Field device tool interface specification -- Part 303-1: Communication profile integration - IEC 61784 CP 3/1 and CP 3/2

IEC 62453-303-1:2009(E) provides information for integrating the PROFIBUS protocol into the FDT interface specification (IEC 62453-2). This part of the IEC 62453 specifies communication and other services. This specification neither contains the FDT specification nor modifies it. Communication Profile 3/1 and Communication Profile 3/2 (commonly known as PROFIBUSTM1) defines communication profiles based on IEC 61158-2 Type 3, IEC 61158-3-3, IEC 61158-4-3, IEC 61158-5-3, and IEC 61158-6-3. The basic profiles CP 3/1 (PROFIBUS DP) and CP 3/2 (PROFIBUS PA) are defined in IEC 61784-1.   This publication is to be read in conjunction with IEC 62453-2:2009.

Field Device Tool (FDT)-Schnittstellenspezifikation - Teil 303-1: Integration von Kommunikationsprofilen - IEC 61784 Kommunikationsprofile (CP) 3/1 und 3/2

Spécification des interfaces des outils des dispositifs de terrain (FDT) - Partie 303-1: Intégration des profils de communication - CEI 61784 CP 3/1 et CP 3/2

La CEI 62453-303-1:2009 donne des informations pour intégrer le protocole PROFIBUS dans la spécification d'interface FDT (CEI 62453-2). La présente partie de la CEI 62453 spécifie les services de communication et autres services.

Specifikacija vmesnika orodja procesne naprave - 303-1. del: Integracija komunikacijskih profilov - IEC 61784 CP 3/1 in CP 3/2 (IEC 62453-303-1:2009)

Komunikacijski profil 3/1 in komunikacijski profil 3/2 (splošno znana kot PROFIBUS™1) opredeljujeta komunikacijske profile na osnovi IEC 61158-2, tipa 3, IEC 61158-3-3, IEC 61158-4-3, IEC 61158-5-3 in IEC 61158-6-3. Osnovna profila CP 3/1 (PROFIBUS DP) in CP 3/2 (PROFIBUS PA) sta določena v IEC 61784-1. Ta del IEC 62453 podaja informacije za integriranje protokola PROFIBUS v specifikacijo vmesnika orodja procesne naprave(IEC 62453-2). Ta del IEC 62453 opredeljuje komunikacijo in druge storitve. Ta specifikacija ne vsebuje specifikacije orodja procesne naprave niti je ne spreminja.

General Information

Status
Published
Publication Date
15-Dec-2009
Current Stage
6060 - National Implementation/Publication (Adopted Project)
Start Date
26-Nov-2009
Due Date
31-Jan-2010
Completion Date
16-Dec-2009

Relations

Effective Date
13-Nov-2017

Overview

EN 62453-303-1:2009 / IEC 62453-303-1:2009 defines how the PROFIBUS communication profiles are integrated into the Field Device Tool (FDT) interface specification. Published by CLC/CENELEC and produced by IEC TC65, this part provides protocol-specific communication and service definitions for PROFIBUS CP 3/1 (PROFIBUS DP) and CP 3/2 (PROFIBUS PA) (IEC 61784 CP 3/1 and CP 3/2). It is intended to be read in conjunction with IEC 62453-2 (FDT concepts and detailed description) and does not alter the core FDT specification.

Key topics and technical requirements

This standard specifies the protocol-specific mappings and services required to integrate PROFIBUS into the FDT framework. Major technical topics include:

  • PROFIBUS device model and bus category mappings for FDT/DTM (Device Type Manager).
  • Access to instance and device data via DTM-provided Process Channel objects and services.
  • Configuration and parameterization approaches for PROFIBUS devices (monolithic and modular DTMs).
  • Support and behavior for DPV0 and DPV1 communication variants.
  • Handling of PROFIBUS slaves operating without a cyclic master and master/slave parameter sets.
  • Bus Master Configuration Part (BMCP) structure and how BMCP data maps to FDT data types.
  • Protocol-specific usage of general and common FDT data types, including GSD information for device descriptions.
  • Network management and communication data types, channel parameters, and error reporting via Communication Channel.
  • Device identification, topology scan, scan identification and mapping to FDT semantics.
  • ProfiSafe parameter handling for safety-related PROFIBUS devices.

Applications and who uses it

This standard is practical for organizations and professionals involved in industrial automation who need to integrate PROFIBUS devices into FDT-enabled engineering and asset-management tools:

  • Device manufacturers creating DTMs for PROFIBUS DP/PA devices.
  • System integrators and plant engineers implementing FDT-based device management across PROFIBUS networks.
  • DCS/PLC vendors providing FDT/DTM support in engineering tools.
  • Maintenance and asset management teams using FDT tools for device diagnostics, parameterization and lifecycle management.
  • Automation architects designing multi-vendor PROFIBUS systems with standardized device integration.

Related standards

  • IEC 62453-2 / EN 62453-2 (FDT concepts and detailed description) - required companion document.
  • IEC 61784-1 (Fieldbus profiles - CP 3/1 & CP 3/2 definitions).
  • IEC 61158 series (PROFIBUS physical, data-link and application layer Type 3 elements).
  • IEC 62453-1 (FDT overview and guidance).

