Essais de tenue à fréquence industrielle entre sections et sur les enroulements
secondaires . 46

60044-2 © IEC:1997 – 3 –
CONTENTS
Page
FOREWORD . 7
Clause
1 General. 9
1.1 Scope. 9
1.2 Normative references. 9
2 Definitions. 11
2.1 General definitions.11
2.2 Additional definitions for single-phase inductive protective voltage transformers. 15
3 General requirements. 15
4 Normal and special service conditions. 17
4.1 Normal service conditions. 17
4.2 Special service conditions. 19
4.3 System earthing.19
5 Ratings. 21
5.1 Standard values of rated voltages. 21
5.2 Standard values of rated output. 21
5.3 Standard values of rated voltage factor . 23
5.4 Limits of temperature rise . 23
6 Design requirements. 25
6.1 Insulation requirements. 25
6.2 Short-circuit withstand capability. 33
6.3 Mechanical requirements. 35
7 Classification of tests. 35
7.1 Type tests. 37
7.2 Routine tests. 37
7.3 Special tests. 37
8 Type tests. 37
8.1 Temperature-rise test. 37
8.2 Short-circuit withstand capability test . 39
8.3 Impulse test on primary winding. 39
8.4 Wet test for outdoor type transformers . 43
9 Routine tests. 43
9.1 Verification of terminal markings. 43
9.2 Power-frequency withstand tests on primary windings and partial discharge
measurement. 43
9.3 Power-frequency withstand tests between sections and on secondary windings. 47

– 4 – 60044-2 © CEI:1997
Articles Page
10 Essais spéciaux. 46
10.1 Essai au choc coupé sur l'enroulement primaire . 46
10.2 Mesure de la capacité et du facteur de dissipation diélectrique . 48
10.3 Essais mécaniques. 48
11 Marquages. 52
11.1 Marquage de la plaque signalétique . 52
11.2 Marquage des bornes . 52
12 Prescriptions pour la précision des transformateurs inductifs de tension monophasés
pour mesures . 53
12.1 Désignation de la classe de précision d’un transformateur de tension pour mesures. 54
12.2 Limites de l'erreur de tension et du déphasage des transformateurs de tension
pour mesures . 54
12.3 Essais de type concernant la précision des transformateurs de tension
pour mesures . 54
12.4 Essais individuels concernant la précision des transformateurs de tension
pour mesures . 56
12.5 Marquage de la plaque signalétique d'un transformateur de tension pour mesures . 56
13 Prescriptions complémentaires pour les transformateurs de tension monophasés
pour protection . 56
13.1 Désignation de la classe de précision d’un transformateur inductifs de tension
pour protection . 56
13.2 Limites de l'erreur de tension et du déphasage des transformateurs de tension
pour protection . 56
13.3 Tensions assignées de l’enroulement secondaire de tension résiduelle. 58
13.4 Puissance de l’enroulement secondaire de tension résiduelle . 58
13.5 Classe de précision de l’enroulement secondaire de tension résiduelle . 60
13.6 Essais de type concernant les transformateurs de tension pour protection . 60
13.7 Essais individuels concernant les transformateurs de tension pour protection. 60
13.8 Marquage de la plaque signalétique d'un transformateur de tension
pour protection. 60
Figures. 62

60044-2 © IEC:1997 – 5 –
Clause Page
10 Special tests. 47
10.1 Chopped impulse test on primary winding . 47
10.2 Measurement of capacitance and dielectric dissipation factor . 49
10.3 Mechanical tests. 49
11 Markings. 53
11.1 Rating plate markings . 53
11.2 Terminal markings. 53
12 Accuracy requirements for single-phase inductive measuring voltage transformers. 53
12.1 Accuracy class designation for measuring voltage transformers. 55
12.2 Limits of voltage error and phase displacement for measuring voltage
transformers. 55
12.3 Type tests for accuracy of measuring voltage transformers. 55
12.4 Routine tests for accuracy of measuring voltage transformers. 57
12.5 Marking of the rating plate of a measuring voltage transformer . 57
13 Additional requirements for single-phase inductive protective voltage transformers . 57
13.1 Accuracy class designation for protective voltage transformers. 57
13.2 Limits of voltage error and phase displacement for protective voltage transformers . 57
13.3 Rated voltages for secondary windings intended to produce a residual voltage . 59
13.4 Output for secondary windings intended to produce a residual voltage. 59
13.5 Accuracy class for secondary windings intended to produce a residual voltage . 61
13.6 Type tests for protective voltage transformers. 61
13.7 Routine tests for protective voltage transformers . 61
13.8 Marking of the rating plate of a protective voltage transformer. 61
Figures. 63

– 6 – 60044-2 © CEI:1997
COMMISSION ÉLECTROTECHNIQUE INTERNATIONALE
_________
TRANSFORMATEURS DE MESURE –
Partie 2: Transformateurs inductifs de tension
AVANT-PROPOS
1) La CEI (Commission Electrotechnique Internationale) est une organisation mondiale de normalisation composée
de l'ensemble des comités électrotechniques nationaux (Comités nationaux de la CEI). La CEI a pour objet de
favoriser la coopération internationale pour toutes les questions de normalisation dans les domaines de
l'électricité et de l'électronique. A cet effet, la CEI, entre autres activités, publie des Normes Internationales.
Leur élaboration est confiée à des comités d'études, aux travaux desquels tout Comité national intéressé par le
sujet traité peut participer. Les organisations internationales, gouvernementales et non gouvernementales, en
liaison avec la CEI, participent également aux travaux. La CEI collabore étroitement avec l'Organisation
Internationale de Normalisation (ISO), selon des conditions fixées par accord entre les deux organisations.
2) Les décisions ou accords officiels de la CEI concernant les questions techniques, représentent, dans la mesure
du possible un accord international sur les sujets étudiés, étant donné que les Comités nationaux intéressés
sont représentés dans chaque comité d’études.
3) Les documents produits se présentent sous la forme de recommandations internationales. Ils sont publiés
comme normes, rapports techniques ou guides et agréés comme tels par les Comités nationaux.
4) Dans le but d'encourager l'unification internationale, les Comités nationaux de la CEI s'engagent à appliquer de
façon transparente, dans toute la mesure possible, les Normes internationales de la CEI dans leurs normes
nationales et régionales. Toute divergence entre la norme CEI et la norme nationale ou régionale
correspondante doit être indiquée en termes clairs dans cette dernière.
5) La CEI n’a fixé aucune procédure concernant le marquage comme indication d’approbation et sa responsabilité
n’est pas engagée quand un matériel est déclaré conforme à l’une de ses normes.
6) L’attention est attirée sur le fait que certains des éléments de la présente Norme internationale peuvent faire
l’objet de droits de propriété intellectuelle ou de droits analogues. La CEI ne saurait être tenue pour
responsable de ne pas avoir identifié de tels droits de propriété et de ne pas avoir signalé leur existence.
La Norme internationale CEI 60044-2 a été établie par le comité d'études 38 de la CEI:
Transformateurs de mesure.
La présente norme annule et remplace la deuxième édition de la CEI 186 (1987), la
modification 1 (1988) et l'amendement 2 (1995) seulement en ce qui concerne les transfor-
mateurs inductifs de tension. La CEI 186 reste encore en vigueur pour les transformateurs
condensateurs de tension.
Le texte de cette norme est issu des documents suivants:
FDIS Rapport de vote
38/162/FDIS 38/175/RVD
Le rapport de vote indiqué dans le tableau ci-dessus donne toute information sur le vote ayant
abouti à l'approbation de cette norme.

60044-2 © IEC:1997 – 7 –
INTERNATIONAL ELECTROTECHNICAL COMMISSION
_________
INSTRUMENT TRANSFORMERS –
Part 2: Inductive voltage transformers
FOREWORD
1) The IEC (International Electrotechnical Commission) is a worldwide organization for standardization comprising
all national electrotechnical committees (IEC National Committees). The object of the IEC is to promote
international co-operation on all questions concerning standardization in the electrical and electronic fields. To
this end and in addition to other activities, the IEC publishes International Standards. Their preparation is
entrusted to technical committees; any IEC National Committee interested in the subject dealt with may
participate in this preparatory work. International, governmental and non-governmental organizations liaising
with the IEC also participate in this preparation. The IEC collaborates closely with the International Organization
for Standardization (ISO) in accordance with conditions determined by agreement between the two
organizations.
2) The formal decisions or agreements of the IEC on technical matters, express as nearly as possible, an
international consensus of opinion on the relevant subjects since each technical committee has representation
from all interested National Committees.
3) The documents produced have the form of recommendations for international use and are published in the form
of standards, technical reports or guides and they are accepted by the National Committees in that sense.
4) In order to promote international unification, IEC National Committees undertake to apply IEC International
Standards transparently to the maximum extent possible in their national and regional standards. Any
divergence between the IEC Standard and the corresponding national or regional standard shall be clearly
indicated in the latter.
5) The IEC provides no marking procedure to indicate its approval and cannot be rendered responsible for any
equipment declared to be in conformity with one of its standards.
6) Attention is drawn to the possibility that some of the elements of this International Standard may be the subject
of patent rights. IEC shall not be held responsible for identifying any or all such patent rights.
International Standard IEC 60044-2 has been prepared by IEC technical committee 38: Instrument
transformers.
This standard cancels and replaces the second edition of IEC 186 (1987), its amendment 1
(1988) and amendment 2 (1995) only as far as the inductive voltage transformers are
concerned. IEC 186 remains in force for the capacitor voltage transformers.
The text of this standard is based on the following documents:
FDIS Report on voting
38/162/FDIS 38/175/RVD
Full information on the voting for the approval of this standard can be found in the report on
voting indicated in the above table.

