Thermal insulation products for building equipment and industrial installations - Factory made flexible elastomeric foam (FEF) products - Specification

This European Standard specifies the requirements for factory made flexible elastomeric foam products which are used for the thermal insulation of building equipment and industrial installations with an operating temperature in the range of approximately - 200 °C to + 175 °C.
NOTE   Below an operating temperature of - 50 °C, tests regarding the suitability of the products in the intended application shall be performed. Manufacturer's advice should be heeded in all cases.
The products are manufactured in the form of sheets, tubes, rolls and tapes with or without coating and/or self-adhesive backing and/or different closure systems.
This European Standard describes product characteristics and includes procedures for testing, evaluation of conformity, marking and labelling.
Products covered by this standard are also used in prefabricated thermal insulation systems and composite panels; the performance of systems incorporating these products is not covered.
This European Standard does not specify the required level of a given property that shall be achieved by a product to demonstrate fitness for purpose in a particular application. The levels required for a given application can be found in regulations and invitations to tender.
Products with a declared thermal conductivity greater than 0,050 W/(m•K) at 10 °C are not covered by this standard.
This European Standard does not cover products for the insulation of the building structure.
The normative part of this standard does not cover compressive stress (see Annex D, Clause D.5).

Wärmedämmstoffe für die technische Gebäudeausrüstung und für betriebstechnische Anlagen in der Industrie - Werkmäßig hergestellte Produkte aus flexiblem Elastomerschaum (FEF) - Spezifikation

Diese Europäische Norm legt die Anforderungen für werkmäßig hergestellte Produkte aus flexiblem Elastomerschaum fest, die als Wärmedämmstoffe für die technische Gebäudeausrüstung und für betriebstechnische Anlagen in der Industrie im Temperaturbereich von etwa 200 °C bis 175 °C benutzt werden.
ANMERKUNG   Unterhalb einer Betriebstemperatur von 50 °C sind Prüfungen bezüglich der Eignung der Produkte für den beabsichtigten Anwendungsfall durchzuführen. In jedem Fall sollten die Empfehlungen des Herstellers beachtet werden.
Die Produkte werden in der Form von Platten, Schläuchen, Rollen und Bändern mit oder ohne Beschichtung und/oder Klebeschutzschicht und/oder verschiedene Verschlusssysteme hergestellt.
Diese Europäische Norm beschreibt die Produkteigenschaften und enthält die Prüfverfahren und Fest-legungen für die Konformitätsbewertung, die Kennzeichnung und die Etikettierung.
Die in dieser Norm beschriebenen Produkte werden auch in vorgefertigten Wärmedämmsystemen und Mehr-schicht-Verbundplatten angewendet; die Eigenschaften von Systemen, in die diese Produkte integriert sind, werden nicht behandelt.
Diese Europäische Norm legt keine Leistungsstufen für eine vorgegebene Eigenschaft fest, die ein Produkt erreichen muss, um für einen bestimmten Anwendungsfall tauglich zu sein. Für bestimmte Anwendungen benötigte Stufen können Regelwerken oder Ausschreibungen entnommen werden.
Diese Europäische Norm gilt nicht für Produkte, deren Nennwert der Wärmeleitfähigkeit größer ist als 0,050 W/(mK) bei 10 °C.
Diese Europäische Norm gilt nicht für Produkte, die zur Dämmung des Bauwerks bestimmt sind.
Die Druckspannung wird im normativen Teil dieser Norm nicht behandelt (siehe Anhang D, D.5).

Produits isolants thermiques pour l'équipement du bâtiment et les installations industrielles - Produits manufacturés en mousse élastomère flexible (FEF) - Spécification

La présente Norme européenne spécifie les exigences relatives aux produits manufacturés en mousse élastomère flexible, utilisés pour l’isolation thermique de l’équipement du bâtiment et des installations industrielles, dont la température de service est approximativement comprise entre – 200 °C et + 175 °C.
NOTE 1   En cas de température de service inférieure à – 50 °C, des essais sur l’aptitude des produits à l’utilisation prévue doivent être réalisés. Il convient de se référer systématiquement aux conseils du fabricant.
Les produits sont manufacturés sous la forme de feuilles, de tubes, de rouleaux, et de rubans avec ou sans enduit de finition et/ou envers autocollant et/ou différents systèmes de fermeture.
La présente Norme européenne décrit les caractéristiques de ces produits et comporte des modes opératoires d’essai, d’évaluation de conformité, de marquage et d’étiquetage.
Les produits couverts par la présente norme sont également utilisés dans les systèmes d’isolation thermique préfabriqués et les panneaux composites ; les performances des systèmes incorporant ces produits ne sont pas traitées.
La présente Norme européenne ne spécifie pas le niveau requis pour une propriété donnée que doit posséder un produit pour démontrer son aptitude à une application particulière. Les niveaux requis pour une application donnée peuvent être trouvés dans les réglementations et les appels d’offre.
Les produits dont la conductivité thermique déclarée est supérieure à 0,050 W/(m•K) à 10 °C ne sont pas couverts par la présente norme.
La présente Norme européenne ne couvre pas les produits pour l’isolation des structures de bâtiments.
La partie normative de la présente norme ne couvre pas la contrainte en compression (voir Annexe D, D.5).

