SIST EN 60947-4-2:2000/A2:2007
(Amendment)Low-voltage switchgear and controlgear -- Part 4-2: Contactors and motor-starters - AC semiconductor motor controllers and starters
Low-voltage switchgear and controlgear -- Part 4-2: Contactors and motor-starters - AC semiconductor motor controllers and starters
Superseded by EN 60947-4-2:2012
Niederspannungsschaltgeräte -- Teil 4-2: Schütze und Motorstarter - Halbleiter-Motor-Steuergeräte und -Starter für Wechselspannungen
Appareillage à basse tension -- Partie 4-2: Contacteurs et démarreurs de moteurs - Gradateurs et démarreurs à semiconducteurs de moteurs à courant alternatif
Nizkonapetostne stikalne in krmilne naprave – 4-2. del: Kontaktorji in motorski zaganjalniki – Polprevodniški krmilniki in zaganjalniki motorjev na izmenični tok – Dopolnilo A2 (IEC 60947-4-2:1999/A2:2006)
General Information
Relations
Standards Content (Sample)
SLOVENSKI STANDARD
SIST EN 60947-4-2:2000/A2:2007
01-september-2007
1DGRPHãþD
SIST EN 60947-4-2:1998/A2:2000
1L]NRQDSHWRVWQHVWLNDOQHLQNUPLOQHQDSUDYH±GHO.RQWDNWRUMLLQPRWRUVNL
]DJDQMDOQLNL±3ROSUHYRGQLãNLNUPLOQLNLLQ]DJDQMDOQLNLPRWRUMHYQDL]PHQLþQLWRN±
'RSROQLOR$,(&$
Low-voltage switchgear and controlgear -- Part 4-2: Contactors and motor-starters - AC
semiconductor motor controllers and starters (IEC 60947-4-2:1999/A2:2006)
Niederspannungsschaltgeräte -- Teil 4-2: Schütze und Motorstarter - Halbleiter-Motor-
Steuergeräte und -Starter für Wechselspannungen (IEC 60947-4-2:1999/A2:2006)
Appareillage a basse tension -- Partie 4-2: Contacteurs et démarreurs de moteurs -
Gradateurs et démarreurs a semiconducteurs de moteurs a courant alternatif (IEC 60947
-4-2:1999/A2:2006)
Ta slovenski standard je istoveten z: EN 60947-4-2:2000/A2:2006
ICS:
29.130.20 Nizkonapetostne stikalne in Low voltage switchgear and
krmilne naprave controlgear
SIST EN 60947-4-2:2000/A2:2007 en,fr,de
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.
---------------------- Page: 1 ----------------------
EUROPEAN STANDARD
EN 60947-4-2/A2
NORME EUROPÉENNE
December 2006
EUROPÄISCHE NORM
ICS 29.130.20
English version
Low-voltage switchgear and controlgear
Part 4-2: Contactors and motor-starters
AC semiconductor motor controllers and starters
(IEC 60947-4-2:1999/A2:2006)
Appareillage à basse tension Niederspannungsschaltgeräte
Partie 4-2: Contacteurs Teil 4-2: Schütze und Motorstarter -
et démarreurs de moteurs - Halbleiter-Motor-Steuergeräte
Gradateurs et démarreurs und -Starter für Wechselspannungen
à semiconducteurs de moteurs (IEC 60947-4-2:1999/A2:2006)
à courant alternatif
(CEI 60947-4-2:1999/A2:2006)
This amendment A2 modifies the European Standard EN 60947-4-2:2000; it was approved by CENELEC on
2006-12-01. CENELEC members are bound to comply with the CEN/CENELEC Internal Regulations which
stipulate the conditions for giving this amendment the status of a national standard without any alteration.
Up-to-date lists and bibliographical references concerning such national standards may be obtained on
application to the Central Secretariat or to any CENELEC member.
This amendment exists in three official versions (English, French, German). A version in any other language
made by translation under the responsibility of a CENELEC member into its own language and notified to the
Central Secretariat has the same status as the official versions.