– 8 – 60044-2 © CEI:1997
TRANSFORMATEURS DE MESURE –
Partie 2: Transformateurs inductifs de tension
1 Généralités
1.1 Domaine d'application
La présente partie de la CEI 44 est applicable aux transformateurs inductifs neufs destinés à
être utilisés avec des appareils de mesure électriques et des dispositifs électriques de
protection, de fréquence comprise entre 15 Hz et 100 Hz.
Elle s’applique principalement aux transformateurs à enroulements séparés, mais elle est
valable aussi, dans la mesure du possible, pour les autotransformateurs. La présente norme
n'est pas applicable aux transformateurs utilisés dans les laboratoires.
NOTE – Bien que la présente norme ne comporte aucun article relatif aux exigences particulières pour les
transformateurs triphasés, il a été estimé que les prescriptions générales des articles 3 à 11 pourraient leur être
applicables. C'est pourquoi l'on trouve dans ces articles quelques références à leur cas (voir 2.1.4, 5.1.1, 5.2,
et 11.2).
L’article 13 comprend les prescriptions et les essais qui complètent, en ce qui concerne les
transformateurs de tension monophasés pour protection, ceux qui sont indiqués dans les
articles 3 à 12. Les prescriptions de l'article 13 se rapportent en particulier aux transformateurs
qui doivent avoir une précision pour actionner des systèmes de protection pour des tensions
apparaissant en cas de défauts.
1.2 Références normatives
Les documents normatifs suivants contiennent des dispositions qui, par suite de la référence qui y est
faite, constituent des dispositions valables pour la présente partie de la CEI 44. Au moment de la
publication, les éditions indiquées étaient en vigueur. Tout document normatif est sujet à révision et les
parties prenantes aux accords fondés sur la présente partie de la CEI 44 sont invitées à rechercher la
possibilité d’appliquer les éditions les plus récentes des documents normatifs indiqués ci-après. Les
membres de la CEI et de l’ISO possèdent le registre des Normes internationales en vigueur.
CEI 28: 1925, Spécification internationale d'un cuivre-type recuit
CEI 38: 1983, Tensions normales de la CEI
CEI 50(321): 1986, Vocabulaire Electrotechnique International – Chapitre 321: Transformateurs
de mesure
CEI 60-1: 1989, Techniques des essais à haute tension – Première partie: Définitions et
prescriptions générales relatives aux essais
CEI 71-1: 1993, Coordination de l'isolement – Partie 1: Définitions, principes et règles
CEI 85: 1984, Evaluation et classification thermiques de l'isolation électrique
CEI 270: 1981, Mesure des décharges partielles
CEI 721: Classification des conditions d'environnement
CEI 815: 1986, Guide pour le choix des isolateurs sous pollution

60044-2 © IEC:1997 – 9 –
INSTRUMENT TRANSFORMERS –
Part 2: Inductive voltage transformers
1 General
1.1 Scope
This part of IEC 44 applies to new inductive voltage transformers for use with electrical
measuring instruments and electrical protective devices at frequencies from 15 Hz to 100 Hz.
Although this standard relates basically to transformers with separate windings, it is also
applicable, where appropriate, to auto-transformers. This standard does not apply to trans-
formers for use in laboratories.
NOTE – Requirements specific to three-phase voltage transformers are not included in this standard but, so far
as they are relevant, the requirements in clauses 3 to 11 apply to these transformers and a few references to
them are included in those clauses (e.g. see 2.1.4, 5.1.1, 5.2, and 11.2).
Clause 13 covers the requirements and tests, in addition to those in clauses 3 to 12, that are
necessary for single-phase inductive protective voltage transformers. The requirements of
clause 13 apply particularly to transformers which are required to have sufficient accuracy to
operate protective systems at voltages that occur under fault conditions.
1.2 Normative references
The following normative documents contain provisions which, through reference in this text,
constitute provisions of this part of IEC 44. At the time of publication, the editions indicated
were valid. All normative documents are subject to revision, and parties to agreements based
on this part of IEC 44 are encouraged to investigate the possibility of applying the most recent
editions of the normative documents indicated below. Members of IEC and ISO maintain
registers of currently valid International Standards.
IEC 28: 1925, International standard of resistance for copper
IEC 38: 1983, IEC standard voltages
IEC 50(321): 1986, International Electrotechnical Vocabulary – Chapter 321: Instrument
transformers
IEC 60-1: 1989, High-voltage test techniques – Part 1: General definitions and test requirements
IEC 71-1: 1993, Insulation co-ordination – Part 1: Definitions, principles and rules
IEC 85: 1984, Thermal evaluation and classification of electrical insulation
IEC 270: 1981, Partial discharge measurements
IEC 721: Classification of environmental conditions
IEC 815: 1986, Guide for the selection of insulators in respect of polluted conditions

– 10 – 60044-2 © CEI:1997
2 Définitions
Pour les besoins de la présente partie de la CEI 44, les définitions suivantes s'appliquent.
2.1 Définitions générales
2.1.1 transformateur de mesure: Transformateur destiné à alimenter des appareils de
mesure, des compteurs, des relais et autres appareils analogues. [VEI 321-01-01 modifiée]
2.1.2 transformateur de tension: Transformateur de mesure dans lequel la tension
secondaire est, dans les conditions normales d'emploi, pratiquement proportionnelle à la
tension primaire et déphasée par rapport à celle-ci d'un angle voisin de zéro, pour un sens
approprié des connexions. [VEI 321-03-01]
2.1.3 transformateur de tension non mis à la terre: Transformateur de tension dont toutes
les parties de l'enroulement primaire, y compris les bornes, sont isolées par rapport à la terre à
un niveau qui correspond à son niveau d'isolement assigné.
2.1.4 transformateur de tension mis à la terre: Transformateur de tension monophasé
destiné à avoir l'une des extrémités de son enroulement primaire reliée directement à la terre
ou transformateur de tension triphasé destiné à avoir le point neutre de son enroulement
primaire relié directement à la terre.
2.1.5 enroulement primaire: Enroulement auquel est appliquée la tension à transformer.
2.1.6 enroulement secondaire: Enroulement qui alimente les circuits de tension des
appareils de mesure, des compteurs, des relais et circuits analogues.
2.1.7 circuit secondaire: Circuit extérieur alimenté par l'enroulement secondaire d'un
transformateur.
2.1.8 tension primaire assignée: Valeur de la tension primaire qui figure dans la désignation
du transformateur et d'après laquelle sont déterminées ses conditions de fonctionnement.
[VEI 321-01-12 modifiée]
2.1.9 tension secondaire assignée: Valeur de la tension secondaire qui figure dans la
désignation du transformateur et d'après laquelle sont déterminées ses conditions de
fonctionnement. [VEI 321-01-16 modifiée]
2.1.10 rapport de transformation: Rapport de la tension primaire réelle à la tension
secondaire réelle. [VEI 321-01-18 modifiée]
2.1.11 rapport de transformation assigné: Rapport de la tension primaire assignée à la
tension secondaire assignée. [VEI 321-01-20 modifiée]
2.1.12 erreur de tension (erreur de rapport): Erreur que le transformateur introduit dans la
mesure d'une tension et qui provient de ce que le rapport de transformation n'est pas égal au
rapport de transformation assigné. [VEI 321-01-22 modifiée]
L'erreur de tension, exprimée en pour-cent, est donnée par la formule:
KU −U
ns p
erreur de tension %= × 100
U
p

K est le rapport de transformation assigné;
n
U est la tension primaire;
p
U est la tension secondaire correspondant à la tension U dans les conditions de la mesure.
s p
2.1.13 déphasage: Différence de phase entre les vecteurs des tensions primaire et
secondaire, le sens des vecteurs étant choisi de façon que cet angle soit nul pour un
transformateur parfait. [VEI 321-01-23 modifiée]

60044-2 © IEC:1997 – 11 –
2 Definitions
For the purpose of this part of IEC 44, the following definitions apply.
2.1 General definitions
2.1.1 instrument transformer: A transformer intended to supply measuring instruments,
meters, relays and other similar apparatus. [IEV 321-01-01 modified]
2.1.2 voltage transformer: An instrument transformer in which the secondary voltage, in
normal conditions of use, is substantially proportional to the primary voltage and differs in
phase from it by an angle which is approximately zero for an appropriate direction of the
connections. [IEV 321-03-01]
2.1.3 unearthed voltage transformer: A voltage transformer which has all parts of its
primary winding, including terminals, insulated from earth to a level corresponding to its rated
insulation level.
2.1.4 earthed voltage transformer: A single-phase voltage transformer which is intended to
have one end of its primary winding directly earthed or a three-phase voltage transformer which
is intended to have the star-point of its primary winding directly earthed.
2.1.5 primary winding: The winding to which the voltage to be transformed is applied.
2.1.6 secondary winding: The winding which supplies the voltage circuits of measuring
instruments, meters, relays or similar apparatus.
2.1.7 secondary circuit: The external circuit supplied by the secondary winding of a
transformer.
2.1.8 rated primary voltage: The value of the primary voltage which appears in the designation of
the transformer and on which its performance is based. [IEV 321-01-12 modified]
2.1.9 rated secondary voltage: The value of the secondary voltage which appears in the
designation of the transformer and on which its performance is based. [IEV 321-01-16
modified]
2.1.10 actual transformation ratio: The ratio of the actual primary voltage to the actual
secondary voltage. [IEV 321-01-18 modified]
2.1.11 rated transformation ratio: The ratio of the rated primary voltage to the rated
secondary voltage. [IEV 321-01-20 modified]
2.1.12 voltage error (ratio error): The error which a transformer introduces into the
measurement of a voltage and which arises when the actual transformation ratio is not equal to
the rated transformation ratio. [IEV 321-01-22 modified]
The voltage error, expressed in per cent, is given by the formula:
KU −U
ns p
voltage error %= × 100
U
p
where
K is the rated transformation ratio;
n
U is the actual primary voltage;
p
U is the actual secondary voltage when U is applied under the conditions of measurement.
s p
2.1.13 phase displacement: The difference in phase between the primary voltage and the
secondary voltage vectors, the direction of the vectors being so chosen that the angle is zero
for a perfect transformer. [IEV 321-01-23 modified]

– 12 – 60044-2 © CEI:1997
Le déphasage est considéré comme positif lorsque le vecteur de la tension secondaire est en avance
sur le vecteur de la tension primaire. Il est exprimé habituellement en minutes ou en centiradians.
NOTE – Cette définition n'est rigoureuse que pour des tensions sinusoïdales.
2.1.14 classe de précision: Désignation appliquée à un transformateur de tension dont les
erreurs restent dans des limites spécifiées pour des conditions d'emploi spécifiées.
2.1.15 charge: Admittance du circuit secondaire, exprimée en siemens, avec indication du
facteur de puissance (en retard ou en avance).
NOTE – La charge est généralement exprimée par la puissance apparente, en voltampères, absorbée à un
facteur de puissance spécifié et sous la tension secondaire assignée.
2.1.16 charge de précision: Valeur de la charge sur laquelle sont basées les conditions de précision.
2.1.17 puissance
2.1.17.1 puissance de précision: Valeur de la puissance apparente (en voltampères à un facteur
de puissance spécifié) que le transformateur peut fournir au circuit secondaire à la tension
secondaire assignée lorsqu'il est raccordé à sa charge de précision. [VEI 321-01-27 modifiée]
2.1.17.2 puissance thermique limite: Valeur de la puissance apparente, référée à la tension
assignée, que le transformateur peut fournir au circuit secondaire, quand la tension assignée est
appliquée au primaire, sans excéder les limites pour l'échauffement spécifiées en 5.4.
NOTES
1 En cette condition il est possible que les limites de l'erreur soient dépassées.
2 En cas de plusieurs enroulements secondaires, la valeur de la puissance thermique limite doit être spécifiée
pour chaque enroulement.
3 L'utilisation simultanée de plusieurs enroulements secondaires n'est pas admise sans un accord entre
constructeur et acheteur.
2.1.18 tension la plus élevée pour le matériel: Tension efficace entre phases la plus élevée
pour laquelle est conçue l'isolation du transformateur.
2.1.19 niveau d'isolement assigné: Combinaison des valeurs de tension qui caractérise l'isolation
du transformateur en ce qui concerne son aptitude à supporter les contraintes diélectriques.
2.1.20 réseau à neutre isolé: Réseau dont aucun point neutre n’a de connexion
intentionnelle à la terre, à l'exception des liaisons à haute impédance destinées à des
dispositifs de protection ou de mesure. [VEI 601-02-24]
2.1.21 réseau à neutre directement à la terre: Réseau dont le ou les points neutres sont
reliés directement à la terre. [VEI 601-02-25]
2.1.22 réseau à neutre non directement à la terre: Réseau dont le ou les points neutres sont
reliés à la terre par l’intermédiaire d’impédances destinées à limiter les courants de défaut à la terre.
[VEI 601-02-26]
2.1.23 réseau compensé par bobine d’extinction: Réseau dont un ou plusieurs points
neutres sont reliés à la terre par des réactances compensant approximativement la
composante capacitive du courant de défaut monophasé à la terre. [VEI 601-02-27]
NOTE – Pour un réseau compensé par bobine d’extinction, le courant résiduel dans le défaut est limité à tel
point qu’un arc de défaut dans l’air est généralement auto-extinguible.
2.1.24 facteur de défaut à la terre: En un emplacement donné d’un réseau triphasé, et pour
un schéma d’exploitation donné de ce réseau, rapport entre d’une part la tension efficace la
plus élevée, à la fréquence du réseau, entre une phase saine et la terre pendant un défaut à la
terre affectant une phase quelconque ou plusieurs phases en un point quelconque du réseau,
et d’autre part la valeur efficace de la tension entre phase et terre à la fréquence du réseau qui
serait obtenue à l’emplacement considéré en l’absence du défaut. [VEI 603-03-06]

