ISO/TC 165/WG 7 - Connections and assemblies
Assemblages et composants
General Information
The design method provided in this document addresses vibration induced by walking action of occupants and covers the following timber floor systems: a) Light frame floors built with timber joists spaced at a distance of no more than 610 mm with a layer of structural wood-based subfloor that is connected to the joists using mechanical fasteners or adhesive. The area density of a bare light frame floors without a screed (topping) and ceiling is not greater than 25 kg/m2. Figure 1 shows such a light frame floor. b) Mass timber floors built with mass timber panels such as cross laminated timber (CLT). This document consists of three elements: a) a baseline vibrational serviceability design criterion for timber floors using fundamental natural frequency and 1 kN static point load deflection as the design parameters including two types of design criteria, coupled and decoupled criteria; b) equations for calculating the design parameters; c) guidelines for the design values of the physical and mechanical properties of floor components. The design method is based on the assumption that the floor system has a single span and simple support conditions.
- Standard15 pagesEnglish languagesale 15% off
The purpose of this document is to extract the methods for determining the yield and ultimate characteristics and ductility of joints and assemblies from test data by reviewing existing standards in Europe, North America and Far East Asia and to provide the basic data for unifying the evaluation methods of parameters by clarifying their similarities and differences. These parameters are applied for determining the seismic performance of timber structures. This document deals with the method for determining the mechanical properties of individual joints and assemblies, and it does not refer to the seismic performance of the entire structure.
- Technical report38 pagesEnglish languagesale 15% off
This document provides standard test methods for determining the vertical load, axial load and torsional moment capacity as well as deflection characteristics of preformed three-dimensional joist hangers that are used primarily for securing one timber member to another (the header can be concrete or masonry). The joist hangers primarily transfer vertical loads from the supported member to the supporting member, but they can also be required to transfer axial loads from the supported member to the supporting member. NOTE 1 Structural steel sections can also be substituted as the header, but are not covered in this document. NOTE 2 One secondary mechanism to be considered is the effect of rotation of the supported member about its longitudinal axis on the joist hanger.
- Standard17 pagesEnglish languagesale 15% off
ISO 18402:2016 specifies test methods for determining, for use in roofs, the structural properties of double-sided load bearing structural insulated panels having - two face layers, at least one of which is a wood-based structural panel, and - a core made of a thermally insulating material having sufficient shear strength to cause the face layers to act together structurally.
- Standard21 pagesEnglish languagesale 15% off
- Standard21 pagesFrench languagesale 15% off
ISO 19049:2016 defines the test method for horizontal diaphragms including floors and horizontal and sloped roofs under static loads. This test method is designated to evaluate the static shear capacity of a typical segment of a diaphragm under applied static loads, and to evaluate the stiffness of the diaphragm assembly.
- Standard9 pagesEnglish languagesale 15% off
ISO 18324:2016 specifies test procedures to measure natural frequencies, modal damping ratios and static deflection under a concentrated load of laboratory or field timber floors. These parameters have been found to correlate well with human perception to timber floor vibration response caused by human-induced excitation under normal use. It is intended that the test procedures can be applied in lieu of calculation to quantify some or all of the above parameters that are used to evaluate the vibrational serviceability of the test floor. The subsequent use of the measured parameters to evaluate vibrational serviceability is, however, outside the scope of this International Standard. ISO published a series of International Standards on the application of modal testing and analysis to determine natural frequencies, modal damping ratios, and other dynamic properties of a structure. For the measurement of dynamic parameters such as natural frequencies and modal damping ratios, modal testing is proposed in this International Standard. It is assumed that the test operators possess the required equipment and fundamental knowledge to perform such a test. The theory of modal testing and analysis has been well documented in Reference [4].
- Standard13 pagesEnglish languagesale 15% off
ISO 17754:2014 specifies a test method to determine the torsional resistance to driving of screws in solid timber or glued laminated timber or other wood-based materials. The method is used primarily to ensure the torque that may be applied to install screws will be less than the specified failure torque of the screw.
- Standard6 pagesEnglish languagesale 15% off
ISO 21581:2010 specifies static and cyclic test methods as a basis for the derivation of lateral load resisting parameters which are required in the wind and seismic design of shear walls in timber buildings.
- Standard14 pagesEnglish languagesale 15% off
ISO 16670:2003 is intended to provide a cyclic test method as a basis for the derivation of parameters which are required in seismic design of timber structures. The method includes procedures to develop the envelope curves (backbone or skeleton curves, an example is given in Clause A.5.) for joints subjected to a cyclic displacement schedule which produces representative demands imposed on the joints by earthquakes. It does not include criteria for parameters which are, at times, stipulated in national standards or building codes. ISO 16670:2003 is intended for joints subjected to lateral load and is not applicable to joints subjected to withdrawal forces. ISO 16670:2003 is applicable to joints made with mechanical fasteners used in timber structures loaded under seismic action.
- Standard9 pagesEnglish languagesale 15% off
ISO 8970:2010 specifies a method, based on density, for the selection of pieces of wood used in determining the strength and stiffness properties of connections made with mechanical fasteners.
- Standard3 pagesEnglish languagesale 15% off
- Standard4 pagesFrench languagesale 15% off





