Standard Test Method for Fire Testing of Stacked Chairs

SIGNIFICANCE AND USE
5.1 This test method provides a means of measuring a variety of fire-test-response characteristics resulting from burning a stack of five stacking chairs. After ignition using a propane gas burner, the test specimen is permitted to burn freely under well-ventilated conditions. The most important fire-test-response characteristic measured in this test method is the rate of heat release, which quantifies the intensity of the fire generated.  
5.2 The rate of heat release is measured by the principle of oxygen consumption. Annex A3 discusses the assumptions and limitations.  
5.3 This test method also provides measures of other fire-test-response characteristics, including smoke obscuration (as the rate of smoke release, total smoke released or optical density of smoke), combustion gas release (as concentrations of combustion gases), and mass loss, that are important to making decisions on fire safety.  
5.4 In the majority of fires, the most important gaseous components of smoke are the carbon oxides present in all fires. They are indicators of the toxicity of the atmosphere and of the completeness of combustion. Measurement of concentrations of carbon oxides are useful for two purposes: as part of fire hazard assessment calculations and to improve the accuracy of heat-release measurements. Other toxic combustion gases, which are specific to certain materials, are also indicators of the toxicity of the atmospheres, but are less crucial for determining combustion completeness and are optional measures; however fire hazard assessment often requires their measurement.  
5.5 The type of ignition chosen (flaming source) is common in both accidental and intentional fires in public occupancies. This test method is thus applicable to stacked chairs in public occupancies. Such facilities include, but are not limited to, health-care facilities, old-age convalescent and board and care homes, college dormitories and residence halls, and hotels and motels.  
5.6 One of the fo...
SCOPE
1.1 This is a fire-test-response standard.  
1.2 This test method provides a means of determining the burning behavior of stacking chairs used in public occupancies by measuring specific fire-test responses when a stack of chairs is subjected to a specified flaming ignition source under well ventilated conditions.  
1.3 This test method is limited to stacked chairs.  
1.4 Test data are obtained describing the burning behavior following application of a specific ignition source, from ignition until all burning has ceased, a period of one hour has elapsed, or flashover under test conditions appears inevitable.  
1.5 This test method does not provide information on the fire performance of stacked chairs under fire conditions other than those conditions specified in this test method. In particular, this test method does not apply to smoldering ignition by cigarettes. See 5.11 for further information.  
1.6 The rate of heat release of the burning test specimen is measured by an oxygen consumption method. See 5.11.4 for further information.  
1.7 Other measurements are the production of light-obscuring smoke and the concentrations of certain toxic gas species in the combustion gases. See 5.11.5 for further information.  
1.8 The burning behavior is documented visually by photographic or video recordings.  
1.9 This standard is used to measure and describe the response of materials, products, or assemblies to heat and flame under controlled conditions, but does not by itself incorporate all factors required for fire hazard or fire risk assessment of the materials, products or assemblies under actual fire conditions.  
1.10 Fire testing is inherently hazardous. Adequate safeguards for personnel and property shall be employed in conducting these tests.  
1.11 Use the SI system of units in referee decisions; see IEEE/ASTM SI-10. The units given in parentheses are for information only.  
1.12 This standard does not purpo...

General Information

Status
Published
Publication Date
14-Nov-2021
Technical Committee
E05 - Fire Standards

Relations

Effective Date
01-Jan-2024
Effective Date
01-Dec-2023
Effective Date
01-Sep-2023
Effective Date
01-Jul-2020
Effective Date
01-Jan-2020
Effective Date
01-Jul-2019
Effective Date
15-Apr-2019
Effective Date
01-Mar-2019
Effective Date
15-Dec-2018
Effective Date
01-Oct-2018
Effective Date
01-Jul-2018
Effective Date
01-Mar-2018
Effective Date
01-Mar-2018
Effective Date
01-Nov-2017
Effective Date
01-Aug-2017

Overview

ASTM E1822-21: Standard Test Method for Fire Testing of Stacked Chairs provides a comprehensive approach for assessing the fire-test-response characteristics of stacking chairs typically used in public occupancies. Developed by ASTM International, this standard specifies a controlled procedure to ignite a stack of five identical stacking chairs using a propane gas burner, measuring their fire behavior under well-ventilated conditions. The primary outcomes measured are the rate of heat release, smoke production, combustion gas concentrations, and mass loss. The test simulates real-world scenarios where stacked chairs might be present, such as in health-care facilities, dormitories, hotels, and other public buildings, supporting effective fire safety evaluations.

Key Topics

  • Rate of Heat Release Measurement: The central measurement in this standard is the rate of heat release, which quantifies the fire's intensity. This is determined using the oxygen consumption method, a widely recognized approach in fire testing for measuring how much oxygen the burning chairs consume over time.
  • Smoke Production and Obscuration: The standard records both the total and peak rates of smoke release, as well as optical density, to evaluate visibility impairment during a fire and the associated risks of smoke.
  • Combustion Gas Analysis: Concentrations of key combustion gases, primarily carbon monoxide and carbon dioxide, are measured. These help in understanding the toxicity and completeness of combustion, important factors in fire hazard assessments.
  • Mass Loss: The reduction in mass of the chair stack due to burning is tracked continuously to determine material flammability and burning behavior.
  • Test Configurations: Three main test setups are defined:
    • Test Configuration A: Smaller room layout.
    • Test Configuration B: Larger room layout.
    • Test Configuration C: Open calorimeter.
  • Documentation: All burning behavior is visually documented through photographic or video records.

Applications

  • Public Building Safety Assessments: ASTM E1822-21 is crucial for evaluating stacked chairs commonly found in public spaces-such as hospitals, elder care facilities, dormitories, hotels, and similar venues-where fire risk must be minimized.
  • Product Development and Certification: Furniture manufacturers and suppliers use this standard to demonstrate compliance with fire safety requirements, support product improvement, and achieve necessary certifications for market access.
  • Regulatory and Risk Assessments: Authorities Having Jurisdiction (AHJs), fire safety engineers, and inspectors utilize results from this test method to inform building code compliance and conduct risk analyses.
  • Comparative Analysis: The method enables comparative performance testing of different chair models to determine relative fire risk and inform material choices.

Related Standards

When assessing fire performance or planning comprehensive fire testing programs, the following standards are often referenced alongside ASTM E1822-21:

  • ASTM E84: Test Method for Surface Burning Characteristics of Building Materials
  • ASTM E1354: Test Method for Heat and Visible Smoke Release Rates Using an Oxygen Consumption Calorimeter
  • ASTM E1537: Test Method for Fire Testing of Upholstered Furniture
  • ASTM E1474: Determination of Heat Release Rate of Upholstered Furniture and Mattress Components
  • ASTM E1590: Fire Testing of Mattresses
  • ISO 9705: Full Scale Room Test for Surface Products
  • NFPA 289: Standard Method of Fire Test for Individual Fuel Packages

Practical Value

ASTM E1822-21 supports robust fire safety protocols by offering a repeatable, reliable method for evaluating the burning behavior and fire hazards associated with stacked chairs in public settings. Adoption of this test method helps organizations improve occupant safety, comply with regulatory standards, and inform material and design selections that mitigate fire risk. As fire testing and fire risk management become more prominent in the design and regulation of public interior spaces, using standards like ASTM E1822-21 is essential for maintaining high levels of fire safety and protecting lives.

Keywords: fire testing, stacked chairs, ASTM E1822-21, rate of heat release, smoke obscuration, combustion gas analysis, mass loss, public occupancy fire safety, furniture flammability standards, chair fire test method.

Buy Documents

Standard

ASTM E1822-21 - Standard Test Method for Fire Testing of Stacked Chairs

English language (24 pages)
sale 15% off
sale 15% off
Standard

REDLINE ASTM E1822-21 - Standard Test Method for Fire Testing of Stacked Chairs

English language (24 pages)
sale 15% off
sale 15% off

Get Certified

Connect with accredited certification bodies for this standard

NSF International

Global independent organization facilitating standards development and certification.

ANAB United States Verified

CIS Institut d.o.o.

Personal Protective Equipment (PPE) certification body. Notified Body NB-2890 for EU Regulation 2016/425 PPE.

SA Slovenia Verified

Kiwa BDA Testing

Building and construction product certification.

RVA Netherlands Verified

Sponsored listings

Frequently Asked Questions

ASTM E1822-21 is a standard published by ASTM International. Its full title is "Standard Test Method for Fire Testing of Stacked Chairs". This standard covers: SIGNIFICANCE AND USE 5.1 This test method provides a means of measuring a variety of fire-test-response characteristics resulting from burning a stack of five stacking chairs. After ignition using a propane gas burner, the test specimen is permitted to burn freely under well-ventilated conditions. The most important fire-test-response characteristic measured in this test method is the rate of heat release, which quantifies the intensity of the fire generated. 5.2 The rate of heat release is measured by the principle of oxygen consumption. Annex A3 discusses the assumptions and limitations. 5.3 This test method also provides measures of other fire-test-response characteristics, including smoke obscuration (as the rate of smoke release, total smoke released or optical density of smoke), combustion gas release (as concentrations of combustion gases), and mass loss, that are important to making decisions on fire safety. 5.4 In the majority of fires, the most important gaseous components of smoke are the carbon oxides present in all fires. They are indicators of the toxicity of the atmosphere and of the completeness of combustion. Measurement of concentrations of carbon oxides are useful for two purposes: as part of fire hazard assessment calculations and to improve the accuracy of heat-release measurements. Other toxic combustion gases, which are specific to certain materials, are also indicators of the toxicity of the atmospheres, but are less crucial for determining combustion completeness and are optional measures; however fire hazard assessment often requires their measurement. 5.5 The type of ignition chosen (flaming source) is common in both accidental and intentional fires in public occupancies. This test method is thus applicable to stacked chairs in public occupancies. Such facilities include, but are not limited to, health-care facilities, old-age convalescent and board and care homes, college dormitories and residence halls, and hotels and motels. 5.6 One of the fo... SCOPE 1.1 This is a fire-test-response standard. 1.2 This test method provides a means of determining the burning behavior of stacking chairs used in public occupancies by measuring specific fire-test responses when a stack of chairs is subjected to a specified flaming ignition source under well ventilated conditions. 1.3 This test method is limited to stacked chairs. 1.4 Test data are obtained describing the burning behavior following application of a specific ignition source, from ignition until all burning has ceased, a period of one hour has elapsed, or flashover under test conditions appears inevitable. 1.5 This test method does not provide information on the fire performance of stacked chairs under fire conditions other than those conditions specified in this test method. In particular, this test method does not apply to smoldering ignition by cigarettes. See 5.11 for further information. 1.6 The rate of heat release of the burning test specimen is measured by an oxygen consumption method. See 5.11.4 for further information. 1.7 Other measurements are the production of light-obscuring smoke and the concentrations of certain toxic gas species in the combustion gases. See 5.11.5 for further information. 1.8 The burning behavior is documented visually by photographic or video recordings. 1.9 This standard is used to measure and describe the response of materials, products, or assemblies to heat and flame under controlled conditions, but does not by itself incorporate all factors required for fire hazard or fire risk assessment of the materials, products or assemblies under actual fire conditions. 1.10 Fire testing is inherently hazardous. Adequate safeguards for personnel and property shall be employed in conducting these tests. 1.11 Use the SI system of units in referee decisions; see IEEE/ASTM SI-10. The units given in parentheses are for information only. 1.12 This standard does not purpo...