CENELEC members are the national electrotechnical committees of Austria, Belgium, Cyprus, the Czech
Republic, Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia,
Lithuania, Luxembourg, Malta, the Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain,
Sweden, Switzerland and the United Kingdom.
CENELEC
European Committee for Electrotechnical Standardization
Comité Européen de Normalisation Electrotechnique
Europäisches Komitee für Elektrotechnische Normung
Central Secretariat: rue de Stassart 35, B - 1050 Brussels
© 2006 CENELEC - All rights of exploitation in any form and by any means reserved worldwide for CENELEC members.
Ref. No. EN 60947-4-2:2000/A2:2006 E
---------------------- Page: 2 ----------------------
EN 60947-4-2:2000/A2:2006 - 2 -
Foreword
The text of document 17B/1499/FDIS, future amendment 2 to IEC 60947-4-2:1999, prepared by SC 17B,
Low-voltage switchgear and controlgear, of IEC TC 17, Switchgear and controlgear, was submitted to the
IEC-CENELEC parallel vote and was approved by CENELEC as amendment A2 to EN 60947-4-2:2000
on 2006-12-01.
The following dates were fixed:
– latest date by which the amendment has to be
implemented at national level by publication of
an identical national standard or by endorsement (dop) 2007-09-01
– latest date by which the national standards conflicting
with the amendment have to be withdrawn (dow) 2009-12-01
Annex ZA has been added by CENELEC.
__________
Endorsement notice
The text of amendment 2:2006 to the International Standard IEC 60947-4-2:1999 was approved by
CENELEC as an amendment to the European Standard without any modification.
__________
---------------------- Page: 3 ----------------------
- 3 - EN 60947-4-2:2000/A2:2006
Replace Annex ZA of EN 60947-4-2:2000 by:
Annex ZA
(normative)
Normative references to international publications
with their corresponding European publications
The following referenced documents are indispensable for the application of this document. For dated
references, only the edition cited applies. For undated references, the latest edition of the referenced
document (including any amendments) applies.
NOTE When an international publication has been modified by common modifications, indicated by (mod), the relevant EN/HD
applies.
Publication Year Title EN/HD Year
IEC 60034-1 2004 Rotating electrical machines EN 60034-1 2004
Part 1: Rating and performance
IEC 60050-161 1990 International Electrotechnical Vocabulary - -
A1 1997 (IEV) - -
A2 1998 Chapter 161: Electromagnetic compatibility - -
IEC 60085 2004 Electrical insulation - Thermal classification EN 60085 2004
IEC 60146 Series Semiconductor convertors - General EN 60146 Series
requirements and line commutated convertors
IEC 60269-1 1998 Low-voltage fuses EN 60269-1 1998
A1 2005 Part 1: General requirements A1 2005
IEC 60410 1973 Sampling plans and procedures for inspection - -
by attributes
IEC 60439-1 1999 Low-voltage switchgear and controlgear EN 60439-1 1999
A1 2004 assemblies A1 2004
Part 1: Type-tested and partially type-tested
assemblies
IEC 60664 Series Insulation coordination for equipment within EN 60664 Series
low-voltage systems
IEC 60947-1 2004 Low-voltage switchgear and controlgear EN 60947-1 2004
Part 1: General rules + corr. November 2004
IEC/TR 61000-2-1 1990 Electromagnetic compatibility (EMC) - -
Part 2: Environment - Section 1: Description
of the environment - Electromagnetic
environment for low-frequency conducted
disturbances and signalling in public power