Toplotnoizolacijski proizvodi za opremo stavb in industrijske inštalacije - Proizvodi iz fleksibilne elastomerne pene (FEF) - Specifikacija

Ta evropski standard določa zahteve za proizvode iz fleksibilne elastomerne pene, ki se uporabljajo za toplotno izolacijo opreme stavb in industrijskih inštalacij z razponom delovne temperature približno od –200 °C do 175 °C. OPOMBA Pod delovno temperaturo –50 °C se izvajajo preskusi v zvezi z ustreznostjo proizvodov za nameravano uporabo. V vseh primerih je treba upoštevati napotke proizvajalca. Proizvodi so izdelani v obliki plošč, cevi, kolutov in trakov z ali brez laka in/ali samolepilne zadnje strani in/ali z različnimi sistemi zapiranja. Ta evropski standard opisuje lastnosti proizvodov ter zajema postopke za preskušanje, vrednotenje skladnosti, označevanje in etiketiranje. Proizvodi iz tega standarda se uporabljajo tudi v predizdelanih sistemih toplotne izolacije in vezanih ploščah; lastnosti sistemov iz teh proizvodov niso opisane. Ta evropski standard ne določa zahtevane ravni določene lastnosti, ki jo mora proizvod doseči, da se dokaže njegova primernost namenu za posamezno vrsto uporabe. Zahtevane ravni za posamezno uporabo so določene v uredbah in javnih razpisih. Proizvodi z deklarirano toplotno prevodnostjo, višjo od 0,050 W/mK pri 10 °C, v tem standardu niso zajeti. Ta evropski standard ne zajema proizvodov za izolacijo stavbne strukture. Normativen del tega standarda ne zajema tlačne napetosti (glej dodatek D, D.5).

General Information

Status
Withdrawn
Publication Date
29-Jan-2013
Withdrawal Date
13-Apr-2025
Current Stage
9960 - Withdrawal effective - Withdrawal
Start Date
09-Dec-2015
Completion Date
14-Apr-2025

Relations

Effective Date
19-Jan-2023
Effective Date
24-Oct-2012
Effective Date
16-Dec-2015
Standard

EN 14304:2010+A1:2013

English language
37 pages
Preview
Preview
e-Library read for
1 day

Frequently Asked Questions

EN 14304:2009+A1:2013 is a standard published by the European Committee for Standardization (CEN). Its full title is "Thermal insulation products for building equipment and industrial installations - Factory made flexible elastomeric foam (FEF) products - Specification". This standard covers: This European Standard specifies the requirements for factory made flexible elastomeric foam products which are used for the thermal insulation of building equipment and industrial installations with an operating temperature in the range of approximately - 200 °C to + 175 °C. NOTE Below an operating temperature of - 50 °C, tests regarding the suitability of the products in the intended application shall be performed. Manufacturer's advice should be heeded in all cases. The products are manufactured in the form of sheets, tubes, rolls and tapes with or without coating and/or self-adhesive backing and/or different closure systems. This European Standard describes product characteristics and includes procedures for testing, evaluation of conformity, marking and labelling. Products covered by this standard are also used in prefabricated thermal insulation systems and composite panels; the performance of systems incorporating these products is not covered. This European Standard does not specify the required level of a given property that shall be achieved by a product to demonstrate fitness for purpose in a particular application. The levels required for a given application can be found in regulations and invitations to tender. Products with a declared thermal conductivity greater than 0,050 W/(m•K) at 10 °C are not covered by this standard. This European Standard does not cover products for the insulation of the building structure. The normative part of this standard does not cover compressive stress (see Annex D, Clause D.5).

