IEC 61000-3-12:2004
(Main)Electromagnetic compatibility (EMC) - Part 3-12: Limits - Limits for harmonic currents produced by equipment connected to public low-voltage systems with input current > 16 A and ≤ 75 A per phase
Electromagnetic compatibility (EMC) - Part 3-12: Limits - Limits for harmonic currents produced by equipment connected to public low-voltage systems with input current > 16 A and ≤ 75 A per phase
Deals with the limitation of harmonic currents injected into the public supply system. The limits given in this International Standard are applicable to electrical and electronic equipment with a rated input current exceeding 16 A and up to and including 75 A per phase, intended to be connected to public low-voltage a.c. distribution systems of the following types: - nominal voltage up to 240 V, single-phase, two or three wires; - nominal voltage up to 690 V, three-phase, three or four wires; - nominal frequency 50 Hz or 60 Hz. Other distribution systems are excluded. The limits given in this edition apply to equipment when connected to 230/400 V, 50 Hz systems. This standard applies to equipment intended to be connected to low-voltage systems interfacing with the public supply at the low-voltage level. It does not apply to equipment intended to be connected only to private low-voltage systems interfacing with the public supply only at the medium- or high-voltage level. This standard defines: a) requirements and emission limits for equipment; b) methods for type tests and simulations. Tests according to this International Standard are type tests of complete pieces of equipment. Conformity with this standard can also be determined by validated simulations.
Compatibilité électromagnétique (CEM) - Partie 3-12: Limites - Limites pour les courants harmoniques produits par les appareils connectés aux réseaux publics basse tension ayant un courant appelé > 16 A et ≤ 75 A par phase
Traite de la limitation des courants harmoniques injectés dans le réseau public d'alimentation. Les limites définies dans la présente Norme internationale sont applicables aux appareils électriques et électroniques ayant un courant assigné d'entrée supérieur à 16 A et inférieur ou égal à 75 A par phase, destinés à être connectés aux réseaux publics de distribution en courant alternatif basse tension des types suivants: - tension nominale jusqu'à 240 V, monophasé, deux ou trois conducteurs; - tension nominale jusqu'à 690 V, triphasé, trois ou quatre conducteurs; - fréquence nominale 50 Hz ou 60 Hz. Les autres réseaux de distribution sont exclus. Les limites définies dans la présente édition s'appliquent aux appareils connectés aux réseaux 230/400 V, 50 Hz. La présente norme s'applique aux appareils destinés à être raccordés à des réseaux basse tension connectés au réseau public d'alimentation au niveau basse tension. Elle ne s'applique pas aux appareils destinés à être raccordés uniquement à des réseaux basse tension privés connectés au réseau public d'alimentation seulement au niveau moyenne ou haute tension. Cette norme définit: a) les exigences et limites d'émissions pour les appareils; b) les méthodes d'essai de type et de simulation. Les essais réalisés conformément à la présente Norme internationale sont des essais de type sur des équipements complets. La conformité à la présente norme peut également être déterminée au moyen de simulations validées.
General Information
Relations
Standards Content (Sample)
NORME CEI
INTERNATIONALE
IEC
61000-3-12
INTERNATIONAL
Première édition
STANDARD
First edition
2004-11
Compatibilité électromagnétique (CEM) –
Partie 3-12:
Limites – Limites pour les courants harmoniques
produits par les appareils connectés aux réseaux
publics basse tension ayant un courant appelé
>16 A et ≤≤≤≤75 A par phase
Electromagnetic compatibility (EMC) –
Part 3-12:
Limits – Limits for harmonic currents produced
by equipment connected to public low-voltage
systems with input current >16 A and ≤≤≤≤75 A
per phase
Numéro de référence
Reference number
CEI/IEC 61000-3-12:2004
Numérotation des publications Publication numbering
Depuis le 1er janvier 1997, les publications de la CEI As from 1 January 1997 all IEC publications are
sont numérotées à partir de 60000. Ainsi, la CEI 34-1 issued with a designation in the 60000 series. For
devient la CEI 60034-1. example, IEC 34-1 is now referred to as IEC 60034-1.
Editions consolidées Consolidated editions
Les versions consolidées de certaines publications de la The IEC is now publishing consolidated versions of its
CEI incorporant les amendements sont disponibles. Par publications. For example, edition numbers 1.0, 1.1
exemple, les numéros d’édition 1.0, 1.1 et 1.2 indiquent and 1.2 refer, respectively, to the base publication,
respectivement la publication de base, la publication de the base publication incorporating amendment 1 and
base incorporant l’amendement 1, et la publication de the base publication incorporating amendments 1
base incorporant les amendements 1 et 2. and 2.