Keywords: FDT, Field Device Tool, PROFIBUS, IEC 62453-303-1, EN 62453-303-1, communication profile integration, CP 3/1, CP 3/2, IEC 61784, DPV0, DPV1, DTM, GSD, BMCP, ProfiSafe.

Standard

SIST EN 62453-303-1:2010

English language
63 pages
Preview
Preview
e-Library read for
1 day

Frequently Asked Questions

SIST EN 62453-303-1:2010 is a standard published by the Slovenian Institute for Standardization (SIST). Its full title is "Field device tool interface specification -- Part 303-1: Communication profile integration - IEC 61784 CP 3/1 and CP 3/2". This standard covers: IEC 62453-303-1:2009(E) provides information for integrating the PROFIBUS protocol into the FDT interface specification (IEC 62453-2). This part of the IEC 62453 specifies communication and other services. This specification neither contains the FDT specification nor modifies it. Communication Profile 3/1 and Communication Profile 3/2 (commonly known as PROFIBUS<sup>TM1</sup>) defines communication profiles based on IEC 61158-2 Type 3, IEC 61158-3-3, IEC 61158-4-3, IEC 61158-5-3, and IEC 61158-6-3. The basic profiles CP 3/1 (PROFIBUS DP) and CP 3/2 (PROFIBUS PA) are defined in IEC 61784-1. This publication is to be read in conjunction with <a href='http://webstore.iec.ch/webstore/webstore.nsf/artnum/043140'>IEC 62453-2:2009</a>.

IEC 62453-303-1:2009(E) provides information for integrating the PROFIBUS protocol into the FDT interface specification (IEC 62453-2). This part of the IEC 62453 specifies communication and other services. This specification neither contains the FDT specification nor modifies it. Communication Profile 3/1 and Communication Profile 3/2 (commonly known as PROFIBUS<sup>TM1</sup>) defines communication profiles based on IEC 61158-2 Type 3, IEC 61158-3-3, IEC 61158-4-3, IEC 61158-5-3, and IEC 61158-6-3. The basic profiles CP 3/1 (PROFIBUS DP) and CP 3/2 (PROFIBUS PA) are defined in IEC 61784-1. This publication is to be read in conjunction with <a href='http://webstore.iec.ch/webstore/webstore.nsf/artnum/043140'>IEC 62453-2:2009</a>.

SIST EN 62453-303-1:2010 is classified under the following ICS (International Classification for Standards) categories: 25.040.40 - Industrial process measurement and control; 35.240.50 - IT applications in industry. The ICS classification helps identify the subject area and facilitates finding related standards.

SIST EN 62453-303-1:2010 has the following relationships with other standards: It is inter standard links to SIST EN IEC 62453-303-1:2010/A1:2018. Understanding these relationships helps ensure you are using the most current and applicable version of the standard.

You can purchase SIST EN 62453-303-1:2010 directly from iTeh Standards. The document is available in PDF format and is delivered instantly after payment. Add the standard to your cart and complete the secure checkout process. iTeh Standards is an authorized distributor of SIST standards.

Standards Content (Sample)


SLOVENSKI STANDARD
01-januar-2010
Specifikacija vmesnika orodja procesne naprave - 303-1. del: Integracija
komunikacijskih profilov - IEC 61784 CP 3/1 in CP 3/2 (IEC 62453-303-1:2009)
Field device tool interface specification -- Part 303-1: Communication profile integration -
IEC 61784 CP 3/1 and CP 3/2
Field Device Tool (FDT)-Schnittstellenspezifikation - Teil 303-1: Integration von
Kommunikationsprofilen - IEC 61784 Kommunikationsprofile (CP) 3/1 und 3/2
Spécification des interfaces des outils des dispositifs de terrain (FDT) - Partie 303-1:
Intégration des profils de communication - CEI 61784 CP 3/1 et CP 3/2
Ta slovenski standard je istoveten z: EN 62453-303-1:2009
ICS:
25.040.40 Merjenje in krmiljenje Industrial process
industrijskih postopkov measurement and control
35.240.50 Uporabniške rešitve IT v IT applications in industry
industriji
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.

EUROPEAN STANDARD
EN 62453-303-1
NORME EUROPÉENNE
October 2009
EUROPÄISCHE NORM
ICS 25.040.40; 35.100.05; 35.110

English version
Field device tool (FDT) interface specification -
Part 303-1: Communication profile integration -
IEC 61784 CP 3/1 and CP 3/2
(IEC 62453-303-1:2009)
Spécification des interfaces des outils Field Device Tool (FDT)-
des dispositifs de terrain (FDT) - Schnittstellenspezifikation -
Partie 303-1: Intégration des profils Teil 303-1: Integration
de communication - von Kommunikationsprofilen -
CEI 61784 CP 3/1 et CP 3/2 Kommunikationsprofile (CP)
(CEI 62453-303-1:2009) 3/1 und 3/2 nach IEC 61784
(IEC 62453-303-1:2009)
This European Standard was approved by CENELEC on 2009-08-01. CENELEC members are bound to comply
with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this European Standard
the status of a national standard without any alteration.

Up-to-date lists and bibliographical references concerning such national standards may be obtained on
application to the Central Secretariat or to any CENELEC member.

This European Standard exists in three official versions (English, French, German). A version in any other
language made by translation under the responsibility of a CENELEC member into its own language and notified
to the Central Secretariat has the same status as the official versions.