This European Standard specifies the requirements for factory made flexible elastomeric foam products which are used for the thermal insulation of building equipment and industrial installations with an operating temperature in the range of approximately - 200 °C to + 175 °C. NOTE Below an operating temperature of - 50 °C, tests regarding the suitability of the products in the intended application shall be performed. Manufacturer's advice should be heeded in all cases. The products are manufactured in the form of sheets, tubes, rolls and tapes with or without coating and/or self-adhesive backing and/or different closure systems. This European Standard describes product characteristics and includes procedures for testing, evaluation of conformity, marking and labelling. Products covered by this standard are also used in prefabricated thermal insulation systems and composite panels; the performance of systems incorporating these products is not covered. This European Standard does not specify the required level of a given property that shall be achieved by a product to demonstrate fitness for purpose in a particular application. The levels required for a given application can be found in regulations and invitations to tender. Products with a declared thermal conductivity greater than 0,050 W/(m•K) at 10 °C are not covered by this standard. This European Standard does not cover products for the insulation of the building structure. The normative part of this standard does not cover compressive stress (see Annex D, Clause D.5).

EN 14304:2009+A1:2013 is classified under the following ICS (International Classification for Standards) categories: 91.100.60 - Thermal and sound insulating materials. The ICS classification helps identify the subject area and facilitates finding related standards.

EN 14304:2009+A1:2013 has the following relationships with other standards: It is inter standard links to EN 14304:2009, EN 14304:2009/FprA1, EN 14304:2015. Understanding these relationships helps ensure you are using the most current and applicable version of the standard.

EN 14304:2009+A1:2013 is associated with the following European legislation: EU Directives/Regulations: 305/2011, 89/106/EEC; Standardization Mandates: M/103. When a standard is cited in the Official Journal of the European Union, products manufactured in conformity with it benefit from a presumption of conformity with the essential requirements of the corresponding EU directive or regulation.

EN 14304:2009+A1:2013 is available in PDF format for immediate download after purchase. The document can be added to your cart and obtained through the secure checkout process. Digital delivery ensures instant access to the complete standard document.

Standards Content (Sample)


2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.Toplotnoizolacijski proizvodi za opremo stavb in industrijske inštalacije - Proizvodi iz fleksibilne elastomerne pene (FEF) - SpecifikacijaWärmedämmstoffe für die technische Gebäudeausrüstung und für betriebstechnische Anlagen in der Industrie - Werkmäßig hergestellte Produkte aus flexiblem Elastomerschaum (FEF) - SpezifikationProduits isolants thermiques pour l'équipement du bâtiment et les installations industrielles - Produits manufacturés en mousse élastomère flexible (FEF) - SpécificationThermal insulation products for building equipment and industrial installations - Factory made flexible elastomeric foam (FEF) products - Specification91.100.60Thermal and sound insulating materialsICS:Ta slovenski standard je istoveten z:EN 14304:2009+A1:2013SIST EN 14304:2010+A1:2013en,fr,de01-maj-2013SIST EN 14304:2010+A1:2013SLOVENSKI
STANDARDSIST EN 14304:20101DGRPHãþD

EUROPEAN STANDARD NORME EUROPÉENNE EUROPÄISCHE NORM
EN 14304:2009+A1
January 2013 ICS 91.100.60 Supersedes EN 14304:2009English Version
Thermal insulation products for building equipment and industrial installations - Factory made flexible elastomeric foam (FEF) products - Specification
Produits isolants thermiques pour l'équipement du bâtiment et les installations industrielles - Produits manufacturés en mousse élastomère flexible (FEF) - Spécification
Wärmedämmstoffe für die technische Gebäudeausrüstung und für betriebstechnische Anlagen in der Industrie - Werkmäßig hergestellte Produkte aus flexiblem Elastomerschaum (FEF) - Spezifikation This European Standard was approved by CEN on 29 September 2009 and includes Amendment 1 approved by CEN on 11 November 2012.
CEN members are bound to comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this European Standard the status of a national standard without any alteration. Up-to-date lists and bibliographical references concerning such national standards may be obtained on application to the CEN-CENELEC Management Centre or to any CEN member.
This European Standard exists in three official versions (English, French, German). A version in any other language made by translation under the responsibility of a CEN member into its own language and notified to the CEN-CENELEC Management Centre has the same status as the official versions.
CEN members are the national standards bodies of Austria, Belgium, Bulgaria, Croatia, Cyprus, Czech Republic, Denmark, Estonia, Finland, Former Yugoslav Republic of Macedonia, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland, Turkey and United Kingdom.
EUROPEAN COMMITTEE FOR STANDARDIZATION
COMITÉ EUROPÉEN DE NORMALISATION EUROPÄISCHES KOMITEE FÜR NORMUNG
Management Centre:
Avenue Marnix 17,
B-1000 Brussels © 2013 CEN All rights of exploitation in any form and by any means reserved worldwide for CEN national Members. Ref. No. EN 14304:2009+A1:2013: ESIST EN 14304:2010+A1:2013