60044-2 © IEC:1997 – 13 –
The phase displacement is said to be positive when the secondary voltage vector leads the
primary voltage vector. It is usually expressed in minutes or centiradians.
NOTE – This definition is strictly correct for sinusoidal voltages only.
2.1.14 accuracy class: A designation assigned to a voltage transformer, the errors of which
remain within specified limits under prescribed conditions of use.
2.1.15 burden: The admittance of the secondary circuit expressed in siemens and power
factor (lagging or leading).
NOTE – The burden is usually expressed as the apparent power in voltamperes, absorbed at a specified power
factor and at the rated secondary voltage.
2.1.16 rated burden: The value of the burden on which the accuracy requirements of this
specification are based.
2.1.17 output
2.1.17.1  rated output: The value of the apparent power (in voltamperes at a specified power
factor) which the transformer is intended to supply to the secondary circuit at the rated
secondary voltage and with rated burden connected to it. [IEV 321-01-27 modified]
2.1.17.2  thermal limiting output: The value of the apparent power referred to rated voltage
which can be taken from a secondary winding, at rated primary voltage applied, without
exceeding the limits of temperature rise of 5.4.
NOTES
1 In this condition the limits of error may be exceeded.
2 In the case of more than one secondary winding, the thermal limiting output is to be given separately.
3 The simultaneous use of more than one secondary winding is not admitted unless there is an agreement
between manufacturer and purchaser.
2.1.18 highest voltage for equipment: The highest r.m.s. phase-to-phase voltage for which
a transformer is designed in respect of its insulation.
2.1.19 rated insulation level: The combination of voltage values which characterizes the
isolation of a transformer with regard to its capability to withstand dielectric stresses.
2.1.20 isolated neutral system: A system where the neutral point is not intentionally
connected to earth, except for high impedance connections for protection or measurement
purposes. [IEV 601-02-24]
2.1.21 solidly earthed neutral system: A system whose neutral point(s) is(are) earthed
directly. [IEV 601-02-25]
2.1.22 impedance earthed (neutral) system: A system whose neutral point(s) is(are) earthed
through impedances to limit earth fault currents. [IEV 601-02-26]
2.1.23 resonant earthed (neutral) system: A system in which one or more neutral points are
connected to earth through reactances which approximately compensate the capacitive component
of a single-phase-to-earth fault current. [IEV 601-02-27]
NOTE – With resonant earthing of a system, the residual current in the fault is limited to such an extent that an
arcing fault in air is self-extinguishing.
2.1.24 earth fault factor: At a
...


IEC 60044-2
Edition 1.2 2003-02
INTERNATIONAL
STANDARD
NORME
INTERNATIONALE
Instrument transformers –
Part 2: Inductive voltage transformers

Transformateurs de mesure –
Partie 2: Transformateurs inductifs de tension
All rights reserved. Unless otherwise specified, no part of this publication may be reproduced or utilized in any form or by
any means, electronic or mechanical, including photocopying and microfilm, without permission in writing from either IEC or
IEC's member National Committee in the country of the requester.
If you have any questions about IEC copyright or have an enquiry about obtaining additional rights to this publication,
please contact the address below or your local IEC member National Committee for further information.

Droits de reproduction réservés. Sauf indication contraire, aucune partie de cette publication ne peut être reproduite
ni utilisée sous quelque forme que ce soit et par aucun procédé, électronique ou mécanique, y compris la photocopie
et les microfilms, sans l'accord écrit de la CEI ou du Comité national de la CEI du pays du demandeur.
Si vous avez des questions sur le copyright de la CEI ou si vous désirez obtenir des droits supplémentaires sur cette
publication, utilisez les coordonnées ci-après ou contactez le Comité national de la CEI de votre pays de résidence.

IEC Central Office
3, rue de Varembé
CH-1211 Geneva 20
Switzerland
Email: inmail@iec.ch
Web: www.iec.ch
About the IEC
The International Electrotechnical Commission (IEC) is the leading global organization that prepares and publishes
International Standards for all electrical, electronic and related technologies.

About IEC publications
The technical content of IEC publications is kept under constant review by the IEC. Please make sure that you have the
latest edition, a corrigenda or an amendment might have been published.
ƒ Catalogue of IEC publications: www.iec.ch/searchpub
The IEC on-line Catalogue enables you to search by a variety of criteria (reference number, text, technical committee,…).
It also gives information on projects, withdrawn and replaced publications.
ƒ IEC Just Published: www.iec.ch/online_news/justpub
Stay up to date on all new IEC publications. Just Published details twice a month all new publications released. Available
on-line and also by email.
ƒ Electropedia: www.electropedia.org
The world's leading online dictionary of electronic and electrical terms containing more than 20 000 terms and definitions
in English and French, with equivalent terms in additional languages. Also known as the International Electrotechnical
Vocabulary online.
ƒ Customer Service Centre: www.iec.ch/webstore/custserv
If you wish to give us your feedback on this publication or need further assistance, please visit the Customer Service
Centre FAQ or contact us:
Email: csc@iec.ch
Tel.: +41 22 919 02 11
Fax: +41 22 919 03 00
A propos de la CEI
La Commission Electrotechnique Internationale (CEI) est la première organisation mondiale qui élabore et publie des
normes internationales pour tout ce qui a trait à l'électricité, à l'électronique et aux technologies apparentées.

A propos des publications CEI
Le contenu technique des publications de la CEI est constamment revu. Veuillez vous assurer que vous possédez
l’édition la plus récente, un corrigendum ou amendement peut avoir été publié.
ƒ Catalogue des publications de la CEI: www.iec.ch/searchpub/cur_fut-f.htm
Le Catalogue en-ligne de la CEI vous permet d’effectuer des recherches en utilisant différents critères (numéro de référence,
texte, comité d’études,…). Il donne aussi des informations sur les projets et les publications retirées ou remplacées.
ƒ Just Published CEI: www.iec.ch/online_news/justpub
Restez informé sur les nouvelles publications de la CEI. Just Published détaille deux fois par mois les nouvelles
publications parues. Disponible en-ligne et aussi par email.
ƒ Electropedia: www.electropedia.org
Le premier dictionnaire en ligne au monde de termes électroniques et électriques. Il contient plus de 20 000 termes et
définitions en anglais et en français, ainsi que les termes équivalents dans les langues additionnelles. Egalement appelé
Vocabulaire Electrotechnique International en ligne.
ƒ Service Clients: www.iec.ch/webstore/custserv/custserv_entry-f.htm
Si vous désirez nous donner des commentaires sur cette publication ou si vous avez des questions, visitez le FAQ du
Service clients ou contactez-nous:
Email: csc@iec.ch
Tél.: +41 22 919 02 11
Fax: +41 22 919 03 00
IEC 60044-2
Edition 1.2 2003-02
INTERNATIONAL
STANDARD
NORME
INTERNATIONALE
Instrument transformers –
Part 2: Inductive voltage transformers

Transformateurs de mesure –
Partie 2: Transformateurs inductifs de tension

INTERNATIONAL
ELECTROTECHNICAL
COMMISSION
COMMISSION
ELECTROTECHNIQUE
PRICE CODE
INTERNATIONALE
CP
CODE PRIX
ICS 17.220.20; 29.180 ISBN 2-8318-6837-8

– 2 – 60044-2  CEI:1997+A1:2000+A2:2002
SOMMAIRE
AVANT-PROPOS . 8
1 Généralités .10
1.1 Domaine d'application .10
1.2 Références normatives .10
2 Définitions.12
2.1 Définitions générales .12
2.2 Définitions complémentaires pour les transformateurs inductifs
de tension monophasés pour protection .20
3 Prescriptions générales.20
4 Conditions de service normales et spéciales.20
4.1 Conditions de service normales.20
4.2 Conditions de service spéciales .22
4.3 Installations de mise à la terre.24
5 Valeurs normales .24
5.1 Valeurs normales des tensions assignées .24
5.2 Valeurs normales de la puissance de précision .26
5.3 Valeurs normales du facteur de tension assigné.26
5.4 Limites d'échauffement .28
6 Prescriptions relatives à la conception.30
6.1 Prescriptions relatives à l'isolement.30
6.2 Tenue au court-circuit .40
6.3 Prescriptions mécaniques .42
7 Classification des essais .42
7.1 Essais de type .44
7.2 Essais individuels .44
7.3 Essais spéciaux .44
8 Essais de type .46
8.1 Essai d'échauffement.46
8.2 Essai de tenue au court-circuit .46
8.3 Essai au choc sur l'enroulement primaire .48
8.4 Essai sous pluie pour les transformateurs du type extérieur.50
8.5 Mesure des perturbations radioélectriques .52
9 Essais individuels.54
9.1 Vérification du marquage des bornes .54
9.2 Essais de tenue à fréquence industrielle sur les enroulements primaires
et mesure des décharges partielles .56
9.3 Essais de tenue à fréquence industrielle entre sections
et sur les enroulements secondaires .60
10 Essais spéciaux .60
10.1 Essai au choc coupé sur l'enroulement primaire .60
10.2 Mesure de la capacité et du facteur de dissipation diélectrique .62
10.3 Essais mécaniques .62
10.4 Mesure des surtensions transmises .64

