Abstract

Applies to controllers intended for starting, controlling and stopping stationary fire pumps, including automatic and non-automatic types for alternating current electric motor or diesel engine driven fire pumps. It is anticipated that a controller only controls a single driver. Controllers for electric motor driven fire pumps always include suitable short-circuit protection as an integral part of the controller. These controllers may include an integral power transfer switch. These controllers are rated 1 000 V a.c. maximum. Controllers for diesel engine driven fire pumps include electrical circuits that operate various control and supervisory functions such as remote control (starting and stopping), alarms, signals, indicators, and the proper operation of battery chargers. The most significant purpose of this technical specification is to characterize the unique features of fire pump controllers. A further purpose is to prescribe a procedure for exercising the controllers to verify that the unique features are operative. For the purpose of this technical specification, this procedure is described as the "fire pump controller test protocol". The object of this technical specification is to state the following: a) The unique characteristics of fire pump controllers, their associated equipment and their operational functions; b) The conditions with which fire pump controllers should comply with reference to 1) their construction; 2) their critical components including the mounting, arrangement, wiring and connections; 3) the degrees of protection provided by their enclosures; 4) their modes of actuation; 5) their operation and behaviour under normal, overload and short-circuit conditions; 6) their capability to annunciate significant events; 7) their electromagnetic compatibility for the environment into which they are placed; c) The tests intended for confirming that these conditions have been met, and the methods to be adopted for these tests; d) The information to be given with the equipment, or in the manufacturer's literature. In this context, this technical specification gives the requirements for all of the electrical functions associated with both the electric motor driven and the diesel engine driven fire pumps. Special applications such as explosive atmospheres, nuclear installations, ships, aircraft, etc. are not covered by this technical specification. Referring to electric power sources, the requirements of this technical specification apply only to the extent that they place limits on the nature, behaviour and characteristics of the electrical energy that is supplied to the service entrance (see IEC 60364-5-55). The requirements of this technical specification do not apply to the method or means by which the electrical energy is generated nor to the installation between the origin of the installation and the fire pump controller, which are to be found in IEC 60364 series. This technical specification does not apply to diesel engine driven electric generators which may be associated with a stationary fire pump installation. EMC considerations are correlated with other IEC standards for similar products: a) for electric fire pump controllers, EMC considerations are covered by this technical specification, and b) for diesel engine fire pump controllers, d.c. batteries are the intended source of electrical control power.

Status
Replaced
Publication Date
29-Jun-2003
Current Stage
DELPUB - Deleted publication - 99 Deleted
Start Date
24-Jan-2007

Buy Documents

Technical specification

IEC TS 62091:2003 - Low-voltage switchgear and controlgear - Controllers for drivers of stationary fire pumps Released:6/30/2003

ISBN:2-8318-7121-2
English and French language (117 pages)
sale 15% off
Preview
sale 15% off
Preview

Relations

Effective Date
28-Jun-2024

Buy Documents

Technical specification

IEC TS 62091:2003 - Low-voltage switchgear and controlgear - Controllers for drivers of stationary fire pumps Released:6/30/2003

ISBN:2-8318-7121-2
English and French language (117 pages)
sale 15% off
Preview
sale 15% off
Preview

Get Certified

Connect with accredited certification bodies for this standard

IMQ S.p.A. (Certification)

Italian electrical product certification.

ACCREDIA Italy Verified

SLG Prüf- und Zertifizierungs GmbH

German testing and certification body.

DAKKS Germany Verified

UL Solutions

Global safety science company with testing, inspection and certification.

ANAB United States Verified

Sponsored listings

Frequently Asked Questions

IEC TS 62091:2003 is a technical specification published by the International Electrotechnical Commission (IEC). Its full title is "Low-voltage switchgear and controlgear - Controllers for drivers of stationary fire pumps". This standard covers: Applies to controllers intended for starting, controlling and stopping stationary fire pumps, including automatic and non-automatic types for alternating current electric motor or diesel engine driven fire pumps. It is anticipated that a controller only controls a single driver. Controllers for electric motor driven fire pumps always include suitable short-circuit protection as an integral part of the controller. These controllers may include an integral power transfer switch. These controllers are rated 1 000 V a.c. maximum. Controllers for diesel engine driven fire pumps include electrical circuits that operate various control and supervisory functions such as remote control (starting and stopping), alarms, signals, indicators, and the proper operation of battery chargers. The most significant purpose of this technical specification is to characterize the unique features of fire pump controllers. A further purpose is to prescribe a procedure for exercising the controllers to verify that the unique features are operative. For the purpose of this technical specification, this procedure is described as the "fire pump controller test protocol". The object of this technical specification is to state the following: a) The unique characteristics of fire pump controllers, their associated equipment and their operational functions; b) The conditions with which fire pump controllers should comply with reference to 1) their construction; 2) their critical components including the mounting, arrangement, wiring and connections; 3) the degrees of protection provided by their enclosures; 4) their modes of actuation; 5) their operation and behaviour under normal, overload and short-circuit conditions; 6) their capability to annunciate significant events; 7) their electromagnetic compatibility for the environment into which they are placed; c) The tests intended for confirming that these conditions have been met, and the methods to be adopted for these tests; d) The information to be given with the equipment, or in the manufacturer's literature. In this context, this technical specification gives the requirements for all of the electrical functions associated with both the electric motor driven and the diesel engine driven fire pumps. Special applications such as explosive atmospheres, nuclear installations, ships, aircraft, etc. are not covered by this technical specification. Referring to electric power sources, the requirements of this technical specification apply only to the extent that they place limits on the nature, behaviour and characteristics of the electrical energy that is supplied to the service entrance (see IEC 60364-5-55). The requirements of this technical specification do not apply to the method or means by which the electrical energy is generated nor to the installation between the origin of the installation and the fire pump controller, which are to be found in IEC 60364 series. This technical specification does not apply to diesel engine driven electric generators which may be associated with a stationary fire pump installation. EMC considerations are correlated with other IEC standards for similar products: a) for electric fire pump controllers, EMC considerations are covered by this technical specification, and b) for diesel engine fire pump controllers, d.c. batteries are the intended source of electrical control power.