CENELEC members are the national electrotechnical committees of Austria, Belgium, Bulgaria, Cyprus, the
Czech Republic, Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia,
Lithuania, Luxembourg, Malta, the Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain,
Sweden, Switzerland and the United Kingdom.

CENELEC
European Committee for Electrotechnical Standardization
Comité Européen de Normalisation Electrotechnique
Europäisches Komitee für Elektrotechnische Normung

Central Secretariat: Avenue Marnix 17, B - 1000 Brussels

© 2009 CENELEC - All rights of exploitation in any form and by any means reserved worldwide for CENELEC members.
Ref. No. EN 62453-303-1:2009 E

Foreword
The text of document 65E/127/FDIS, future edition 1 of IEC 62453-303-1, prepared by SC 65E, Devices and
integration in enterprise systems, of IEC TC 65, Industrial-process measurement, control and automation,
was submitted to the IEC-CENELEC parallel vote and was approved by CENELEC as EN 62453-303-1 on
2009-08-01.
Each part of the EN 62453-3xy series is intended to be read in conjunction with EN 62453-2.
The following dates were fixed:
– latest date by which the EN has to be implemented
at national level by publication of an identical
national standard or by endorsement (dop) 2010-05-01
– latest date by which the national standards conflicting
with the EN have to be withdrawn (dow) 2012-08-01
Annex ZA has been added by CENELEC.
__________
Endorsement notice
The text of the International Standard IEC 62453-303-1:2009 was approved by CENELEC as a European
Standard without any modification.
In the official version, for Bibliography, the following notes have to be added for the standards indicated:
[5] IEC 61158-6 NOTE  Harmonized as EN 61158-6:2004 (not modified).
[7] IEC 61158-5 NOTE  Harmonized as EN 61158-5:2004 (not modified).
__________
- 3 - EN 62453-303-1:2009
Annex ZA
(normative)
Normative references to international publications
with their corresponding European publications

The following referenced documents are indispensable for the application of this document. For dated
references, only the edition cited applies. For undated references, the latest edition of the referenced
document (including any amendments) applies.

NOTE  When an international publication has been modified by common modifications, indicated by (mod), the relevant EN/HD
applies.
Publication Year Title EN/HD Year

IEC 61131-3 2003 Programmable controllers - EN 61131-3 2003
Part 3: Programming languages
IEC 61158 Series Industrial communication networks - EN 61158 Series
Fieldbus specifications
1) 2)
IEC 61158-2 – Industrial communication networks - EN 61158-2 2008
Fieldbus specifications -
Part 2: Physical layer specification and service
definition
1) 2)
IEC 61158-3-3 – Industrial communication networks - EN 61158-3-3 2008
Fieldbus specifications -
Part 3-3: Data-link layer service definition -
Type 3 elements
1) 2)
IEC 61158-4-3 – Industrial communication networks - EN 61158-4-3 2008
Fieldbus specifications -
Part 4-3: Data-link layer protocol specification -
Type 3 elements
1) 2)
IEC 61158-5-3 – Industrial communication networks - EN 61158-5-3 2008
Fieldbus specifications -
Part 5-3: Application layer service definition -
Type 3 elements
1) 2)
IEC 61158-6-3 – Industrial communication networks - EN 61158-6-3 2008
Fieldbus specifications -
Part 6-3: Application layer protocol specification
- Type 3 elements
1) 2)
IEC 61784-1 – Industrial communication networks - Profiles - EN 61784-1 2008
Part 1: Fieldbus profiles
IEC 62453-1 2009 Field device tool (FDT) interface specification - EN 62453-1 2009
Part 1: Overview and guidance
IEC 62453-2 2009 Field device tool (FDT) interface specification - EN 62453-2 2009
Part 2: Concepts and detailed description

1)
Undated reference.
2)
Valid edition at date of issue.

IEC 62453-303-1 ®
Edition 1.0 2009-06
INTERNATIONAL
STANDARD
Field device tool (FDT) interface specification –
Part 303-1: Communication profile integration – IEC 61784 CP 3/1 and CP 3/2

INTERNATIONAL
ELECTROTECHNICAL
COMMISSION
PRICE CODE
XA
ICS 25.040.40; 35.100.05; 35.110 ISBN 2-8318-1050-1
– 2 – 62453-303-1 © IEC:2009(E)
CONTENTS
FOREWORD.5
INTRODUCTION.7
1 Scope.8
2 Normative references .8
3 Terms, definitions, symbols, abbreviated terms and conventions .9
3.1 Terms and definitions .9
3.2 Symbols and abbreviated terms.9
3.3 Conventions .9
3.3.1 Data type names and references to data types .9
3.3.2 Vocabulary for requirements.9
3.3.3 Use of UML .9
4 Bus category .10
5 Access to instance and device data.10
5.1 Process Channel objects provided by DTM.10
5.2 DTM services to access instance and device data .10
6 Protocol specific behavior.10
6.1 PROFIBUS device model .10
6.2 Configuration and parameterization of PROFIBUS devices.11
6.2.1 General .11
6.2.2 Monolithic DTM for a modular PROFIBUS device .12
6.2.3 Modular DTM for a modular PROFIBUS device.12
6.3 Support for DPV0 configuration .13
6.4 PROFIBUS slaves operating without a cyclic PROFIBUS master .13
6.5 PROFIBUS-related information of a slave DTM .13
6.5.1 General .13
6.5.2 Bus Master Configuration Part (BMCP).14
7 Protocol specific usage of general data types .24
8 Protocol specific common data types.26
9 Network management data types.26
9.1 General .26
9.1.1 Configuration.26
9.1.2 Process Channel .27
9.1.3 Parameterization .27
9.2 Master-bus parameter set.28
9.3 Slave bus parameter set.28
9.4 Module and channel data .29
9.5 GSD information.32
9.5.1 General .32
9.5.2 GSD for gateway devices .32
10 Communication data types .33
10.1 General .33
10.2 Error information provided by Communication Channel .33
10.3 DPV0 communication .33
10.4 DPV1 communication .40
11 Channel parameter data types.43