Informations supplémentaires Further information on IEC publications
sur les publications de la CEI
Le contenu technique des publications de la CEI est The technical content of IEC publications is kept
constamment revu par la CEI afin qu'il reflète l'état under constant review by the IEC, thus ensuring that
actuel de la technique. Des renseignements relatifs à the content reflects current technology. Information
cette publication, y compris sa validité, sont dispo- relating to this publication, including its validity, is
nibles dans le Catalogue des publications de la CEI available in the IEC Catalogue of publications
(voir ci-dessous) en plus des nouvelles éditions, (see below) in addition to new editions, amendments
amendements et corrigenda. Des informations sur les and corrigenda. Information on the subjects under
sujets à l’étude et l’avancement des travaux entrepris consideration and work in progress undertaken by the
par le comité d’études qui a élaboré cette publication, technical committee which has prepared this
ainsi que la liste des publications parues, sont publication, as well as the list of publications issued,
également disponibles par l’intermédiaire de: is also available from the following:
• Site web de la CEI (www.iec.ch) • IEC Web Site (www.iec.ch)
• Catalogue des publications de la CEI • Catalogue of IEC publications
Le catalogue en ligne sur le site web de la CEI The on-line catalogue on the IEC web site
(www.iec.ch/searchpub) vous permet de faire des (www.iec.ch/searchpub) enables you to search by a
recherches en utilisant de nombreux critères, variety of criteria including text searches,
comprenant des recherches textuelles, par comité technical committees and date of publication. On-
d’études ou date de publication. Des informations en line information is also available on recently
ligne sont également disponibles sur les nouvelles issued publications, withdrawn and replaced
publications, les publications remplacées ou retirées, publications, as well as corrigenda.
ainsi que sur les corrigenda.
• IEC Just Published • IEC Just Published
Ce résumé des dernières publications parues This summary of recently issued publications
(www.iec.ch/online_news/justpub) est aussi dispo- (www.iec.ch/online_news/justpub) is also available
nible par courrier électronique. Veuillez prendre by email. Please contact the Customer Service
contact avec le Service client (voir ci-dessous) Centre (see below) for further information.
pour plus d’informations.
• Service clients • Customer Service Centre
Si vous avez des questions au sujet de cette If you have any questions regarding this
publication ou avez besoin de renseignements publication or need further assistance, please
supplémentaires, prenez contact avec le Service contact the Customer Service Centre:
clients:
Email: custserv@iec.ch Email: custserv@iec.ch
Tél: +41 22 919 02 11 Tel: +41 22 919 02 11
Fax: +41 22 919 03 00 Fax: +41 22 919 03 00
.
NORME CEI
INTERNATIONALE
IEC
61000-3-12
INTERNATIONAL
Première édition
STANDARD
First edition
2004-11
Compatibilité électromagnétique (CEM) –
Partie 3-12:
Limites – Limites pour les courants harmoniques
produits par les appareils connectés aux réseaux
publics basse tension ayant un courant appelé
>16 A et ≤≤≤≤75 A par phase
Electromagnetic compatibility (EMC) –
Part 3-12:
Limits – Limits for harmonic currents produced
by equipment connected to public low-voltage
systems with input current >16 A and ≤≤≤≤75 A
per phase
IEC 2004 Droits de reproduction réservés Copyright - all rights reserved
Aucune partie de cette publication ne peut être reproduite ni No part of this publication may be reproduced or utilized in any
utilisée sous quelque forme que ce soit et par aucun procédé, form or by any means, electronic or mechanical, including
électronique ou mécanique, y compris la photocopie et les photocopying and microfilm, without permission in writing from
microfilms, sans l'accord écrit de l'éditeur. the publisher.
International Electrotechnical Commission, 3, rue de Varembé, PO Box 131, CH-1211 Geneva 20, Switzerland
Telephone: +41 22 919 02 11 Telefax: +41 22 919 03 00 E-mail: inmail@iec.ch Web: www.iec.ch
CODE PRIX
U
PRICE CODE
Commission Electrotechnique Internationale
International Electrotechnical Commission
МеждународнаяЭлектротехническаяКомиссия
Pour prix, voir catalogue en vigueur
For price, see current catalogue
– 2 – 61000-3-12 CEI:2004
SOMMAIRE
AVANT-PROPOS .4
INTRODUCTION.8
1 Domaine d'application.10
2 Références normatives.12
3 Termes et définitions .12
4 Conditions de mesure .20
4.1 Courant fondamental de référence .20
4.2 Mesure des courants harmoniques.20
4.3 Matériel comprenant plusieurs éléments autonomes .24
5 Exigences et limites pour le matériel .24
5.1 Méthodes de commande.24
5.2 Limites d’émission.26
6 Documentation du produit .32
7 Conditions d’essai et de simulation .34
7.1 Exigences relatives aux mesures directes .34
7.2 Exigences relatives aux simulations .36
7.3 Conditions générales pour l'essai et la simulation.38
Annexe A (normative) Illustration des limites pour les courants harmoniques .40