SIGNIFICANCE AND USE 5.1 This test method provides a means of measuring a variety of fire-test-response characteristics resulting from burning a stack of five stacking chairs. After ignition using a propane gas burner, the test specimen is permitted to burn freely under well-ventilated conditions. The most important fire-test-response characteristic measured in this test method is the rate of heat release, which quantifies the intensity of the fire generated. 5.2 The rate of heat release is measured by the principle of oxygen consumption. Annex A3 discusses the assumptions and limitations. 5.3 This test method also provides measures of other fire-test-response characteristics, including smoke obscuration (as the rate of smoke release, total smoke released or optical density of smoke), combustion gas release (as concentrations of combustion gases), and mass loss, that are important to making decisions on fire safety. 5.4 In the majority of fires, the most important gaseous components of smoke are the carbon oxides present in all fires. They are indicators of the toxicity of the atmosphere and of the completeness of combustion. Measurement of concentrations of carbon oxides are useful for two purposes: as part of fire hazard assessment calculations and to improve the accuracy of heat-release measurements. Other toxic combustion gases, which are specific to certain materials, are also indicators of the toxicity of the atmospheres, but are less crucial for determining combustion completeness and are optional measures; however fire hazard assessment often requires their measurement. 5.5 The type of ignition chosen (flaming source) is common in both accidental and intentional fires in public occupancies. This test method is thus applicable to stacked chairs in public occupancies. Such facilities include, but are not limited to, health-care facilities, old-age convalescent and board and care homes, college dormitories and residence halls, and hotels and motels. 5.6 One of the fo... SCOPE 1.1 This is a fire-test-response standard. 1.2 This test method provides a means of determining the burning behavior of stacking chairs used in public occupancies by measuring specific fire-test responses when a stack of chairs is subjected to a specified flaming ignition source under well ventilated conditions. 1.3 This test method is limited to stacked chairs. 1.4 Test data are obtained describing the burning behavior following application of a specific ignition source, from ignition until all burning has ceased, a period of one hour has elapsed, or flashover under test conditions appears inevitable. 1.5 This test method does not provide information on the fire performance of stacked chairs under fire conditions other than those conditions specified in this test method. In particular, this test method does not apply to smoldering ignition by cigarettes. See 5.11 for further information. 1.6 The rate of heat release of the burning test specimen is measured by an oxygen consumption method. See 5.11.4 for further information. 1.7 Other measurements are the production of light-obscuring smoke and the concentrations of certain toxic gas species in the combustion gases. See 5.11.5 for further information. 1.8 The burning behavior is documented visually by photographic or video recordings. 1.9 This standard is used to measure and describe the response of materials, products, or assemblies to heat and flame under controlled conditions, but does not by itself incorporate all factors required for fire hazard or fire risk assessment of the materials, products or assemblies under actual fire conditions. 1.10 Fire testing is inherently hazardous. Adequate safeguards for personnel and property shall be employed in conducting these tests. 1.11 Use the SI system of units in referee decisions; see IEEE/ASTM SI-10. The units given in parentheses are for information only. 1.12 This standard does not purpo...

ASTM E1822-21 is classified under the following ICS (International Classification for Standards) categories: 13.220.40 - Ignitability and burning behaviour of materials and products; 97.140 - Furniture. The ICS classification helps identify the subject area and facilitates finding related standards.

ASTM E1822-21 has the following relationships with other standards: It is inter standard links to ASTM E176-24, ASTM E84-23d, ASTM E84-23c, ASTM E800-20, ASTM E1474-20, ASTM E84-19b, ASTM E84-19a, ASTM E84-19, ASTM E176-18a, ASTM E84-18b, ASTM E84-18a, ASTM E84-18, ASTM E176-18, ASTM E84-17a, ASTM E84-17. Understanding these relationships helps ensure you are using the most current and applicable version of the standard.

ASTM E1822-21 is available in PDF format for immediate download after purchase. The document can be added to your cart and obtained through the secure checkout process. Digital delivery ensures instant access to the complete standard document.

Standards Content (Sample)