Applies to controllers intended for starting, controlling and stopping stationary fire pumps, including automatic and non-automatic types for alternating current electric motor or diesel engine driven fire pumps. It is anticipated that a controller only controls a single driver. Controllers for electric motor driven fire pumps always include suitable short-circuit protection as an integral part of the controller. These controllers may include an integral power transfer switch. These controllers are rated 1 000 V a.c. maximum. Controllers for diesel engine driven fire pumps include electrical circuits that operate various control and supervisory functions such as remote control (starting and stopping), alarms, signals, indicators, and the proper operation of battery chargers. The most significant purpose of this technical specification is to characterize the unique features of fire pump controllers. A further purpose is to prescribe a procedure for exercising the controllers to verify that the unique features are operative. For the purpose of this technical specification, this procedure is described as the "fire pump controller test protocol". The object of this technical specification is to state the following: a) The unique characteristics of fire pump controllers, their associated equipment and their operational functions; b) The conditions with which fire pump controllers should comply with reference to 1) their construction; 2) their critical components including the mounting, arrangement, wiring and connections; 3) the degrees of protection provided by their enclosures; 4) their modes of actuation; 5) their operation and behaviour under normal, overload and short-circuit conditions; 6) their capability to annunciate significant events; 7) their electromagnetic compatibility for the environment into which they are placed; c) The tests intended for confirming that these conditions have been met, and the methods to be adopted for these tests; d) The information to be given with the equipment, or in the manufacturer's literature. In this context, this technical specification gives the requirements for all of the electrical functions associated with both the electric motor driven and the diesel engine driven fire pumps. Special applications such as explosive atmospheres, nuclear installations, ships, aircraft, etc. are not covered by this technical specification. Referring to electric power sources, the requirements of this technical specification apply only to the extent that they place limits on the nature, behaviour and characteristics of the electrical energy that is supplied to the service entrance (see IEC 60364-5-55). The requirements of this technical specification do not apply to the method or means by which the electrical energy is generated nor to the installation between the origin of the installation and the fire pump controller, which are to be found in IEC 60364 series. This technical specification does not apply to diesel engine driven electric generators which may be associated with a stationary fire pump installation. EMC considerations are correlated with other IEC standards for similar products: a) for electric fire pump controllers, EMC considerations are covered by this technical specification, and b) for diesel engine fire pump controllers, d.c. batteries are the intended source of electrical control power.

IEC TS 62091:2003 is classified under the following ICS (International Classification for Standards) categories: 29.130.20 - Low voltage switchgear and controlgear. The ICS classification helps identify the subject area and facilitates finding related standards.

IEC TS 62091:2003 has the following relationships with other standards: It is inter standard links to IEC 62091:2007. Understanding these relationships helps ensure you are using the most current and applicable version of the standard.

IEC TS 62091:2003 is available in PDF format for immediate download after purchase. The document can be added to your cart and obtained through the secure checkout process. Digital delivery ensures instant access to the complete standard document.

Standards Content (Sample)


SPÉCIFICATION CEI
TECHNIQUE IEC
TS 62091
TECHNICAL
Première édition
SPECIFICATION
First edition
2003-06
Appareillage à basse tension –
Appareils de commande des entraînements
de pompes à incendie fixes
Low-voltage switchgear and controlgear –
Controllers for drivers of stationary
fire pumps
Numéro de référence
Reference number
CEI/IEC/TS 62091:2003
Numérotation des publications Publication numbering

Depuis le 1er janvier 1997, les publications de la CEI As from 1 January 1997 all IEC publications are

sont numérotées à partir de 60000. Ainsi, la CEI 34-1 issued with a designation in the 60000 series. For

devient la CEI 60034-1. example, IEC 34-1 is now referred to as IEC 60034-1.