Annexe B (normative) Formules d'interpolation approximatives.42
Annexe C (informative) Appareils non conformes aux exigences et limites de la
présente norme.46
Annexe D (informative) Informations sur le facteur PWHD .48
Bibliographie .52
Figure 1 – Définition du déphasage du courant harmonique de rang 5 (I en avance par
α > 0).18
rapport à U ,
p1
Figure 2 – Définition du déphasage du courant harmonique de rang 5 (I en retard par
rapport à U , α < 0).20
p1 5
Figure A.1 – Limites du courant harmonique de rang 5 en fonction de R .40
sce
Tableau 1 – Valeurs de la période d'observation.24
Tableau 2 – Limites d'émission en courant pour le matériel autre que le matériel
triphasé équilibré .28
Tableau 3 – Limites d'émission en courant pour le matériel triphasé équilibré .30
Tableau 4 – Limites d'émission en courant pour le matériel triphasé équilibré sous
certaines conditions spécifiées .30
61000-3-12 IEC:2004 – 3 –
CONTENTS
FOREWORD.5
INTRODUCTION.9
1 Scope.11
2 Normative references.13
3 Terms and definitions .13
4 Measurement conditions.21
4.1 Reference fundamental current.21
4.2 Harmonic current measurement .21
4.3 Equipment consisting of several self-contained items .25
5 Requirements and limits for equipment .25
5.1 Control methods.25
5.2 Limits for emission.27
6 Product documentation.33
7 Test and simulation conditions .35
7.1 Requirements for direct measurement .35
7.2 Requirements for simulation .37
7.3 General conditions for test and simulation.39
Annex A (normative) Illustration of limits for harmonic currents .41
Annex B (normative) Approximate interpolation formulas .43
Annex C (informative) Equipment not complying with the requirements and limits
of this standard .47
Annex D (informative) Information on the PWHD factor.49
Bibliography .53
th
Figure 1 – Definition of the 5 harmonic current phase angle (I leads U , α > 0) .19
5 p1 5
th
Figure 2 – Definition of the 5 harmonic current phase angle (I lags U , α < 0) .21
5 p1 5
th
Figure A.1 – Limits of the 5 harmonic current as functions of R .41
sce
Table 1 – Values of the observation period .25
Table 2 – Current emission limits for equipment other than balanced three-phase
equipment.29
Table 3 – Current emission limits for balanced three-phase equipment .31
Table 4 – Current emission limits for balanced three-phase equipment under specified
conditions .31
– 4 – 61000-3-12 CEI:2004
COMMISSION ÉLECTROTECHNIQUE INTERNATIONALE
____________
COMPATIBILITÉ ÉLECTROMAGNÉTIQUE (CEM) –
Partie 3-12: Limites – Limites pour les courants harmoniques
produits par les appareils connectés aux réseaux publics basse tension
ayant un courant appelé >16 A et ≤≤≤≤75 A par phase
AVANT-PROPOS
1) La Commission Electrotechnique Internationale (CEI) est une organisation mondiale de normalisation composée
de l'ensemble des comités électrotechniques nationaux (Comités nationaux de la CEI). La CEI a pour objet de
favoriser la coopération internationale pour toutes les questions de normalisation dans les domaines de
l'électricité et de l'électronique. A cet effet, la CEI – entre autres activités – publie des Normes internationales,
des Spécifications techniques, des Rapports techniques, des Spécifications accessibles au public (PAS) et des
Guides (ci-après dénommés "Publication(s) de la CEI"). Leur élaboration est confiée à des comités d'études,
aux travaux desquels tout Comité national intéressé par le sujet traité peut participer. Les organisations
internationales, gouvernementales et non gouvernementales, en liaison avec la CEI, participent également aux
travaux. La CEI collabore étroitement avec l'Organisation Internationale de Normalisation (ISO), selon des
conditions fixées par accord entre les deux organisations.
2) Les décisions ou accords officiels de la CEI concernant les questions techniques représentent, dans la mesure
du possible, un accord international sur les sujets étudiés, étant donné que les Comités nationaux de la CEI
intéressés sont représentés dans chaque comité d’études.
3) Les Publications de la CEI se présentent sous la forme de recommandations internationales et sont agréées
comme telles par les Comités nationaux de la CEI. Tous les efforts raisonnables sont entrepris afin que la CEI
s'assure de l'exactitude du contenu technique de ses publications; la CEI ne peut pas être tenue responsable de
l'éventuelle mauvaise utilisation ou interprétation qui en est faite par un quelconque utilisateur final.
4) Dans le but d'encourager l'uniformité internationale, les Comités nationaux de la CEI s'engagent, dans toute la
mesure possible, à appliquer de façon transparente les Publications de la CEI dans leurs publications
nationales et régionales. Toutes divergences entre toutes Publications de la CEI et toutes publications
nationales ou régionales correspondantes doivent être indiquées en termes clairs dans ces dernières.
5) La CEI n’a prévu aucune procédure de marquage valant indication d’approbation et n'engage pas sa
responsabilité pour les équipements déclarés conformes à une de ses Publications.
6) Tous les utilisateurs doivent s'assurer qu'ils sont en possession de la dernière édition de cette publication.