60044-2  IEC:1997+A1:2000+A2:2002 – 3 –
CONTENTS
FOREWORD . 9
1 General.11
1.1 Scope .11
1.2 Normative references.11
2 Definitions.13
2.1 General definitions.13
2.2 Additional definitions for single-phase inductive protective voltage transformers .21
3 General requirements.21
4 Normal and special service conditions .21
4.1 Normal service conditions .21
4.2 Special service conditions .23
4.3 System earthing.25
5 Ratings .25
5.1 Standard values of rated voltages .25
5.2 Standard values of rated output.27
5.3 Standard values of rated voltage factor .27
5.4 Limits of temperature rise .29
6 Design requirements .31
6.1 Insulation requirements.31
6.2 Short-circuit withstand capability .41
6.3 Mechanical requirements .43
7 Classification of tests .43
7.1 Type tests.45
7.2 Routine tests.45
7.3 Special tests .45
8 Type tests .47
8.1 Temperature-rise test.47
8.2 Short-circuit withstand capability test.47
8.3 Impulse test on primary winding .49
8.4 Wet test for outdoor type transformers .51
8.5 Radio interference voltage measurement.53
9 Routine tests.55
9.1 Verification of terminal markings .55
9.2 Power-frequency withstand tests on primary windings
and partial discharge measurement.57
9.3 Power-frequency withstand tests between sections
and on secondary windings .61
10 Special tests .61
10.1 Chopped impulse test on primary winding.61
10.2 Measurement of capacitance and dielectric dissipation factor .63
10.3 Mechanical tests .63
10.4 Transmitted overvoltage measurement.65

– 4 – 60044-2  CEI:1997+A1:2000+A2:2002
11 Marquage .68
11.1 Marquage de la plaque signalétique .68
11.2 Marquage des bornes .68
12 Prescriptions pour la précision des transformateurs inductifs
de tension monophasés pour mesures .70
12.1 Désignation de la classe de précision d’un transformateur
de tension pour mesures.70
12.2 Limites de l'erreur de tension et du déphasage des transformateurs
de tension pour mesures.70
12.3 Essais de type concernant la précision des transformateurs
de tension pour mesures.72
12.4 Essais individuels concernant la précision des transformateurs
de tension pour mesures.72
12.5 Marquage de la plaque signalétique d'un transformateur
de tension pour mesures.72
13 Prescriptions complémentaires pour les transformateurs inductifs
de tension monophasés pour protection .74
13.1 Désignation de la classe de précision d’un transformateur
de tension pour protection.74
13.2 Limites de l'erreur de tension et du déphasage des transformateurs
de tension pour protection.74
13.3 Tensions assignées de l’enroulement secondaire de tension résiduelle .76
13.4 Puissance de l’enroulement secondaire de tension résiduelle .76
13.5 Classe de précision de l’enroulement secondaire de tension résiduelle.76
13.6 Essais de type concernant les transformateurs de tension pour protection.78
13.7 Essais individuels concernant les transformateurs de tension pour protection .78
13.8 Marquage de la plaque signalétique d'un transformateur
de tension pour protection.78
Figure 1 – Facteur correctif pour l'altitude .80
Figure 2 – Circuit d’essai pour la mesure des décharges partielles.82
Figure 3 – Variante de circuit d’essai pour la mesure des décharges partielles.82
Figure 4 – Exemple de circuit d’essai équilibré pour la mesure des décharges partielles .84
Figure 5 – Exemple de circuit d’étalonnage pour la mesure des décharges partielles.84
Figure 6 – Transformateur monophasé avec bornes primaires totalement isolées
et un seul circuit secondaire .86
Figure 7 – Transformateur monophasé avec une borne primaire neutre à isolement réduit
et un seul circuit secondaire .86
Figure 8 – Ensemble triphasé avec un seul circuit secondaire .86
Figure 9 – Transformateur monophasé avec deux circuits secondaires .88
Figure 10 – Ensemble triphasé avec deux circuits secondaires.88
Figure 11 – Transformateur monophasé avec un circuit secondaire à prises multiples.88
Figure 12 – Ensemble triphasé avec un circuit secondaire à prises multiples .88
Figure 13 – Transformateur monophasé avec deux circuits secondaires à prises multiples .90
Figure 14 – Transformateur monophasé avec un enroulement de tension résiduelle.90
Figure 15 – Transformateur triphasé avec enroulement de tension résiduelle.90
Figure 16 – Exemple type de plaque signalétique.92

60044-2  IEC:1997+A1:2000+A2:2002 – 5 –
11 Markings.69
11.1 Rating plate markings .69
11.2 Terminal markings .69
12 Accuracy requirements for single-phase inductive measuring voltage transformers .71
12.1 Accuracy class designation for measuring voltage transformers.71
12.2 Limits of voltage error and phase displacement
for measuring voltage transformers .71
12.3 Type tests for accuracy of measuring voltage transformers.73
12.4 Routine tests for accuracy of measuring voltage transformers .73
12.5 Marking of the rating plate of a measuring voltage transformer .73
13 Additional requirements for single-phase inductive protective voltage transformers .75
13.1 Accuracy class designation for protective voltage transformers.75
13.2 Limits of voltage error and phase displacement
for protective voltage transformers .75
13.3 Rated voltages for secondary windings intended to produce a residual voltage .77
13.4 Output for secondary windings intended to produce a residual voltage .77
13.5 Accuracy class for secondary windings intended to produce a residual voltage .77
13.6 Type tests for protective voltage transformers .79
13.7 Routine tests for protective voltage transformers .79
13.8 Marking of the rating plate of a protective voltage transformer .79
Figure 1 – Altitude correction factor .81
Figure 2 – Test circuit for partial discharge measurement .83
Figure 3 – Alternative circuit for partial discharge measurement.83
Figure 4 – Example of balanced test circuit for partial discharge measurement .85
Figure 5 – Example of calibration circuit for partial discharge measurement .85
Figure 6 – Single-phase transformer with fully insulated terminals
and a single secondary.87
Figure 7 – Single-phase transformer with a neutral primary terminal
with reduced insulation and a single secondary.87
Figure 8 – Three-phase assembly with a single secondary .87
Figure 9 – Single-phase transformer with two secondaries .89
Figure 10 – Three-phase assembly with two secondaries .89
Figure 11 – Single-phase transformer with one multi-tap secondary .89
Figure 12 – Three-phase assembly with one multi-tap secondary.89
Figure 13 – Single-phase transformer with two multi-tap secondaries.91
Figure 14 – Single-phase transformer with one residual voltage winding.91
Figure 15 – Three-phase transformer with one residual voltage winding .91
Figure 16 – Example of a typical rating plate.93

– 6 – 60044-2  CEI:1997+A1:2000+A2:2002
Figure 17 – Circuit de mesure.54
Figure 18 – Mesure des surtensions transmises: Circuit d’essai et installation
pour essai GIS .94
Figure 19 – Mesure des surtensions transmises: Installation générale pour essais .94
Figure 20 – Mesure des surtensions transmises: Formes de l’onde d’essai .96
Tableau 1 – Catégories de température .20
Tableau 2 – Valeurs normales du facteur de tension assigné .28
Tableau 3 – Limites d'échauffement des enroulements .30
Tableau 4 – Niveaux d'isolement assignés pour les enroulements primaires de trans-
formateur avec une tension la plus élevée pour le matériel U inférieure à 300 kV .32
m
Tableau 5 – Niveaux d'isolement assignés pour les enroulements primaires de trans-
formateur avec une tension la plus élevée pour le matériel U égale ou supérieure à 300 kV.34
m
Tableau 6 – Tensions de tenue à fréquence industrielle pour les enroulements primaires
de transformateurs avec une tension la plus élevée pour le matériel U égale
m
ou supérieure à 300 kV.34
Tableau 7 – Tensions d'essai de décharges partielles et niveaux admissibles .36
Tableau 8 – Longueurs de la ligne de fuite.38
Tableau 9 – Charges d'essai de tenue statique .42
Tableau 10 – Modalités d’application des charges d’essai aux bornes primaires de ligne.66
Tableau 11 – Limites de l’erreur de tension et du déphasage transformateurs
de tension pour mesures .72
Tableau 12 – Limites de l'erreur de tension et du déphasage des transformateurs
de tension pour protection .74
Tableau 13 – Tensions assignées de l'enroulement secondaire de tension résiduelle .76
Tableau 14 – Limites des surtensions transmises .40

60044-2  IEC:1997+A1:2000+A2:2002 – 7 –
Figure 17 – Measuring circuit.55
Figure 18 – Transmitted Overvoltages measurement: Test Circuit and GIS Test set-up .95
Figure 19 – Transmitted Overvoltages measurement: General Test set-up .95
Figure 20 – Transmitted Overvoltages measurement: Test Waveforms .97
Table 1 – Temperature categories .21
Table 2 – Standard values of rated voltage factors.29
Table 3 – Limits of temperature rise of windings .31
Table 4 – Rated insulation levels for transformer primary windings having highest voltage
for equipment U < 300 kV.33
m
Table 5 – Rated insulation levels for primary windings having highest voltage
for equipment U ≥ 300 kV.35
m
Table 6 – Power-frequency withstand voltages for transformer primary windings
having voltage for equipment U ≥ 300 kV.35
m
Table 7 – Partial discharge test voltages and permissible levels.37
Table 8 – Creepage distances .39
Table 9 – Static withstand test loads.43
Table 10 – Modalities of application of the test loads to be applied
to the line primary terminals.67
Table 11 – Limits of voltage error and phase displacement measuring
voltage transformers.73
Table 12 – Limits of voltage error and phase displacement
for protective voltage transformers.75
Table 13 – Rated voltages for secondary intended to produce a residual voltage.77
Table 14 – Transmitted overvoltage limits .41

– 8 – 60044-2 © CEI:1997+A1:2000+A2:2002
COMMISSION ÉLECTROTECHNIQUE INTERNATIONALE
____________
TRANSFORMATEURS DE MESURE –
Partie 2: Transformateurs inductifs de tension

AVANT-PROPOS
1) La CEI (Commission Électrotechnique Internationale) est une organisation mondiale de normalisation composée
de l'ensemble des comités électrotechniques nationaux (Comités nationaux de la CEI). La CEI a pour objet de
favoriser la coopération internationale pour toutes les questions de normalisation dans les domaines de
l'électricité et de l'électronique. A cet effet, la CEI, entre autres activités, publie des Normes internationales.
Leur élaboration est confiée à des comités d'études, aux travaux desquels tout Comité national intéressé par le
sujet traité peut participer. Les organisations internationales, gouvernementales et non gouvernementales, en
liaison avec la CEI, participent également aux travaux. La CEI collabore étroitement avec l'Organisation
Internationale de Normalisation (ISO), selon des conditions fixées par accord entre les deux organisations.
2) Les décisions ou accords officiels de la CEI concernant les questions techniques représentent, dans la mesure
du possible, un accord international sur les sujets étudiés, étant donné que les Comités nationaux intéressés
sont représentés dans chaque comité d’études.
3) Les documents produits se présentent sous la forme de recommandations internationales. Ils sont publiés
comme normes, spécifications techniques, rapports techniques ou guides et agréés comme tels par les Comités
nationaux.
4) Dans le but d'encourager l'unification internationale, les Comités nationaux de la CEI s'engagent à appliquer de
façon transparente, dans toute la mesure possible, les Normes internationales de la CEI dans leurs normes
nationales et régionales. Toute divergence entre la norme de la CEI et la norme nationale ou régionale
correspondante doit être indiquée en termes clairs dans cette dernière.
5) La CEI n’a fixé aucune procédure concernant le marquage comme indication d’approbation et sa responsabilité
n’est pas engagée quand un matériel est déclaré conforme à l’une de ses normes.
6) L’attention est attirée sur le fait que certains des éléments de la présente Norme internationale peuvent faire
l’objet de droits de propriété intellectuelle ou de droits analogues. La CEI ne saurait être tenue pour
responsable de ne pas avoir identifié de tels droits de propriété et de ne pas avoir signalé leur existence.