supply systems
IEC 61000-3-2 2005 Electromagnetic compatibility (EMC) EN 61000-3-2 2006
Part 3-2: Limits - Limits for harmonic current
emissions (equipment input current <= 16 A
per phase)
IEC 61000-4-2 1995 Electromagnetic compatibility (EMC) EN 61000-4-2 1995
A1 1998 Part 4-2: Testing and measurement A1 1998
A2 2000 techniques - Electrostatic discharge A2 2001
immunity test
---------------------- Page: 4 ----------------------
EN 60947-4-2:2000/A2:2006 - 4 -
Publication Year Title EN/HD Year
IEC 61000-4-3 2006 Electromagnetic compatibility (EMC) EN 61000-4-3 2006
Part 4-3 : Testing and measurement
techniques - Radiated, radio-frequency,
electromagnetic field immunity test
1)
IEC 61000-4-4 1995 Electromagnetic compatibility (EMC) EN 61000-4-4 1995
A1 2000 Part 4-4: Testing and measurement A1 2001
A2 2001 techniques - Electrical fast transient/burst A2 2001
immunity test
2)
IEC 61000-4-5 1995 Electromagnetic compatibility (EMC) EN 61000-4-5) 1995
A1 2000 Part 4-5: Testing and measurement A1 2001
techniques - Surge immunity test
IEC 61000-4-6 2003 Electromagnetic compatibility (EMC) - -
A1 2004 Part 4-6: Testing and measurement
techniques - Immunity to conducted
disturbances, induced by radio-frequency
fields
3)
IEC 61000-4-11 1994 Electromagnetic compatibility (EMC) EN 61000-4-11 1994
A1 2000 Part 4-11: Testing and measurement A1 2001
techniques - Voltage dips, short interruptions
and voltage variations immunity tests
IEC 61131-2 2003 Programmable controllers EN 61131-2 2003
Part 2: Equipment requirements and tests + corr. August 2003
CISPR 11 (mod) 2003 Industrial scientific and medical (ISM) radio-
4)
A1 (mod) 2004 frequency equipment - Electromagnetic EN 55011 200X
disturbance characteristics - Limits and
methods of measurement
5) 4)
CISPR 14-1 - Electromagnetic compatibility - EN 55014-1 200X
Requirements for household appliances,
electric tools and similar apparatus
Part 1: Emission
1)
EN 61000-4-4 is superseded by EN 61000-4-4:2004, which is based on IEC 61000-4-4:2004.
2)
EN 61000-4-5 is superseded by EN 61000-4-5:2006, which is based on IEC 61000-4-5:2005.
3)
EN 61000-4-11 is superseded by EN 61000-4-11:2004, which is based on IEC 61000-4-11:2004.
4)
To be published.
5)
Undated reference.
---------------------- Page: 5 ----------------------
NORME CEI
INTERNATIONALE
IEC
60947-4-2
INTERNATIONAL
1999
STANDARD
AMENDEMENT 2
AMENDMENT 2
2006-11
Amendement 2
Appareillage à basse tension –
Partie 4-2:
Contacteurs et démarreurs de moteurs –
Gradateurs et démarreurs à semiconducteurs
de moteurs à courant alternatif
Amendment 2
Low-voltage switchgear and controlgear –
Part 4-2:
Contactors and motor-starters –
AC semiconductor motor controllers and starters
© IEC 2006 Droits de reproduction réservés ⎯ Copyright - all rights reserved
International Electrotechnical Commission, 3, rue de Varembé, PO Box 131, CH-1211 Geneva 20, Switzerland
Telephone: +41 22 919 02 11 Telefax: +41 22 919 03 00 E-mail: inmail@iec.ch Web: www.iec.ch
CODE PRIX
V
Commission Electrotechnique Internationale
PRICE CODE
International Electrotechnical Commission
МеждународнаяЭлектротехническаяКомиссия
Pour prix, voir catalogue en vigueur
For price, see current catalogue
---------------------- Page: 6 ----------------------
60947-4-2 Amend. 2 © IEC:2006 – 3 –
FOREWORD
This amendment has been prepared by subcommittee 17B: Low-voltage switchgear and
controlgear, of IEC technical committee 17: Switchgear and controlgear.