62453-303-1 © IEC:2009(E) – 3 –
12 Device identification .46
12.1 General .46
12.2 Protocol specific handling of the data type STRING.46
12.3 Common device type identification data types .46
12.4 Topology scan data types.51
12.5 Scan identification data types.52
12.6 Device type identification data types – provided by DTM .54
12.7 Identification information in GUI .57
13 ProfiSafe .57
13.1 Motivation .57
13.2 General parameter handling .57
13.3 ProfiSafe individual device parameter .58
Bibliography.60

Figure 1 – Part 303-1 of the IEC 62453 series .7
Figure 2 – FDT PROFIBUS device model.11
Figure 3 – Example for IO data within datagrams.30
Figure 4 – F-Parameter and individual device parameter .58
Figure 5 – Data structure of ProfiSafe individual device parameters.59

Table 1 – Protocol identifiers .10
Table 2 – Physical layer identifiers.10
Table 3 – BMPC Part1 – General configuration.15
Table 4 – BMPC Part2 – Parameter data .15
Table 5 – BMPC Part3 – Configuration data.16
Table 6 – Part 4: Address table and slave user parameters .17
Table 7 – Part 4: Extended Prm data .17
Table 8 – Complete BMCP.18
Table 9 – Protocol specific usage of general data types.24
Table 10 – Bus parameter set for master device .28
Table 11 – Bus parameter set for slave device.29
Table 12 – Signal channels within the data frame .31
Table 13 – Simple DPV0 communication data types.34
Table 14 – Structured DPV0Communication data types .34
Table 15 – Availability of services for Master Class1 (C1).39
Table 16 – Availability of services for Master Class2 (C2).39
Table 17 – Simple DPV1 communication data types.40
Table 18 – Structured DPV1 communication data types .41
Table 19 – Mapping of DPV1 data types to FDT data types.43
Table 20 – Simple ChannelParameter data types.44
Table 21 – Structured ChannelParameter data types .45
Table 22 – Identification data types with Profibus DP specific mapping.47
Table 23 – Identification data types with Profibus I&M specific mapping .48
Table 24 – Identification data types with Profibus PA specific mapping .50

– 4 – 62453-303-1 © IEC:2009(E)
Table 25 – Simple identification data types with protocol independent semantics.51
Table 26 – Structured identification data types with protocol independent semantics .51
Table 27 – Simple topology scan data types .51
Table 28 – Structured topology scan data types.51
Table 29 – Simple scan identification data types.52
Table 30 – Structured scan identification data types .52
Table 31 – Structured device identification data types.55

62453-303-1 © IEC:2009(E) – 5 –
INTERNATIONAL ELECTROTECHNICAL COMMISSION
____________
FIELD DEVICE TOOL (FDT) INTERFACE SPECIFICATION –

Part 303-1: Communication profile integration –
IEC 61784 CP 3/1 and CP 3/2
FOREWORD
1) The International Electrotechnical Commission (IEC) is a worldwide organization for standardization comprising
all national electrotechnical committees (IEC National Committees). The object of IEC is to promote
international co-operation on all questions concerning standardization in the electrical and electronic fields. To
this end and in addition to other activities, IEC publishes International Standards, Technical Specifications,
Technical Reports, Publicly Available Specifications (PAS) and Guides (hereafter referred to as “IEC
Publication(s)”). Their preparation is entrusted to technical committees; any IEC National Committee interested
in the subject dealt with may participate in this preparatory work. International, governmental and non-
governmental organizations liaising with the IEC also participate in this preparation. IEC collaborates closely
with the International Organization for Standardization (ISO) in accordance with conditions determined by
agreement between the two organizations.
2) The formal decisions or agreements of IEC on technical matters express, as nearly as possible, an international
consensus of opinion on the relevant subjects since each technical committee has representation from all
interested IEC National Committees.
3) IEC Publications have the form of recommendations for international use and are accepted by IEC National
Committees in that sense. While all reasonable efforts are made to ensure that the technical content of IEC
Publications is accurate, IEC cannot be held responsible for the way in which they are used or for any
misinterpretation by any end user.
4) In order to promote international uniformity, IEC National Committees undertake to apply IEC Publications
transparently to the maximum extent possible in their national and regional publications. Any divergence
between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in
the latter.
5) IEC provides no marking procedure to indicate its approval and cannot be rendered responsible for any
equipment declared to be in conformity with an IEC Publication.
6) All users should ensure that they have the latest edition of this publication.
7) No liability shall attach to IEC or its directors, employees, servants or agents including individual experts and
members of its technical committees and IEC National Committees for any personal injury, property damage or
other damage of any nature whatsoever, whether direct or indirect, or for costs (including legal fees) and
expenses arising out of the publication, use of, or reliance upon, this IEC Publication or any other IEC
Publications.
8) Attention is drawn to the Normative references cited in this publication. Use of the referenced publications is
indispensable for the correct application of this publication.
9) Attention is drawn to the possibility that some of the elements of this IEC Publication may be the subject of
patent rights. IEC shall not be held responsible for identifying any or all such patent rights.
International Standard IEC 62453-303-1 been prepared by subcommittee 65E: Devices and
integration in enterprise systems, of IEC technical committee 65: Industrial-process
measurement, control and automation.
This part, in conjunction with the other parts of the first edition of the IEC 62453 series
cancels and replaces IEC/PAS 62453-1, IEC/PAS 62453-2, IEC/PAS 62453-3, IEC/PAS
62453-4 and IEC/PAS 62453-5 published in 2006, and constitutes a technical revision.
Each part of the IEC 62453-3xy series is intended to be read in conjunction with IEC 62453-2.