La Norme internationale CEI 60044-2 a été établie par le comité d'études 38 de la CEI:
Transformateurs de mesure.
La présente version consolidée de la CEI 60044-2 comprend la première édition (1997)
[documents 38/162/FDIS et 38/175/RVD], son amendement 1 (2000) [documents 38/244/FDIS
et 38/254/RVD] et son amendement 2 (2002) [documents 38/286/FDIS et 38/290/RVD].
Le contenu technique de cette version consolidée est donc identique à celui de l'édition de
base et à ses amendements; cette version a été préparée par commodité pour l'utilisateur.
Elle porte le numéro d'édition 1.2.
Une ligne verticale dans la marge indique où la publication de base a été modifiée par les
amendements 1 et 2.
Le comité a décidé que le contenu de la publication de base et de ses amendements ne sera
pas modifié avant 2005. A cette date, la publication sera
• reconduite;
• supprimée;
• remplacée par une édition révisée, ou
• amendée.
60044-2 © IEC:1997+A1:2000+A2:2002 – 9 –
INTERNATIONAL ELECTROTECHNICAL COMMISSION
____________
INSTRUMENT TRANSFORMERS –
Part 2: Inductive voltage transformers

FOREWORD
1) The IEC (International Electrotechnical Commission) is a worldwide organization for standardization comprising
all national electrotechnical committees (IEC National Committees). The object of the IEC is to promote
international co-operation on all questions concerning standardization in the electrical and electronic fields. To
this end and in addition to other activities, the IEC publishes International Standards. Their preparation is
entrusted to technical committees; any IEC National Committee interested in the subject dealt with may
participate in this preparatory work. International, governmental and non-governmental organizations liaising
with the IEC also participate in this preparation. The IEC collaborates closely with the International Organization
for Standardization (ISO) in accordance with conditions determined by agreement between the two
organizations.
2) The formal decisions or agreements of the IEC on technical matters express, as nearly as possible, an
international consensus of opinion on the relevant subjects since each technical committee has representation
from all interested National Committees.
3) The documents produced have the form of recommendations for international use and are published in the form
of standards, technical specifications, technical reports or guides and they are accepted by the National
Committees in that sense.
4) In order to promote international unification, IEC National Committees undertake to apply IEC International
Standards transparently to the maximum extent possible in their national and regional standards. Any
divergence between the IEC Standard and the corresponding national or regional standard shall be clearly
indicated in the latter.
5) The IEC provides no marking procedure to indicate its approval and cannot be rendered responsible for any
equipment declared to be in conformity with one of its standards.
6) Attention is drawn to the possibility that some of the elements of this International Standard may be the subject
of patent rights. The IEC shall not be held responsible for identifying any or all such patent rights.

International Standard IEC 60044-2 has been prepared by IEC technical committee 38:
Instrument transformers.
This consolidated version of IEC 60044-2 consists of the first edition (1997) [documents
38/162/FDIS and 38/175/RVD], its amendment 1 (2000) [documents 38/244/FDIS and
38/254/RVD] and its amendment 2 (2002) [documents 38/286/FDIS and 38/290/RVD].
The technical content is therefore identical to the base edition and its amendments and has
been prepared for user convenience.
It bears the edition number 1.2.
A vertical line in the margin shows where the base publication has been modified by
amendments 1 and 2.
The committee has decided that the contents of the base publication and its amendments will
remain unchanged until 2005. At this date, the publication will be
• reconfirmed;
• withdrawn;
• replaced by a revised edition, or
• amended.
– 10 – 60044-2  CEI:1997+A1:2000+A2:2002
TRANSFORMATEURS DE MESURE –
Partie 2: Transformateurs inductifs de tension
1 Généralités
1.1 Domaine d'application
La présente partie de la CEI 60044 est applicable aux transformateurs inductifs neufs destinés
à être utilisés avec des appareils de mesure électriques et des dispositifs électriques de
protection, de fréquence comprise entre 15 Hz et 100 Hz.
Elle s’applique principalement aux transformateurs à enroulements séparés, mais elle est
valable aussi, dans la mesure du possible, pour les autotransformateurs. La présente norme
n'est pas applicable aux transformateurs utilisés dans les laboratoires.
NOTE Bien que la présente norme ne comporte aucun article relatif aux exigences particulières pour les
transformateurs triphasés, il a été estimé que les prescriptions générales des articles 3 à 11 pourraient leur être
applicables. C'est pourquoi l'on trouve dans ces articles quelques références à leur cas (voir 2.1.4, 5.1.1, 5.2, et 11.2).
L’article 13 comprend les prescriptions et les essais qui complètent, en ce qui concerne les
transformateurs de tension monophasés pour protection, ceux qui sont indiqués dans les
articles 3 à 12. Les prescriptions de l'article 13 se rapportent en particulier aux transformateurs
qui doivent avoir une précision pour actionner des systèmes de protection pour des tensions
apparaissant en cas de défauts.
1.2 Références normatives
Les documents de référence suivants sont indispensables pour l'application du présent
document. Pour les références datées, seule l'édition citée s'applique. Pour les références non
datées, la dernière édition du document de référence s'applique (y compris les éventuels
amendements).
CEI 60028:1925, Spécification internationale d'un cuivre-type recuit
CEI 60038:1983, Tensions normales de la CEI
CEI 60050(321):1986, Vocabulaire Electrotechnique International (VEI) – Chapitre 321:
Transformateurs de mesure
CEI 60060-1:1989, Techniques des essais à haute tension – Première partie: Définitions et
prescriptions générales relatives aux essais
CEI 60071-1:1993, Coordination de l'isolement – Partie 1: Définitions, principes et règles
CEI 60085:1984, Evaluation et classification thermiques de l'isolation électrique
CEI 60270:1981, Mesure des décharges partielles
CEI 60721: Classification des conditions d'environnement
CEI 60815:1986, Guide pour le choix des isolateurs sous pollution
CISPR 18-2:1986, Caractéristiques des lignes et des équipements à haute tension relatives
aux perturbations radioélectriques – Deuxième partie: Méthodes de mesure et procédure
d'établissement des limites
60044-2  IEC:1997+A1:2000+A2:2002 – 11 –
INSTRUMENT TRANSFORMERS –
Part 2: Inductive voltage transformers
1 General
1.1 Scope
This part of IEC 60044 applies to new inductive voltage transformers for use with electrical
measuring instruments and electrical protective devices at frequencies from 15 Hz to 100 Hz.
Although this standard relates basically to transformers with separate windings, it is also
applicable, where appropriate, to auto-transformers. This standard does not apply to trans-
formers for use in laboratories.
NOTE Requirements specific to three-phase voltage transformers are not included in this standard but, so far as
they are relevant, the requirements in clauses 3 to 11 apply to these transformers and a few references to them are
included in those clauses (e.g. see 2.1.4, 5.1.1, 5.2, and 11.2).
Clause 13 covers the requirements and tests, in addition to those in clauses 3 to 12, that are
necessary for single-phase inductive protective voltage transformers. The requirements of
clause 13 apply particularly to transformers which are required to have sufficient accuracy to
operate protective systems at voltages that occur under fault conditions.
1.2 Normative references
The following referenced documents are indispensable for the application of this document. For
dated references, only the edition cited applies. For undated references, the latest edition of
the referenced document (including any amendments) applies.
IEC 60028:1925, International standard of resistance for copper
IEC 60038:1983, IEC standard voltages
IEC 60050(321):1986, International Electrotechnical Vocabulary (IEV) – Chapter 321:
Instrument transformers
IEC 60060-1:1989, High-voltage test techniques – Part 1: General definitions and test
requirements
IEC 60071-1:1993, Insulation co-ordination – Part 1: Definitions, principles and rules
IEC 60085:1984, Thermal evaluation and classification of electrical insulation
IEC 60270:1981, Partial discharge measurements
IEC 60721: Classification of environmental conditions
IEC 60815:1986, Guide for the selection of insulators in respect of polluted conditions
CISPR 18-2:1986, Radio interference characteristics of overhead power lines and high-voltage
equipment – Part 2: Methods of measurement and procedure for determining limits

