ASTM C1071-00
(Specification)Standard Specification for Fibrous Glass Duct Lining Insulation (Thermal and Sound Absorbing Material)
Standard Specification for Fibrous Glass Duct Lining Insulation (Thermal and Sound Absorbing Material)
SCOPE
1.1 This specification covers fibrous glass insulation used as a thermal and sound absorbing liner for interior surfaces of ducts, plenums, and other air handling equipment that handle air up to 250oF (121oC).
1.2 The values stated in inch-pound units are the standard. The SI values in parentheses are for information only.
1.3
General Information
Relations
Standards Content (Sample)
NOTICE: This standard has either been superseded and replaced by a new version or withdrawn.
Contact ASTM International (www.astm.org) for the latest information
Designation: C 1071 – 00
Standard Specification for
Fibrous Glass Duct Lining Insulation (Thermal and Sound
1
Absorbing Material)
This standard is issued under the fixed designation C 1071; the number immediately following the designation indicates the year of
original adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. A
superscript epsilon (e) indicates an editorial change since the last revision or reapproval.
2
1. Scope Vapor Sorption of Unfaced Mineral Fiber Insulation
C 1114 Test Method for Steady-StateThermalTransmission
1.1 This specification covers fibrous glass insulation used as
2
Properties by Means of the Thin-Heater Apparatus
a thermal and sound absorbing liner for interior surfaces of
C 1304 Test Method for Assessing the Odor Emission of
ducts, plenums, and other air handling equipment that handle
2
Thermal Insulation Materials
air up to 250°F (121°C).
C 1338 Test Method for Determining Fungi Resistance of
1.2 The values stated in inch-pound units are the standard.
2
Insulation Materials and Facings
The SI values in parentheses are for information only.
E 84 Test Method for Surface Burning Characteristics of
1.3 This standard does not purport to address all of the
3
Building Materials
safety concerns, if any, associated with its use. It is the
E 795 Practices for Mounting Test Specimens During
responsibility of the user of this standard to establish appro-
2
Sound Absorption Tests
priate safety and health practices and determine the applica-
G 21 Practice for Determining Resistance of Synthetic
bility of regulatory limitations prior to use.
4
Polymer Materials to Fungi
2. Referenced Documents G 22 Practice for Determining Resistance of Plastics to
4
Bacteria
2.1 ASTM Standards:
2.2 Other Standards:
C 167 Test Methods for Thickness and Density of Blanket
5
2
NAIMA Fibrous Glass Duct Liner Standard
or Batt Thermal Insulations
6
SMACNA HVAC Duct Construction Standards
C 168 Terminology Relating to Thermal Insulating Materi-
2
UL723 Test for Surface Burning Characteristics of Building
als
7
Materials
C 177 Test Method for Steady-State Heat Flux Measure-
NFPA 255 Standard Method of Test of Surface Burning
ments and Thermal Transmission Properties by Means of
8
2
Characteristics of Building Materials
the Guarded-Hot-Plate Apparatus
NFPA 259 Standard Test Method for Potential Heat of
C 390 Criteria for Sampling and Acceptance of Preformed
8
2
Building Materials
Thermal Insulation Lots
CAN/ULC-S102-M88 Standard Method of Test for Surface
C 411 Test Method for Hot-Surface Performance of High-
2
Burning Characteristics of Building Materials andAssem-
Temperature Thermal Insulation
9
blies
C 423 Test Method for Sound Absorption and Sound Ab-
2
sorption Coefficients by the Reverberation Room Method
3. Terminology
C 518 Test Method for Steady-State Heat Flux Measure-
3.1 For definitions of terms used in this specification, see
ments and Thermal Transmission Properties by Means of
2
Terminology C 168.
the Heat Flow Meter Apparatus
C 665 Specification for Mineral-Fiber Blanket Thermal In-
3
sulation for Light Frame Construction and Manufactured
Annual Book of ASTM Standards, Vol 04.07.
2
4
Housing Annual Book of ASTM Standards, Vol 14.04.
5
Available from North American Insulation Manufacturers Association, 44
C 1104/C 1104M Test Method for Determining the Water
Canal Center Plaza, Suite 310, Alexandria, VA 22314.
6
Available from Sheet Metal and Air Conditioning Contractors National
Association, Inc., 4201 Lafayette Center Drive, Chantilly, VA 22021-1209.
1 7
This specification is under the jurisdiction of ASTM Committee C16 on Available from Underwriters Laboratories Inc., 333 Pfingsten Road, North-
Thermal Insulation and is the direct responsibility of Subcommittee C16.23 on brook, Illinois 60062–2096.
8
Blanket and Loose Fill Insulation. Available from National Fire ProtectionAssociation, 1 Batterymarch Park, PO
Current edition approved Dec. 10, 2000. Published January 2001. Originally Box 9101, Quincy, MA 02269–9101.
9
published as C 1071 – 86. Last previous edition C 1071 – 98. Available from Underwriters Laboratories of Canada, 7 Crouse Road, Scarbor-
2
Annual Book of ASTM Standards, Vol 04.06. ough, Ontario, Canada M1R 3A9.
Copyright © ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959, United States.
1
---------------------- Page: 1 ----------------------
C 1071
4. Classification shall have a maximum flame spread index of 25 and a
maximum smoke developed index of 50.
4.1 The insulation covered by this specification shall be of
7.8 Apparent Thermal Conductivity—When tested in accor-
the following types:
dance with 12.10, the apparent thermal conductivity (k) of the
4.1.1 Type I—Blanket in roll form up to 200 ft (61 m) in
2
insulation,
...