This international standard was developed in accordance with internationally recognized principles on standardization established in the Decision on Principles for the
Development of International Standards, Guides and Recommendations issued by the World Trade Organization Technical Barriers to Trade (TBT) Committee.
Designation: E1822 − 21 An American National Standard
Standard Test Method for
Fire Testing of Stacked Chairs
This standard is issued under the fixed designation E1822; the number immediately following the designation indicates the year of
original adoption or, in the case of revision, the year of last revision.Anumber in parentheses indicates the year of last reapproval.A
superscript epsilon (´) indicates an editorial change since the last revision or reapproval.
1. Scope* 1.10 Fire testing is inherently hazardous. Adequate safe-
guards for personnel and property shall be employed in
1.1 This is a fire-test-response standard.
conducting these tests.
1.2 This test method provides a means of determining the
1.11 Use the SI system of units in referee decisions; see
burningbehaviorofstackingchairsusedinpublicoccupancies
IEEE/ASTM SI-10. The units given in parentheses are for
bymeasuringspecificfire-testresponseswhenastackofchairs
information only.
is subjected to a specified flaming ignition source under well
1.12 This standard does not purport to address all of the
ventilated conditions.
safety concerns, if any, associated with its use. It is the
1.3 This test method is limited to stacked chairs.
responsibility of the user of this standard to establish appro-
1.4 Test data are obtained describing the burning behavior
priate safety, health, and environmental practices and deter-
following application of a specific ignition source, from
mine the applicability of regulatory limitations prior to use.
ignition until all burning has ceased, a period of one hour has
1.13 This international standard was developed in accor-
elapsed, or flashover under test conditions appears inevitable.
dance with internationally recognized principles on standard-
ization established in the Decision on Principles for the
1.5 This test method does not provide information on the
Development of International Standards, Guides and Recom-
fire performance of stacked chairs under fire conditions other
mendations issued by the World Trade Organization Technical
than those conditions specified in this test method. In
Barriers to Trade (TBT) Committee.
particular, this test method does not apply to smoldering
ignition by cigarettes. See 5.11 for further information.
2. Referenced Documents
1.6 The rate of heat release of the burning test specimen is
2.1 ASTM Standards:
measured by an oxygen consumption method. See 5.11.4 for
D123Terminology Relating to Textiles
further information.
E84Test Method for Surface Burning Characteristics of
1.7 Other measurements are the production of light-
Building Materials
obscuring smoke and the concentrations of certain toxic gas
E176Terminology of Fire Standards
species in the combustion gases. See 5.11.5 for further infor-
E800GuideforMeasurementofGasesPresentorGenerated
mation.
During Fires
E1354Test Method for Heat and Visible Smoke Release
1.8 The burning behavior is documented visually by photo-
Rates for Materials and Products Using an Oxygen Con-
graphic or video recordings.
sumption Calorimeter
1.9 This standard is used to measure and describe the
E1474Test Method for Determining the Heat Release Rate
response of materials, products, or assemblies to heat and
of Upholstered Furniture and Mattress Components or
flame under controlled conditions, but does not by itself
Composites Using a Bench Scale Oxygen Consumption
incorporate all factors required for fire hazard or fire risk
Calorimeter
assessment of the materials, products or assemblies under
E1537Test Method for Fire Testing of Upholstered Furni-
actual fire conditions.
ture
E1590Test Method for Fire Testing of Mattresses
This test method is under the jurisdiction of ASTM Committee E05 on Fire
Standards and is the direct responsibility of Subcommittee E05.15 on Furnishings
and Contents. For referenced ASTM standards, visit the ASTM website, www.astm.org, or
Current edition approved Nov. 15, 2021. Published December 2021. Originally contact ASTM Customer Service at service@astm.org. For Annual Book of ASTM
approved in 1996. Last previous edition approved in 2017 as E1822–17. DOI: Standards volume information, refer to the standard’s Document Summary page on
10.1520/E1822-21. the ASTM website.
*A Summary of Changes section appears at the end of this standard
Copyright © ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959. United States
E1822 − 21
IEEE/ASTM SI-10American National Standard for Use of 3.2.5 upholstery cover material, n—the outermost layer of
theInternationalSystemofUnits(SI):TheModernMetric fabric or related material used to enclose the main support
System system, or upholstery materials, or both, used in the furniture
unit.
2.2 ISO Standards:
ISO 4880 Burning Behaviour of Textiles and Textile
3.2.6 upholsterymaterial,n—thepadding,stuffing,orfilling
Products—Vocabulary
material used in a furniture item, which may be either loose or
ISO 9705Fire Tests—Full Scale Room Test for Surface
attached, enclosed by an upholstery cover material, or located
Products
between the upholstery cover material and support system, if
ISO 13943Fire Safety—Vocabulary
present.
2.3 UL Standards:
3.2.6.1 Discussion—This includes, but is not limited to,
UL 1056Fire Test of Upholstered Furniture (withdrawn)
material such as foams, cotton batting, polyester fiberfill,
UL 1895Fire Test of Mattresses (withdrawn)
bonded cellulose, or down.
2.4 CA Standards:
4. Summary of Test Method
CATB 129,Flammability Test Procedure for Mattresses for
Use in Public Buildings
4.1 Thisfire-test-responsetestmethoddeterminesanumber
CA TB 133,Flammability Test Procedure for Seating Fur-
of fire-test-response characteristics associated with a stack of
niture for Use in Public Occupancies (withdrawn)
five stacking chairs, ignited with a propane gas burner. Mea-
2.5 NFPA Standard: surements to be made include the rate of heat and smoke
NFPA289Standard Method of Fire Test for Individual Fuel
release, total amount of heat released, rates and concentrations
Packages of carbon oxides released, and rates and amounts of mass of
2.6 Other Document: test specimen lost. Other optional measurements are also
described.
Nordtest Method NT Fire 032Upholstered Furniture: Burn-
ing Behavior—Full Scale Test
4.2 In Test Configurations A and B, the test specimen is
placed on a weighing platform located in a test room. An
3. Terminology
exhausthood,connectedtoaduct,islocatedatthedoorwayof
3.1 Definitions—For definitions of terms used in this test
the room.
method and associated with fire issues, refer to Terminology
4.3 In Test Configuration C, the test specimen is placed on
E176 and ISO 13943. In case of conflict, the definitions in
a weighing platform located directly under a hood.
Terminology E176 shall prevail. For definitions of terms used
4.4 Heat, smoke, and combustion gas release instrumenta-
in this test method and associated with textile issues refer to
tion is placed in the duct.
Terminology D123 and ISO 4880. In case of conflict, the
definitions in Terminology D123 shall prevail.
4.5 Additional (optional) instrumentation placed in the test
3.2 Definitions of Terms Specific to This Standard:
room is also described.
3.2.1 stacking chair, n—chair that is intended to be stacked
when not in use. 5. Significance and Use
3.2.2 test specimen, n—stack of five identical stacking 5.1 This test method provides a means of measuring a
chairs.
varietyoffire-test-responsecharacteristicsresultingfromburn-
ing a stack of five stacking chairs. After ignition using a
3.2.3 upholstered, adj—covered with material (as fabric or
propane gas burner, the test specimen is permitted to burn
padding) to provide a soft surface.
freely under well-ventilated conditions. The most important
3.2.4 upholstered seating furniture, n—a unit of interior
fire-test-response characteristic measured in this test method is
furnishing that (1) contains any surface that is covered, in
therateofheatrelease,whichquantifiestheintensityofthefire
whole or in part, with a fabric or other upholstery cover
generated.
material, (2) contains upholstery material, and (3) is intended
5.2 The rate of heat release is measured by the principle of
or promoted for sitting upon.
oxygenconsumption.AnnexA3discussestheassumptionsand
limitations.
Available from International Organization for Standardization (ISO), ISO
5.3 This test method also provides measures of other fire-
Central Secretariat, Chemin de Blandonnet 8, CP 401, 1214 Vernier, Geneva,
Switzerland, https://www.iso.org.
test-response characteristics, including smoke obscuration (as
AvailablefromUnderwritersLaboratories(UL)(hardcopyonly),333Pfingsten
the rate of smoke release, total smoke released or optical
Rd., Northbrook, IL60062-2096, http://www.ul.com. UL1056 withdrawn /August
density of smoke), combustion gas release (as concentrations
11, 2000. UL 1895 withdrawn Feb. 11, 2000.
of combustion gases), and mass loss, that are important to
Available from California Bureau of Household Goods and Services (BHGS),
State of California, Department of Consumer Affairs, 3485 Orange Grove Ave.,
making decisions on fire safety.
North Highlands, CA 95660-5595, https://bhgs.dca.ca.gov/industry/tb129.pdf and
5.4 In the majority of fires, the most important gaseous
https://bhgs.dca.ca.gov/industry/tb133.pdf
Available from National Fire Protection Association (NFPA), 1 Batterymarch
componentsofsmokearethecarbonoxidespresentinallfires.
Park, Quincy, MA 02169-7471, http://www.nfpa.org.
Theyareindicatorsofthetoxicityoftheatmosphereandofthe
Available from Nordtest, P.O. Box 22, SF-00341, Helsingfors, Finland,
completeness of combustion. Measurement of concentrations
http://www.nordtest.info/wp/1991/05/14/upholstered-furniture-burning-behaviour-
full-scale-test-nt-fire-032/ of carbon oxides are useful for two purposes: as part of fire
E1822 − 21
hazard assessment calculations and to improve the accuracy of 5.11.5 As yet, there is not a known direct correlation
heat-release measurements. Other toxic combustion gases, betweensmokeobscurationorsmoketoxicitymeasurementsin
whicharespecifictocertainmaterials,arealsoindicatorsofthe the exhaust duct and overall fire hazard.
toxicityoftheatmospheres,butarelesscrucialfordetermining
6. Apparatus
combustion completeness and are optional measures; however
fire hazard assessment often requires their measurement.
6.1 Room Layout and Instrumentation:
6.1.1 Test Room Layout (Test Configuration A)—The test
5.5 Thetypeofignitionchosen(flamingsource)iscommon
room shall have dimensions of 2.44 m 6 25 mm by 3.66 m 6
in both accidental and intentional fires in public occupancies.
25 mm by 2.44 m 6 25 mm high (8 by 12 by 8 ft). The room
This test method is thus applicable to stacked chairs in public
shallhavenoopeningsotherthanadoorwayopening0.76m 6
occupancies. Such facilities include, but are not limited to,
6.4 mm by 2.03 m 6 6.4 mm (30 by 80 in.), located as
health-care facilities, old-age convalescent and board and care
indicated in Fig. 1, and other small openings, as necessary to
homes, college dormitories and residence halls, and hotels and
maketestmeasurements.Constructthetestroomofwoodenor
motels.
metal studs and line it with fire-rated gypsum wallboard or
5.6 One of the following three configurations is to be used
calcium silicate wallboard. Position a hood, as described in
in this test method:
Annex A1, outside the room doorway, such that it collects all
5.6.1 Test Configuration A—Atest room with the following
of the combustion gases. There shall be no obstructions to the
dimensions: 3.66 by 2.44 by 2.44 m high (12 by 8 by 8 ft).
air supply to the test setup.
5.6.2 Test Configuration B—Atest room with the following
NOTE 1—Both Type X gypsum wallboard and calcium silicate wall-
dimensions: 3.66 by 3.05 by 2.44 m high (12 by 10 by 8 ft).
boardwithanominalthicknessofatleast13mm(0.5in.)havebeenfound
5.6.3 Test Configuration C—An open calorimeter (or furni-
acceptable. If the thickness of the wallboard used is greater, it will not
affect the results of this test method.
ture calorimeter).
6.1.2 Test Room Layout (Test Configuration B)—The test
5.7 Rooms of other dimensions are acceptable where it has
room shall have dimensions of 3.05 m 6 25 mm by 3.66 m 6
been shown that equivalent test results are obtained.
25 mm by 2.44 m 6 25 mm high (10 by 12 by 8 ft).The room
5.8 Measurements in the three test configurations listed in
5.6 have been shown to give similar results for heat release in
the duct and mass loss up to a rate of heat release of 600 kW
(1).
5.9 Measurements of temperatures, gas concentrations, and
smoke obscuration in the room are dependent on room size.
5.10 Studies on the flammability performance of furniture
indicate that bench-scale fire tests are useful for preliminary
evaluations of component materials for substitution purposes
(see Appendix X3).
5.11 Limitations:
5.11.1 This test method is not applicable to ignition by
cigarettes or by any other smoldering source.
5.11.2 The ignition source in this test method is a flaming
source. Moreover, this particular ignition source has been
showntobeabletoprovideadistinctionamongdifferentkinds
of stacked chairs. However, the fraction of actual flaming
stackedchairfiresoccurringwithignitionsmoreorlessintense
than that used here is not known.
5.11.3 Itisnotknownwhethertheresultsofthistestmethod
will be equally valid when stacking chairs are burned under
conditions different from those specified. In particular, it is
unclearwhethertheuseofadifferentignitionsource,thesame
ignition source but having a different duration of flame
exposure, or a different gas-flow rate will change the results.
5.11.4 Thevalueofrateofheatreleasecorrespondingtothe
critical limit between propagating fires and nonpropagating
fires is not known.
NOTE 1—See text for tolerances; room instrumentation is optional.
Theboldfacenumbersinparenthesesrefertothelistofreferencesattheendof
this test method. FIG. 1 Test Room Configuration for Test Configuration A
E1822 − 21
shallhavenoopeningsotherthanadoorwayopening0.97m 6 6.1.3.3 The air supply to the calorimeter shall be sufficient
6.4 mm by 2.06 m 6 6.4 mm (38 by 81 in.), located as so that it does not affect the burning process.
indicated in Fig. 2, and other small openings, as necessary to 6.1.4 General Discussion of Room Layout:
maketestmeasurements.Constructthetestroomofwoodenor 6.1.4.1 Heatreleasemeasurementsintheduct,madeinTest
metal studs, and line it with fire-rated gypsum wallboard or Configurations A, B, and C have been shown to give similar