Editions consolidées Consolidated editions

Les versions consolidées de certaines publications de la The IEC is now publishing consolidated versions of its

CEI incorporant les amendements sont disponibles. Par publications. For example, edition numbers 1.0, 1.1

exemple, les numéros d’édition 1.0, 1.1 et 1.2 indiquent and 1.2 refer, respectively, to the base publication,
respectivement la publication de base, la publication de the base publication incorporating amendment 1 and
base incorporant l’amendement 1, et la publication de the base publication incorporating amendments 1
base incorporant les amendements 1 et 2. and 2.
Informations supplémentaires Further information on IEC publications
sur les publications de la CEI
Le contenu technique des publications de la CEI est The technical content of IEC publications is kept
constamment revu par la CEI afin qu'il reflète l'état under constant review by the IEC, thus ensuring that
actuel de la technique. Des renseignements relatifs à the content reflects current technology. Information
cette publication, y compris sa validité, sont dispo- relating to this publication, including its validity, is
nibles dans le Catalogue des publications de la CEI available in the IEC Catalogue of publications
(voir ci-dessous) en plus des nouvelles éditions, (see below) in addition to new editions, amendments
amendements et corrigenda. Des informations sur les and corrigenda. Information on the subjects under
sujets à l’étude et l’avancement des travaux entrepris consideration and work in progress undertaken by the
par le comité d’études qui a élaboré cette publication, technical committee which has prepared this
ainsi que la liste des publications parues, sont publication, as well as the list of publications issued,
également disponibles par l’intermédiaire de: is also available from the following:
• Site web de la CEI (www.iec.ch) • IEC Web Site (www.iec.ch)
• Catalogue des publications de la CEI • Catalogue of IEC publications
Le catalogue en ligne sur le site web de la CEI The on-line catalogue on the IEC web site
(http://www.iec.ch/searchpub/cur_fut.htm) vous permet (http://www.iec.ch/searchpub/cur_fut.htm) enables
de faire des recherches en utilisant de nombreux you to search by a variety of criteria including text
critères, comprenant des recherches textuelles, par searches, technical committees and date of
comité d’études ou date de publication. Des publication. On-line information is also available
informations en ligne sont également disponibles sur on recently issued publications, withdrawn and
les nouvelles publications, les publications rempla- replaced publications, as well as corrigenda.
cées ou retirées, ainsi que sur les corrigenda.
• IEC Just Published • IEC Just Published
Ce résumé des dernières publications parues This summary of recently issued publications
(http://www.iec.ch/online_news/justpub/jp_entry.htm) (http://www.iec.ch/online_news/justpub/jp_entry.htm)
est aussi disponible par courrier électronique. is also available by email. Please contact the
Veuillez prendre contact avec le Service client Customer Service Centre (see below) for further
(voir ci-dessous) pour plus d’informations. information.

• Service clients • Customer Service Centre
Si vous avez des questions au sujet de cette If you have any questions regarding this
publication ou avez besoin de renseignements publication or need further assistance, please
supplémentaires, prenez contact avec le Service contact the Customer Service Centre:
clients:
Email: custserv@iec.ch Email: custserv@iec.ch
Tél: +41 22 919 02 11 Tel: +41 22 919 02 11
Fax: +41 22 919 03 00 Fax: +41 22 919 03 00
.
SPÉCIFICATION CEI
TECHNIQUE IEC
TS 62091
TECHNICAL
Première édition
SPECIFICATION
First edition
2003-06
Appareillage à basse tension –
Appareils de commande des entraînements
de pompes à incendie fixes
Low-voltage switchgear and controlgear –
Controllers for drivers of stationary
fire pumps
 IEC 2003 Droits de reproduction réservés  Copyright - all rights reserved
Aucune partie de cette publication ne peut être reproduite ni No part of this publication may be reproduced or utilized in any
utilisée sous quelque forme que ce soit et par aucun procédé, form or by any means, electronic or mechanical, including
électronique ou mécanique, y compris la photocopie et les photocopying and microfilm, without permission in writing from
microfilms, sans l'accord écrit de l'éditeur. the publisher.
International Electrotechnical Commission, 3, rue de Varembé, PO Box 131, CH-1211 Geneva 20, Switzerland
Telephone: +41 22 919 02 11 Telefax: +41 22 919 03 00 E-mail: inmail@iec.ch  Web: www.iec.ch
CODE PRIX
XA
Commission Electrotechnique Internationale PRICE CODE
International Electrotechnical Commission
Международная Электротехническая Комиссия
Pour prix, voir catalogue en vigueur
For price, see current catalogue

– 2 – TS 62091  CEI:2003
SOMMAIRE
AVANT-PROPOS . 6

INTRODUCTION .10

1 Domaine d’application et objet .14

2 Références normatives .16

3 Termes et définitions .20

4 Classification .26

4.1 Appareil de commande de pompe à incendie électrique.26

4.2 Appareil de commande de pompe à incendie résidentielle (entraînée
seulement par un moteur électrique).28
4.3 Appareil de commande de pompe à incendie à moteur diesel .28
4.4 Appareil de commande de pompe à mousse (entraînée soit par un moteur
électrique soit par un moteur diesel) .28
5 Caractéristiques.28
5.1 Grandeurs électriques .28
5.2 Hiérarchie d’importance des diverses caractéristiques.28
5.3 Appareil de commande de pompe à incendie électrique.30
5.4 Appareil de commande de pompe à incendie électrique monophasée.32
5.5 Appareil de commande de pompe à incendie à moteur diesel .32
5.6 Appareil de commande de pompe à mousse.32
5.7 Protocole d’essai des appareils de commande des pompes à incendie.34
6 Informations sur le matériel.34
6.1 Valeurs assignées et autres caractéristiques électriques .34
6.2 Marquage .36
6.3 Instructions d’installation, de fonctionnement et d’entretien .42
7 Conditions normales de service, de montage et de transport .42
7.1 Généralités.42
7.2 Température de l’eau.42
7.3 Humidité .42
7.4 Degrés de pollution.42
7.5 Considérations CEM .42
8 Prescriptions relatives à la construction, au fonctionnement et au comportement.42
8.1 Généralités.42