7) Aucune responsabilité ne doit être imputée à la CEI, à ses administrateurs, employés, auxiliaires ou
mandataires, y compris ses experts particuliers et les membres de ses comités d'études et des Comités
nationaux de la CEI, pour tout préjudice causé en cas de dommages corporels et matériels, ou de tout autre
dommage de quelque nature que ce soit, directe ou indirecte, ou pour supporter les coûts (y compris les frais
de justice) et les dépenses découlant de la publication ou de l'utilisation de cette Publication de la CEI ou de
toute autre Publication de la CEI, ou au crédit qui lui est accordé.
8) L'attention est attirée sur les références normatives citées dans cette publication. L'utilisation de publications
référencées est obligatoire pour une application correcte de la présente publication.
9) L’attention est attirée sur le fait que certains des éléments de la présente Publication de la CEI peuvent faire
l’objet de droits de propriété intellectuelle ou de droits analogues. La CEI ne saurait être tenue pour
responsable de ne pas avoir identifié de tels droits de propriété et de ne pas avoir signalé leur existence.
La Norme internationale CEI 61000-3-12 a été préparée par le sous-comité 77A: Phénomènes
basse fréquence, du comité d'études 77 de la CEI: Compatibilité électromagnétique.
Cette première édition remplace la CEI 61000-3-4, publiée en 1998, pour les appareils ayant
un courant appelé ≤75 A par phase. Pour les appareils ayant un courant appelé >75 A par
phase, la CEI 61000-3-4 demeure valide.
61000-3-12 IEC:2004 – 5 –
INTERNATIONAL ELECTROTECHNICAL COMMISSION
____________
ELECTROMAGNETIC COMPATIBILITY (EMC) –
Part 3-12: Limits – Limits for harmonic currents
produced by equipment connected to public low-voltage systems with
input current >16 A and ≤≤≤≤75 A per phase
FOREWORD
1) The International Electrotechnical Commission (IEC) is a worldwide organization for standardization comprising
all national electrotechnical committees (IEC National Committees). The object of IEC is to promote
international co-operation on all questions concerning standardization in the electrical and electronic fields. To
this end and in addition to other activities, IEC publishes International Standards, Technical Specifications,
Technical Reports, Publicly Available Specifications (PAS) and Guides (hereafter referred to as “IEC
Publication(s)”). Their preparation is entrusted to technical committees; any IEC National Committee interested
in the subject dealt with may participate in this preparatory work. International, governmental and non-
governmental organizations liaising with the IEC also participate in this preparation. IEC collaborates closely
with the International Organization for Standardization (ISO) in accordance with conditions determined by
agreement between the two organizations.
2) The formal decisions or agreements of IEC on technical matters express, as nearly as possible, an international
consensus of opinion on the relevant subjects since each technical committee has representation from all
interested IEC National Committees.
3) IEC Publications have the form of recommendations for international use and are accepted by IEC National
Committees in that sense. While all reasonable efforts are made to ensure that the technical content of IEC
Publications is accurate, IEC cannot be held responsible for the way in which they are used or for any
misinterpretation by any end user.
4) In order to promote international uniformity, IEC National Committees undertake to apply IEC Publications
transparently to the maximum extent possible in their national and regional publications. Any divergence
between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in
the latter.
5) IEC provides no marking procedure to indicate its approval and cannot be rendered responsible for any
equipment declared to be in conformity with an IEC Publication.
6) All users should ensure that they have the latest edition of this publication.
7) No liability shall attach to IEC or its directors, employees, servants or agents including individual experts and
members of its technical committees and IEC National Committees for any personal injury, property damage or
other damage of any nature whatsoever, whether direct or indirect, or for costs (including legal fees) and
expenses arising out of the publication, use of, or reliance upon, this IEC Publication or any other IEC
Publications.
8) Attention is drawn to the Normative references cited in this publication. Use of the referenced publications is
indispensable for the correct application of this publication.
9) Attention is drawn to the possibility that some of the elements of this IEC Publication may be the subject of
patent rights. IEC shall not be held responsible for identifying any or all such patent rights.
International Standard IEC 61000-3-12 has been prepared by sub-committee 77A: Low
frequency phenomena, of IEC technical committee 77: Electromagnetic compatibility.
This first edition replaces IEC 61000-3-4, published in 1998, for equipment with input current
≤75 A per phase. For equipment with input current >75 A per phase, IEC 61000-3-4 remains
valid.
– 6 – 61000-3-12 CEI:2004
Le texte de cette norme est issu des documents suivants:
FDIS Rapport de vote
77A/470/FDIS 77A/478/RVD
Le rapport de vote indiqué dans le tableau ci-dessus donne toute information sur le vote ayant
abouti à l'approbation de cette norme.
Cette publication a été rédigée selon les Directives ISO/CEI, Partie 2.
Le comité a décidé que le contenu de cette publication ne sera pas modifié avant la date de
maintenance indiquée sur le site web de la CEI sous «http://webstore.iec.ch» dans les données
relatives à la publication recherchée. A cette date, la publication sera
• reconduite;
• supprimée;
• remplacée par une édition révisée, ou
• amendée.