calcium silicate wallboard. Position a hood, as described in results for heat release rates below 600 kW (see X1.4) (1).
Annex A1, outside the room doorway, such that it collects all 6.1.5 Other Test Room Furnishings—The test room shall
of the combustion gases. There shall be no obstructions to the contain no furnishings except for the test specimen.
air supply to the test setup. 6.1.6 Location of Test Specimen, for Test Configurations A
or B—Position the test specimen on a weighing platform in a
NOTE 2—Both Type X gypsum wallboard and calcium silicate wall-
corner.Ensurethatthetestspecimenisatadistanceofbetween
boardwithanominalthicknessofatleast13mm(0.5in.)havebeenfound
0.10and0.25m(4and10in.)frombothwalls(Fig.1andFig.
acceptable. If the thickness of the wallboard used is greater, it will not
affect the results of this test method.
2).
6.1.7 Location of Test Specimen, for Test Configuration
6.1.3 Open Calorimeter Layout (Test Configuration C):
C—Position the test specimen on a weighing platform under-
6.1.3.1 The area surrounding the test specimen in an open
neath the hood.
calorimeter layout shall be sufficiently large that there are no
heat radiation effects from the walls or any other nearby
6.2 Ignition Source:
objects. The airflow to the test specimen shall be symmetrical
6.2.1 Use as the ignition source a gas burner in the shape of
from all sides.
a T, as shown in Fig. 3.
6.1.3.2 If the heat release rate of the test specimen is below
6.2.2 Construct the burner of stainless steel with wall
600 kW, a load cell sited under a hood, and where the distance
thicknesses of 0.89 6 0.05 mm (0.035 6 0.002 in.). Make the
betweenthetestspecimenandanywallis1m(3.3ft)ormore,
head of theT205 6 10 mm (8 6 0.4 in.) long and 13 61mm
is acceptable.
(0.5 6 0.04 in.) outside diameter. Plug the ends of the T. As
showninFig.3(a)andFig.3(b),constructtheburnerwithtwo
sets of holes equally spaced and centered along the head of the
3(a) Burner Head Showing Top Set of Holes
3(b) Burner Head Showing Bottom Set of Holes
3(c) Side View of Burner Showing Orientation of the Head with the Handle
NOTE 1—See text for tolerances; room instrumentation is optional. NOTE 1—See text for tolerances.
FIG. 2 Test Room Configuration for Test Configuration B FIG. 3 View of T-Shaped Gas Burner
E1822 − 21
burner and oriented 90° to one another. One set consists of 14
holes and the other set of nine holes, each hole spaced 13 6 1
mm (0.5 6 0.04 in.) from the next. Make the holes 1 6 0.04
mm (0.039 6 0.002 in.) in diameter.
NOTE 3—It is common for the burner holes to become clogged
following a test. Inspect burner holes after each test and clean thoroughly
if required. Take care not to enlarge the holes when cleaning them.
6.2.3 Construct the handle of the burner of stainless steel
withthesamediameterandthicknessasthehead.Weldittothe
head in the orientation shown in Fig. 3(c). When the 14 holes
in the head are oriented 45° above the horizontal and the nine
holes are oriented 45° below the horizontal, the handle is
NOTE 1—This example of upholstered chairs has no gaps between the
seats or backs. The burner is placed below the bottom of the seat cushion
approximately 30° above the horizontal. Construct the handle
frame.
such that it is at least 450 mm (18 in.) long to facilitate its
FIG. 4 Positioning of the Ignition Source—T Burner
attachment to the support and the propane line.
NOTE 4—To align the burner to the test specimen properly, it is
6.3.2 Construct a thermal barrier large enough to prevent
necessary to position the head as described below; therefore, the angle
melting or falling material from the tested stacked chairs
between the handle and the head is not critical.
specimen from falling off the thermal barrier. The barrier shall
6.2.4 Usepropanegaswithaknownnetheatofcombustion
consist of a galvanized steel pan with a gypsum board lining
of46.5 60.5MJ/kgasafuelforthisignitionsource.Meterthe
placedonthetestspecimen.Thebarriershallbeusedtoprotect
flow rate of propane at 12 6 0.25 L/min, at a pressure of 101
theloadcell.Thepanshallbeconstructedofnominally1.6mm
6 5 kPa (standard atmospheric pressure measured at the flow
( ⁄16in.)thicksteel,andhavedimensionsofnolessthan1.0by
gage), and a temperature of 20 6 5 °C or at a flow equivalent
1.0 m (39 by 39 in.), with a uniform raised lip of the same
to these values. Use flexible tubing fed into the handle of the
material, 100 6 10 mm (approximately 4 in.) high, on each
burner to deliver the propane to the burner. Maintain the flow
side, to catch falling material. The bottom of the pan shall be
rate constant of propane while the flame is lit. Mount the
covered by a tight-fitting section of standard gypsum board
burneronanadjustablepole,withacounterweightifnecessary,
(finish side up), of nominally 13 mm (0.5 in.) thickness. The
to allow the burner to be positioned in the proper location for
gypsumboardshallbecleanbeforethestartofatest;theboard
ignition of the test specimen and then swung out of the way
shall be replaced for each test.
after the propane gas flame is turned off.
6.3.3 Measure the test specimen mass continuously with a
6.2.5 The approximate ratio of heat release rate output to device capable of an accuracy of no less than 6150guptoat
gas flow rate is 1.485 kW min/L under standard conditions. least 90 kg. Install it in such a way that neither the heat from
Thus, the calculated rate of heat release from the burner at the the burning test specimen nor any eccentricity of the load will
temperature and pressure given above is 17.8 kW. affect the accuracy. Do not make any range shifts during
measurements. Install all parts of the mass measuring device
6.2.6 Location of Gas Burner:
below the top level of the thermal barrier.
6.2.6.1 Orienttheburnerwithrespecttothetestspecimenas
6.3.4 The distance from the upper surface of the thermal
shown in Fig. 3 (a, b, and c).
barrier to floor level shall not exceed 0.3 m (12 in.). The area
6.2.6.2 Ensure that the horizontal plane of the head of the
betweenthethermalbarrierandthefloorlevelshallbeshielded
burner (depicted in Fig. 3(c)) is level with the bottom horizon-
byaskirtattheperimeterofthebarriertopreventliftingforces
tal surface of the lowest chair in the test specimen. This
due to fire-induced air flow that influence the measurement.
orientation shall be such that the 14 holes are directed at the
6.4 Exhaust Collection System:
test specimen at an angle of 45° above the horizontal, and the
6.4.1 General:
nine holes are directed under the lowest chair in the test
6.4.1.1 Construct the exhaust collection system with the
specimenatanangle45°belowthehorizontal.Thehandlewill
following minimal requirements: a blower, steel hood, duct,
be set, nominally, at 30 ° above the horizontal.
bidirectional probe, thermocouple(s), oxygen measurement
6.2.6.3 Locate the burner during ignition in such a way that
system, smoke obscuration measurement system (white light
the burner is parallel with the front edge of the lowest chair in
photocelllamp/detectororlaser),andcombustiongassampling
the test specimen, 25 62mm(1 6 0.1 in.) from the vertical
andanalysissystem.Constructtheexhaustcollectionsystemas
edge of the chair and 50 62mm(2 6 0.1 in.) below the
shown in Fig. 5 and as explained in Annex A1.
bottomhorizontaledgeofthelowestchairinthetestspecimen,
6.4.1.2 Ensurethatthesystemforcollectingthesmoke(that
as shown in Fig. 4.
includes gaseous combustion products) has sufficient exhaust
6.3 Mass Loss Measurements:
capacity and is designed in such a way that all of the
6.3.1 Use a weighing platform to measure the mass of the combustion products leaving the burning test specimen are
burning test specimen continuously. Construct a weighing collected. Design the capacity of the evacuation system such
platformconsistingofahorizontalthermalbarrier,asdescribed that it will exhaust minimally all combustion gases leaving the
in 6.3.2, and placed on top of a mass measuring device. test specimen (see A1.1.4).
E1822 − 21
response time to a stepwise change of the duct flow rate shall
not exceed5sto reach 90% of the final value.
6.6 Combustion Gas Analysis:
6.6.1 SamplingLine—Constructthesamplinglinetubesofa
material not influencing the concentration of the combustion
gas species to be analyzed. The following sequence of the gas
train has been shown to be acceptable: sampling probe, soot
filter, cold trap, gas path pump, vent valve, plastic drying
column and carbon dioxide removal columns (if used), flow
controller, and oxygen analyzer (see Fig. 6 and Annex A2).
Alternative designs of the sampling line must yield equivalent
results. The gas train shall also include appropriate spanning
and zeroing facilities.
6.6.2 Oxygen Measurement—Measure the oxygen concen-
tration with an accuracy of 60.01 vol % oxygen, or better, in
order to have adequate measurements of rate of heat release.
Take the combustion gas sample from the end of the sampling
FIG. 5 Design of Hood and Exhaust System
line. Calculate the time delay, including the time constant of
the instrument, from the test room; it is a function of the
exhaust duct flow rate. This time delay shall not exceed 60 s
6.4.1.3 Placeprobesforsamplingofcombustiongasandfor
(see Annex A2).
measurement of flow rate in accordance with 6.5.
6.6.3 Carbon Monoxide and Carbon Dioxide
6.4.1.4 Make all measurements of smoke obscuration, gas
Measurement—Measure the combustion gas species with an
concentrations, or flow rates at a position in the exhaust duct
instrument having an accuracy of at least 60.1 vol % for
where the exhaust is mixed uniformly so there is a nearly
carbon dioxide and 60.02 vol % for carbon monoxide. A
uniform velocity across the duct section.
suitableoutputrangeisfrom0to1vol%forcarbonmonoxide
6.4.1.5 To ensure uniform mixing of the exhaust, provide a
andfrom0to6vol%forcarbondioxide.Takethecombustion
straight section of duct before the measuring system having a
gas sample from the end of the sampling line. Calculate the
length equal to at least eight times the inside diameter of the
time delay, including the time constant of the instrument, from
duct. If a measuring system is positioned at a distance of less
the test room; it is a function of the exhaust duct flow rate. It
than eight diameters, demonstrate the achievement of equiva-
shall be a maximum of 60 s (see Annex A2).
lent results.
6.6.4 For optional measurement of other combustion gases
6.5 Instrumentation in Exhaust Duct:
see A2.3.3.
6.5.1 The following specifications are minimum require-
6.7 Smoke Obscuration Measurement:
mentsforexhaustductinstrumentation.Additionalinformation
is given in Annex A2. 6.7.1 Install an optical system for measurement of the light
6.5.2 Flow Rate—Measure the flow rate in the exhaust duct obscuration across the centerline of the exhaust duct. Deter-
by a bidirectional probe or an equivalent measuring system mine the optical density of the smoke by measuring the light
with an accuracy of at least 66% (see Annex A2). The transmitted with a photometer system consisting of a white
FIG. 6 Schematic of Gas Train
E1822 − 21
light source and a photocell/detector or a laser system for 8.2.2 Asuitablecalibrationburnerisasanddiffusionburner
measurement of light obscuration across the centerline of the with a 0.3 by 0.3 m (12 by 12 in.) top surface and a 0.15 m (6
exhaust duct. in.) depth. Construct such a gas burner with a 25 mm (1 in.)
6.7.2 One photometer system found suitable consists of a thick plenum. Alternatively, use a minimum 100 mm (4 in.)
lamp, lenses, an aperture, and a photocell (see Fig. 7 and layer of Ottawa sand to provide the horizontal surface through
AnnexA2).Constructthesystemsosootdepositsontheoptics which the gas is supplied. This burner is shown in Fig. 9. The
duringatest.Donotreducethelighttransmissionbymorethan gas supply to the burner shall be propane (the same quality
5%. usedfortheignitionburner)ormethane.Thegasfortheburner
6.7.3 Alternatively, instrumentation constructed using a 0.5 flameshallnotbepremixedwithair.Metertheflowrateofgas
to2.0mWhelium-neonlaserinsteadofawhite-lightsystemis and keep it constant throughout the calibration test.
also acceptable (see Fig. 8, Fig. A1.1, and Annex A2). It has
8.2.3 Another suitable calibration burner is a pipe with an
been shown that white-light and laser systems will provide innerdiameterof100 61.5mm(4in.)suppliedwithgasfrom
similar results (see Refs (2-5)).
beneath (see ISO 9705).The gas for the burner flame shall not
be premixed with air.
7. Test Specimen
8.2.4 Obtain a minimum of two calibration points. Obtain a
7.1 The test specimen is a stack of five identical stacking lower heat release rate value of 40 kW and then a higher heat
chairs, or prototype thereof. release rate value of 160 kW.Approximate propane flow rates
for any required heat release rate value are estimated using the
7.2 If prototype stacking chairs are used, the prototypes
following constant: 1.485 kW min/L, determined at a pressure
shall, in all respects, reflect the construction of the actual
of 101 6 5 kPa (standard atmospheric pressure; measured at
stacking chairs.
the flow gage) and a temperature of 20 6 5 °C.
7.3 Fire tests of stacking chairs have shown that the fire
8.2.5 Take measurements at least once every 6 s and start 1
performance of stacked chairs is significantly affected by chair
min prior to ignition of the burner. Determine the average rate
design and configuration, the gap between adjacent seat
of heat release over a period of at least 1 min by the oxygen
surfaces, and the vertical gap between adjacent seat backs.
consumption method and calculating the heat release rate from
Therefore,itiscriticaltoensurethatthefivestackingchairsare
the gas mass flow rate and the net heat of combustion. The
carefully stacked in accordance with the design features of the
difference between the two values shall not exceed 5%. This
chairs to be tested.
comparison shall be made only after steady-state conditions
have been reached.
8. Calibration
8.2.6 Perform a calibration test in accordance with 8.5 prior
8.1 Calibrateallinstrumentscarefullywithstandardsources
to each continuous test series. Perform a full basic calibration
afterinitialinstallation.Amongtheinstrumentstobecalibrated
on a new system or when modifications are introduced.
are load cells or weighing platforms, smoke meters, flow or
8.2.7 When calibrating a new system, or when modifica-
velocity transducers, and gas analyzers. Perform recalibration
tions are introduced, check the response time of the measuring
tests on the entire system, for example using standard output
system by the following test sequence:
burners.
Time, min Burner Output, kW
8.2 Heat Release: 0–5 0
5–10 40
8.2.1 Perform the calibration of the heat release instrumen-
10–15 160