The text of this amendment is based on the following documents:
FDIS Report on voting
17B/1499/FDIS 17B/1524/RVD
Full information on the voting for the approval of this amendment can be found in the report
on voting indicated in the above table.
The committee has decided that the contents of this amendment and the base publication will
remain unchanged until the maintenance result date indicated on the IEC web site under
"http://webstore.iec.ch" in the data related to the specific publication. At this date, the
publication will be
• reconfirmed;
• withdrawn;
• replaced by a revised edition, or
• amended.
________________
Page 3
CONTENTS
Modify the title of Clause 3 to read:
3 Definitions, symbols and abbreviations
Insert the following:
3.3 Symbols and abbreviations
Delete Subclause 5.9.
Delete Subclause 9.4.
Replace the title of Annexes B and C by the following:
Annex B Vacant
Annex C (normative) Co-ordination at the crossover current between the starter and
associated SCPD
Insert the title of Annex K:
Annex K (normative) Extended functions within electronic overload relays
Insert the following:
Figure 3 – Thermal memory test
---------------------- Page: 7 ----------------------
60947-4-2 Amend. 2 © IEC:2006 – 5 –
Figure 4 – Multiple of current setting limits for ambient air temperature compensated time-
delay overload relays
Figure C.1 – Examples of time-current withstand characteristic
Figure K.1 – Test circuit for the verification of the operating characteristic of a residual current
electronic overload relay
Replace the title of Table 4 by the following:
Table 4 – Minimum overload current withstand time (T ) in relation to overload current ratio
x
(X) and corresponding to overload relay trip class (see Table 19)
Insert the following:
Table 19 – Trip classes of overload relays
Table 20 – Limits of operation of time-delay overload relays when energized on all poles
Table 21 – Limits of operation of three-pole time-delay overload relays when energized on two
poles only
Delete Tables B.1, B.2 and B.3.
Insert the following:
Table C.1 – Test conditions
Table K.1 – Operating time of residual current electronic overload relays
Page 13
1 Scope and object
Modify the existing text of the sixth paragraph to read:
“Contactors, overload relays and control circuit devices used in controllers and starters … “
Page 15 and amendment 1, page 5
2 Normative references
Replace the existing text of first paragraph by the following:
The following referenced documents are indispensable for the application of this document.
For dated references, only the edition cited applies. For undated references, the latest edition
of the referenced document (including any amendments) applies.
---------------------- Page: 8 ----------------------
60947-4-2 Amend. 2 © IEC:2006 – 7 –
Replace the reference to IEC 60034-1:1996 by the following:
IEC 60034-1:2004, Rotating electrical machines – Part 1: Rating and performance
Add, after IEC 60050(161), the following references:
Amendment 1 (1997)
Amendment 2 (1998)
Replace the reference to IEC 60085:1984 by the following:
IEC 60085:2004, Electrical insulation – Thermal classification
Insert the following new reference:
IEC 60146 (all parts), Semiconductor convertors
Add, after IEC 60269-1, the following reference:
Amendment 1 (2005)
Replace the reference to IEC 60439-1:1992 by the following:
IEC 60439-1:1999, Low-voltage switchgear and controlgear assemblies – Part 1: Type-tested
and partially type-tested assemblies
Amendment 1 (2004)
Replace the reference to IEC 60947-1:1999 by the following:
IEC 60947-1:2004, Low-voltage switchgear and controlgear – Part 1: General rules
Replace the reference to IEC 61000-3-2:1995 by the following:
IEC 61000-3-2:2005, Electromagnetic compatibility (EMC) – Part 3-2: Limits – Limits for