61000-3-12 IEC:2004 – 7 –
The text of this standard is based on the following documents:
FDIS Report on voting
77A/470/FDIS 77A/478/RVD
Full information on the voting for the approval of this standard can be found in the report on
voting indicated in the above table.
This publication has been drafted in accordance with the ISO/IEC Directives, Part 2.
The committee has decided that the contents of this publication will remain unchanged until the
maintenance result date indicated on the IEC web site under "http://webstore.iec.ch" in the data
related to the specific publication. At this date, the publication will be
• reconfirmed;
• withdrawn;
• replaced by a revised edition, or
• amended.
– 8 – 61000-3-12 CEI:2004
INTRODUCTION
La série CEI 61000 est publiée en différentes parties suivant la structure ci-dessous:
Partie 1: Généralités
Considérations générales (introduction, principes fondamentaux)
Définitions, terminologie
Partie 2: Environnement
Description de l’environnement
Classification de l’environnement
Niveaux de compatibilité
Partie 3: Limites
Limites d’émissions
Limites d’immunité (dans la mesure où elles ne relèvent pas des comités de produits)
Partie 4: Techniques d’essai et de mesure
Techniques de mesure
Techniques d’essai
Partie 5: Guides d’installation et d’atténuation
Guides d’installation
Méthodes et dispositifs d’atténuation
Partie 6: Normes génériques
Partie 9: Divers
Chaque partie est à son tour subdivisée en plusieurs parties, publiées soit comme normes
internationales soit comme spécifications techniques ou rapports techniques, dont certaines
ont déjà été publiées en tant que sections. D’autres seront publiées avec le numéro de partie,
suivi d’un tiret et d’un second numéro identifiant la subdivision (exemple: 61000-6-1).
La présente Norme internationale est une norme de famille de produits.
61000-3-12 IEC:2004 – 9 –
INTRODUCTION
IEC 61000 is published in separate parts according to the following structure:
Part 1: General
General considerations (introduction, fundamental principles)
Definitions, terminology
Part 2: Environment
Description of the environment
Classification of the environment
Compatibility levels
Part 3: Limits
Emission limits
Immunity limits (in so far as they do not fall under the responsibility of the product
committees)
Part 4: Testing and measurement techniques
Measurement techniques
Testing techniques
Part 5: Installation and mitigation guidelines
Installation guidelines
Mitigation methods and devices
Part 6: Generic standards
Part 9: Miscellaneous
Each part is further subdivided into several parts, published either as International Standards
or as technical specifications or technical reports, some of which have already been published
as sections. Others will be published with the part number followed by a dash and a second
number identifying the subdivision (example: 61000-6-1).
This International Standard is a Product Family Standard.
– 10 – 61000-3-12 CEI:2004
COMPATIBILITÉ ÉLECTROMAGNÉTIQUE (CEM) –
Partie 3-12: Limites – Limites pour les courants harmoniques
produits par les appareils connectés aux réseaux publics basse tension
ayant un courant appelé >16 A et ≤≤≤≤ 75 A par phase
1 Domaine d'application
La présente partie de la CEI 61000 traite de la limitation des courants harmoniques injectés
dans le réseau public d'alimentation. Les limites définies dans la présente Norme internationale
sont applicables aux appareils électriques et électroniques ayant un courant assigné d’entrée
supérieur à 16 A et inférieur ou égal à 75 A par phase, destinés à être connectés aux réseaux
publics de distribution en courant alternatif basse tension des types suivants:
• tension nominale jusqu'à 240 V, monophasé, deux ou trois conducteurs;
• tension nominale jusqu'à 690 V, triphasé, trois ou quatre conducteurs;
• fréquence nominale 50 Hz ou 60 Hz.
Les autres réseaux de distribution sont exclus. Les limites définies dans la présente édition
s'appliquent aux appareils connectés aux réseaux 230/400 V, 50 Hz. Voir également l'Article 5.
NOTE Les limites pour les autres réseaux seront ajoutées dans une future édition de la présente norme.
La présente norme s'applique aux appareils destinés à être raccordés à des réseaux basse
tension connectés au réseau public d'alimentation au niveau basse tension. Elle ne s'applique
pas aux appareils destinés à être raccordés uniquement à des réseaux basse tension privés
connectés au réseau public d’alimentation seulement au niveau moyenne ou haute tension.
NOTE 1 Le domaine d'application de la présente norme se limite aux appareils connectés aux réseaux publics
d'alimentation basse tension, les émissions produites par des appareils installés sur les réseaux basse tension
privés pouvant être contrôlées globalement au point de couplage commun MT au moyen de procédures définies
dans la CEI 61000-3-6 et/ou par le biais d'accords contractuels conclus entre l’exploitant du réseau de distribution
et le client. On s’attend à ce que les exploitants de réseaux privés gèrent l'environnement CEM de façon à en
garantir la conformité avec les dispositions définies dans la CEI 61000-3-6 et/ou les accords contractuels.