– 6 – 62453-303-1 © IEC:2009(E)
The text of this standard is based on the following documents:
FDIS Report on voting
65E/127/FDIS 65E/140/RVD
Full information on the voting for the approval of this standard can be found in the report on
voting indicated in the above table.
This publication has been drafted in accordance with the ISO/IEC Directives, Part 2.
A list of all parts of the IEC 62453 series, under the general title Field Device Tool (FDT)
interface specification, can be found on the IEC website.
The committee has decided that the contents of this publication will remain unchanged until
the maintenance result date indicated on the IEC web site under "http://webstore.iec.ch" in
the data related to the specific publication. At this date, the publication will be
• reconfirmed,
• withdrawn,
• replaced by a revised edition, or
• amended.
A bilingual version of this publication may be issued at a later date.

62453-303-1 © IEC:2009(E) – 7 –
INTRODUCTION
This part of IEC 62453 is an interface specification for developers of FDT (Field Device Tool)
components for function control and data access within a client/server architecture. The
specification is a result of an analysis and design process to develop standard interfaces to
facilitate the development of servers and clients by multiple vendors that need to interoperate
seamlessly.
With the integration of fieldbusses into control systems, there are a few other tasks which
need to be performed. In addition to fieldbus- and device-specific tools, there is a need to
integrate these tools into higher-level system-wide planning- or engineering tools. In
particular, for use in extensive and heterogeneous control systems, typically in the area of the
process industry, the unambiguous definition of engineering interfaces that are easy to use for
all those involved is of great importance.
A device-specific software component, called DTM (Device Type Manager), is supplied by the
field device manufacturer with its device. The DTM is integrated into engineering tools via the
FDT interfaces defined in this specification. The approach to integration is in general open for
all kinds of fieldbusses and thus meets the requirements for integrating different kinds of
devices into heterogeneous control systems.
Figure 1 shows how IEC 62453–303-1 is aligned in the structure of the IEC 62453 series.
Part 303-1
Communication
profile integration –
IEC 61784 CP 3/1
and CP 3/2
IEC  1127/09
Figure 1 – Part 303-1 of the IEC 62453 series

– 8 – 62453-303-1 © IEC:2009(E)
FIELD DEVICE TOOL (FDT) INTERFACE SPECIFICATION –

Part 303-1: Communication profile integration –
IEC 61784 CP 3/1 and CP 3/2
1 Scope
Communication Profile 3/1 and Communication Profile 3/2 (commonly known as
PROFIBUS™ ) defines communication profiles based on IEC 61158-2 Type 3, IEC 61158-3-3,
IEC 61158-4-3, IEC 61158-5-3, and IEC 61158-6-3. The basic profiles CP 3/1 (PROFIBUS
DP) and CP 3/2 (PROFIBUS PA) are defined in IEC 61784-1.
This part of IEC 62453 provides information for integrating the PROFIBUS protocol into the
FDT interface specification (IEC 62453–2).
This part of the IEC 62453 specifies communication and other services.
This specification neither contains the FDT specification nor modifies it.
2 Normative references
The following referenced documents are indispensable for the application of this specification.
For dated references, only the edition cited applies. For undated references, the latest edition
of the referenced document (including any amendments) applies
IEC 61131-3:2003, Programmable controllers – Part 3: Programming languages
IEC 61158 (all parts), Industrial communication networks – Fieldbus specifications
IEC 61158-2, Industrial communication networks – Fieldbus specifications – Part 2: Physical
layer specification and service definition
IEC 61158-3-3, Industrial communication networks – Fieldbus specifications – Part 3-3: Data-
link layer service definition – Type 3 elements
IEC 61158-4-3 Industrial communication networks – Fieldbus specifications – Part 4-3: Data-
link layer protocol specification – Type 3 elements
IEC 61158-5-3: Industrial communication networks – Fieldbus specifications – Part 5-3:
Application layer service definition – Type 3 elements
IEC 61158-6-3, Industrial communication networks – Fieldbus specifications – Part 6-3:
Application layer protocol specification – Type 3 elements
IEC 61784-1, Industrial communication networks – Profiles – Part 1: Fieldbus profiles
—————————
PROFIBUS™ is a trade names of the non-profit organization PROFIBUS Nutzerorganisation e.V. (PNO). This
information is given for the convenience of users of this International Standard and does not constitute an
endorsement by IEC of the trade name holder or any of its products. Compliance to this standard does not
require use of the registered logos for PROFIBUS™. Use of the registered logos for PROFIBUS™ requires
permission of PNO.
62453-303-1 © IEC:2009(E) – 9 –
IEC 62453-1:2009, Field Device Tool (FDT) interface specification – Part 1: Overview and
guidance
IEC 62453–2:2009, Field Device Tool (FDT) interface specification – Part 2: Concepts and
detailed description
3 Terms, definitions, symbols, abbreviated terms and conventions
3.1 Terms and definitions
For the purposes of this document, the terms and definitions given in IEC 62453–1 and
IEC 62453–2 apply.
3.1.1
bus interface module
module of a field device that provides the connection to the fieldbus
3.1.2
CP 3/1
Communication profile of CPF3, featuring asynchronous transmission; RS 485 (ANSI TIA/EIA
RS-485-A); optional RS 485-IS; plastic fiber; glass multi mode fiber or glass single mode
fiber; PCF fiber
3.1.3
CP 3/2
Communication profile of CPF3, featuring synchronous transmission; manchester coded and
bus powered (MBP); optional intrinsically safe (MBP-IS) and lower power (MBP-LP)
3.2 Symbols and abbreviated terms
For the purposes of this document, the symbols and abbreviations given in IEC 62453–1,
IEC 62453–2 and the following apply.
BIM Bus Interface Module
BMCP Bus Master Configuration Part
GSD General Station Description