tation in the exhaust duct by burning propane or methane gas
15–20 0
and comparing the heat release rates calculated from the
The response of the system to a stepwise change of the heat
metered gas input and those calculated from the measured
output from the burner shall be a maximum of 12 s to 90% of
oxygen consumption. The value of net heat of combustion for
final value.
methaneis50.0MJ/kgandforpropaneis46.5MJ/kg.Position
8.2.8 Perform the calibration given in 8.2.7 with the initial
theburnerinthesamelocationwherethetestspecimenistobe
duct air flow rate equal to that to be used in the test procedure.
placed during the test. Measure the gas flow rate at a pressure
8.2.9 The change in measured rate of heat release, compar-
of 101 6 5 kPa (standard atmospheric pressure, measured at
ing time average values over 1 min, shall not be more than
the flow gage) and a temperature of 20 6 5 °C.
10% of the actual heat output from the burner.
8.2.10 The use of a higher rate of heat release for
calibration, for example 500 kW, will generally lead to higher
accuracy in the test results.
8.3 Mass Loss—Perform calibration of the mass-measuring
device by loading the weighing platform with known masses
correspondingtothemeasuringrangeofinterest,toensurethat
the requirements of accuracy in 6.3.3 are fulfilled. Carry out
this calibration daily, prior to testing.
8.4 SmokeObscuration—Calibratethesmokemeterinitially
FIG. 7 Optical System Using a White Light to read correctly for two neutral density filters of significantly
E1822 − 21
FIG. 8 Laser Extinction Beam
8.5 GasAnalysis—Calibratethegasanalyzersdaily,priorto
testing (see Guide E800).
9. Conditioning
9.1 Prior to testing, condition the chairs for at least 48 h in
an atmosphere at a temperature of 21 64°C(70 6 7 °F) and
a relative humidity of less than 60%. Test the specimen as
soon as possible after removal from such conditions if the test
room conditions differ from the above. Report the time
between removal from the conditioning room and the start of
testing.
10. Procedure
10.1 Initial Conditions:
10.1.1 The ambient temperature shall be above 15 °C (60
°F) and the relative humidity shall be below 75%.
10.1.2 The horizontal air flow, measured at both the surface
and at a horizontal distance of 0.5 m (20 in.) from the edge of
−1
the weighing platform, shall not exceed 0.5 m/s .
10.1.3 Position the test specimen centrally on the weighing
platform.
10.1.4 Have available means for extinguishing a fully de-
veloped fire.
10.2 Test Procedure:
10.2.1 Perform the measurements needed to obtain the
descriptive information needed for the test report.
10.2.2 Weigh the test specimen immediately upon removal
from conditioning room and immediately before the start of
NOTE 1—See text for tolerances.
test.
FIG. 9 Calibration Gas Burner
10.2.3 PlacetheT-shapedpropanegasburnerinfrontofthe
test specimen, as specified in 6.2.6. Confirm that burner holes
have been cleaned (see Note 3).
10.2.4 Begin all recording and measuring devices 2 min
different values, and also at 100% transmission. The use of
before starting the ignition burner.
neutral density filters at 0.5 and 1.0 values of optical density
hasbeenshowntobesatisfactoryforthiscalibration.Oncethis 10.2.5 Light the ignition burner.
calibration is set, only the zero value of extinction coefficient 10.2.6 Exposethetestspecimentothegasburnerflamesfor
(100% transmission) must be verified each day, prior to 80s,ataflowrateof12L/min,determinedatapressureof101
testing. Investigate any excessive departure from the zero line 6 5 kPa (standard atmospheric pressure, measured at the flow
at the end of a test, and correct it. gage) and a temperature of 20 6 5 °C.
E1822 − 21
10.2.7 Extinguishthegasflameandremovetheburnerafter 12.2 Include the following test results in the test report (see
the specified burning period (80 s). also appendixes):
10.2.8 Perform a photographic or a video recording before 12.2.1 Table of numerical results containing the following:
andduringeachtest.Anindicationofelapsedtime,givingtime 12.2.1.1 Peak rate of heat release (in kW), and the time at
to the nearest 1 s, shall appear in all photographic records. which it occurred,
10.2.9 During the test, record the following events and the 12.2.1.2 Total heat released (in MJ),
timewhentheyoccur,withrespecttothetimeofignitionofthe
12.2.1.3 Total heat released at 10 min (in MJ),
2 −1
burner: 12.2.1.4 Peakrateofsmokerelease(inm /s ),andthetime
10.2.9.1 Ignition of the first igniting chair,
at which it occurred,
10.2.9.2 Location of the flame front at various appropriate 12.2.1.5 Total smoke released (in m ),
times,
12.2.1.6 Total smoke released at 10 min (in m ),
10.2.9.3 Melting and dripping, 12.2.1.7 Total mass loss (in kg),
10.2.9.4 Formation of flaming droplets, 12.2.1.8 Total mass loss at 10 min (in kg),
10.2.9.5 Occurrence of pool fire under the test specimen,
12.2.1.9 Total percentage of mass loss (in %),
10.2.9.6 General description of the burning behavior, and 12.2.1.10 Peak concentration of carbon monoxide (in ppm),
10.2.9.7 Any other event of special interest.
12.2.1.11 Peak temperatures (in °C),
10.2.10 Terminate the test after the first of the following: 12.2.1.12 Equation used to calculate rate of heat release,
10.2.10.1 All signs of combustion have ceased,
12.2.1.13 Peak optical density of smoke (optional),
10.2.10.2 One hour of testing has elapsed, or 12.2.1.14 Average optical density of smoke, over the 10-
10.2.10.3 Flashover appears inevitable. min period including the peak (optional),
10.2.11 Note, from visual inspection of the specimen after 12.2.1.15 Total percentage of combustible mass loss (in %)
the test, the approximate percentage of each surface that was (optional),
burned or charred, and the approximate depth of fire damage. 12.2.1.16 Average yield of carbon monoxide (in g CO/g
fuel) (optional),
11. Calculation 12.2.1.17 Average yield of carbon dioxide (in g CO /g fuel)
(optional),
11.1 Considerations for heat release measurements are pre-
12.2.1.18 Carbon monoxide/carbon dioxide molar yield ra-
sented in AnnexA3. Calculate the heat release data, using the
tio (optional), and
equations presented in A4.1. The testing laboratory shall
12.2.1.19 Average yield of any other measured combustion
choose one of the equations given in A4.1 for calculating heat
gas (in g combustion gas/g fuel) (optional).
release, based on the gas analyzers installed.
12.2.2 Graphical Results (Optional):
11.2 Calculate the smoke release data using the equations
12.2.2.1 Plot of rate of heat release versus time,
presented in A4.2.
12.2.2.2 Plot of rate of smoke release versus time,
11.3 Calculate the gas yield data using the equations pre- 12.2.2.3 Plot of optical density versus time,
sented in A4.3.
12.2.2.4 Plot of mass loss versus time,
12.2.2.5 Plot of concentration of carbon monoxide versus
12. Report time,
12.2.2.6 Plot of concentration of carbon dioxide versus
12.1 Report the following descriptive information:
time,
12.1.1 Name and address of the testing laboratory,
12.2.2.7 Plots of concentration of any other measured com-
12.1.2 Date and identification number of the report,
bustion gas versus time,
12.1.3 Name and address of the test requester,
12.2.2.8 Plot of mass flow rate in the exhaust duct versus
12.1.4 Test configuration used: A, B, or C,
time,
12.1.5 Nameofproductmanufacturerorsupplier,ifknown,
12.2.2.9 Plot of duct temperature versus time, and
12.1.6 Name or other identification marks and description
12.2.2.10 Report smoke obscuration, carbon monoxide and
of the chairs,
temperature measurements in the room in the same fashion, if
12.1.7 Linear dimensions (height, width, depth) of each
they have been made.
individual chair and of the test specimen,
12.2.3 Descriptive Results:
12.1.8 Total mass, thickness of the main components and
12.2.3.1 Photographs or videotape of the fire development,
mass of combustible portion of each test specimen,
and
12.1.8.1 Weight change of the test specimen between re-
12.2.3.2 All available information requested in 10.2.9
moval from conditioning room and start of test,
through 10.2.11.
12.1.9 Density, or mass per unit surface area of the main
components in each chair, if known,
13. Precision and Bias
12.1.10 Conditioning of the chairs,
12.1.11 Date of the test, 13.1 Precision:
12.1.12 Test number and any special remarks, and 13.1.1 Initial Repeatability—The results of a repeatability
12.1.13 Time between the removal from conditioning room study from one laboratory, involving six different sets of
and start of testing. stacked chairs are shown in Table 1 and Table X4.1 to Table
E1822 − 21
TABLE 1 Stacking Chair Test Results—Chair Set 6 (See X4.6)
NOTE 1—A and B represent the constant and coefficient of the equation:
r srepeatabilityd 5 A1B*property
NOTE2—RSD%andAvgrepresenttheaveragesof,respectively,thepercentagerelativestandarddeviationsandaveragevaluesforeverytypeofstack
tested.
Peak Heat Total Heat Peak Smoke Total Smoke Time to Peak
Initial Mass, Mass Loss,
Release Rate, Released, Release Rate, Released, Heat Release Rate,
kg kg
2 2
kW MJ m /s m min
A 0.14 −79 41 0.48 163 0.30 −0.59
B 0.011 0.25 −0.065 −0.0058 0.022 0.075 0.26
Avg 37.7 863 265 5.1 1235 9.6 12.1
RSD% 1 14 14 17 18 16 20
X4.6. Three tests were conducted for each type of stacking statistical considerations and information from the test lab
chair in Test Configuration C (furniture calorimeter). The reports submitted. It should be noted that some tests in some
percentage relative standard deviation or coefficient of varia- laboratories were incorrectly terminated before the mandated
tion) (100 times the ratio of the standard deviation and the end point, after some guidelines were exceeded. The complete
average) for various properties (initial mass, peak heat release set of major data was also analyzed, without eliminating any
rate, total heat release, peak smoke release rate, total smoke datapoint,withthestatisticalanalysisincludedasTable3.Itis
release, mass loss, and time to peak heat release rate) were
possible to conduct an analysis of the data that excludes all
averaged for all tests (see Table 1). The constant (A) and
incorrect data but does not exclude outliers, but that was not
coefficient (B) correspond to the terms in the equation:
done. A Research Report has been submitted to ASTM which
includesalltheinformationrequiredforafullunderstandingof
Repeatability ~r! 5 A1B*property (1)
results. The user is encouraged to consult this research report
The results shows that the average of the relative standard
entitled: “Test Methods E1537 & E1822 Interlaboratory Pre-
deviations is less than 25% for all properties analyzed,
cision Study, Prepared by:ASTM E05.15” (2001). The abbre-
although some individual relative standard deviations also
viations used are as follows: peak rate of heat release (Pk
exceed 20%.
RHR), total heat released (THR), mass loss at 10 min (Mass
13.1.2 Interlaboratory Repeatability and Reproducibility—
Loss @ 10), peak rate of smoke release (Pk RSR), total smoke
Table 2 and Table 3 show the precision obtained in an
released (RSR), standard deviation for repeatability and repro-
interlaboratory round-robin evaluation conducted with 4
ducibility (STD repeat and STD Repro), relative standard
laboratories, using three sets of stacking chairs (labeled S1 to
deviationforrepeatabilityandreproducibility(RSDrepeatand
S3), stacked in groups of 5 for test, supplied by different
RSD Repro), repeatability (r) and Reproducibility (Repro).
manufacturers, and all commercially available. Two of the
13.2 Bias:
laboratories conducted the tests using the “ASTM room,” and
the other two used the “California room.” The data obtained 13.2.1 No information is presented on the bias of the
from all four laboratories were analyzed. In Table 2, outliers procedure in this test method because correct values of
and "obviously incorrect data" were excluded, using standard fire-test-response characteristics of stacked chairs can only be
TABLE 2 Intralaboratory and Interlaboratory Precision Results of Round Robin Evaluation Excluding Outliers and Incorrect Data
Stack Property/Units Average STD repeat STD Repro r R RSD repeat RSD Repro
S1 Pk RHR/kW 14.7 4.3 4.3 12.0 12.0 29.2 29.2
S2 Pk RHR/kW 23.6 8.7 8.7 24.5 24.5 37.0 37.0
S3 Pk RHR/kW 503.4 156.4 156.4 437.8 437.8 31.1 31.1
S1 THR @ 10/MJ 1.7 1.6 1.6 4.4 4.4 94.4 94.4
S2 THR @ 10/MJ 3.8 2.1 2.1 5.8 5.8 53.8 53.8
S3 THR @ 10/MJ 70.8 39.8 39.8 111.6 111.6 56.3 56.3
S1 time to Pk RHR/s 110.9 29.9 64.7 83.8 181.1 27.0 58.3
S2 time to Pk RHR/s 436.0 745.2 745.2 2086.5 2086.5 170.9 170.9
S3 time to Pk RHR/s 595.5 131.2 131.2 367.3 367.3 22.0 22.0
S1 Mass Loss @ 10/kg 0.2 0.3 0.3 0.8 0.8 167.0 167.0
S2 Mass Loss @ 10/kg 0.3 0.1 0.2 0.4 0.6 49.9 75.6
S3 Mass Loss @ 10/kg 7.2 2.4 2.4 6.6 6.6 32.6 32.6
S1 Pk RSR, m /s 0.6 1.1 1.1 3.1 2.1 174.3 174.3
S2 Pk RSR, m /s 1.0 0.7 0.9 1.9 2.4 67.7 85.1
S3 Pk RSR, m /s 1.9 0.7 0.7 2.0 2.0 37.0 37.0
S1 TSR, m 91.6 45.4 78.3 127.1 219.3 49.6 85.5
S2 TSR, m 78.2 61.1 64.5 171.1 180.6 78.1 82.4
S3 TSR, m 697.1 210.1 350.1 588.2 980.3 30.1 50.2
S1 time to Pk RSR/s 119.9 45.1 45.1 126.3 126.3 137.6 137.6
S2 time to Pk RSR/s 82.9 6.0 6.0 16.9 16.9 7.3 7.3
S3 time to Pk RSR/s 793.2 955.8 955.8 2676.3 2676.3 120.5 120.5
E1822 − 21
TABLE 3 Intralaboratory and Interlaboratory Precision Results of Round Robin Evaluation of Without Excluding Outliers or Incorrect
Data
Stack # labs Average STD repeat STD Repro r R RSD repeat RSD Repro
Peak RHr/kW
S1 4 63.2 86.02 119.3 240.9 334.0 136.1 188.8
S2 4 38.2 50.8 53.2 142.2 149.0 133.0 139.3
S3 4 505.7 78.9 163.6 220.9 458.1 15.6 32.4
Total Heat Released @ 10 min/MJ
S1 4 1.74 0.79 0.79 2.2 2.2 45.4 45.4
S2 4 3.73 1.11 2.08 3.1 5.8 29.8 55.8
S3 4 71.5 20.8 46.7 58.2 130.8 29.1 65.3
time to peak RHR/s
S1 4 349 430 556 1204.0 1556.8 123.2 159.3
S2 4 631 820 979 2296.0 2741.2 130.0 155.2
S3 4 592 72.8 173.7 203.8 486.4 12.3 29.3
Mass Loss @ 10 min/kg
S1 4 0.19 0.15 0.24 0.4 0.7 78.9 126.3
S2 4 1.47 4.11 4.29 11.5 12.0 279.6 291.8
S3 4 7.15 1.16 4.73 3.2 13.2 16.2 66.2
Peak RSR/m /s
S1 4 0.71 0.55 0.78 1.5 2.2 77.5 109.9
S2 4 1.02 0.68 1.27 1.9 3.6 66.7 124.5
S3 4 4.32 3.78 5.97 10.6 16.7 87.5 138.2
Total Smoke Released @ 10 min/m
S1 4 68.3 74.3 92.3 208.0 258.4 108.8 135.1
S2 4 259 52.8 433 147.8 1212.4 20.4 167.2
S3 4 929 964 10010 2699.2 28028.0 103.8 1077.5
Total Smoke Released entire test/m
S1 4 177.5 299.6 301.5 838.9 844.2 168.8 169.9
S2 4 1539 1165 3073 3262.0 8604.4 75.7 199.7
S3 4 816 484 721 1355.2 2018.8 59.3 88.4
time to peak RSR/s
S1 4 218 201 264 562.8 739.2 92.2 121.1
S2 4 442 804 969 2251.2 2713.2 181.9 219.2
S3 4 715 509 717 1425.2 2007.6 71.2 100.3
defined in terms of a test method. Within this limitation, this testing relevant to this test method, this is not practical, since
testmethodhasnoknownbias
...