8.2 Prescriptions relatives à la construction des appareils de série.44
8.3 Priorité des opérations des appareils de commande de pompe à incendie .48
8.4 Prescriptions relatives à la construction et au fonctionnement des
composants .48
8.5 Priorité des opérations des appareils de commande de pompe à incendie
électrique .56
8.6 Prescriptions relatives au fonctionnement et au comportement des appareils
de commande électriques .58
8.7 Appareils de commande de pompe à incendie résidentielle .66
8.8 Appareils de commande de pompe à incendie à moteur diesel .68
8.9 Manœuvre automatique d’un appareil de commande de pompe à moteur
diesel – activation par la pression.72
8.10 Manœuvre automatique d’un appareil de commande de pompe à moteur
diesel – activation indépendante de la pression .72

TS 62091  IEC:2003 – 3 –
CONTENTS
FOREWORD . 7

INTRODUCTION .11

1 Scope and object .15

2 Normative references.17

3 Terms and definitions .21

4 Classification .27

4.1 Electric fire pump controller .27

4.2 Residential fire pump controller (driven by an electric motor only).29
4.3 Diesel engine fire pump controller.29
4.4 Foam pump controller (driven either by an electric motor or by a diesel
engine) .29
5 Characteristics.29
5.1 Electrical quantities .29
5.2 Hierarchy of importance for the various characteristics .29
5.3 Electric fire pump controller .31
5.4 Single phase fire pump controller.33
5.5 Diesel engine fire pump controller.33
5.6 Foam pump controller .33
5.7 Fire pump controller test protocol .35
6 Product information.35
6.1 Rated values and other electrical characteristics .35
6.2 Marking .37
6.3 Instructions for installation, operation and maintenance.43
7 Normal service, mounting and transport conditions .43
7.1 General .43
7.2 Water temperature.43
7.3 Humidity .43
7.4 Degrees of pollution.43
7.5 EMC considerations.43
8 Constructional, functional and performance requirements .43
8.1 General .43
8.2 Constructional requirements for the type-tested devices .45

8.3 Priority of operations for electric fire pump controllers .49
8.4 Functional and performance requirements for components .49
8.5 Priority of operations for electric fire pump controllers .57
8.6 Functional and performance requirements for electric controllers.59
8.7 Residential fire pump controllers.67
8.8 Diesel engine fire-pump controllers.69
8.9 Automatic operation of a diesel engine drive controller – pressure actuated .73
8.10 Automatic operation of a diesel engine drive controller – non-pressure
actuated .73

– 4 – TS 62091  CEI:2003
8.11 Méthodes d’arrêt.74

8.12 Essai .76

8.13 Prescriptions supplémentaires relatives au fonctionnement et au

comportement des appareils de commande de pompe à mousse.76

8.14 Prescriptions de CEM .76

9 Essais.78

9.1 Nature des essais.78

9.2 Conformité aux dispositions constructives .78

9.3 Conformité aux prescriptions fonctionnelles.78

9.4 CEM .90

9.5 Essais fonctionnels pour la CEM.94
9.6 Essais individuels .94
Annexe A (normative) Compatibilité électromagnétique.106
Annexe B (informative) Eléments informatifs .114
Bibliographie .116
Figure 1 – Disposition générale pour un appareil de commande de pompe à incendie
électrique convenant pour deux sources d’alimentation, dont l’une est une alimentation
de secours sur site.100
Figure 2 – Disposition générale pour un appareil de commande de pompe à incendie
électrique convenant pour une source d’alimentation unique.102
Figure 3 — Diagramme typique pour un appareil de commande de pompe à incendie à
moteur diesel convenant pour une source d’alimentation monophasée.104
Figure A.1 – Exemples d’accès .106
Tableau 1 – Numérotation des bornes des appareils de commande de pompe
à incendie à moteur diesel .96
Tableau 2 − Espace de courbure pour le câblage des bornes sur site.96
Tableau 3 – Critères d’évaluation.98
Tableau 4 – Vérification du pouvoir de fermeture .98
Tableau A.1 − Limites d’émission pour l’environnement B (Ces limites sont extraites du

CISPR 11 sans modification, uniquement pour information) .108
Tableau A.2 – Essais d’immunité pour l’environnement A.110
Tableau A.3 – Critères d'acceptation lorsque les perturbations électromagnétiques
sont présentes (critères de comportement pendant les essais).112