– 12 – 60044-2  CEI:1997+A1:2000+A2:2002
2 Définitions
Pour les besoins de la présente partie de la CEI 60044, les définitions suivantes s'appliquent.
2.1 Définitions générales
2.1.1
transformateur de mesure
transformateur destiné à alimenter des appareils de mesure, des compteurs, des relais et
autres appareils analogues
[VEI 321-01-01 modifiée]
2.1.2
transformateur de tension
transformateur de mesure dans lequel la tension secondaire est, dans les conditions normales
d'emploi, pratiquement proportionnelle à la tension primaire et déphasée par rapport à celle-ci
d'un angle voisin de zéro, pour un sens approprié des connexions
[VEI 321-03-01]
2.1.3
transformateur de tension non mis à la terre
transformateur de tension dont toutes les parties de l'enroulement primaire, y compris les
bornes, sont isolées par rapport à la terre à un niveau qui correspond à son niveau d'isolement
assigné
2.1.4
transformateur de tension mis à la terre
transformateur de tension monophasé destiné à avoir l'une des extrémités de son enroulement
primaire reliée directement à la terre ou transformateur de tension triphasé destiné à avoir le
point neutre de son enroulement primaire relié directement à la terre
2.1.5
enroulement primaire
enroulement auquel est appliquée la tension à transformer
2.1.6
enroulement secondaire
enroulement qui alimente les circuits de tension des appareils de mesure, des compteurs, des
relais et circuits analogues
2.1.7
circuit secondaire
circuit extérieur alimenté par l'enroulement secondaire d'un transformateur
2.1.8
tension primaire assignée
valeur de la tension primaire qui figure dans la désignation du transformateur et d'après
laquelle sont déterminées ses conditions de fonctionnement
[VEI 321-01-12 modifiée]
2.1.9
tension secondaire assignée
valeur de la tension secondaire qui figure dans la désignation du transformateur et d'après
laquelle sont déterminées ses conditions de fonctionnement
[VEI 321-01-16 modifiée]
60044-2  IEC:1997+A1:2000+A2:2002 – 13 –
2 Definitions
For the purpose of this part of IEC 60044, the following definitions apply.
2.1 General definitions
2.1.1
instrument transformer
a transformer intended to supply measuring instruments, meters, relays and other similar
apparatus
[IEV 321-01-01 modified]
2.1.2
voltage transformer
an instrument transformer in which the secondary voltage, in normal conditions of use, is
substantially proportional to the primary voltage and differs in phase from it by an angle which
is approximately zero for an appropriate direction of the connections
[IEV 321-03-01]
2.1.3
unearthed voltage transformer
a voltage transformer which has all parts of its primary winding, including terminals, insulated
from earth to a level corresponding to its rated insulation level
2.1.4
earthed voltage transformer
a single-phase voltage transformer which is intended to have one end of its primary winding
directly earthed or a three-phase voltage transformer which is intended to have the star-point of
its primary winding directly earthed
2.1.5
primary winding
the winding to which the voltage to be transformed is applied
2.1.6
secondary winding
the winding which supplies the voltage circuits of measuring instruments, meters, relays or
similar apparatus
2.1.7
secondary circuit
the external circuit supplied by the secondary winding of a transformer
2.1.8
rated primary voltage
the value of the primary voltage which appears in the designation of the transformer and on
which its performance is based
[IEV 321-01-12 modified]
2.1.9
rated secondary voltage
the value of the secondary voltage which appears in the designatio
...


NORME CEI
INTERNATIONALE IEC
60044-2
INTERNATIONAL
Edition 1.1
STANDARD
2000-11
Edition 1:1997 consolidée par l'amendement 1:2000
Edition 1:1997 consolidated with amendment 1:2000
Transformateurs de mesure –
Partie 2:
Transformateurs inductifs de tension
Instrument transformers –
Part 2:
Inductive voltage transformers
Numéro de référence
Reference number
CEI/IEC 60044-2:1997+A1:2000
Numérotation des publications Publication numbering
Depuis le 1er janvier 1997, les publications de la CEI As from 1 January 1997 all IEC publications are
sont numérotées à partir de 60000. Ainsi, la CEI 34-1 issued with a designation in the 60000 series. For
devient la CEI 60034-1. example, IEC 34-1 is now referred to as IEC 60034-1.
Editions consolidées Consolidated editions
Les versions consolidées de certaines publications de la The IEC is now publishing consolidated versions of its
CEI incorporant les amendements sont disponibles. Par publications. For example, edition numbers 1.0, 1.1
exemple, les numéros d’édition 1.0, 1.1 et 1.2 indiquent and 1.2 refer, respectively, to the base publication,
respectivement la publication de base, la publication de the base publication incorporating amendment 1 and
base incorporant l’amendement 1, et la publication de the base publication incorporating amendments 1
base incorporant les amendements 1 et 2. and 2.
Informations supplémentaires Further information on IEC publications
sur les publications de la CEI
Le contenu technique des publications de la CEI est The technical content of IEC publications is kept
constamment revu par la CEI afin qu'il reflète l'état under constant review by the IEC, thus ensuring that
actuel de la technique. Des renseignements relatifs à the content reflects current technology. Information
cette publication, y compris sa validité, sont dispo- relating to this publication, including its validity, is
nibles dans le Catalogue des publications de la CEI available in the IEC Catalogue of publications
(voir ci-dessous) en plus des nouvelles éditions, (see below) in addition to new editions, amendments
amendements et corrigenda. Des informations sur les and corrigenda. Information on the subjects under
sujets à l’étude et l’avancement des travaux entrepris consideration and work in progress undertaken by the
par le comité d’études qui a élaboré cette publication, technical committee which has prepared this
ainsi que la liste des publications parues, sont publication, as well as the list of publications issued,
également disponibles par l’intermédiaire de: is also available from the following:
• Site web de la CEI (www.iec.ch) • IEC Web Site (www.iec.ch)
• Catalogue des publications de la CEI • Catalogue of IEC publications
Le catalogue en ligne sur le site web de la CEI The on-line catalogue on the IEC web site
(www.iec.ch/catlg-f.htm) vous permet de faire des (www.iec.ch/catlg-e.htm) enables you to search
recherches en utilisant de nombreux critères, by a variety of criteria including text searches,
comprenant des recherches textuelles, par comité technical committees and date of publication. On-
d’études ou date de publication. Des informations line information is also available on recently
en ligne sont également disponibles sur les issued publications, withdrawn and replaced
nouvelles publications, les publications rempla- publications, as well as corrigenda.
cées ou retirées, ainsi que sur les corrigenda.
• IEC Just Published
• IEC Just Published
Ce résumé des dernières publications parues
This summary of recently issued publications
(www.iec.ch/JP.htm) est aussi disponible par
(www.iec.ch/JP.htm) is also available by email.
courrier électronique. Veuillez prendre contact
Please contact the Customer Service Centre (see
avec le Service client (voir ci-dessous) pour plus
below) for further information.
d’informations.
• Service clients
• Customer Service Centre
Si vous avez des questions au sujet de cette
If you have any questions regarding this
publication ou avez besoin de renseignements
publication or need further assistance, please
supplémentaires, prenez contact avec le Service
contact the Customer Service Centre:
clients:
Email: custserv@iec.ch
Email: custserv@iec.ch
Tél: +41 22 919 02 11
Tel: +41 22 919 02 11
Fax: +41 22 919 03 00
Fax: +41 22 919 03 00
.
NORME CEI
INTERNATIONALE IEC
60044-2
INTERNATIONAL
Edition 1.1
STANDARD
2000-11
Edition 1:1997 consolidée par l'amendement 1:2000
Edition 1:1997 consolidated with amendment 1:2000
Transformateurs de mesure –
Partie 2:
Transformateurs inductifs de tension
Instrument transformers –
Part 2:
Inductive voltage transformers
 IEC 2000 Droits de reproduction réservés  Copyright - all rights reserved
Aucune partie de cette publication ne peut être reproduite ni No part of this publication may be reproduced or utilized in
utilisée sous quelque forme que ce soit et par aucun procédé, any form or by any means, electronic or mechanical,
électronique ou mécanique, y compris la photocopie et les including photocopying and microfilm, without permission in
microfilms, sans l'accord écrit de l'éditeur. writing from the publisher.
International Electrotechnical Commission 3, rue de Varembé Geneva, Switzerland
Telefax: +41 22 919 0300 e-mail: inmail@iec.ch IEC web site http://www.iec.ch
CODE PRIX
Commission Electrotechnique Internationale
CM
PRICE CODE
International Electrotechnical Commission
Pour prix, voir catalogue en vigueur
For price, see current catalogue

– 2 – 60044-2  CEI:1997+A1:2000
SOMMAIRE
Pages
AVANT-PROPOS . 8
Articles
1 Généralités .10
1.1 Domaine d'application . 10
1.2 Références normatives . 10
2 Définitions. 12
2.1 Définitions générales. 12
2.2 Définitions complémentaires pour les transformateurs inductifs
de tension monophasés pour protection . 20
3 Prescriptions générales . 20
4 Conditions de service normales et spéciales. 20
4.1 Conditions de service normales. 20
4.2 Conditions de service spéciales. 22
4.3 Installations de mise à la terre. 24
5 Valeurs normales . 24
5.1 Valeurs normales des tensions assignées . 24
5.2 Valeurs normales de la puissance de précision. 26
5.3 Valeurs normales du facteur de tension assigné . 26
5.4 Limites d'échauffement . 28
6 Prescriptions relatives à la conception. 30
6.1 Prescriptions relatives à l'isolement. 30
6.2 Tenue au court-circuit . 38
6.3 Prescriptions mécaniques . 40
7 Classification des essais . 40
7.1 Essais de type. 42
7.2 Essais individuels. 42
7.3 Essais spéciaux . 42
8 Essais de type. 44
8.1 Essai d'échauffement . 44
8.2 Essai de tenue au court-circuit . 44
8.3 Essai au choc sur l'enroulement primaire. 46
8.4 Essai sous pluie pour les transformateurs du type extérieur. 48
8.5 Mesure des perturbations radioélectriques . 50
9 Essais individuels. 52
9.1 Vérification du marquage des bornes. 52
9.2 Essais de tenue à fréquence industrielle sur les enroulements primaires
et mesure des décharges partielles . 54
9.3 Essais de tenue à fréquence industrielle entre sections et sur
les enroulements secondaires . 58
10 Essais spéciaux . 58
10.1 Essai au choc coupé sur l'enroulement primaire . 58
10.2 Mesure de la capacité et du facteur de dissipation diélectrique . 60
10.3 Essais mécaniques . 60

60044-2  IEC:1997+A1:2000 – 3 –
CONTENTS
Page
FOREWORD . 9
Clause
1 General. 11
1.1 Scope . 11
1.2 Normative references. 11
2 Definitions. 13
2.1 General definitions . 13
2.2 Additional definitions for single-phase inductive protective
voltage transformers . 21
3 General requirements. 21
4 Normal and special service conditions . 21
4.1 Normal service conditions . 21
4.2 Special service conditions . 23
4.3 System earthing . 25
5 Ratings . 25
5.1 Standard values of rated voltages. 25
5.2 Standard values of rated output. 27
5.3 Standard values of rated voltage factor. 27
5.4 Limits of temperature rise. 29
6 Design requirements . 31
6.1 Insulation requirements . 31
6.2 Short-circuit withstand capability . 39
6.3 Mechanical requirements . 41
7 Classification of tests . 41
7.1 Type tests . 43
7.2 Routine tests. 43
7.3 Special tests . 43
8 Type tests . 45
8.1 Temperature-rise test. 45
8.2 Short-circuit withstand capability test. 45
8.3 Impulse test on primary winding . 47
8.4 Wet test for outdoor type transformers . 49
8.5 Radio interference voltage measurement. 51
9 Routine tests.53
9.1 Verification of terminal markings . 53
9.2 Power-frequency withstand tests on primary windings
and partial discharge measurement. 55
9.3 Power-frequency withstand tests between sections and on secondary windings . 59
10 Special tests . 59
10.1 Chopped impulse test on primary winding. 59
10.2 Measurement of capacitance and dielectric dissipation factor . 61
10.3 Mechanical tests . 61