3.3 Conventions
3.3.1 Data type names and references to data types
The conventions for naming and referencing of data types are explained in IEC 62453-2,
Clause A.1
3.3.2 Vocabulary for requirements
The following expressions are used when specifying requirements.
Usage of “shall” or “mandatory” No exceptions allowed.
Usage of “should” or “recommended” Strong recommendation. It may make sense in special
exceptional cases to differ from the described behaviour.
Usage of “can’ or “optional’ Function or behaviour may be provided, depending on defined
conditions.
3.3.3 Use of UML
Figures in this document are using the UML notation as defined in Annex A of IEC 62453–1.

– 10 – 62453-303-1 © IEC:2009(E)
4 Bus category
CP 3/1 and CP 3/2 protocols are identified in the protocolId element of the structured data
type 'fdt:BusCategory' by the following unique identifiers (Table 1):
Table 1 – Protocol identifiers
Identifier value ProtocolId name Description
036D1497-387B-11D4-86E1-00E0987270B9 'Profibus DP/V0' Support of Profibus DP V0 protocol
036D1499-387B-11D4-86E1-00E0987270B9 'Profibus DP/V1' Support of Profibus DP V1 protocol
CP 3/1 AND CP 3/2 protocols are using the following unique identifiers in physicalLayer
members within PhysicalLayer data type (Table 2):
Table 2 – Physical layer identifiers
Identifier value Description
036D1590-387B-11D4-86E1-00E0987270B9 IEC 61158-2 (Profibus PA)
036D1591-387B-11D4-86E1-00E0987270B9 RS485
036D1592-387B-11D4-86E1-00E0987270B9 Fiber
036D1593-387B-11D4-86E1-00E0987270B9 Ethernet

5 Access to instance and device data
5.1 Process Channel objects provided by DTM
The minimum set of provided data should be: Process values modelled as channel objects
including the ranges and scaling
5.2 DTM services to access instance and device data
The services InstanceDataInformation and DeviceDataInformation shall provide access to at
least all parameters of the Physical Block and the status and Out value of the Function Blocks
shall be exposed.
According to IEC 62453-2, at least one set of semantic information (one per supported
fieldbus protocol) shall be provided for each accessible data object, using the
‘SemanticInformation’ general data type. The corresponding data type ‘applicationDomain’
shall have a value defined for Profibus and the data type ‘semanticId’ shall have an
appropriate value, as specified in Table 9.
6 Protocol specific behavior
6.1 PROFIBUS device model
FDT extends the PROFIBUS device model by using Process Channels for description of I/O
values (see Figure 2).
62453-303-1 © IEC:2009(E) – 11 –

IEC  1128/09
Figure 2 – FDT PROFIBUS device model
6.2 Configuration and parameterization of PROFIBUS devices
6.2.1 General
In a GSD-based configuration tool the user defines the configuration and sets the appropriate
parameters for the modules. The configuration tool creates the configuration string and the
parameter string that are used to set up the slave properly.
With FDT the configuration and parameterization of the devices is no longer executed only by
a central component; it moved partly into the DTMs. A DTM is responsible for providing
configuration and parameterization information for the cyclic master that puts the PROFIBUS
slaves in operation.
A DTM is used to adjust a field device to its specific application. Within PROFIBUS, there are
three different aspects of adjustment:
• parameterization: usr prm data (used in the PROFIBUS service SET_PRM for setting up
the cyclic communication and the specific behavior of the device);