TS 62091  IEC:2003 – 5 –
8.11 Methods of stopping .75

8.12 Testing .77

8.13 Additional functional and performance requirements for foam pump

controllers .77

8.14 EMC requirements .77

9 Tests .79

9.1 Kinds of test .79

9.2 Compliance with construction requirements .79

9.3 Compliance with performance requirements.79

9.4 EMC .91

9.5 Functional tests for EMC.95
9.6 Routine tests .95
Annex A (normative) Electromagnetic compatibility .107
Annex B (informative) Informative material.115
Bibliography.117
Figure 1 – General arrangement for the electric fire pump controller suitable for two
power sources, one of which is on-site standby power .101
Figure 2 – General arrangement for the electric fire pump controller suitable for a
single power source .103
Figure 3 — Typical block diagram for the diesel engine fire pump controller suitable for
a single phase power source.105
Figure A.1 – Examples of ports .107
Table 1 – Diesel fire pump controller terminal numbering .97
Table 2 − Wire bending space at field wiring terminals .97
Table 3 – Assessment criteria .99
Table 4 – Verification of making capacity .99
Table A.1 − Emission limits for environment B (These limits have been copied for
information only without alteration from CISPR 11) .109
Table A.2 – Immunity tests for environment A .111
Table A.3 – Acceptance criteria when electromagnetic disturbances are present
(performance criteria during tests).113

– 6 – TS 62091  CEI:2003
COMMISSION ÉLECTROTECHNIQUE INTERNATIONALE

____________
APPAREILLAGE À BASSE TENSION –

APPAREILS DE COMMANDE DES ENTRAÎNEMENTS

DE POMPES À INCENDIE FIXES
AVANT-PROPOS
1) La CEI (Commission Electrotechnique Internationale) est une organisation mondiale de normalisation
composée de l'ensemble des comités électrotechniques nationaux (Comités nationaux de la CEI). La CEI a
pour objet de favoriser la coopération internationale pour toutes les questions de normalisation dans les
domaines de l'électricité et de l'électronique. A cet effet, la CEI, entre autres activités, publie des Normes
internationales. Leur élaboration est confiée à des comités d'études, aux travaux desquels tout Comité national
intéressé par le sujet traité peut participer. Les organisations internationales, gouvernementales et non
gouvernementales, en liaison avec la CEI, participent également aux travaux. La CEI collabore étroitement
avec l'Organisation Internationale de Normalisation (ISO), selon des conditions fixées par accord entre les
deux organisations.
2) Les décisions ou accords officiels de la CEI concernant les questions techniques représentent, dans la mesure
du possible, un accord international sur les sujets étudiés, étant donné que les Comités nationaux intéressés
sont représentés dans chaque comité d’études.
3) Les documents produits se présentent sous la forme de recommandations internationales. Ils sont publiés
comme normes, spécifications techniques, rapports techniques ou guides et agréés comme tels par les
Comités nationaux.
4) Dans le but d'encourager l'unification internationale, les Comités nationaux de la CEI s'engagent à appliquer de
façon transparente, dans toute la mesure possible, les Normes internationales de la CEI dans leurs normes
nationales et régionales. Toute divergence entre la norme de la CEI et la norme nationale ou régionale
correspondante doit être indiquée en termes clairs dans cette dernière.
5) La CEI n’a fixé aucune procédure concernant le marquage comme indication d’approbation et sa responsabilité
n’est pas engagée quand un matériel est déclaré conforme à l’une de ses normes.
6) L’attention est attirée sur le fait que certains des éléments de la présente spécification technique peuvent faire
l’objet de droits de propriété intellectuelle ou de droits analogues. La CEI ne saurait être tenue pour
responsable de ne pas avoir identifié de tels droits de propriété et de ne pas avoir signalé leur existence.
La tâche principale des comités d’études de la CEI est l’élaboration des Normes
internationales. Exceptionnellement, un comité d’études peut proposer la publication
d’une spécification technique
• lorsqu’en dépit de maints efforts, l’accord requis ne peut être réalisé en faveur de la
publication d’une Norme internationale, ou
• lorsque le sujet en question est encore en cours de développement technique ou quand,
pour une raison quelconque, la possibilité d’un accord pour la publication d’une Norme
internationale peut être envisagée pour l’avenir mais pas dans l’immédiat.

Les spécifications techniques font l’objet d’un nouvel examen trois ans au plus tard après leur
publication afin de décider éventuellement de leur transformation en Normes internationales.
La CEI 62091, qui est une spécification technique, a été établie par le sous-comité 17B:
Appareillage à basse tension, du comité d’études 17 de la CEI: Appareillage.
Le texte de cette spécification technique est issu des documents suivants:
Projet d’enquête Rapport de vote
17B/1248/DTS 17B/1279/RVC
Le rapport de vote indiqué dans le tableau ci-dessus donne toute information sur le vote ayant
abouti à l'approbation de cette spécification technique.