harmonic current emissions (equipment input current ≤16 A per phase)
Add, after IEC 61000-4-2, the following references:
Amendment 1 (1998)
Amendment 2 (2000)
Replace the reference to IEC 61000-4-3:1995 by the following:
IEC 61000-4-3:2006, Electromagnetic compatibility (EMC) – Part 4-3: Testing and
measurement techniques – Radiated radio-frequency electromagnetic field immunity test
Add, after IEC 61000-4-4, the following references:
Amendment 1 (2000)
Amendment 2 (2001)
---------------------- Page: 9 ----------------------
60947-4-2 Amend. 2 © IEC:2006 – 9 –
Add, after IEC 61000-4-5, the following reference:
Amendment 1 (2000)
Replace the reference to IEC 61000-4-6:1996 by the following:
IEC 61000-4-6:2003, Electromagnetic compatibility (EMC) – Part 4-6: Testing and
measurement techniques – Immunity to conducted disturbances, induced by radio-frequency
fields
Amendment 1 (2004)
Add, after IEC 61000-4-11, the following reference:
Amendment 1 (2000)
Insert the following new reference:
IEC 61131-2:2003, Programmable controllers – Part 2: Equipment requirements and tests
Replace the reference to CISPR 11:1997 by the following:
CISPR 11:2003, Industrial, scientific and medical (ISM) radio-frequency equipment –
Electromagnetic disturbance characteristics – Limits and methods of measurement
Amendment 1 (2004)
Replace the reference to CISPR 14-1:1993 by the following:
CISPR 14-1, Electromagnetic compatibility – Requirements for household appliances, electric
tools and similar apparatus – Part 1: Emission
Delete the reference to CISPR 14-2:1993.
Page 17 and Amendment 1, page 5
3 Definitions
Replace the existing title by the following:
3 Definitions, symbols and abbreviations
Insert, after the first paragraph the following alphabetical index of definitions:
Reference
A
AC semiconductor motor controller . 3.1.1.1
B
Burst (of pulses or oscillations) . 3.2.7
Bypassed controller . 3.1.29
---------------------- Page: 10 ----------------------
60947-4-2 Amend. 2 © IEC:2006 – 11 –
C
CO operation . 3.1.30
Controlled acceleration . 3.1.5
Controlled deceleration. 3.1.6
Controlled running. 3.1.7
Current-limit function . 3.1.3
E
Electromagnetic compatibility, EMC (abbreviation). 3.2.1
Electromagnetic disturbance . 3.2.3
Electromagnetic emission . 3.2.2
F
Full-on (state of controllers) . 3.1.10
H
Hybrid motor controllers or starters, form HxA (where x = 1, 2 or 3) . 3.1.2.1
Hybrid motor controllers or starters, form HxB . 3.1.2.2
I
Inhibit time. 3.1.26
J
Jam sensitive electronic overload relay. 3.1.25
M
Manoeuvre. 3.1.4
Minimum load current . 3.1.11
O
O operation. 3.1.31
OFF-state leakage current . 3.1.13
OFF-time. 3.1.28
ON-state. 3.1.9
ON-time. 3.1.27
Open position . 3.1.2.3
Operating capability. 3.1.16
Operating cycle (of a controller). 3.1.15
Operation (of a controller). 3.1.14
Overload current profile . 3.1.17
P
Phase loss sensitive overload relay or release. 3.1.21
Prospective locked rotor current . 3.1.8
R
Radio (frequency) disturbance . 3.2.4
Radio frequency interference, RFI (abbreviation) . 3.2.5
Rating index . 3.1.18
S
Semiconductor direct-on-line (DOL) motor controller (form 3) . 3.1.1.1.3
Semiconductor motor controller (form 1) . 3.1.1.1.1
Semiconductor motor starter (form 1, form 2, form 3). 3.1.1.2
Semiconductor soft-start motor controller (form 2). 3.1.1.1.2
Stall sensitive electronic overload relay . 3.1.24
---------------------- Page: 11 ----------------------
60947-4-2 Amend. 2 © IEC:2006 – 13 –
T
Transient (adjective and noun). 3.2.6
Trip-free controller or starter . 3.1.20
Tripping operation (of a controller or starter). 3.1.19
U
Under-current relay or release . 3.1.22
Under-voltage relay or release. 3.1.23
V
Voltage surge . 3.2.8
3.1.1.1
Number the existing note as NOTE 1.