Factory production control . 20 Annex B (normative)
Determination of minimum service temperature . 22 Annex C (normative)
Thermal conductivity measurement . 25 Annex D (informative)
Additional properties . 26 Annex ZA (informative)
Clauses of this European Standard addressing the provisions of the EU Construction Products Directive . 28 Bibliography . 37
Figures Figure ZA.1 — Example of CE marking information . 36
Tables Table 1 — Dimensional tolerances . 11 Table 2 — Test methods, specimens and conditions . 15 Table A.1 — Minimum product testing frequencies . 20 Table A.2 — Minimum product testing frequencies for the reaction to fire characteristics . 21 Table D.1 — Test methods, specimens and conditions . 27 Table ZA.1 — Relevant clauses . 29 Table ZA.2 — System(s) of attestation of conformity . 31 Table ZA.3 — Assignment of evaluation of conformity tasks for products under system 1 . 32 Table ZA.4 — Assignment of evaluation of conformity tasks for products under system 3 or system 3 combined with system 4 for reaction to fire . 33
Locally responsible authorities and contracting entities, who are bound by EU Directives to specify their requirements using European harmonized product standards, are allowed to demand additional properties outside the provisions of this standard if this is technically necessary because of prevailing operational conditions of the building equipment or the industrial installation projected or because of safety regulations. This European Standard contains five annexes:  Annex A (normative), Factory production control  Annex B (normative), Determination of minimum service temperature  Annex C (normative), Thermal conductivity measurement  Annex D (informative), Additional properties  Annex ZA (informative), Clauses of this European Standard addressing the provisions of the EU Construction Products Directive This document includes a bibliography. This European Standard is one of a series of standards for insulation products used in building equipment and industrial installations, but this standard can be used in other areas, where appropriate. In pursuance of Resolution BT 20/1993 revised, CEN/TC 88 have proposed defining the standards listed below as a European package of standards, setting (21 months after availability) as the date of withdrawal (dow) of national standards which conflict with the European standards of this package. The package of standards comprises the following group of interrelated standards for the specifications of factory made thermal insulation products, all of which come within the scope of CEN/TC 88: SIST EN 14304:2010+A1:2013

— Specification EN 14313, Thermal insulation products for building equipment and industrial installations — Factory made polyethylene foam (PEF) products — Specification EN 14314, Thermal insulation products for building equipment and industrial installations — Factory made phenolic foam (PF) products — Specification According to the CEN/CENELEC Internal Regulations, the national standards organizations of the following countries are bound to implement this European Standard: Austria, Belgium, Bulgaria, Croatia, Cyprus, Czech Republic, Denmark, Estonia, Finland, Former Yugoslav Republic of Macedonia, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland, Turkey and the United Kingdom.
NOTE Below an operating temperature of - 50 °C, tests regarding the suitability of the products in the intended application shall be performed. Manufacturer's advice should be heeded in all cases. The products are manufactured in the form of sheets, tubes, rolls and tapes with or without coating and/or self-adhesive backing and/or different closure systems. This European Standard describes product characteristics and includes procedures for testing, evaluation of conformity, marking and labelling. Products covered by this standard are also used in prefabricated thermal insulation systems and composite panels; the performance of systems incorporating these products is not covered. This European Standard does not specify the required level of a given property that shall be achieved by a product to demonstrate fitness for purpose in a particular application. The levels required for a given application can be found in regulations and invitations to tender. Products with a declared thermal conductivity greater than 0,050 W/(m·K) at 10 °C are not covered by this standard. This European Standard does not cover products for the insulation of the building structure. The normative part of this standard does not cover compressive stress (see Annex D, D.5). 2 Normative references The following referenced documents are indispensable for the application of this document. For dated references, only the edition cited applies. For undated references, the latest edition of the referenced document (including any amendments) applies. EN 822, Thermal insulating products for building applications — Determination of length and width EN 823, Thermal insulating products for building applications — Determination of thickness EN 824, Thermal insulating products for building applications — Determination of squareness EN 1604, Thermal insulating products for building applications — Determination of dimensional stability under specified temperature and humidity conditions EN 1609, Thermal insulating products for building applications — Determination of short term water absorption by partial immersion EN 12085, Thermal insulating products for building applications — Determination of linear dimensions of test specimens EN 12086, Thermal insulating products for building applications — Determination of water vapour transmission properties EN 12667, Thermal performance of building materials and products — Determination of thermal resistance by means of guarded hot plate and heat flow meter methods — Products of high and medium thermal resistance SIST EN 14304:2010+A1:2013