TS 62091  IEC:2003 – 7 –
INTERNATIONAL ELECTROTECHNICAL COMMISSION

____________
LOW-VOLTAGE SWITCHGEAR AND CONTROLGEAR –

CONTROLLERS FOR DRIVERS OF STATIONARY FIRE PUMPS

FOREWORD
1) The IEC (International Electrotechnical Commission) is a worldwide organization for standardization comprising

all national electrotechnical committees (IEC National Committees). The object of the IEC is to promote

international co-operation on all questions concerning standardization in the electrical and electronic fields. To
this end and in addition to other activities, the IEC publishes International Standards. Their preparation is
entrusted to technical committees; any IEC National Committee interested in the subject dealt with may
participate in this preparatory work. International, governmental and non-governmental organizations liaising
with the IEC also participate in this preparation. The IEC collaborates closely with the International
Organization for Standardization (ISO) in accordance with conditions determined by agreement between the
two organizations.
2) The formal decisions or agreements of the IEC on technical matters express, as nearly as possible, an
international consensus of opinion on the relevant subjects since each technical committee has representation
from all interested National Committees.
3) The documents produced have the form of recommendations for international use and are published in the form
of standards, technical specifications, technical reports or guides and they are accepted by the National
Committees in that sense.
4) In order to promote international unification, IEC National Committees undertake to apply IEC International
Standards transparently to the maximum extent possible in their national and regional standards. Any
divergence between the IEC Standard and the corresponding national or regional standard shall be clearly
indicated in the latter.
5) The IEC provides no marking procedure to indicate its approval and cannot be rendered responsible for any
equipment declared to be in conformity with one of its standards.
6) Attention is drawn to the possibility that some of the elements of this technical specification may be the subject
of patent rights. The IEC shall not be held responsible for identifying any or all such patent rights.
The main task of IEC technical committees is to prepare International Standards. In
exceptional circumstances, a technical committee may propose the publication of a technical
specification when
• the required support cannot be obtained for the publication of an International Standard,
despite repeated efforts, or
• the subject is still under technical development or where, for any other reason, there is the
future but no immediate possibility of an agreement on an International Standard.
Technical specifications are subject to review within three years of publication to decide
whether they can be transformed into International Standards.

IEC 62091, which is a technical specification, has been prepared by subcommittee 17B:
Low-voltage switchgear and controlgear, of IEC technical committee 17: Switchgear and
controlgear.
The text of this technical specification is based on the following documents:
Enquiry draft Report on voting
17B/1248/DTS 17B/1279/RVC
Full information on the voting for the approval of this technical specification can be found in
the report on voting indicated in the above table.

– 8 – TS 62091  CEI:2003
Cette publication a été rédigée selon les Directives ISO/CEI, Partie 2.

Le comité a décidé que le contenu de cette publication ne sera pas modifié avant 2005.
A cette date, la publication sera

• remplacée par une Norme internationale

• reconduite;
• supprimée;
• remplacée par une édition révisée, ou

• amendée.
TS 62091  IEC:2003 – 9 –
This publication has been drafted in accordance with the ISO/IEC Directives, Part 2.

The committee has decided that the contents of this publication will remain unchanged until
2005. At this date, the publication will be

• transformed into an International Standard;

• reconfirmed;
• withdrawn;
• replaced by a revised edition, or

• amended.
– 10 – TS 62091  CEI:2003
INTRODUCTION
La CEI 62091 concerne les matériels de sécurité et est basée en partie sur la NFPA 20

(1996) Standard for the Installation of Centrifugal Fire Pumps. Lorsque l’on fait appel à un

signal automatique, à un signal électrique manuel ou à la mise en marche manuelle

d’urgence, il est attendu que l’appareil de commande démarre le pilote de la pompe (moteur

électrique ou moteur diesel) parce que «l’immeuble est en feu». L’échec de cette mission

augmentera le dommage du feu à l’immeuble, à ce qu’il contient et aux personnes à

l’intérieur.
Ces appareils de commande diffèrent de ceux qui sont conformes à la CEI 60947 en ce que

leur position de défaut est l’état MARCHE. Ils sont destinés à être installés conformément aux
prescriptions locales qui les placent généralement dans des locaux de pompes ou des postes
de pompes qui ont un degré spécifié de protection contre le feu. Ces endroits ont souvent des
tuyaux aériens d’aspersion, ils peuvent être munis de sprinklers et sont à proximité de salles
protégées abritant d'autres matériels de distribution du bâtiment.
Les pompes à incendie sont prévues pour augmenter la pression de l’eau. Beaucoup de
systèmes d’arrosage (sprinklers) sont présumés avoir de petites fuites pour lesquelles sont
installées des «jockey pumps» (dites aussi pompes d’appoint) qui maintiennent la pression
désirée dans les tuyaux d’arrosage évitant ainsi de trop nombreux démarrages et arrêts de la
pompe à incendie principale. L’expérience a montré que cette fuite d’eau s’écoulant dans la
pompe à incendie (au repos) pendant de longues périodes d’inactivité de la pompe peut
transporter du sable, des agrégats, des pierres, de la rouille qui se rassemblent dans la
pompe à incendie. Ces pollutions peuvent empêcher un démarrage normal jusqu’à ce que la
roue à palette de la pompe accélère pour nettoyer son logement. La présente spécification
technique reconnaît les conditions d’une sous-utilisation des pompes à incendie en autorisant
un courant de blocage du rotor jusqu’à 20 s, que le démarrage soit «à froid» (démarrage
initial) ou «à chaud» (redémarrages). Le démarrage d’une pompe endommagée peut causer
un dommage temporaire ou permanent aux conducteurs électriques, aux matériels et au
moteur parce que son arrêt pour protéger le matériel pourrait éventuellement favoriser sa
destruction par le feu avec celle du bâtiment et ce qu’il contient.
Plusieurs exemples de construction et d’installation entre un appareil de commande de
pompe à incendie et d’autres appareils de commande comprennent ce qui suit:
1) tous les appareils de commande de pompe à incendie
a) Les conducteurs du circuit principal et les composants sont considérés comme
sacrificiels (c’est-à-dire que des niveaux de dommages temporaires ou permanents
sont autorisés) durant toute tentative de démarrage d’un moteur/pompe endommagé et
de le conserver opérationnel.
b) Ils sont réputés fournir un degré de fiabilité important pour démarrer automatiquement