NOTE 2 Si le matériel est destiné à être connecté uniquement à des réseaux privés, il convient que le fabricant le
précise de manière très explicite dans la documentation des produits concernés.
NOTE 3 Le matériel professionnel ayant un courant appelé ≤ 16 A par phase et qui n’est pas conforme aux
exigences et limites de la CEI 61000-3-2 peut être autorisé à être connecté à certains types de réseaux
d'alimentation basse tension, de la même façon que le matériel ayant un courant appelé > 16 A par phase et qui
n’est pas conforme aux exigences et limites de la présente norme CEI 61000-3-12 (voir l’Annexe C).
NOTE 4 Les limites de la présente norme ne s'appliquent pas aux filtres harmoniques autonomes.
Cette norme définit:
a) les exigences et limites d'émissions pour les appareils;
b) les méthodes d'essai de type et de simulation.
Les essais réalisés conformément à la présente Norme internationale sont des essais de type
sur des équipements complets.
La conformité à la présente norme peut également être déterminée au moyen de simulations
validées.
61000-3-12 IEC:2004 – 11 –
ELECTROMAGNETIC COMPATIBILITY (EMC) –
Part 3-12: Limits – Limits for harmonic currents
produced by equipment connected to public low-voltage systems with
input current >16 A and ≤≤75 A per phase
≤≤
1 Scope
This part of IEC 61000 deals with the limitation of harmonic currents injected into the public
supply system. The limits given in this International Standard are applicable to electrical and
electronic equipment with a rated input current exceeding 16 A and up to and including 75 A
per phase, intended to be connected to public low-voltage a.c. distribution systems of the
following types:
• nominal voltage up to 240 V, single-phase, two or three wires;
• nominal voltage up to 690 V, three-phase, three or four wires;
• nominal frequency 50 Hz or 60 Hz.
Other distribution systems are excluded. The limits given in this edition apply to equipment
when connected to 230/400 V, 50 Hz systems. See also Clause 5.
NOTE The limits for the other systems will be added in a future edition of this standard.
This standard applies to equipment intended to be connected to low-voltage systems
interfacing with the public supply at the low-voltage level. It does not apply to equipment
intended to be connected only to private low-voltage systems interfacing with the public supply
only at the medium- or high-voltage level.
NOTE 1 The scope of this standard is limited to equipment connected to public low voltage systems because
emissions from equipment installed in private low voltage systems can be controlled in aggregate at the MV point of
common coupling using procedures defined in IEC 61000-3-6 and/or by means of contractual agreements between
the distribution network operator and the customer. It is expected that operators of private systems will manage the
EMC environment in a manner that ensures compliance with the provisions given in IEC 61000-3-6 and/or the
contractual agreements.
NOTE 2 If the equipment is intended to be connected only to private systems, the manufacturer should make this
very clear in the product documentation.
NOTE 3 Professional equipment with input current ≤ 16 A per phase and that does not comply with the
requirements and limits of standard IEC 61000-3-2 may be permitted to be connected to certain types of low voltage
supplies, in the same way as equipment with input current > 16 A per phase and that does not comply with the
requirements and limits of the present standard IEC 61000-3-12 (see Annex C).
NOTE 4 The limits in this standard are not applicable to stand-alone harmonic filters.
This standard defines:
a) requirements and emission limits for equipment;
b) methods for type tests and simulations.
Tests according to this International Standard are type tests of complete pieces of equipment.
Conformity with this standard can also be determined by validated simulations.
– 12 – 61000-3-12 CEI:2004
2 Références normatives
Les documents de référence suivants sont indispensables pour l'application du présent
document. Pour les références datées, seule l'édition citée s'applique. Pour les références non
datées, la dernière édition du document de référence s'applique (y compris les éventuels
amendements).
CEI 60038, Tensions normales de la CEI
CEI 60050-161, Vocabulaire électrotechnique international (VEI) – Chapitre 161: Compatibilité
électromagnétique
CEI 61000-2-2, Compatibilité électromagnétique (CEM) – Partie 2-2: Environnement – Niveaux
de compatibilité pour les perturbations conduites à basse fréquence et la transmission des
signaux sur les réseaux publics d'alimentation basse tension
CEI 61000-2-4, Compatibilité électromagnétique (CEM) – Partie 2-4: Environnement – Niveaux
de compatibilité dans les installations industrielles pour les perturbations conduites à basse
fréquence
CEI 61000-3-2, Compatibilité électromagnétique (CEM) – Partie 3-2: Limites – Limites pour les
émissions de courant harmonique (courant appelé par les appareils ≤16 A par phase)
CEI 61000-4-7, Compatibilité électromagnétique (CEM) – Partie 4-7: Techniques d'essai et de
mesure – Guide général relatif aux mesures d'harmoniques et d'interharmoniques, ainsi qu'à
l'appareillage de mesure, applicable aux réseaux d'alimentation et aux appareils qui y sont
raccordés
3 Termes et définitions
Pour les besoins du présent document, les définitions données dans la CEI 60050(161) ainsi
que les définitions suivantes s'appliquent.