This document is not an ASTM standard and is intended only to provide the user of an ASTM standard an indication of what changes have been made to the previous version. Because
it may not be technically possible to adequately depict all changes accurately, ASTM recommends that users consult prior editions as appropriate. In all cases only the current version
of the standard as published by ASTM is to be considered the official document.
Designation: E1822 − 17 E1822 − 21 An American National Standard
Standard Test Method for
Fire Testing of Stacked Chairs
This standard is issued under the fixed designation E1822; the number immediately following the designation indicates the year of
original adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. A
superscript epsilon (´) indicates an editorial change since the last revision or reapproval.
1. Scope*
1.1 This is a fire-test-response standard.
1.2 This test method provides a means of determining the burning behavior of stacking chairs used in public occupancies by
measuring specific fire-test responses when a stack of chairs is subjected to a specified flaming ignition source under well ventilated
conditions.
1.3 This test method is limited to stacked chairs.
1.4 Test data are obtained describing the burning behavior following application of a specific ignition source, from ignition until
all burning has ceased, a period of 1 hone hour has elapsed, or flashover under test conditions appears inevitable.
1.5 This test method does not provide information on the fire performance of stacked chairs under fire conditions other than those
conditions specified in this test method. In particular, this test method does not apply to smoldering ignition by cigarettes. See 5.11
for further information.
1.6 The rate of heat release of the burning test specimen is measured by an oxygen consumption method. See 5.11.4 for further
information.
1.7 Other measurements are the production of light-obscuring smoke and the concentrations of certain toxic gas species in the
combustion gases. See 5.11.5 for further information.
1.8 The burning behavior is documented visually by photographic or video recordings.
1.9 This standard is used to measure and describe the response of materials, products, or assemblies to heat and flame under
controlled conditions, but does not by itself incorporate all factors required for fire hazard or fire risk assessment of the materials,
products or assemblies under actual fire conditions.
1.10 Fire testing is inherently hazardous. Adequate safeguards for personnel and property shall be employed in conducting these
tests.
This test method is under the jurisdiction of ASTM Committee E05 on Fire Standards and is the direct responsibility of Subcommittee E05.15 on Furnishings and
Contents.
Current edition approved Nov. 1, 2017Nov. 15, 2021. Published December 2017December 2021. Originally approved in 1996. Last previous edition approved in 20132017
as E1822 – 13.E1822 – 17. DOI: 10.1520/E1822-17.10.1520/E1822-21.
*A Summary of Changes section appears at the end of this standard
Copyright © ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959. United States
E1822 − 21
1.11 Use the SI system of units in referee decisions; see IEEE/ASTM SI-10. The units given in parentheses are for information
only.
1.12 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility
of the user of this standard to establish appropriate safety, health, and environmental practices and determine the applicability of
regulatory limitations prior to use.
1.13 This international standard was developed in accordance with internationally recognized principles on standardization
established in the Decision on Principles for the Development of International Standards, Guides and Recommendations issued
by the World Trade Organization Technical Barriers to Trade (TBT) Committee.
2. Referenced Documents
2.1 ASTM Standards:
D123 Terminology Relating to Textiles
E84 Test Method for Surface Burning Characteristics of Building Materials
E176 Terminology of Fire Standards
E800 Guide for Measurement of Gases Present or Generated During Fires
E1354 Test Method for Heat and Visible Smoke Release Rates for Materials and Products Using an Oxygen Consumption
Calorimeter
E1474 Test Method for Determining the Heat Release Rate of Upholstered Furniture and Mattress Components or Composites
Using a Bench Scale Oxygen Consumption Calorimeter
E1537 Test Method for Fire Testing of Upholstered Furniture
E1590 Test Method for Fire Testing of Mattresses
IEEE/ASTM SI-10 American National Standard for Use of the International System of Units (SI): The Modern Metric System
2.2 ISO Standards:
ISO 4880 Burning Behaviour of Textiles and Textile Products—Vocabulary
ISO 9705 Fire Tests—Full Scale Room Test for Surface Products
ISO 13943 Fire Safety—Vocabulary
2.3 UL Standards:
UL 1056 Fire Test of Upholstered Furniture (withdrawn)
UL 1895 Fire Test of Mattresses (withdrawn)
2.4 CA Standards:
CA TB 129, Flammability Test Procedure for Mattresses for Use in Public Buildings
CA TB 133, Flammability Test Procedure for Seating Furniture for Use in Public Occupancies (withdrawn)
2.5 NFPA Standard:
NFPA 289 Standard Method of Fire Test for Individual Fuel Packages
2.6 Other Document:
Nordtest Method NT Fire 032 Upholstered Furniture: Burning Behavior—Full Scale Test
3. Terminology
3.1 Definitions—For definitions of terms used in this test method and associated with fire issues, refer to Terminology E176 and
ISO 13943. In case of conflict, the definitions in Terminology E176 shall prevail. For definitions of terms used in this test method
and associated with textile issues refer to Terminology D123 and ISO 4880. In case of conflict, the definitions in Terminology D123
shall prevail.
3.2 Definitions of Terms Specific to This Standard:
3.2.1 stacking chair, n—chair that is intended to be stacked when not in use.
For referenced ASTM standards, visit the ASTM website, www.astm.org, or contact ASTM Customer Service at service@astm.org. For Annual Book of ASTM Standards
volume information, refer to the standard’s Document Summary page on the ASTM website.
Available from International Organization for Standardization (ISO), 1, ch. de la Voie-Creuse, Case postale 56, CH-1211, Geneva 20, Switzerland, http://www.iso.ch.ISO
Central Secretariat, Chemin de Blandonnet 8, CP 401, 1214 Vernier, Geneva, Switzerland, https://www.iso.org.
Available from Underwriters Laboratories (UL) (hard copy only), 333 Pfingsten Rd., Northbrook, IL 60062-2096, http://www.ul.com. UL 1056 withdrawn / August 11,
2000. UL 1895 withdrawn Feb. 11, 2000.
Available from California Bureau of Home Furnishings and Thermal Insulation,Household Goods and Services (BHGS), State of California, Department of Consumer
Affairs, 3485 Orange Grove Ave., North Highlands, CA 95660-5595.95660-5595, https://bhgs.dca.ca.gov/industry/tb129.pdf and https://bhgs.dca.ca.gov/industry/tb133.pdf
Available from National Fire Protection Association (NFPA), 1 Batterymarch Park, Quincy, MA 02169-7471, http://www.nfpa.org.
Available from Nordtest, P.O. Box 22, SF-00341, Helsingfors, Finland.Finland, http://www.nordtest.info/wp/1991/05/14/upholstered-furniture-burning-behaviour-full-
scale-test-nt-fire-032/
E1822 − 21
3.2.2 test specimen, n—stack of five identical stacking chairs.
3.2.3 upholstered, adj—covered with material (as fabric or padding) to provide a soft surface.
3.2.4 upholstered seating furniture, n—a unit of interior furnishing that (1) contains any surface that is covered, in whole or in part,
with a fabric or other upholstery cover material, (2) contains upholstery material, and (3) is intended or promoted for sitting upon.
3.2.5 upholstery cover material, n—the outermost layer of fabric or related material used to enclose the main support system, or
upholstery materials, or both, used in the furniture unit.
3.2.6 upholstery material, n—the padding, stuffing, or filling material used in a furniture item, which may be either loose or
attached, enclosed by an upholstery cover material, or located between the upholstery cover material and support system, if present.
3.2.6.1 Discussion—
This includes, but is not limited to, material such as foams, cotton batting, polyester fiberfill, bonded cellulose, or down.
4. Summary of Test Method
4.1 This fire-test-response test method determines a number of fire-test-response characteristics associated with a stack of five
stacking chairs, ignited with a propane gas burner. Measurements to be made include the rate of heat and smoke release, total
amount of heat released, rates and concentrations of carbon oxides released, and rates and amounts of mass of test specimen lost.
Other optional measurements are also described.
4.2 In Test Configurations A and B, the test specimen is placed on a weighing platform located in a test room. An exhaust hood,
connected to a duct, is located at the doorway of the room.
4.3 In Test Configuration C, the test specimen is placed on a weighing platform located directly under a hood.
4.4 Heat, smoke, and combustion gas release instrumentation is placed in the duct.
4.5 Additional (optional) instrumentation placed in the test room is also described.
5. Significance and Use
5.1 This test method provides a means of measuring a variety of fire-test-response characteristics resulting from burning a stack
of five stacking chairs. After ignition using a propane gas burner, the test specimen is permitted to burn freely under well-ventilated
conditions. The most important fire-test-response characteristic measured in this test method is the rate of heat release, which
quantifies the intensity of the fire generated.
5.2 The rate of heat release is measured by the principle of oxygen consumption. Annex A3 discusses the assumptions and
limitations.
5.3 This test method also provides measures of other fire-test-response characteristics, including smoke obscuration (as the rate
of smoke release, total smoke released or optical density of smoke), combustion gas release (as concentrations of combustion
gases), and mass loss, that are important to making decisions on fire safety.
5.4 In the majority of fires, the most important gaseous components of smoke are the carbon oxides present in all fires. They are
indicators of the toxicity of the atmosphere and of the completeness of combustion. Measurement of concentrations of carbon
oxides are useful for two purposes: as part of fire hazard assessment calculations and to improve the accuracy of heat-release
measurements. Other toxic combustion gases, which are specific to certain materials, are also indicators of the toxicity of the
atmospheres, but are less crucial for determining combustion completeness and are optional measures; however fire hazard
assessment often requires their measurement.
5.5 The type of ignition chosen (flaming source) is common in both accidental and intentional fires in public occupancies. This
E1822 − 21
test method is thus applicable to stacked chairs in public occupancies. Such facilities include, but are not limited to, health-care
facilities, old-age convalescent and board and care homes, college dormitories and residence halls, and hotels and motels.
5.6 One of the following three configurations is to be used in this test method:
5.6.1 Test Configuration A—A test room with the following dimensions: 3.66 by 2.44 by 2.44 m high (12 by 8 by 8 ft).
5.6.2 Test Configuration B—A test room with the following dimensions: 3.66 by 3.05 by 2.44 m high (12 by 10 by 8 ft).
5.6.3 Test Configuration C—An open calorimeter (or furniture calorimeter).
5.7 Rooms of other dimensions are acceptable where it has been shown that equivalent test results are obtained.
5.8 Measurements in the three test configurations listed in 5.6 have been shown to give similar results for heat release in the duct
and mass loss up to a rate of heat release of 600 kW (1).
5.9 Measurements of temperatures, gas concentrations, and smoke obscuration in the room are dependent on room size.
5.10 Studies on the flammability performance of furniture indicate that bench-scale fire tests are useful for preliminary evaluations
of component materials for substitution purposes (see Appendix X3).
5.11 Limitations:
5.11.1 This test method is not applicable to ignition by cigarettes or by any other smoldering source.
5.11.2 The ignition source in this test method is a flaming source. Moreover, this particular ignition source has been shown to be
able to provide a distinction among different kinds of stacked chairs. However, the fraction of actual flaming stacked chair fires
occurring with ignitions more or less intense than that used here is not known.
5.11.3 It is not known whether the results of this test method will be equally valid when stacking chairs are burned under
conditions different from those specified. In particular, it is unclear whether the use of a different ignition source, the same ignition
source but having a different duration of flame exposure, or a different gas-flow rate will change the results.
5.11.4 The value of rate of heat release corresponding to the critical limit between propagating fires and nonpropagating fires is
not known.
5.11.5 As yet, there is not a known direct correlation between smoke obscuration or smoke toxicity measurements in the exhaust
duct and overall fire hazard.
6. Apparatus
6.1 Room Layout and Instrumentation:
6.1.1 Test Room Layout (Test Configuration A)—The test room shall have dimensions of 2.44 m 6 25 mm by 3.66 m 6 25 mm
by 2.44 m 6 25 mm high (8 by 12 by 8 ft). The room shall have no openings other than a doorway opening 0.76 m 6 6.4 mm
by 2.03 m 6 6.4 mm (30 by 80 in.), located as indicated in Fig. 1, and other small openings, as necessary to make test
measurements. Construct the test room of wooden or metal studs and line it with fire-rated gypsum wallboard or calcium silicate
wallboard. Position a hood, as described in Annex A1, outside the room doorway, such that it collects all of the combustion gases.
There shall be no obstructions to the air supply to the test setup.
NOTE 1—Both Type X gypsum wallboard and calcium silicate wallboard with a nominal thickness of at least 13 mm (0.5 in.) have been found acceptable.
If the thickness of the wallboard used is greater, it will not affect the results of this test method.
6.1.2 Test Room Layout (Test Configuration B)—The test room shall have dimensions of 3.05 m 6 25 mm by 3.66 m 6 25 mm
The boldface numbers in parentheses refer to the list of references at the end of this test method.
E1822 − 21
NOTE 1—See text for tolerances; room instrumentation is optional.
FIG. 1 Test Room Configuration for Test Configuration A