– 12 – 62453-303-1 © IEC:2009(E)
• application parameterization: application specific parameters (transmitted via acyclic
read/write PROFIBUS services);
• configuration: configuration data (used in the PROFIBUS service CHK_CFG for definition
of the format and length of the input/output data that are transmitted within cyclic
communication).
The application parameterization transmitted via acyclic communication is not in the scope of
this document. Within this document the term parameterization represents communication
parameterization (SET_PRM).
6.2.2 Monolithic DTM for a modular PROFIBUS device
A monolithic DTM is one single DTM that represents the complete device with its Bus
Interface Module (BIM) and its I/O modules. In general, such a DTM offers a configuration
dialog (presentation object) that allows definition of the used BIM and modules. The
configuration dialog must be available via the FDT standard function “Configure” (see [1] 4.3
Operation Configuration).
Not all PROFIBUS devices require a configuration dialog. That is why not all DTMs provide
the “Configure” function. This is valid only for non-modular PROFIBUS devices if the usr prm
data cannot be changed.
The configuration dialog allows changing the data only in offline mode if the data set can be
locked.
6.2.3 Modular DTM for a modular PROFIBUS device
Separate DTMs represent the BIM (Device DTM) and the particular I/O modules (Module
DTMs). The effort developing such a modular DTM is normally higher than in the case of a
monolithic DTM, because:
• a private protocol has to be implemented between BIM and I/O modules to ensure that
only a Module DTM can be added to the BIM DTM. This requires an own protocol ID and
the adaptation / creation of communication;
• in some cases, additional private interfaces are necessary to exchange information
between Device DTM for BIM and Module DTMs.
Implementing a Modular DTM results in the following advantages:
• the project represents the device structure;
• the user is able to access module-related information directly as a function of the Module
DTM;
• the FDT specification defines a mechanism to identify DTMs. With these mechanisms it is
possible to provide support for scanning the modules below the BIM and generate the
topology automatically;
• supporting a new type of BIM or I/O module requires an additional DTM “only” and does
not affect existing components. This may result in reduced test effort.
The configuration data to set up the PROFIBUS configuration must be provided by the Device
DTM (representing the BIM). This configuration data may be generated from information of
the instantiated Child DTMs and by using a configuration dialog.
Modular DTMs should be provided for modular devices (e.g. a plant operator may add/remove
modules). Monolithic DTMs are used to represent devices that show no modularity (e.g. PA
devices).
62453-303-1 © IEC:2009(E) – 13 –
6.3 Support for DPV0 configuration
A PROFIBUS slave is configured by a cyclic master and communicates via PROFIBUS DP. In
addition to this the slave may support DPV1 communication.
A Gateway DTM for a PROFIBUS slave does not have to provide communication for the DPV0
communication schema. For example, there is a remote I/O system with HART modules. It
may have a Gateway DTM that requires the DPV1 protocol and provides the HART protocol
(defined in the information document and in the parameter document). This enables HART
Device DTMs to communicate with their devices via the Gateway DTM and via
Communication DTM for DPV1. Following the specification the Gateway DTM delivers channel
parameter documents for both protocols DPV1 and HART. The protocolId is a member of
NetworkManagementInfo data type.
The Process Channels must provide ChannelParameter documents for DPV1 including all
information to allow integration into the control system (e.g. DPAddress of the IO value if
available).
6.4 PROFIBUS slaves operating without a cyclic PROFIBUS master
In most cases, a PROFIBUS slave is configured and parameterized by a cyclic PROFIBUS
master device. So a running master device in the network is required.
Some slaves are able to allow acyclic communication without a running cyclic master.
Especially in the case of gateway functionality this is an eminent advantage because they
allow the parameterization of field devices connected to them by using an acyclic bus master.
So instrument specialists are able to work with field devices also in case the controller is not
yet working.
If a master starts communication, these devices start to detect bus speed and settings to
react properly. This may take some time.
In the following, two cases are described that a user may keep in mind when working with
such devices.
Use case 1:
The user performs a network scan. The Communication DTM tries to read diagnostic data via
a GetDiagnose Request but does not receive a response. The device is not detected by the
Communication DTM. This occurs mostly when the device has a low PROFIBUS address. The
reason is that the device has not completed bus speed / bus setting detection as it was asked
for their diagnostic data. The workaround is to give these devices a higher PROFIBUS
address.
Use Cases 2:
The user tries to connect a field device linked to the gateway that supports DPV1 without a
running cyclic master. This can lead to an error message because the gateway device has not
completed bus speed / bus setting detection as it was asked for a connection. So the user has
to try to connect again. This happens only in very rare situations.
6.5 PROFIBUS-related information of a slave DTM
6.5.1 General
The information used by a cyclic master device to set up the PROFIBUS network properly and
allow cyclic communication between control system and slave devices is provided by a DTM
in
– 14 – 62453-303-1 © IEC:2009(E)
• Bus Master Configuration Part (BMCP);
• GSD information;
• internal topology,
• pocess channels.
A DTM of a PROFIBUS slave must deliver these parts of PROFIBUS-related information to
get integrated into a FDT-based Engineering System. In the next subclauses, a more detailed
description is given on how to generate and how to provide this information. This depends on
the kind of DTM (see 6.2 Configuration and parameterization of PROFIBUS devices).
6.5.2 Bus Master Configuration Part (BMCP)
6.5.2.1 BMCP introduction
The BMCP of one single DTM instance describes the actual parameter and configuration data
of the corresponding PROFIBUS slave. Each DTM representing a PROFIBUS slave device
must provide a Bus Master Configuration Part. The BMCP is provided in the
busMasterConfigurationPart member of NetworkManagementInfo data type. This information
is obtained by calling service NetworkManagementInfoRead.
The BMCP includes information about the configuration and the parameters for the slave. The
BMCP is provided by the DTM and is required in order to generate the master configuration.
The BMCP contains data which might be changed during master configuration. That means
that the BMCP may be changed and transferred back to the slave DTM by calling
NetworkManagementInfoWrite. A Slave DTM must accept the new information and recompute
the configuration / internal parameters to match the new BMCP.
DTM must check whether the new values are according to the capabilities of the device. The
NetworkManagementInfoWrite call will be refused if the device can not handle the new values.
6.5.2.2 Creating the BMCP
This subclause explains the meaning of the individual elements of the BMCP in details.
The BCMP may be generated from the GSD information of a PROFIBUS device.
The BMCP is divided into four parts that are explained in the following subclauses.
The explanations use the GSD keywords and reference the PROFIBUS specification. See
also the table with complete BMCP in 6.5.2.2.1 .
6.5.2.2.1 Part 1: From Slave_Para_Len to Octet 15
The first part consists of a fixed set of bytes described in the table below.