– 4 – 60044-2  CEI:1997+A1:2000
Articles Pages
11 Marquage. 64
11.1 Marquage de la plaque signalétique . 64
11.2 Marquage des bornes. 64
12 Prescriptions pour la précision des transformateurs inductifs
de tension monophasés pour mesures. 66
12.1 Désignation de la classe de précision d’un transformateur
de tension pour mesures. 66
12.2 Limites de l'erreur de tension et du déphasage des transformateurs de
tension pour mesures. 66
12.3 Essais de type concernant la précision des transformateurs
de tension pour mesures . 68
12.4 Essais individuels concernant la précision des transformateurs
de tension pour mesures . 68
12.5 Marquage de la plaque signalétique d'un transformateur de tension
pour mesures. 68
13 Prescriptions complémentaires pour les transformateurs inductifs
de tension monophasés pour protection. 68
13.1 Désignation de la classe de précision d’un transformateur de tension
pour protection. 68
13.2 Limites de l'erreur de tension et du déphasage des transformateurs
de tension pour protection . 70
13.3 Tensions assignées de l’enroulement secondaire de tension résiduelle. 70
13.4 Puissance de l’enroulement secondaire de tension résiduelle . 72
13.5 Classe de précision de l’enroulement secondaire de tension résiduelle . 72
13.6 Essais de type concernant les transformateurs de tension pour protection . 72
13.7 Essais individuels concernant les transformateurs de tension pour protection . 74
13.8 Marquage de la plaque signalétique d'un transformateur de tension
pour protection. 74
Figure 1 – Facteur correctif pour l'altitude . 76
Figure 2 – Circuit d’essai pour la mesure des décharges partielles. 78
Figure 3 – Variante de circuit d’essai pour la mesure des décharges partielles . 78
Figure 4 – Exemple de circuit d’essai équilibré pour la mesure des décharges partielles . 80
Figure 5 – Exemple de circuit d’étalonnage pour la mesure des décharges partielles. 80
Figure 6 – Transformateur monophasé avec bornes primaires totalement isolées
et un seul circuit secondaire . 82
Figure 7 – Transformateur monophasé avec une borne primaire neutre à isolement réduit
et un seul circuit secondaire . 8 2
Figure 8 – Ensemble triphasé avec un seul circuit secondaire . 82
Figure 9 – Transformateur monophasé avec deux circuits secondaires . 84
Figure 10 – Ensemble triphasé avec deux circuits secondaires . 84
Figure 11 – Transformateur monophasé avec un circuit secondaire à prises multiples. 84
Figure 12 – Ensemble triphasé avec un circuit secondaire à prises multiples . 84
Figure 13 – Transformateur monophasé avec deux circuits secondaires
à prises multiples . . 86
Figure 14 – Transformateur monophasé avec un enroulement de tension résiduelle. 86
Figure 15 – Transformateur triphasé avec enroulement de tension résiduelle. 86
Figure 16 – Exemple type de plaque signalétique. 88
Figure 17 – Circuit de mesure. 52

60044-2  IEC:1997+A1:2000 – 5 –
Clause Page
11 Markings . 65
11.1 Rating plate markings . 65
11.2 Terminal markings . 65
12 Accuracy requirements for single-phase inductive measuring voltage transformers . 67
12.1 Accuracy class designation for measuring voltage transformers. 67
12.2 Limits of voltage error and phase displacement for
measuring voltage transformers . 67
12.3 Type tests for accuracy of measuring voltage transformers. 69
12.4 Routine tests for accuracy of measuring voltage transformers . 69
12.5 Marking of the rating plate of a measuring voltage transformer . 69
13 Additional requirements for single-phase inductive protective voltage transformers . 69
13.1 Accuracy class designation for protective voltage transformers. 69
13.2 Limits of voltage error and phase displacement for
protective voltage transformers . 71
13.3 Rated voltages for secondary windings intended to produce a residual voltage. 71
13.4 Output for secondary windings intended to produce a residual voltage . 73
13.5 Accuracy class for secondary windings intended to produce a residual voltage . 73
13.6 Type tests for protective voltage transformers . 73
13.7 Routine tests for protective voltage transformers . 75
13.8 Marking of the rating plate of a protective voltage transformer . 75
Figure 1 – Altitude correction factor . 77
Figure 2 – Test circuit for partial discharge measurement . 79
Figure 3 – Alternative circuit for partial discharge measurement . 79
Figure 4 – Example of balanced test circuit for partial discharge measurement. 81
Figure 5 – Example of calibration circuit for partial discharge measurement . 81
Figure 6 – Single-phase transformer with fully insulated terminals and a single secondary. 83
Figure 7 – Single-phase transformer with a neutral primary terminal
with reduced insulation and a single secondary . 83
Figure 8 – Three-phase assembly with a single secondary . 83
Figure 9 – Single-phase transformer with two secondaries . 85
Figure 10 – Three-phase assembly with two secondaries . 85
Figure 11 – Single-phase transformer with one multi-tap secondary . 85
Figure 12 – Three-phase assembly with one multi-tap secondary. 85
Figure 13 – Single-phase transformer with two multi-tap secondaries . 87
Figure 14 – Single-phase transformer with one residual voltage winding. 87
Figure 15 – Three-phase transformer with one residual voltage winding . 87
Figure 16 – Example of a typical rating plate . 89
Figure 17 – Measuring circuit. 53

– 6 – 60044-2  CEI:1997+A1:2000
Pages
Tableau 1 – Catégories de température . 20
Tableau 2 – Valeurs normales du facteur de tension assigné . 28
Tableau 3 – Limites d'échauffement des enroulements . 30
Tableau 4 – Niveaux d'isolement assignés pour les enroulements primaires de
transformateur avec une tension la plus élevée pour le matériel U inférieure à 300 kV . 32
m
Tableau 5 – Niveaux d'isolement assignés pour les enroulements primaires
de transformateur avec une tension la plus élevée pour le matériel U égale
m
ou supérieure à 300 kV. 34
Tableau 6 – Tensions de tenue à fréquence industrielle pour les enroulements primaires
de transformateurs avec une tension la plus élevée pour le matériel U égale
m
ou supérieure à 300 kV. 34
Tableau 7 – Tensions d'essai de décharges partielles et niveaux admissibles . 36
Tableau 8 – Longueurs de la ligne de fuite. 38
Tableau 9 – Charges d'essai de tenue statique . 40
Tableau 10 – Modalités d’application des charges d’essai aux bornes primaires de ligne. 62
Tableau 11 – Limites de l’erreur de tension et du déphasage transformateurs
de tension pour mesures . 66
Tableau 12 – Limites de l'erreur de tension et du déphasage des transformateurs
de tension pour protection . 70
Tableau 13 – Tensions assignées de l'enroulement secondaire de tension résiduelle . 70

60044-2  IEC:1997+A1:2000 – 7 –
Page
Table 1 – Temperature categories . 21
Table 2 – Standard values of rated voltage factors . 29
Table 3 – Limits of temperature rise of windings. 31
Table 4 – Rated insulation levels for transformer primary windings having
highest voltage for equipment U < 300 kV. 33
m
Table 5 – Rated insulation levels for primary windings having highest voltage
for equipment U ≥ 300 kV . 35
m
Table 6 – Power-frequency withstand voltages for transformer primary windings
having voltage for equipment U ≥ 300 kV . 35
m
Table 7 – Partial discharge test voltages and permissible levels . 37
Table 8 – Creepage distances . 39
Table 9 – Static withstand test loads . 41
Table 10 – Modalities of application of the test loads to be applied to
the line primary terminals.63
Table 11 – Limits of voltage error and phase displacement measuring
voltage transformers. . 67
Table 12 – Limits of voltage error and phase displacement for protective
voltage transformers. . 71
Table 13 – Rated voltages for secondary intended to produce a residual voltage . 71