by 2.44 m 6 25 mm high (10 by 12 by 8 ft). The room shall have no openings other than a doorway opening 0.97 m 6 6.4 mm
by 2.06 m 6 6.4 mm (38 by 81 in.), located as indicated in Fig. 2, and other small openings, as necessary to make test
measurements. Construct the test room of wooden or metal studs, and line it with fire-rated gypsum wallboard or calcium silicate
wallboard. Position a hood, as described in Annex A1, outside the room doorway, such that it collects all of the combustion gases.
There shall be no obstructions to the air supply to the test setup.
NOTE 2—Both Type X gypsum wallboard and calcium silicate wallboard with a nominal thickness of at least 13 mm (0.5 in.) have been found acceptable.
If the thickness of the wallboard used is greater, it will not affect the results of this test method.
6.1.3 Open Calorimeter Layout (Test Configuration C):
6.1.3.1 The area surrounding the test specimen in an open calorimeter layout shall be sufficiently large that there are no heat
radiation effects from the walls or any other nearby objects. The airflow to the test specimen shall be symmetrical from all sides.
6.1.3.2 If the heat release rate of the test specimen is below 600 kW, a load cell sited under a hood, and where the distance between
the test specimen and any wall is 1 m (3.3 ft) or more, is acceptable.
6.1.3.3 The air supply to the calorimeter shall be sufficient so that it does not affect the burning process.
6.1.4 General Discussion of Room Layout:
6.1.4.1 Heat release measurements in the duct, made in Test Configurations A, B, and C have been shown to give similar results
for heat release rates below 600 kW (see X1.4) (1).
6.1.5 Other Test Room Furnishings—The test room shall contain no furnishings except for the test specimen.
E1822 − 21
NOTE 1—See text for tolerances; room instrumentation is optional.
FIG. 2 Test Room Configuration for Test Configuration B
6.1.6 Location of Test Specimen, for Test Configurations A or B—Position the test specimen on a weighing platform in a corner.
Ensure that the test specimen is at a distance of between 0.10 and 0.25 m (4 and 10 in.) from both walls (Fig. 1 and Fig. 2).
6.1.7 Location of Test Specimen, for Test Configuration C—Position the test specimen on a weighing platform underneath the
hood.
6.2 Ignition Source:
6.2.1 Use as the ignition source a gas burner in the shape of a T, as shown in Fig. 3.
6.2.2 Construct the burner of stainless steel with wall thicknesses of 0.89 6 0.05 mm (0.035 6 0.002 in.). Make the head of the
T205 6 10 mm (8 6 0.4 in.) long and 13 6 1 mm (0.5 6 0.04 in.) outside diameter. Plug the ends of the T. As shown in Fig.
3(a) and Fig. 3(b), construct the burner with two sets of holes equally spaced and centered along the head of the burner and oriented
90° to one another. One set consists of 14 holes and the other set of nine holes, each hole spaced 13 6 1 mm (0.5 6 0.04 in.) from
the next. Make the holes 1 6 0.04 mm (0.039 6 0.002 in.) in diameter.
NOTE 3—It is common for the burner holes to become clogged following a test. Inspect burner holes after each test and clean thoroughly if required. Take
care not to enlarge the holes when cleaning them.
6.2.3 Construct the handle of the burner of stainless steel with the same diameter and thickness as the head. Weld it to the head
in the orientation shown in Fig. 3(c). When the 14 holes in the head are oriented 45° above the horizontal and the nine holes are
E1822 − 21
3(a) Burner Head Showing Top Set of Holes
3(b) Burner Head Showing Bottom Set of Holes
3(c) Side View of Burner Showing Orientation of the Head with the Handle
NOTE 1—See text for tolerances.
FIG. 3 View of T-Shaped Gas Burner
oriented 45° below the horizontal, the handle is approximately 30° above the horizontal. Construct the handle such that it is at least
450 mm (18 in.) long to facilitate its attachment to the support and the propane line.
NOTE 4—To align the burner to the test specimen properly, it is necessary to position the head as described below; therefore, the angle between the handle
and the head is not critical.
6.2.4 Use propane gas with a known net heat of combustion of 46.5 6 0.5 MJ/kg as a fuel for this ignition source. Meter the flow
rate of propane at 12 6 0.25 L/min, at a pressure of 101 6 5 kPa (standard atmospheric pressure measured at the flow gage), and
a temperature of 20 6 5°C 5 °C or at a flow equivalent to these values. Use flexible tubing fed into the handle of the burner to
deliver the propane to the burner. Maintain the flow rate constant of propane while the flame is lit. Mount the burner on an
adjustable pole, with a counterweight if necessary, to allow the burner to be positioned in the proper location for ignition of the
test specimen and then swung out of the way after the propane gas flame is turned off.
6.2.5 The approximate ratio of heat release rate output to gas flow rate is 1.485 kW min/L under standard conditions. Thus, the
calculated rate of heat release from the burner at the temperature and pressure given above is 17.8 kW.
6.2.6 Location of Gas Burner:
6.2.6.1 Orient the burner with respect to the test specimen as shown in Fig. 3 (a, b, and c).
6.2.6.2 Ensure that the horizontal plane of the head of the burner (depicted in Fig. 3(c)) is level with the bottom horizontal surface
of the lowest chair in the test specimen. This orientation shall be such that the 14 holes are directed at the test specimen at an angle
of 45° above the horizontal, and the nine holes are directed under the lowest chair in the test specimen at an angle 45° 45 ° below
the horizontal. The handle will be set, nominally, at 30° 30 ° above the horizontal.
E1822 − 21
6.2.6.3 Locate the burner during ignition in such a way that the burner is parallel with the front edge of the lowest chair in the
test specimen, 25 6 2 mm (1 6 0.1 in.) from the vertical edge of the chair and 50 6 2 mm (2 6 0.1 in.) below the bottom
horizontal edge of the lowest chair in the test specimen, as shown in Fig. 4.
6.3 Mass Loss Measurements:
6.3.1 Use a weighing platform to measure the mass of the burning test specimen continuously. Construct a weighing platform
consisting of a horizontal thermal barrier, as described in 6.3.2, and placed on top of a mass measuring device.
6.3.2 Construct a thermal barrier large enough to prevent melting or falling material from the tested stacked chairs specimen from
falling off the thermal barrier. The barrier shall consist of a galvanized steel pan with a gypsum board lining placed on the test
specimen. The barrier shall be used to protect the load cell. The pan shall be constructed of nominally 1.6 mm ( ⁄16 in.) thick steel,
and have dimensions of no less than 1.0 by 1.0 m (39 by 39 in.), with a uniform raised lip of the same material, 100 6 10 mm
(approximately 4 in.) high, on each side, to catch falling material. The bottom of the pan shall be covered by a tight-fitting section
of standard gypsum board (finish side up), of nominally 13 mm (0.5 in.) thickness. The gypsum board shall be clean before the
start of a test; the board shall be replaced for each test.
6.3.3 Measure the test specimen mass continuously with a device capable of an accuracy of no less than 6150 g up to at least
90 kg. Install it in such a way that neither the heat from the burning test specimen nor any eccentricity of the load will affect the
accuracy. Do not make any range shifts during measurements. Install all parts of the mass measuring device below the top level
of the thermal barrier.
6.3.4 The distance from the upper surface of the thermal barrier to floor level shall not exceed 0.3 m (12 in.). The area between
the thermal barrier and the floor level shall be shielded by a skirt at the perimeter of the barrier to prevent lifting forces due to
fire-induced air flow that influence the measurement.
6.4 Exhaust Collection System:
6.4.1 General:
6.4.1.1 Construct the exhaust collection system with the following minimal requirements: a blower, steel hood, duct, bidirectional
probe, thermocouple(s), oxygen measurement system, smoke obscuration measurement system (white light photocell lamp/
detector or laser), and combustion gas sampling and analysis system. Construct the exhaust collection system as shown in Fig. 5
and as explained in Annex A1.
6.4.1.2 Ensure that the system for collecting the smoke (that includes gaseous combustion products) has sufficient exhaust capacity
and is designed in such a way that all of the combustion products leaving the burning test specimen are collected. Design the
capacity of the evacuation system such that it will exhaust minimally all combustion gases leaving the test specimen (see A1.1.4).
6.4.1.3 Place probes for sampling of combustion gas and for measurement of flow rate in accordance with 6.5.
NOTE 1—This example of upholstered chairs has no gaps between the seats or backs. The burner is placed below the bottom of the seat cushion frame.
FIG. 4 Positioning of the Ignition Source—T Burner
E1822 − 21
FIG. 5 Design of Hood and Exhaust System
6.4.1.4 Make all measurements of smoke obscuration, gas concentrations, or flow rates at a position in the exhaust duct where the
exhaust is mixed uniformly so there is a nearly uniform velocity across the duct section.
6.4.1.5 To ensure uniform mixing of the exhaust, provide a straight section of duct before the measuring system having a length
equal to at least eight times the inside diameter of the duct. If a measuring system is positioned at a distance of less than eight
diameters, demonstrate the achievement of equivalent results.
6.5 Instrumentation in Exhaust Duct:
6.5.1 The following specifications are minimum requirements for exhaust duct instrumentation. Additional information is given
in Annex A2.
6.5.2 Flow Rate—Measure the flow rate in the exhaust duct by a bidirectional probe or an equivalent measuring system with an
accuracy of at least 66 % (see Annex A2). The response time to a stepwise change of the duct flow rate shall not exceed 5 s to
reach 90 % of the final value.
6.6 Combustion Gas Analysis:
6.6.1 Sampling Line—Construct the sampling line tubes of a material not influencing the concentration of the combustion gas
species to be analyzed. The following sequence of the gas train has been shown to be acceptable: sampling probe, soot filter, cold
trap, gas path pump, vent valve, plastic drying column and carbon dioxide removal columns (if used), flow controller, and oxygen
analyzer (see Fig. 6 and Annex A2). Alternative designs of the sampling line must yield equivalent results. The gas train shall also
include appropriate spanning and zeroing facilities.
6.6.2 Oxygen Measurement—Measure the oxygen concentration with an accuracy of 60.01 vol % oxygen, or better, in order to
have adequate measurements of rate of heat release. Take the combustion gas sample from the end of the sampling line. Calculate
the time delay, including the time constant of the instrument, from the test room; it is a function of the exhaust duct flow rate. This
time delay shall not exceed 60 s (see Annex A2).
6.6.3 Carbon Monoxide and Carbon Dioxide Measurement—Measure the combustion gas species with an instrument having an
accuracy of at least 60.1 vol % for carbon dioxide and 60.02 vol % for carbon monoxide. A suitable output range is from 0 to
1 vol % for carbon monoxide and from 0 to 6 vol % for carbon dioxide. Take the combustion gas sample from the end of the
sampling line. Calculate the time delay, including the time constant of the instrument, from the test room; it is a function of the
exhaust duct flow rate. It shall be a maximum of 60 s (see Annex A2).
6.6.4 For optional measurement of other combustion gases see A2.3.3.
E1822 − 21
FIG. 6 Schematic of Gas Train
6.7 Smoke Obscuration Measurement:
6.7.1 Install an optical system for measurement of the light obscuration across the centerline of the exhaust duct. Determine the
optical density of the smoke by measuring the light transmitted with a photometer system consisting of a white light source and
a photocell/detector or a laser system for measurement of light obscuration across the centerline of the exhaust duct.
6.7.2 One photometer system found suitable consists of a lamp, lenses, an aperture, and a photocell (see Fig. 7 and Annex A2).
Construct the system so soot deposits on the optics during a test. Do not reduce the light transmission by more than 5 %.
6.7.3 Alternatively, instrumentation constructed using a 0.5 to 2.0 mW helium-neon laser instead of a white-light system is also
acceptable (see Fig. 8, Fig. A1.1, and Annex A2). It has been shown that white-light and laser systems will provide similar results
(see Refs (2-5)).
7. Test Specimen
7.1 The test specimen is a stack of five identical stacking chairs, or prototype thereof.
7.2 If prototype stacking chairs are used, the prototypes shall, in all respects, reflect the construction of the actual stacking chairs.
7.3 Fire tests of stacking chairs have shown that the fire performance of stacked chairs is significantly affected by chair design
and configuration, the gap between adjacent seat surfaces, and the vertical gap between adjacent seat backs. Therefore, it is critical
to ensure that the five stacking chairs are carefully stacked in accordance with the design features of the chairs to be tested.
8. Calibration
8.1 Calibrate all instruments carefully with standard sources after initial installation. Among the instruments to be calibrated are
FIG. 7 Optical System Using a White Light
E1822 − 21
FIG. 8 Laser Extinction Beam
load cells or weighing platforms, smoke meters, flow or velocity transducers, and gas analyzers. Perform recalibration tests on the
entire system, for example using standard output burners.
8.2 Heat Release:
8.2.1 Perform the calibration of the heat release instrumentation in the exhaust duct by burning propane or methane gas and
comparing the heat release rates calculated from the metered gas input and those calculated from the measured oxygen
consumption. The value of net heat of combustion for methane is 50.0 MJ/kg and for propane is 46.5 MJ/kg. Position the burner
in the same location where the test specimen is to be placed during the test. Measure the gas flow rate at a pressure of 101 6 5
kPa (standard atmospheric pressure, measured at the flow gage) and a temperature of 20 6 5°C.5 °C.
8.2.2 A suitable calibration burner is a sand diffusion burner with a 0.3 by 0.3 m (12 by 12 in.) top surface and a 0.15 m (6 in.)
depth. Construct such a gas burner with a 25 mm (1 in.) thick plenum. Alternatively, use a minimum 100 mm (4 in.) layer of Ottawa