EN ISO 354, Acoustics — Measurement of sound absorption in a reverberation room (ISO 354:2003) EN ISO 3822-1, Acoustics — Laboratory tests on noise emission from appliances and equipment used in water supply installations — Part 1: Method of measurement (ISO 3822-1:1999) EN ISO 4589-1, Plastics — Determination of burning behaviour by oxygen index — Part 1: Guidance
(ISO 4589-1:1996) EN ISO 8497, Thermal insulation — Determination of steady-state thermal transmission properties of thermal insulation for circular pipes (ISO 8497:1994) EN ISO 11654, Acoustics — Sound absorbers for use in buildings — Rating of sound absorption
(ISO 11654:1997) EN ISO 11925-2, Reaction to fire tests — Ignitability of building products subjected to direct impingement of flame — Part 2: Single-flame source test (ISO 11925-2:2002) EN ISO 13787, Thermal insulation products for building equipment and industrial installations — Determination of declared thermal conductivity (ISO 13787:2003) SIST EN 14304:2010+A1:2013

3.1.1.5 thermal insulation process of reducing heat transfer through a system, or to describe a product, component or system which performs that function
3.1.1.6 test specimen single item within a sample or part of an item used for a test
3.1.1.7 Initial Type Test
ITT test(s) performed on a product prior to commencing normal production to prove that the product is capable of conforming to the relevant requirements of a standard
3.1.1.8 building equipment system incorporated in a permanent manner in construction works forming part of the heating, cooling and ventilation installation of those works
3.1.1.9 industrial installation plant and associated vessels, pipes, ducts etc. used by industry to manufacture or store a product or to transfer a fluid
3.1.2 Additional terms and definitions 3.1.2.1 sheet flexible insulation product of rectangular shape with or without facing or adhesive backing SIST EN 14304:2010+A1:2013

NOTE The level is given by the declared value of the characteristic concerned. 3.1.2.5 class combination of two levels of the same property between which the performance will fall 3.1.2.6 production line assemblage of equipment that produces products using a continuous process
3.1.2.7 production unit assemblage of equipment that produces products using a discontinuous process 3.2 Symbols, units and abbreviated terms 3.2.1 Symbols and units used in this standard αp is the practical sound absorption coefficient — αw is the weighted sound absorption coefficient — b is the width mm Di is the inside diameter mm Di,D is the declared inside diameter of a tube mm d is the thickness mm dD is the declared thickness of the product mm ∆εd is the relative change in thickness
% l is the length m or mm LSC,A is the single number descriptor of structure-borne sound
λ is the thermal conductivity W/(m·K) λD is the declared thermal conductivity W/(m·K) µ is the water vapour diffusion resistance factor — v is the deviation from squareness for tubes mm SIST EN 14304:2010+A1:2013

is the symbol of the declared level of soluble fluoride ions MU is the symbol of the declared level of water vapour diffusion resistance factor NA is the symbol of the declared level of soluble sodium ions pH is the symbol of the declared level of the pH-value SI is the symbol of the declared level of soluble silicate ions ST(+) is the symbol of the declared level for maximum service temperature ST(-) is the symbol of the declared level for minimum service temperature WS is the symbol of the declared level for short term water absorption 3.2.2 Abbreviated terms used in this standard FEF is Flexible Elastomeric Foam ITT is Initial Type Test ML is Manufacturer's Literature FPC is Factory Production Control 4 Requirements 4.1 General Product properties shall be assessed in accordance with Clause 5. To comply with this standard, products shall meet the requirements of 4.2, and the requirements of 4.3 as appropriate. NOTE Information on additional properties is given in Annex D. One test result for a product property is the average of the measured values on the number of test specimens given in Table 2. SIST EN 14304:2010+A1:2013