Add the following new NOTE 2:
NOTE 2 In a circuit where the current passes through zero (alternately or otherwise), the effect of "not making" the
current following such a zero value is equivalent to breaking the current.
Page 19
3.1.1.2
Correction in the French text only.
Page 21 and Amendment 1, page 7
Figure 1 – Semiconductor motor control devices
In row “Bypassed hybrid motor controller”:
c
- modify the title to read “Bypassed hybrid motor controller ”;
- delete the reference “(see 8.2.4.2.3)”.
c
Add, at the bottom of the figure, the following new footnote “ ”:
c
For other configurations, tests may be suitably adapted by agreement between the user and the manufacturer.
Page 23
3.1.2.1
Correction in the French text only.
Page 27
3.1.19
Correction in the French text only.
---------------------- Page: 12 ----------------------
60947-4-2 Amend. 2 © IEC:2006 – 15 –
Page 29
3.1.20
Correction on the French text only.
Page 29 and Amendment 1, page 7
Modify definition 3.1.21 as follows:
3.1.21
phase loss sensitive overload relay or release
multipole overload relay or release which operates in case of overload and also in case of
loss of phase in accordance with specified requirements
Insert, after definition 3.1.21, the following new definitions 3.1.22 to 3.1.26:
3.1.22
under-current relay or release
measuring relay or release which operates automatically when the current through it is
reduced below a predetermined value
3.1.23
under-voltage relay or release
measuring relay or release which operates automatically when the voltage applied to it is
reduced below a predetermined value
3.1.24
stall sensitive electronic overload relay
electronic overload relay which operates when the current has not decreased below a
predetermined value for a specific period of time during start-up or when the relay receives
the input indicating there is no rotation of the motor after a predetermined time in accordance
with specified requirements
NOTE Explanation of stall: rotor locked during start.
3.1.25
jam sensitive electronic overload relay
electronic overload relay which operates in the case of overload and also when the current
has increased above a predetermined value for a specific period of time during run in
accordance with specified requirements
NOTE Explanation of jam: high overload occurring after the completion of starting which causes the current to
reach the locked rotor current value of the motor being controlled.
3.1.26
inhibit time
time-delay period during which the tripping function of the relay is inhibited (may be
adjustable)
Renumber definitions 3.1.22 to 3.1.24 as 3.1.27 to 3.1.29 respectively.
Add, after definition 3.1.29, the following new definitions 3.1.30 and 3.1.31:
---------------------- Page: 13 ----------------------
60947-4-2 Amend. 2 © IEC:2006 – 17 –
3.1.30
CO operation
breaking of the circuit by the SCPD resulting from closing the circuit by the equipment under
test
3.1.31
O operation
breaking of the circuit by the SCPD resulting from closing the circuit on the equipment under
test which is in the closed position
Page 31
Modify the existing text of the note of definition 3.2.5 to read:
“… applied to a radio-frequency disturbance or an unwanted signal.”
Add, after definition 3.2.8, the following new subclause:
3.3 Symbols and abbreviations
A Final ambient temperature (9.3.3.3.4)
f
C Final case temperature (9.3.3.3.4)
f
EMC Electromagnetic compatibility
EUT Equipment under test
I Current made and broken (Table 8)
c
I Rated operational current (5.3.2.3)
e
I Leakage current after the blocking and commutating capability test (9.3.3.6.3)
F
I Initial test current (9.3.3.6.2)
init
I OFF-state leakage current (3.1.13)
L
I Prospective locked rotor current (3.1.8)
LRP
I Leakage current before the blocking and commutating capability test (9.3.3.6.3)
O
I Conventional free air thermal current (5.3.2.1)
th
I Conventional enclosed thermal current (5.3.2.2)
the
I Rated uninterrupted current (5.3.2.4)
u
SCPD Short-circuit protective device
U Rated control circuit voltage (5.5)
c
U Rated operational voltage (5.3.1.1)
e
U Rated insulation voltage (5.3.1.2)
i
U Rated impulse withstand voltage (5.3.1.3)
imp
U Power frequency recovery voltage (Table 6)
r
U Rated control supply voltage (5.5)
s
5.1 Summary of characteristics
Delete the last dashed item “switching overvoltages (5.9)”.