– 8 – 60044-2  CEI:1997+A1:2000
COMMISSION ÉLECTROTECHNIQUE INTERNATIONALE
____________
TRANSFORMATEURS DE MESURE –
Partie 2: Transformateurs inductifs de tension
AVANT-PROPOS
1) La CEI (Commission Électrotechnique Internationale) est une organisation mondiale de normalisation composée
de l'ensemble des comités électrotechniques nationaux (Comités nationaux de la CEI). La CEI a pour objet de
favoriser la coopération internationale pour toutes les questions de normalisation dans les domaines de
l'électricité et de l'électronique. A cet effet, la CEI, entre autres activités, publie des Normes internationales.
Leur élaboration est confiée à des comités d'études, aux travaux desquels tout Comité national intéressé par le
sujet traité peut participer. Les organisations internationales, gouvernementales et non gouvernementales, en
liaison avec la CEI, participent également aux travaux. La CEI collabore étroitement avec l'Organisation
Internationale de Normalisation (ISO), selon des conditions fixées par accord entre les deux organisations.
2) Les décisions ou accords officiels de la CEI concernant les questions techniques représentent, dans la mesure
du possible, un accord international sur les sujets étudiés, étant donné que les Comités nationaux intéressés
sont représentés dans chaque comité d’études.
3) Les documents produits se présentent sous la forme de recommandations internationales. Ils sont publiés
comme normes, spécifications techniques, rapports techniques ou guides et agréés comme tels par les Comités
nationaux.
4) Dans le but d'encourager l'unification internationale, les Comités nationaux de la CEI s'engagent à appliquer de
façon transparente, dans toute la mesure possible, les Normes internationales de la CEI dans leurs normes
nationales et régionales. Toute divergence entre la norme de la CEI et la norme nationale ou régionale
correspondante doit être indiquée en termes clairs dans cette dernière.
5) La CEI n’a fixé aucune procédure concernant le marquage comme indication d’approbation et sa responsabilité
n’est pas engagée quand un matériel est déclaré conforme à l’une de ses normes.
6) L’attention est attirée sur le fait que certains des éléments de la présente Norme internationale peuvent faire
l’objet de droits de propriété intellectuelle ou de droits analogues. La CEI ne saurait être tenue pour
responsable de ne pas avoir identifié de tels droits de propriété et de ne pas avoir signalé leur existence.
La Norme internationale CEI 60044-2 a été établie par le comité d'études 38 de la CEI:
Transformateurs de mesure.
La présente norme annule et remplace la deuxième édition de la CEI 60186 (1987), la modification 1
(1988) et l'amendement 2 (1995) seulement en ce qui concerne les transformateurs inductifs de
tension. La CEI 60186 reste encore en vigueur pour les transformateurs condensateurs de tension.
La présente version consolidée de la CEI 60044-2 est issue de la première édition (1997)
[documents 38/162/FDIS et 38/175/RVD], et de son amendement 1 (2000) [documents
38/244/FDIS et 38/254/RVD].
Elle porte le numéro d'édition 1.1.
Une ligne verticale dans la marge indique où la publication de base a été modifiée par
l'amendements 1.
Le comité a décidé que le contenu de la publication de base et de son amendement ne sera
pas modifié avant 2002. A cette date, la publication sera
• reconduite;
• supprimée;
• remplacée par une édition révisée, ou
• amendée.
60044-2  IEC:1997+A1:2000 – 9 –
INTERNATIONAL ELECTROTECHNICAL COMMISSION
____________
INSTRUMENT TRANSFORMERS –
Part 2: Inductive voltage transformers
FOREWORD
1) The IEC (International Electrotechnical Commission) is a worldwide organization for standardization comprising
all national electrotechnical committees (IEC National Committees). The object of the IEC is to promote
international co-operation on all questions concerning standardization in the electrical and electronic fields. To
this end and in addition to other activities, the IEC publishes International Standards. Their preparation is
entrusted to technical committees; any IEC National Committee interested in the subject dealt with may
participate in this preparatory work. International, governmental and non-governmental organizations liaising
with the IEC also participate in this preparation. The IEC collaborates closely with the International Organization
for Standardization (ISO) in accordance with conditions determined by agreement between the two
organizations.
2) The formal decisions or agreements of the IEC on technical matters express, as nearly as possible, an
international consensus of opinion on the relevant subjects since each technical committee has representation
from all interested National Committees.
3) The documents produced have the form of recommendations for international use and are published in the form
of standards, technical specifications, technical reports or guides and they are accepted by the National
Committees in that sense.
4) In order to promote international unification, IEC National Committees undertake to apply IEC International
Standards transparently to the maximum extent possible in their national and regional standards. Any
divergence between the IEC Standard and the corresponding national or regional standard shall be clearly
indicated in the latter.
5) The IEC provides no marking procedure to indicate its approval and cannot be rendered responsible for any
equipment declared to be in conformity with one of its standards.
6) Attention is drawn to the possibility that some of the elements of this International Standard may be the subject
of patent rights. The IEC shall not be held responsible for identifying any or all such patent rights.
International Standard IEC 60044-2 has been prepared by IEC technical committee 38:
Instrument transformers.
This standard cancels and replaces the second edition of IEC 60186 (1987), its amendment 1
(1988) and amendment 2 (1995) only as far as the inductive voltage transformers are
concerned. IEC 60186 remains in force for the capacitor voltage transformers.
This consolidated version of IEC 60044-2 is based on the first edition (1997) [documents
38/162/FDIS and 38/175/RVD], and its amendment 1 (2000) [documents 38/244/FDIS
and 38/254/RVD].
It bears the edition number 1.1.
A vertical line in the margin shows where the base publication has been modified by
amendment 1.
The committee has decided that the contents of the base publication and its amendment will
remain unchanged until 2002. At this date, the publication will be
• reconfirmed;
• withdrawn;
• replaced by a revised edition, or
• amended.
– 10 – 60044-2  CEI:1997+A1:2000
TRANSFORMATEURS DE MESURE –
Partie 2: Transformateurs inductifs de tension
1 Généralités
1.1 Domaine d'application
La présente partie de la CEI 60044 est applicable aux transformateurs inductifs neufs destinés
à être utilisés avec des appareils de mesure électriques et des dispositifs électriques de
protection, de fréquence comprise entre 15 Hz et 100 Hz.
Elle s’applique principalement aux transformateurs à enroulements séparés, mais elle est
valable aussi, dans la mesure du possible, pour les autotransformateurs. La présente norme
n'est pas applicable aux transformateurs utilisés dans les laboratoires.
NOTE Bien que la présente norme ne comporte aucun article relatif aux exigences particulières pour les
transformateurs triphasés, il a été estimé que les prescriptions générales des articles 3 à 11 pourraient leur être
applicables. C'est pourquoi l'on trouve dans ces articles quelques références à leur cas (voir 2.1.4, 5.1.1, 5.2, et 11.2).
L’article 13 comprend les prescriptions et les essais qui complètent, en ce qui concerne les
transformateurs de tension monophasés pour protection, ceux qui sont indiqués dans les
articles 3 à 12. Les prescriptions de l'article 13 se rapportent en particulier aux transformateurs
qui doivent avoir une précision pour actionner des systèmes de protection pour des tensions
apparaissant en cas de défauts.
1.2 Références normatives
Les documents normatifs suivants contiennent des dispositions qui, par suite de la référence
qui y est faite, constituent des dispositions valables pour la présente partie de la CEI 60044.
Au moment de la publication, les éditions indiquées étaient en vigueur. Tout document normatif
est sujet à révision et les parties prenantes aux accords fondés sur la présente partie de la
CEI 60044 sont invitées à rechercher la possibilité d’appliquer les éditions les plus récentes
des documents normatifs indiqués ci-après. Les membres de la CEI et de l’ISO possèdent le
registre des Normes internationales en vigueur.
CEI 60028:1925, Spécification internationale d'un cuivre-type recuit
CEI 60038:1983, Tensions normales de la CEI
CEI 60050(321):1986, Vocabulaire Electrotechnique International (VEI) – Chapitre 321:
Transformateurs de mesure
CEI 60060-1:1989, Techniques des essais à haute tension – Première partie: Définitions et
prescriptions générales relatives aux essais
CEI 60071-1:1993, Coordination de l'isolement – Partie 1: Définitions, principes et règles
CEI 60085:1984, Evaluation et classification thermiques de l'isolation électrique
CEI 60270:1981, Mesure des décharges partielles

60044-2  IEC:1997+A1:2000 – 11 –
INSTRUMENT TRANSFORMERS –
Part 2: Inductive voltage transformers
1 General
1.1 Scope
This part of IEC 60044 applies to new inductive voltage transformers for use with electrical
measuring instruments and electrical protective devices at frequencies from 15 Hz to 100 Hz.
Although this standard relates basically to transformers with separate windings, it is also
applicable, where appropriate, to auto-transformers. This standard does not apply to trans-
formers for use in laboratories.
NOTE Requirements specific to three-phase voltage transformers are not included in this standard but, so far as
they are relevant, the requirements in clauses 3 to 11 apply to these transformers and a few references to them are
included in those clauses (e.g. see 2.1.4, 5.1.1, 5.2, and 11.2).
Clause 13 covers the requirements and tests, in addition to those in clauses 3 to 12, that are
necessary for single-phase inductive protective voltage transformers. The requirements of
clause 13 apply particularly to transformers which are required to have sufficient accuracy to
operate protective systems at voltages that occur under fault conditions.
1.2 Normative references
The following normative documents contain provisions which, through reference in this text,
constitute provisions of this part of IEC 60044. At the time of publication, the editions indicated
were valid. All normative documents are subject to revision, and parties to agreements based
on this part of IEC 60044 are encouraged to investigate the possibility of applying the most
recent editions of the normative documents indicated below. Members of IEC and ISO maintain
registers of currently valid International Standards.
IEC 60028:1925, International standard of resistance for copper
IEC 60038:1983, IEC standard voltages
IEC 60050(321):1986, International Electrotechnical Vocabulary (IEV) – Chapter 321:
Instrument transformers
IEC 60060-1:1989, High-voltage test techniques – Part 1: General definitions and test
requirements
IEC 60071-1:1993, Insulation co-ordination – Part 1: Definitions, principles and rules
IEC 60085:1984, Thermal evaluation and classification of electrical insulation
IEC 60270:1981, Partial discharge measurements

– 12 – 60044-2  CEI:1997+A1:2000
CEI 60721: Classification des conditions d'environnement
CEI 60815:1986, Guide pour le choix des isolateurs sous pollution
CISPR 18-2:1986, Caractéristiques des lignes et des équipements à haute tension relatives
aux perturbations radioélectriques – Deuxième partie: Méthodes de mesure et procédure
d'établissement des limites
2 Définitions
Pour les besoins de la présente partie de la CEI 60044, les définitions suivantes s'appliquent.
2.1 Définitions générales
2.1.1
transformateur de mesure
transformateur destiné à alimenter des appareils de mesure, des compteurs, des relais et
autres appareils analogues
[VEI 321-01-01 modifiée]
2.1.2
transformateur de tension
transformateur de mesure dans lequel la tension secondaire est, dans les conditions normales
d'emploi, pratiquement proportionnelle à la tension primaire et déphasée par rapport à celle-ci
d'un angle voisin de zéro, pour un sens approprié des connexions
[VEI 321-03-01]
2.1.3
transformateur de tension non mis à la terre
transformateur de tension dont toutes les parties de l'enroulement primaire, y compris les
bornes, sont isolées par rapport à la terre à un niveau qui correspond à son niveau d'isolement
assigné
2.1.4
transformateur de tension mis à la terre
transformateur de tension monophasé destiné à avoir l'une des extrémités de son enroulement
primaire reliée directement à la terre ou transformateur de tension triphasé destiné à avoir le
point neutre de son enroulement primaire relié directement à la terre
2.1.5
enroulement primaire
enroulement auquel est appliquée la tension à transformer
2.1.6
enroulement secondaire
enroulement qui alimente les circuits de tension des appareils de mesure, des compteurs, des
relais et circuits analogues
2.1.7
circuit secondaire
circuit extérieur alimenté par l'enroulement secondaire d'un transformateur

60044-2  IEC:1997+A1:2000 – 13 –
IEC 60721: Classification of environmental conditions
IEC 60815:1986, Guide for the selection of insulators in respect of polluted conditions
CISPR 18-2:1986, Radio interference characteristics of overhead power lines and high-voltage
equipment – Part 2: Methods of measurement and procedure for determining limits
2 Definitions
For the purpose of this part of IEC 60044, the following definitions apply.
2.1 General definitions
2.1.1
instrument transformer
a transformer intended to supply measuring instruments, meters, relays and other similar
apparatus
[IEV 321-01-01 modified]
2.1.2
voltage transformer
an instrument transformer in which the secondary voltage, in normal conditions of use, is
substantially proportional to the primary voltage and differs in phase from it by an angle which
is approximately zero for an appropriate direction of the connections
[IEV 321-03-01]
2.1.3
unearthed voltage transformer
a voltage transformer which has all parts of its primary winding, including terminals, insulated
from earth to a level corresponding to its rated insulation level
2.1.4
earthed voltage transformer
a single-phase voltage transformer which is intended to have one end of its primary winding
directly earthed or a three-phase voltage transformer which is intended to have the star-point of
its primary winding directly earthed
2.1.5
primary winding
the winding to which the voltage to be transformed is applied
2.1.6
secondary winding
the winding which supplies the voltage circuits of measuring instruments, meters, relays or
similar apparatus
2.1.7
secondary circuit
the external circuit supplied by the secondary winding of a transformer

– 14 – 60044-2  CEI:1997+A1:2000
2.1.8
tension primaire assignée
valeur de la tension primaire qui figure dans la désignation du transformateur et d'après
laquelle sont déterminées ses conditions de fonctionnement
[VEI 321-01-12 modifiée]
2.1.9
tension secondaire assignée
valeur de la tension secondaire qui figure dans la désignation du transformateur et d'après
laquelle sont déterminées ses conditions de fonctionnement
[VEI 321-01-16 modifiée]
2.1.10
rapport de transformation
rapport de la tension primaire réelle à la tension secondaire réelle
[VEI 321-01-18 modifiée]
2.1.11
rapport de transformation assigné
rapport de la tension primaire assignée à la tension secondaire assi
...

Questions, Comments and Discussion

Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.

Loading comments...