3.1
distorsion harmonique totale
THD
rapport de la valeur efficace des harmoniques (dans ce contexte, courants harmoniques I de
n
rang n) à la valeur efficace du fondamental, soit
I
n
THD =
∑
I
1
n=2
NOTE Cette définition a été choisie conformément à la norme appropriée CEI 61000-2-2.
3.2
distorsion harmonique partielle pondérée
PWHD
rapport de la valeur efficace d'un groupe sélectionné d'harmoniques de rang supérieur
(commençant, dans la présente norme internationale, au quatorzième harmonique), pondéré
par le rang harmonique n, à la valeur efficace du fondamental:
61000-3-12 IEC:2004 – 13 –
2 Normative references
The following referenced documents are indispensable for the application of this document. For
dated references, only the edition cited applies. For undated references, the latest edition of
the referenced document (including any amendments) applies.
IEC 60038, IEC standard voltages
IEC 60050-161, International Electrotechnical Vocabulary (IEV) – Chapter 161: Electro-
magnetic compatibility
IEC 61000-2-2, Electromagnetic compatibility (EMC) – Part 2-2: Environment – Compatibility
levels for low-frequency conducted disturbances and signalling in public low-voltage power
supply systems
IEC 61000-2-4, Electromagnetic compatibility (EMC) – Part 2-4: Environment – Compatibility
levels in industrial plants for low-frequency conducted disturbances
IEC 61000-3-2, Electromagnetic compatibility (EMC) – Part 3-2: Limits – Limits for harmonic
current emissions (equipment input current ≤ 16 A per phase)
IEC 61000-4-7, Electromagnetic compatibility (EMC) – Part 4-7: Testing and measurement
techniques – General guide on harmonics and interharmonics measurements and
instrumentation, for power supply systems and equipment connected thereto
3 Terms and definitions
For the purposes of this document, the definitions given in IEC 60050(161) and the following
definitions apply.
3.1
total harmonic distortion
THD
ratio of the r.m.s. value of the harmonics (in this context harmonic currents I of the order n) to
n
the r.m.s. value of the fundamental, viz.
I
n
THD =
∑
I
1
n=2
NOTE This definition has been chosen in accordance with the relevant standard, IEC 61000-2-2.
3.2
partial weighted harmonic distortion
PWHD
ratio of the r.m.s. value of a selected group of higher order harmonics (in this International
Standard beginning from the fourteenth harmonic), weighted with the harmonic order n, to the
r.m.s. value of the fundamental:
– 14 – 61000-3-12 CEI:2004
I
n
PWHD = n
∑
I
1
n=14
La distorsion harmonique partielle pondérée est utilisée afin de s'assurer que l'incidence des
courants harmoniques de rang supérieur sur les résultats est suffisamment atténuée, et qu'il
n'est pas nécessaire de spécifier des limites individuelles.
3.3
point de couplage commun
PCC
point sur le réseau de distribution public qui est le plus proche du client concerné et auquel
d'autres clients sont ou peuvent être connectés
3.4
matériel monophasé
matériel connecté entre un conducteur de phase et le conducteur de neutre
NOTE Cela inclut les appareils dans lesquels des charges distinctes sont connectées entre un ou plusieurs
conducteurs de phase et le conducteur de neutre.
3.5
matériel entre phases
matériel connecté entre deux conducteurs de phase
Dans les conditions normales d'utilisation, le conducteur de neutre n'est pas utilisé en tant que
conducteur transportant du courant.
3.6
matériel triphasé
matériel connecté aux trois conducteurs de phase
Dans les conditions normales d'utilisation, le conducteur de neutre n'est pas utilisé en tant que
conducteur transportant du courant.
NOTE Un appareil destiné à être connecté à l’ensemble des trois phases et au neutre et dans lequel le conducteur
de neutre est utilisé en tant que conducteur transportant du courant est considéré comme trois matériels
monophasés distincts.
3.6.1
matériel triphasé équilibré
matériel triphasé connecté aux trois conducteurs de phase d'un réseau d'alimentation triphasé,
et qui est conçu de façon à ce que les trois courants de phase aient une amplitude et une
forme d'onde identiques, chaque courant étant décalé d'un tiers de période du fondamental par
rapport aux deux autres
3.6.2
matériel triphasé non équilibré
matériel triphasé connecté aux trois conducteurs de phase d'un réseau d'alimentation triphasé,
et qui n’est pas conçu de façon à ce que les trois courants de phase aient une amplitude et
une forme d'onde identiques, ou dans lequel le décalage entre deux courants de phase
quelconques est différent d'un tiers de période du fondamental
3.7
matériel hybride
combinaison d'une charge triphasée équilibrée et d'une ou plusieurs charges connectées entre
phase et neutre ou entre phases
61000-3-12 IEC:2004 – 15 –
I
n
PWHD = n
∑
I
1
n=14
The partial weighted harmonic distortion is employed in order to ensure that the effects of the
higher order harmonic currents on the results are reduced sufficiently and individual limits need
not be specified.