W/(m·K);  the lowest reference mean test temperature required is - 170 °C. The declared equation/limit curve is the "declared reference" with three significant figures, that is to 0,000 1 W/(m·K) for values below 0,1 W/(m·K) and in 0,001 W/(m·K) for values above 0,1 W/(m·K). This shall be used as a reference for the verification of the declaration. When thermal conductivity is declared as table derived from the equation, rounding upwards to the next 0,001 W/(m·K) has to be done for the full range of the thermal conductivity. NOTE Determinations of the declared thermal conductivity of pipe sections, following EN ISO 8497 having joints in the metering area, include joints as defined in EN ISO 23993. 4.2.2 Dimensions and tolerances 4.2.2.1 Linear dimensions The length, l, width, b, and thickness, d, of sheets, rolls and tapes shall be determined in accordance with EN 822 and EN 823. The length, l, thickness, d, and inside diameter, Di, of tubes shall be determined in accordance with EN 13467. No test result shall deviate from the declared values by more than the tolerances given in Table 1. 4.2.2.2 Squareness Deviation from squareness, Sb, of sheets and rolls shall be determined in accordance with EN 824. Deviation from squareness, v, of tubes shall be determined in accordance with EN 13467. No test result shall deviate from the declared values by more than the tolerances given in Table 1.
Table 1 — Dimensional tolerances Dimensions in millimetres Form of delivery Length Width Thickness Squareness Inside diameter declared tolerance Di ≤ 100 Di > 100 Tubes ± 1,5 % _ dD ≤ 8 8 < dD ≤ 18 18 < dD ≤ 31 dD > 31 ± 1 ± 1,5 ± 2,5 ± 3 3,0 mm Di,D + 1 ≤ Di ≤ Di,D + 4
Di,D + 1 ≤ Di ≤ Di,D + 6 Sheets ± 1,5 % ± 2 % dD ≤ 6
6 < dD ≤ 19 dD > 19 ± 1
± 1,5 ± 2 3,0 mm/m (length/width) – 3,0 mm (thickness) _ _ Rolls + 5 % -1,5 % ± 2 % dD ≤ 6
6 < dD ≤ 19 dD > 19 ± 1
± 1,5 ± 2 3,0 mm/m (length/width) – 3,0 mm (thickness) _ _ Tapes + 5 % -1,5 % ± 2 % dD = 3 – 0,1 + 1,5 _ _ _
4.2.3 Dimensional stability
Dimensional stability under specified temperature and humidity conditions shall be determined in accordance with EN 1604. The test shall be carried out after storage for 48 h at (23 ± 2) °C and (90 ± 5) % relative humidity. The relative reduction in thickness, ∆εd, shall not exceed 3,0 %. The relative changes in length, ∆εl, and width, ∆εb, shall not exceed 2,0 %. This test shall not be performed when the more severe test, described in 4.3.2 is used. 4.2.4 Reaction to fire of the product as placed on the market Reaction to fire classification of the product, as placed on the market, shall be determined in accordance with EN 13501-1 and the basic Mounting and Fixing rules given in EN 15715:2009.
NOTE This classification is compulsory and always included in the CE marking label. EN 13501-1:2007, Table 1, is applicable to products applied to flat surfaces or to curved surfaces with a diameter greater than 300 mm. If a flat product which has a classification according to EN 13501-1:2007, Table 1, is used in a linear application it does not require further classification. EN 13501-1:2007, Table 3, is applicable for products applied on linear objects or with a diameter below or equal 300 mm. SIST EN 14304:2010+A1:2013