---------------------- Page: 14 ----------------------
60947-4-2 Amend. 2 © IEC:2006 – 19 –
Page 41
5.3.5.1 Overload current profile
Replace the existing text of the last paragraph by the following:
For a starter, T is the minimum operating time allowed by the tolerances of the overload
x
relay.
Page 45
5.4 Utilization category
Replace the first sentence of the fourth paragraph by the following:
The first digit of the utilization category identification designates a semiconductor switching
device (e.g. within this standard a semiconductor motor controller or starter).
Page 47 and Amendment 1, page 9
Table 2 – Utilization categories
Replace note 1 by the following:
NOTE 1 The means of bypassing the semiconductor controller or starter may be integral with the controller/starter
or installed separately. It also may be dependant or unrestricted as specified in 8.2.1.7 and 8.2.1.8.
Page 49
5.6 Auxiliary circuits
Add, at the end of this subclause, the following new paragraph:
Digital inputs and/or digital outputs contained in controllers and starters, and intended to be
compatible with PLC’s shall fulfil the requirements of IEC 61131-2.
5.7 Characteristics of relays and releases (overload relays)
Replace the existing text of this subclause by the following:
NOTE In the remainder of this standard, the words "overload relay" will be taken to apply equally to an overload
relay or an overload release, as appropriate.
5.7.1 Summary of characteristics
The characteristics of relays and releases shall be stated in the following terms, whenever
applicable:
---------------------- Page: 15 ----------------------
60947-4-2 Amend. 2 © IEC:2006 – 21 –
– types of relay or release (see 5.7.2);
– characteristic values (see 5.7.3);
– designation and current settings of overload relays (see 5.7.4);
– time-current characteristics of overload relays (see 5.7.5);
– influence of ambient air temperature (see 5.7.6).
5.7.2 Types of relay or release
a) Under-voltage and under-current opening relay or release.
b) Overload time-delay relay the time-lag of which is:
1) dependent on previous load (e.g. thermal or electronic overload relay);
2) dependent on previous load (e.g. thermal or electronic overload relay) and also
sensitive to phase loss (see 3.1.21);
3) independent of previous load (without thermal memory).
c) Instantaneous over-current relay or release (e.g. jam sensitive, see 3.1.25).
d) Other relays or releases (e.g. control relay associated with devices for the thermal
protection of the starter).
e) Stall relay or release.
5.7.3 Characteristic values
a) Release with shunt coil, under-voltage (under-current), over-voltage (instantaneous over
current), current or voltage asymmetry and phase reversal opening relay or release:
− rated voltage (current);
− rated frequency;
− operating voltage (current);
− operating time (when applicable);
− inhibit time (when applicable).
b) Overload relay:
– designation and current settings (see 5.7.4);
– rated frequency, when necessary (for example in the case of a current transformer
operated overload relay);
– time-current characteristics (or range of characteristics), when necessary;
– trip class according to classification in Table 19, or the value of the maximum tripping
time, in seconds, under the conditions specified in 8.2.1.5.1.1.1 and Table 20,
column D, when this time exceeds 30 s;
– number of poles;
– nature of the relay: thermal, electronic or electronic without thermal memory;
– nature of the reset: manual or automatic.
c) Release with residual current sensing relay:
− rated current;
− operating current;
− operating time or time-current characteristic according to Table K.1;
---------------------- Page: 16 ----------------------
60947-4-2 Amend. 2 © IEC:2006 – 23 –
− inhibit time (when applicable);
− type designation (see Annex K).
Table 19 – Trip classes of overload relays
Trip class Tripping time T under the conditions Tripping time T und
...
Questions, Comments and Discussion