le pilote de la pompe et supprimer un feu sur la perception d’une chute de pression
dans le conduit d’arrosage (sprinkler) ou par d’autres matériels de détection
automatique du feu.
c) Il convient que les défauts dans les circuits de commande externes n’empêchent pas
le fonctionnement des pompes par tous les autres moyens internes ou externes.
d) Les circuits de commande externes sont réputés être conçus de telle sorte que la
défaillance de tout circuit externe (ouvert ou en court-circuit) n’empêchera pas le
fonctionnement de la ou des pompes à partir de tous les autres moyens internes ou
externes. La coupure, la déconnexion, la mise en court-circuit des conducteurs ou la
perte de puissance de ces circuits peut provoquer un fonctionnement continu de la
pompe à incendie mais il convient qu’il n’empêche pas, en cas de causes étrangères à
ces circuits externes, le ou les appareils de commande de démarrer la ou les pompes
à incendie.
———————
CEI 60947 (toutes les parties), Appareillage à basse tension.

TS 62091  IEC:2003 – 11 –
INTRODUCTION
IEC 62091 pertains to life-safety equipment and is based in part on NFPA 20 (1996) Standard

for the Installation of Centrifugal Fire Pumps. When called upon to work by automatic signal,

manual-electric signal or manual-emergency actuation, the controller is expected to start the

pump driver (motor or diesel engine) because “the building is on fire”. Failure to carry out its

mission will increase fire damage to the building, its contents and people therein.

These controllers differ from other IEC 60947 compliant controllers in that they default to a

RUN state. They are intended to be located in compliance with local requirements which

generally will place them in pump rooms or pump houses that have some specified degree of

fire protection. These locations often have sweating overhead pipes, are possibly sprinklered
and are in the vicinity of vaults housing other building distribution equipment.
Fire pumps are intended to boost water pressure. Many sprinkler systems are assumed to
have small leaks for which “Jockey Pumps” (also known as make-up pumps) are installed to
maintain desired pressure in the sprinkler pipes, thus preventing the main fire pump from
excessive starts and stops. Experience has shown that leakage water flowing through the fire
pump (at rest) over long periods of pump inactivity can carry sand, aggregates, rocks, rust
and such which collect in the fire pump. These contaminants may prevent normal starting until
the pump impeller accelerates to clear the pump housing. This technical specification
recognizes the condition of under-exercised fire pumps by permitting up to 20 s at locked
rotor current whether the starts are “cold starts” (initial starts) or “hot starts” (restarts).
Starting a distressed pump may cause temporary or permanent damage to electrical
conductors, equipment and the motor because shutdown for equipment protection could
possibly permit its destruction by fire along with the building and its contents.
Several examples of the construction and installation applications between a fire pump
controller and other controllers include the following:
1) all fire pump controllers
a) The main circuit conductors and components are considered to be sacrificial (i.e.
temporary and permanent damage levels are permitted) during any attempt to start a
distressed motor/pump and to keep it operating.
b) They are expected to provide a high degree of reliability to start the pump driver
automatically and suppress a fire upon sensing a pressure drop in the sprinkler pipe or
by other automatic fire detection equipment.
c) Failures in external control circuits should not prevent operations of pumps from all
other internal or other external means.
d) External control circuits are expected to be arranged so that failure of any external
circuit (open or short-circuit) will not prevent operation of pump(s) from all other

internal or external means. Breakage, disconnecting, shorting of the wires or loss of
power to these circuits can cause continuous running of the fire pump but should not
prevent the controller(s) from starting the fire pump(s) due to causes other than these
external circuits.
———————
IEC 60947 (all parts), Low-voltage switchgear and controlgear.

– 12 – TS 62091  CEI:2003
e) Il convient que le démarrage automatique par des moyens externes s’effectue par

l’ouverture d’un contact à ouverture des dispositifs externes pour mettre hors tension

le circuit de commande, normalement sous tension, dans l’appareil de commande.

f) Bien que des boutons de démarrage ou d’autres moyens de démarrage externes

soient autorisés, il convient que l’appareil de commande ne soit pas équipé de moyens

permettant un arrêt à distance (il convient qu’un bouton ARRET à distance ne soit pas

utilisé).
g) Des défauts de démarrage sont autorisés dans le cas où une défaillance des

composants internes de commande permet le démarrage du moteur.