62453-303-1 © IEC:2009(E) – 15 –
Table 3 – BMPC Part1 – General configuration
Byte Name Defined in Notice
0 Slave_Para_Len [5] 6.2.12.1
Length of the BMCP including this value
2 Sl_Flag [5] 6.2.12.2 The following GSD values are used [6]:
• Bit 0 : reserved,
• Bit 1: Extra_Alarm_SAP,
• Bit 2: DPV1_Data_Types,
• Bit 3: DPV1_Supported,
• Bit 4: Publisher_Enable,
• Bit 5 : Fail_Safe, .
The following bits are not based on GSD values:
• Bit 6 : New_Prm,
• Bit 7 : Active
3 Slave Type [5] 6.2.12.3
Value is 0 (= DP-Slave)
4 Max_Diag_Data_Len [5] 6.2.12.4 The following GSD value is used [6]: Max_Diag_Data_Len
5 Max_Alarm_Len [5] 6.2.12.5
6 Max_Channel_Data_Len [5] 6.2.12.6 This field defines how much data can be transferred between
slave and master. In this case, the maximum of these GSD
values [6] must be calculated:
• Max_Data_Len,
• C1_Max_Data_Len plus 4 Bytes (Function Num,
Slot_Number, Length)
7 Diag_Update_Delay [5] 6.2.12.7 The following GSD value is used [6]:Diag_Update_Delay
8 Alarm_Mode [5] 6.2.12.8
9 Add_Sl_Flag [5] 6.2.12.9
10 C1_Timeout [5] 6.2.12.10 The following GSD value is used [6]:C1_Response_Timeout
12 Reserved
6.5.2.2.2 Part 2: Parameter data
Part 2 of the BMCP are the slave parameter data.
Table 4 – BMPC Part2 – Parameter data
Byte Name Defined in Notice
16 Prm_Data_Len [5] 6.2.12.11 Length of the Parameter Data including this value
18 Station Status [5] 6.2.4.1 The following GSD values are used [6]:
• Bit 0-2: reserved,
• Bit 3: WD_On,
• Bit 4: Freeze_Req,
• Bit 5: Sync_Req,
• Bit 6,7(Lock/Unlock Request): [5] Table 402
19 WatchDog1 [5] 6.2.4.2  These values (WD_Fact_1 and WD_Fact_2) depend on the baud rate.
A master should set these values and slaves should handle new
values
20 WatchDog2 [5] 6.2.4.3
21 Min Tsdr [5] 6.2.4.4 Default value is 11 bit times [1]
22 Ident_Number [5] 6.2.3.5 The following GSD value is used [6]: Ident_Number

– 16 – 62453-303-1 © IEC:2009(E)
Byte Name Defined in Notice
24 Group_Ident [5] 6.2.4.5 Indicates the group assignment of the slave in a bitwise coded form
25 DPV1_Status_1 [5] 6.2.4.7 The following GSD values are used [6]:
• Bit 0,1: reserved,
• Bit 2: WD_Base_1ms,
• Bit 3 – 5: reserved,
• Bit 6: Fail_Safe,
• Bit 7 : DPV1_Enable,
These bits report the slave capabilities to the master and are
changed by the MS0 master following its capabilities
26 DPV1_Status_2 [5] 6.2.4.8 The following GSD values are used [6]:
• Bit 0: Check_Cfg_Mode,
• Bit 1: reserved,
• Bit 2: Enable_Update_Alarm,
• Bit 3: Enable_Status_Alarm,
• Bit 4: Enable_Manufacturer_Specific_Alarm,
• Bit 5: Enable_Diagnostic_Alarm,
• Bit 6: Enable_Process_Alarm,
• Bit 7: Enable_Pull_Plug_Alarm,
These bits report the slave capabilities to the master and are
changed by the MS0 master following its capabilities
• Bit 0-2: - ,
27 DPV1_Status_3 [5] 6.2.4.9
• Bit 3: Prm Structure,
• Bit 4: IsoM_Req,
• Bit 5-6: reserved,
• Bit 7: Prm_Cmd
28 User_Prm_Data From Byte 28 of the BMCP, a DTM has to insert additional user
parameter data. The information is given in the GSD file via value of

User_Prm_Data
NOTE 1 It is possible that a module does not have user parameter data. In this case, no para
...