sand to provide the horizontal surface through which the gas is supplied. This burner is shown in Fig. 9. The gas supply to the
burner shall be propane (the same quality used for the ignition burner) or methane. The gas for the burner flame shall not be
premixed with air. Meter the flow rate of gas and keep it constant throughout the calibration test.
8.2.3 Another suitable calibration burner is a pipe with an inner diameter of 100 6 1.5 mm (4 in.) supplied with gas from beneath
(see ISO 9705). The gas for the burner flame shall not be premixed with air.
8.2.4 Obtain a minimum of two calibration points. Obtain a lower heat release rate value of 40 kW and then a higher heat release
rate value of 160 kW. Approximate propane flow rates for any required heat release rate value are estimated using the following
constant: 1.485 kW min/L, determined at a pressure of 101 6 5 kPa (standard atmospheric pressure; measured at the flow gage)
and a temperature of 20 6 5°C.5 °C.
8.2.5 Take measurements at least once every 6 s and start 1 min prior to ignition of the burner. Determine the average rate of heat
release over a period of at least 1 min by the oxygen consumption method and calculating the heat release rate from the gas mass
flow rate and the net heat of combustion. The difference between the two values shall not exceed 5 %. This comparison shall be
made only after steady-state conditions have been reached.
8.2.6 Perform a calibration test in accordance with 8.5 prior to each continuous test series. Perform a full basic calibration on a
new system or when modifications are introduced.
8.2.7 When calibrating a new system, or when modifications are introduced, check the response time of the measuring system by
the following test sequence:
Time, min Burner Output, kW
0–5 0
5–10 40
10–15 160
15–20 0
E1822 − 21
NOTE 1—See text for tolerances.
FIG. 9 Calibration Gas Burner
The response of the system to a stepwise change of the heat output from the burner shall be a maximum of 12 s to 90 % of final
value.
8.2.8 Perform the calibration given in 8.2.7 with the initial duct air flow rate equal to that to be used in the test procedure.
8.2.9 The change in measured rate of heat release, comparing time average values over 1 min, shall not be more than 10 % of the
actual heat output from the burner.
8.2.10 The use of a higher rate of heat release for calibration, for example 500 kW, will generally lead to higher accuracy in the
test results.
8.3 Mass Loss—Perform calibration of the mass-measuring device by loading the weighing platform with known masses
corresponding to the measuring range of interest, to ensure that the requirements of accuracy in 6.3.3 are fulfilled. Carry out this
calibration daily, prior to testing.
8.4 Smoke Obscuration—Calibrate the smoke meter initially to read correctly for two neutral density filters of significantly
different values, and also at 100 % transmission. The use of neutral density filters at 0.5 and 1.0 values of optical density has been
shown to be satisfactory for this calibration. Once this calibration is set, only the zero value of extinction coefficient (100 %
transmission) must be verified each day, prior to testing. Investigate any excessive departure from the zero line at the end of a test,
and correct it.
8.5 Gas Analysis—Calibrate the gas analyzers daily, prior to testing (see Guide E800).
9. Conditioning
9.1 Prior to testing, condition the chairs for at least 48 h in an atmosphere at a temperature of 21 6 4°C 4 °C (70 6 7°F) 7 °F)
E1822 − 21
and a relative humidity of less than 60 %. Test the specimen as soon as possible after removal from such conditions if the test room
conditions differ from the above. Report the time between removal from the conditioning room and the start of testing.
10. Procedure
10.1 Initial Conditions:
10.1.1 The ambient temperature shall be above 15°C (60°F) 15 °C (60 °F) and the relative humidity shall be below 75 %.
10.1.2 The horizontal air flow, measured at both the surface and at a horizontal distance of 0.5 m (20 in.) from the edge of the
−1
weighing platform, shall not exceed 0.5 m/s .
10.1.3 Position the test specimen centrally on the weighing platform.
10.1.4 Have available means for extinguishing a fully developed fire.
10.2 Test Procedure:
10.2.1 Perform the measurements needed to obtain the descriptive information needed for the test report.
10.2.2 Weigh the test specimen immediately upon removal from conditioning room and immediately before the start of test.
10.2.3 Place the T-shaped propane gas burner in front of the test specimen, as specified in 6.2.6. Confirm that burner holes have
been cleaned (see Note 3).
10.2.4 Begin all recording and measuring devices 2 min before starting the ignition burner.
10.2.5 Light the ignition burner.
10.2.6 Expose the test specimen to the gas burner flames for 80 s, at a flow rate of 12 L/min, determined at a pressure of 1016
101 6 5 kPa (standard atmospheric pressure, measured at the flow gage) and a temperature of 20 6 5°C.5 °C.
10.2.7 Extinguish the gas flame and remove the burner after the specified burning period (80 s).
10.2.8 Perform a photographic or a video recording before and during each test. An indication of elapsed time, giving time to the
nearest 1 s, shall appear in all photographic records.
10.2.9 During the test, record the following events and the time when they occur, with respect to the time of ignition of the burner:
10.2.9.1 Ignition of the first igniting chair,
10.2.9.2 Location of the flame front at various appropriate times,
10.2.9.3 Melting and dripping,
10.2.9.4 Formation of flaming droplets,
10.2.9.5 Occurrence of pool fire under the test specimen,
10.2.9.6 General description of the burning behavior, and
10.2.9.7 Any other event of special interest.
10.2.10 Terminate the test after the first of the following:
10.2.10.1 All signs of combustion have ceased,
10.2.10.2 One hour of testing has elapsed, or
E1822 − 21
10.2.10.3 Flashover appears inevitable.
10.2.11 Note, from visual inspection of the specimen after the test, the approximate percentage of each surface that was burned
or charred, and the approximate depth of fire damage.
11. Calculation
11.1 Considerations for heat release measurements are presented in Annex A3. Calculate the heat release data, using the equations
presented in A4.1. The testing laboratory shall choose one of the equations given in A4.1 for calculating heat release, based on
the gas analyzers installed.
11.2 Calculate the smoke release data using the equations presented in A4.2.
11.3 Calculate the gas yield data using the equations presented in A4.3.
12. Report
12.1 Report the following descriptive information:
12.1.1 Name and address of the testing laboratory,
12.1.2 Date and identification number of the report,
12.1.3 Name and address of the test requester,
12.1.4 Test configuration used: A, B, or C,
12.1.5 Name of product manufacturer or supplier, if known,
12.1.6 Name or other identification marks and description of the chairs,
12.1.7 Linear dimensions (height, width, depth) of each individual chair and of the test specimen,
12.1.8 Total mass, thickness of the main components and mass of combustible portion of each test specimen,
12.1.8.1 Weight change of the test specimen between removal from conditioning room and start of test,
12.1.9 Density, or mass per unit surface area of the main components in each chair, if known,
12.1.10 Conditioning of the chairs,
12.1.11 Date of the test,
12.1.12 Test number and any special remarks, and
12.1.13 Time between the removal from conditioning room and start of testing.
12.2 Include the following test results in the test report (see also appendixes):
12.2.1 Table of numerical results containing the following:
12.2.1.1 Peak rate of heat release (in kW), and the time at which it occurred,
12.2.1.2 Total heat released (in MJ),
12.2.1.3 Total heat released at 10 min (in MJ),
E1822 − 21
2 −1
12.2.1.4 Peak rate of smoke release (in m /s ), and the time at which it occurred,
12.2.1.5 Total smoke released (in m ),
12.2.1.6 Total smoke released at 10 min (in m ),
12.2.1.7 Total mass loss (in kg),
12.2.1.8 Total mass loss at 10 min (in kg),
12.2.1.9 Total percentage of mass loss (in %),
12.2.1.10 Peak concentration of carbon monoxide (in ppm),
12.2.1.11 Peak temperatures (in °C),
12.2.1.12 Equation used to calculate rate of heat release,
12.2.1.13 Peak optical density of smoke (optional),
12.2.1.14 Average optical density of smoke, over the 10-min period including the peak (optional),
12.2.1.15 Total percentage of combustible mass loss (in %) (optional),
12.2.1.16 Average yield of carbon monoxide (in g CO/g fuel) (optional),
12.2.1.17 Average yield of carbon dioxide (in g CO /g fuel) (optional),
12.2.1.18 Carbon monoxide/carbon dioxide molar yield ratio (optional), and
12.2.1.19 Average yield of any other measured combustion gas (in g combustion gas/g fuel) (optional).
12.2.2 Graphical Results (Optional):
12.2.2.1 Plot of rate of heat release versus time,
12.2.2.2 Plot of rate of smoke release versus time,
12.2.2.3 Plot of optical density versus time,
12.2.2.4 Plot of mass loss versus time,
12.2.2.5 Plot of concentration of carbon monoxide versus time,
12.2.2.6 Plot of concentration of carbon dioxide versus time,
12.2.2.7 Plots of concentration of any other measured combustion gas versus time,
12.2.2.8 Plot of mass flow rate in the exhaust duct versus time,
12.2.2.9 Plot of duct temperature versus time, and
12.2.2.10 Report smoke obscuration, carbon monoxide and temperature measurements in the room in the same fashion, if they
have been made.
12.2.3 Descriptive Results:
E1822 − 21
12.2.3.1 Photographs or videotape of the fire development, and
12.2.3.2 All available information requested in 10.2.9 through 10.2.11.
13. Precision and Bias
13.1 Precision:
13.1.1 Initial Repeatability—The results of a repeatability study from one laboratory, involving six different sets of stacked chairs
are shown in Table 1 and Table X4.1 to Table X4.6. Three tests were conducted for each type of stacking chair in Test Configuration
C (furniture calorimeter). The percentage relative standard deviation or coefficient of variation) (100 times the ratio of the standard
deviation and the average) for various properties (initial mass, peak heat release rate, total heat release, peak smoke release rate,
total smoke release, mass loss, and time to peak heat release rate) were averaged for all tests (see Table 1). The constant (A) and
coefficient (B) correspond to the terms in the equation:
Repeatability r 5 A1B*property (1)
~ !
The results shows that the average of the relative standard deviations is less than 25 % for all properties analyzed, although some
individual relative standard deviations also exceed 20 %.
13.1.2 Interlaboratory Repeatability and Reproducibility—Table 2 and Table 3 show the precision obtained in an interlaboratory
round-robin evaluation conducted with 4 laboratories, using three sets of stacking chairs (labeled S1 to S3), stacked in groups of
5 for test, supplied by different manufacturers, and all commercially available. Two of the laboratories conducted the tests using
the “ASTM room,” and the other two used the “California room.” The data obtained from all four laboratories were analyzed. In
Table 2, outliers and "obviously incorrect data" were excluded, using standard statistical considerations and information from the
test lab reports submitted. It should be noted that some tests in some laboratories were incorrectly terminated before the mandated
end point, after some guidelines were exceeded. The complete set of major data was also analyzed, without eliminating any data
point, with the statistical analysis included as Table 3. It is possible to conduct an analysis of the data that excludes all incorrect
data but does not exclude outliers, but that was not done. A Research Report has been submitted to ASTM which includes all the
information required for a full understanding of results. The user is encouraged to consult this research report entitled: “Test
Methods E1537 & E1822 Interlaboratory Precision Study, Prepared by: ASTM E05.15” (2001). The abbreviations used are as
follows: peak rate of heat release (Pk RHR), total heat released (THR), mass loss at 10 min (Mass Loss @ 10), peak rate of smoke
release (Pk RSR), total smoke released (RSR), standard deviation for repeatability and reproducibility (STD repeat and STD
Repro), relative standard deviation for repeatability and reproducibility (RSD repeat and RSD Repro), repeatability (r) and
Reproducibility (Repro).
13.2 Bias:
13.2.1 No information is presented on the bias of the procedure in this test method because correct values of fire-test-response
characteristics of stacked chairs can only be defined in terms of a test method. Within this limitation, this test method has no known
bias and is acceptable as a reference test method.
13.2.2 For solid test specimens of unknown chemical composition, as used in building materials, furnishings, and common
occupant fuel load, it has been documented that the use of the oxygen consumption standard value of 13.1 MJ/kg oxygen for the
net amount of heat released per unit of oxygen consumed for complete consumption, results in an expected error band of 65 %
TABLE 1 Stacking Chair Test Results—Chair Set 6 (See X4.6)
NOTE 1—A and B represent the constant and coefficient of the equation:
r srepeatabilityd 5A1B*property
NOTE 2—RSD % and Avg represent the averages of, respectively, the percentage relative standard deviations and average values for every type of stack
tested.
Peak Heat Total Heat Peak Smoke Total Smoke Time to Peak
Initial Mass, Mass Loss,
Release Rate, Released, Release Rate, Released, Heat Release Rate,
kg kg
2 2
kW MJ m /s m min
A 0.14 −79 41 0.48 163 0.30 −0.59
B 0.011 0.25 −0.065 −0.0058 0.022 0.075 0.26
Avg 37.7 863 265 5.1 1235 9.6 12.1
RSD% 1 14 14 17 18 16 20
E1822 − 21
TABLE 2 Intralaboratory and Interlaboratory Precision Results of Round Robin Evaluation Excluding Outliers and Incorrect Data
Stack Property/Units Average STD repeat STD Repro r R RSD repeat RSD Repro
S1 Pk RHR/kW 14.7 4.3 4.3 12.0 12.0 29.2 29.2
S2 Pk RHR/kW 23.6 8.7 8.7 24.5 24.5 37.0 37.0
S3 Pk RHR/kW 503.4 156.4 156.4 437.8 437.8 31.1 31.1
S1 THR @ 10/MJ 1.7 1.6 1.6 4.4 4.4 94.4 94.4
S2 THR @ 10/MJ 3.8 2.1 2.1 5.8 5.8 53.8 53.8
S3 THR @ 10/MJ 70.8 39.8 39.8 111.6 111.6 56.3 56.3
S1 time to Pk RHR/s 110.9 29.9 64.7 83.8 181.1 27.0 58.3
S2 time to Pk RHR/s 436.0 745.2 745.2 2086.5 2086.5 170.9 170.9
S3 time to Pk RHR/s 595.5 131.2 131.2 367.3 367.3 22.0 22.0
S1 Mass Loss @ 10/kg 0.2 0.3
...

Questions, Comments and Discussion

Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.

Loading comments...