2) les appareils de commande de pompe à incendie à moteur électrique

a) Ils sont réputés inclure des dispositifs pour un fonctionnement mécanique manuel
externe à l’appareil de commande dans le cas d’une perte de capacité à fermer le
contacteur électriquement/magnétiquement.
b) Il convient que les appareils de protection contre les surintensités à action thermique
ne soient pas autorisés. Il convient que l’appareil de commande fournisse seulement
une protection contre les courts-circuits et le blocage du rotor.
c) Les déclencheurs de l’appareil de protection de puissance sont réputés permettre à
celui-ci de transporter, pendant une période de temps prolongée, 300 % du courant
assigné d’emploi du moteur.
3) les appareils de commande de pompe à incendie à moteur diesel
a) Il convient qu’ils fournissent les moyens de solliciter automatiquement le moteur sur
une base hebdomadaire.
b) Il convient qu’ils n’empêchent pas un moteur de démarrer, ni un moteur en marche de
s’arrêter, en cas de détection de faible pression de l’huile ou de forte température du
moteur.
En conséquence, l’objectif le plus significatif de la présente spécification technique est de
caractériser les spécificités des appareils de commande des pompes à incendie.

TS 62091  IEC:2003 – 13 –
e) External automatic starting means should be accomplished by opening a normally

closed contact on the external means to de-energize a normally energized control

circuit in the controller.
f) While external start buttons or other starting means are permitted, the controller

should not be equipped with any means to accommodate remote stopping (a remote

STOP button should not be used).

g) Nuisance starts are permitted in the case where a failure of internal control

components might cause the motor to start running.

2) electric motor fire pump controllers

a) They are expected to include means for external, manual mechanical operation of the

controller in the event of loss of ability to close the contactor electrically/magnetically.
b) Thermally reactive over-current protective devices should not be permitted. The
controller should provide short-circuit and locked rotor protection only.
c) Releases of the power-protector device are expected to permit it to carry 300 % of
rated operational motor current for an extended period of time.
3) diesel engine fire pump controllers
a) Should provide means to automatically exercise the engine on a weekly basis.
b) Should not prevent an engine from starting nor shutdown an engine running under
demand conditions due to low oil pressure or high engine temperature.
Therefore, the most significant purpose of this technical specification is to characterize the
unique features of fire pump controllers.

– 14 – TS 62091  CEI:2003
APPAREILLAGE À BASSE TENSION –

APPAREILS DE COMMANDE DES ENTRAÎNEMENTS

DE POMPES À INCENDIE FIXES
1 Domaine d’application et objet

La présente spécification technique est applicable aux appareils de commande destinés au

démarrage, à la commande et à l’arrêt des pompes à incendie fixes, incluant les types
automatiques et non automatiques de pompes à incendie pilotées par un moteur électrique à
courant alternatif ou par un moteur diesel. Il est convenu qu’un appareil de commande
contrôle seulement un pilote unique.
Les appareils de commande des pompes à incendie entraînées par un moteur électrique
comprennent toujours, comme partie intégrante de l’appareil de commande, une protection
adaptée contre les courts-circuits. Ces appareils de commande peuvent inclure un
interrupteur de transfert de puissance intégral. La tension maximale assignée de ces
appareils de commande est de 1 000 V en courant alternatif.
Les appareils de commande des pompes à incendie entraînées par un moteur diesel
comprennent des circuits électriques qui assurent diverses commandes et des fonctions de
supervision telles que la commande à distance (démarrage et arrêt), les alarmes, les signaux,
les indicateurs et le fonctionnement correct des chargeurs de batterie.
L’objectif le plus significatif de la présente spécification technique est de caractériser les
spécificités des appareils de commande des pompes à incendie. Un objectif supplémentaire
est de prescrire une procédure pour solliciter les appareils de commande afin de vérifier que
les spécificités sont opérationnelles. Pour les besoins de la présente spécification technique,
cette procédure est décrite par la «procédure d’essai des appareils de commande des
pompes à incendie».
L’objet de la présente spécification technique est de fixer ce qui suit:
a) les caractéristiques spécifiques des appareils de commande des pompes à incendie, leurs
matériels associés et leurs fonctions opérationnelles;
b) les conditions auxquelles il convient que les appareils de commande des pompes à
incendie soient conformes relativement à
1) leur construction;
2) leurs composants critiques, y compris le montage, la disposition, le câblage et les
connexions;
3) les degrés de protection fournis par leurs enveloppes;
4) leurs modes d’actionnement;
5) leur fonctionnement et leur comportement dans des conditions normales, de surcharge
et de court-circuit;
6) leur capacité à prévoir les événements importants;
7) leur compatibilité électromagnétique pour l’environnement dans lequel ils sont placés;
c) les essais destinés à confirmer que ces conditions ont été satisfaites et les méthodes à
adopter pour ces essais;
d) les informations à donner avec le matériel
...