3.3
point of common coupling
PCC
point in the public system which is closest to the customer concerned and to which other
customers are or may be connected
3.4
single-phase equipment
equipment which is connected between one line conductor and the neutral conductor
NOTE This includes equipment in which separate loads are connected from one or more line conductors to the
neutral conductor
3.5
interphase equipment
equipment which is connected between two line conductors (phases)
The neutral conductor is not used as a current-carrying conductor under normal operating
conditions.
3.6
three-phase equipment
equipment which is connected to the three line conductors
The neutral conductor is not used as a current-carrying conductor under normal operating
conditions.
NOTE Equipment intended to be connected to all three phases and to the neutral and where the neutral conductor
is used as a current-carrying conductor, is considered as three separate single-phase items.
3.6.1
balanced three-phase equipment
three-phase equipment which is connected to the three line conductors of a three-phase supply
and in which the three line or phase currents are designed to be identical in amplitude and
wave-shape, each being displaced from the other two by one-third of a fundamental period
3.6.2
unbalanced three-phase equipment
three-phase equipment which is connected to the three line conductors of a three-phase supply
and in which the three line or phase currents are not designed to be identical in amplitude or
wave-shape, or the displacement between any two is other than one-third of a fundamental period
3.7
hybrid equipment
combination of a balanced three-phase load and one or more loads connected between phase
and neutral or between phases
– 16 – 61000-3-12 CEI:2004
3.8
puissance de court-circuit
S
sc
valeur de la puissance de court-circuit triphasée calculée à partir de la tension nominale du
réseau entre phases U et de l'impédance de phase du réseau Z au niveau du PCC:
nominale
= U / Z
S
sc nominale
où Z est l'impédance du réseau à la fréquence du secteur
3.9
puissance apparente assignée de l’appareil
S
equ
valeur calculée à partir du courant de phase assigné I de l’appareil, tel qu'il est déclaré par
equ
le fabricant, et de la tension assignée U (monophasée) ou U (entre phases), comme suit:
p i
a) S = U I pour le matériel monophasé et la partie monophasée d’un matériel
equ p equ
hybride;
b) S = U I pour le matériel entre phases;
equ i equ
c) S = 3 U I pour le matériel triphasé équilibré et la partie triphasée d’un matériel
equ i equ
hybride;
d) S = 3 U I pour le matériel triphasé non équilibré, où I est la valeur
equ p equ max equ max
maximale des courants efficaces circulant dans l'une quelconque des
trois phases
Dans le cas d’une gamme de tensions, U ou U est une tension nominale du réseau
p i
conformément à la CEI 60038 (par exemple 120 V ou 230 V en monophasé, ou 400 V phase-
phase en triphasé).
3.10
rapport de court-circuit
R
sce
valeur caractéristique d'un appareil définie comme suit:
a) R = S / (3 S ) pour le matériel monophasé et la partie monophasée d’un matériel
sce sc equ
hybride;
b) R = S / (2 S ) pour le matériel entre phases;
sce sc equ
c) R = S / S pour tout matériel triphasé et la partie triphasée d’un matériel
sce sc equ
hybride
NOTE 1 R peut directement se référer à des quantités de base connues au moyen des équations suivantes:
sce
R = U/(√3 × Z × I ) pour le matériel monophasé et la partie monophasée d’un matériel hybride;
sce equ
R = U/(2 × Z × I ) pour le matériel entre phases;
sce equ
R = U/(√3 × Z × I ) pour le matériel triphasé équilibré et la partie triphasée d’un matériel hybride;
sce equ
R = U/(√3 × Z × I ) pour le matériel triphasé non équilibré.
sce equ max
où U = U , et est supposée être égale à U ou √3 × U , selon la valeur adéquate.
nominale i p
NOTE 2 R n'est pas la même grandeur que R , telle que définie dans la CEI 61000-2-6.
sce sc
NOTE 3 Pour le matériel hybride, la méthode pour calculer une valeur unique R est fournie en 5.2.
sce
3.11
courant fondamental de référence
I
valeur efficace de la composante fondamentale du courant de phase assigné I de
equ
l’équipement (voir également 4.1)
61000-3-12 IEC:2004 – 17 –
3.8
short-circuit power
S
sc
value of the three-phase short-circuit power calculated from the nominal interphase system
voltage U and the line impedance Z of the system at the PCC:
nominal
= U / Z
S
sc nominal
where Z is the system impedance at the power frequency
3.9
rated apparent power of the equipment
S
equ
value calculated from the rated line current I of the piece of equipment stated by the
equ
manufacturer and the rated voltage U (single phase) or U (interphase) as follows:
p i
a) S = U I for single-phase equipment and the single-phase part of hybrid
equ p equ
equipment;
b) S = U I for interphase equipment;
equ i equ
c) S = 3 U I for balanced three-phase equipment and the three-phase part of
equ i equ
hybrid equipment;
d) S = 3 U I for unbalanced three-phase equipment, where I is the
equ p equ max equ max
maximum of the r.m.s. currents
...