At the maximum service temperature, ST(+), the mean value of relative change in thickness (reduction), ∆εd shall not exceed 7 %. The maximum service temperature, ST(+), shall be declared below 100 °C in steps of not less than 5 °C and above 100 °C in steps of not less than 10 °C. 4.3.3 Minimum service temperature The manufacturer of an insulation material can choose which minimum service temperature he intends to declare for his product.
This minimum service temperature does not represent any specific physical property and can not be determined by any single standardized test method.
If a minimum service temperature is declared by the manufacturer the following physical properties in line with European test standards have to be declared at the declared minimum service temperature:
a) Thermal conductivity as a function of temperature;
Other physical properties may be agreed upon by the concerned parties in addition.
Using these temperature dependent physical data, the suitability of any specific insulation can be estimated at a given low operational temperature for industrial installations in relation to application related design features.
A low operational temperature cannot be below the minimum service temperature. The minimum service temperature, ST(-), shall be declared in levels with steps of 10 °C. Minimum service temperature within the scope of this standard but above 0 °C need not be tested. 4.3.4 Water absorption Short term water absorption by partial immersion, Wp, shall be determined in accordance with EN 1609 for sheets and rolls or by EN 13472 for tubes. Tests shall be run with specimens of ≥ 15 mm thickness from one sample each being representative for flat products and tubes. No test results of the water absorption Wp, shall exceed 0,1 kg/m2 (WS01). 4.3.5 Water vapour diffusion resistance The water vapour transmission properties shall be determined in accordance with EN 12086 for flat products and in accordance with EN 13469 for tubes and declared as the water vapour diffusion resistance factor, µ. The Water vapour diffusion resistance factor (µ.) shall be declared in levels (MU) with steps of 1 000 up to a value of 15 000. No value shall be less then the declared level (e.g. MU 1 000 (µ ≥ 1 000), MU 15 000 (µ ≥ 15 000) etc.). NOTE 1 The water vapour transmission property and the water vapour diffusion resistance factor, µ, are a function of temperature, see Annex D. NOTE 2 Alternatively, for the declaration of the water vapour transmission properties, the values quoted in
EN ISO 10456 may be used. 4.3.6 Trace quantities of water soluble ions and the pH-value Trace quantities of water soluble chloride, fluoride, silicate and sodium ions and the pH-value shall be determined in accordance with EN 13468. The manufacturer shall declare one or more as appropriate as levels in mg/kg of product and the pH-value as levels in steps of 0,5. For chloride and fluoride, no test result shall exceed the declared value. For silicate and sodium, no test result shall be below the declared value. For the pH-value, no test result shall deviate from the declared value by more than 1,0. NOTE
Due to the fact that traces of halogens may be found in halogen-free Flexible Elastomeric Foam material caused by the inevitable impureness of compounds, the term “halogen-free” should be determined according to DIN/VDE0472-815 (Testing of cables and insulated conductions – halogen-freeness): “plastic materials are halogen-free if the sum of their amount of chloride, bromine and iodine is less then 0,2 % and the amount of fluoride less then 0,1% by weight”. 4.3.7 Structure-borne sound transmission Structure-borne sound transmission shall be determined in accordance with EN 14366 and/or EN ISO 3822-1. SIST EN 14304:2010+A1:2013

2,0 l/s. For comparison the LSC,A of the uninsulated pipe shall also be declared. 4.3.8 Sound absorption The sound absorption coefficient shall be determined in accordance with EN ISO 354 but always without a plenum. The sound absorption characteristics shall be calculated in accordance with EN ISO 11654 using the values for the practical sound absorption coefficient, αp, at the frequencies 125 Hz, 250 Hz, 500 Hz, 1 000 Hz, 2 000 Hz and 4 000 Hz and the single number value for, αw (weighted sound absorption coefficient). αp and αw shall be rounded to the nearest 0,05 (αp > 1 shall be expressed as αp = 1) and declared in levels with steps of 0,05. No result of αp and αw shall be lower than the declared level. 4.3.9 Release of dangerous substances NOTE See Annex ZA. 4.3.10
Continuous glowing combustion Where subject to regulation a manufacturer shall declare the continuous glowing combustion according to national test method where available. NOTE
A European test method is under development and the standard will be amended when this is available. 5 Test methods 5.1 Sampling Flat test specimens shall be taken from the same sample with a total area of not less than 1 m2 or one full-sized sheet and sufficient to cover the needed tests. The shorter side of the sample shall not be less than 300 mm or the full size of the product, whichever is the smaller. Pipe section specimens shall be taken from a sample consisting of at least three full size sections. 5.2 Conditioning No special conditioning of the test specimens is needed unless otherwise specified in the test standard. In case of dispute, the test specimens shall be stored at (23 ± 2) °C and (50 ± 5) % relative humidity for at least
6 h prior to testing. 5.3 Testing 5.3.1 General Table 2 gives the dimensions of the test specimens, the minimum number of test specimens required to get one test result and any specific conditions, which are necessary. Self-adhesive products shall be tested without the release liner. The test may be performed on the unfaced/uncoated product if the facing/coating is known to have no influence on the property. SIST EN 14304:2010+A1:2013

conductivity
EN 12667 or EN 12939 EN ISO 8497
Full size – 1 1 Normally test with specimen thickness > 19 mm See also Annex C For tape, the sheet or roll results are applicable. 4.2.2
Dimensions and
tolerances
All measurements on finished product including coating and adhesive backing length and width EN 822 EN 13467 Full sizeb 1 – thickness EN 823 EN 13467 Full sizeb 1 50 Pa – inside diameter – EN 13467 Full sizeb 1 Squareness EN 824 EN 13467 Full sizeb 1 – 4.2.3 Dimensional stability EN 1604
200 × 200 3 – 4.2.4 Reaction to fire
EN 13501-1 for mounting and fixing see EN 15715:2009 Annex A of EN 15715:2009 4.3.2 Maximum service temperature EN 14706 EN 14707 100 × 100 d max 300 or 100 mm
For pipe sections see EN 14707 3 Sheets shall be full service (total area) glued. Instead of tape, sheets can be measured. Tubes Temperature gradient 50 K/h. For tape, the sheet or roll results are applicable. 4.3.3 Minimum service temperature Annex B
See Annex B 1 Since there is no defined test method to calculate the minimum service temperature an engineering approach has to be taken in order to determine the minimum service temperature SIST EN 14304:2010+A1:2013

EN 12086 EN 13469 See EN 12086:1997, 6.1 5 Set A of test or specified test temperature. For tape, the sheet or roll results are applicable. One dummyc shall be added to every set of five specimens 4.3.6 Trace quantities of water soluble ions and the pH-value EN 13468
7,5 3 Application related temperature 4.3.7 Structure-born sound transmission – EN 14366 EN ISO 3822-1 according to test standards 1 Different from 8.2.3 of EN 14366:2004 the specimen shall not be fixed with clamps because only the sound reduction effect of FEF shall be measured. Test shall be run with a pipe DN 100 at volume flows of 1 l/s and 2 l/s 4.3.8 Sound absorption EN ISO 354 EN ISO 11654 – minimum 10 m² 1 Tests without plenum 4.3.9 Release of dangerous substances d d – – – 4.3.10 Continuous glowing combustion d d – – – a Always full-size product thickness, except 4.2.4. b The specimen can be cut into pieces for convenience reasons, if does not change the result. c A “dummy” is a specimen without desiccant. d Not yet available.
5.3.2 Thermal conductivity For flat test specimens, thermal conductivity shall be determined in accordance with EN 12667 or EN 12939 for thick products. For cylindrical test specimens, thermal conductivity shall be determined in accordance with EN ISO 8497. The tests in accordance with EN ISO 8497 may be replaced by tests in accordance with EN 12667 or EN 12939, provided it has been demonstrated that the results give safe (higher) values.
 Trace quantities of water soluble chloride ions CLi  Trace quantities of water soluble fluoride ions Fi SIST EN 14304:2010+A1:2013

ITT shall be carried out in accordance with EN 13172 for all characteristics declared except thermal conductivity. ITT for the thermal conductivity curve shall be carried out in accordance with EN ISO 13787. For ITT testing of the λ curve and the maximum and minimum service temperatures only one test result is required. 7.3 Factory Production Control
FPC testing shall be made for the characteristics listed in Annex A. The minimum frequencies of tests in the factory production control shall be in accordance with Annex A. When indirect testing is used, the correlation to direct testing shall be established in accordance with EN 13172. 8 Marking and labelling Products conforming to this standard shall be clearly marked, either on the product or on the label or on the packaging, with the following information:  product name or other identifying characteristic; SIST EN 14304:2010+A1:2013

Factory production control Table A.1 — Minimum product testing frequencies Clause Minimum testing frequency a No. Title 4.2.1 Thermal conductivity –
full temperature range 1 per 2 years and indirect testing 1 per 24 h b Examples for indirect testing: density or similar 4.2.2 Dimensions and tolerances Sheets and rolls Pipe sections Length and width 1 per 24 h 1 per 24 h Thickness 1 per 24 h 1 per 24 h Inside diameter _ 1 per 24 h
Squareness 1 per 24 h 1 per 24 h 4.2.3 Dimensional stability 1 per 5 years 4.2.4 Reaction to Fire See Table A.2 4.3.2 Maximum service temperature 1 per 5 years and indirect testing 1 per 24 h 4.3.3 Minimum service temperature 1 per 5 years and indirect testing 1 per 24 h 4.3.4 Water absorption 1 per 5 years 4.3.5 Water vapour diffusion resistance 1 per year or 1 per 2 years and 1 per 6 months indirect testing. Example for indirect testing: electrolytic test method 4.3.6 Trace quantities of water soluble ions and pH 1 per 5 years
4.3.7 Structure-borne sound transmission 1 per 5 years 4.3.8 Sound absorption 1 per 5 years 4.3.9 Release of dangerous substances c 4.3.10 Continuous glowing combustion c a The minimum testing frequencies, expressed in number of
test results required per period, shall be understood as the minimum for continuous production for each production unit / line under stable conditions. In addition to the testing frequencies given above, testing of relevant properties of the product shall be repeated when changes or modifications are made that are likely to affect the conformity of the product. For ITT and FPC, units using the same process in one factory are considered together (as one production line). b Once in every 24 h where there has been production. c Frequencies are not given. SIST EN 14304:2010+A1:2013

No. 4.2.4 Title Direct testingb
Indirect testingc Reaction to fire class Product Componentsd
Substantial Non-substantial Test method Frequency Test method Frequency Test method Frequen
...