Plugs and socket-outlets for household and similar purposes - Part 2-3: Particular requirements for switched socket-outlets without interlock for fixed installations

IEC 60884-2-3:2025 applies to switched socket-outlets without interlock, for fixed installation, for AC only, with or without earthing contact, with a rated voltage not exceeding 440 V and a rated current not exceeding 32 A, intended for household and similar purposes, either indoors or outdoors. This document applies to socket-outlets controlled by a manually operated mechanical switch.
This third edition cancels and replaces the second edition published in 2006. This edition constitutes a technical revision.
This edition includes the following significant technical changes with respect to the previous edition:
a) alignment to IEC 60884-1, fourth edition.

Prises de courant pour usages domestiques et analogues - Partie 2-3: Règles particulières pour les socles de prises de courant avec interrupteurs sans verrouillage pour installations fixes

General Information

Status
Published
Publication Date
20-Feb-2025
Current Stage
PPUB - Publication issued
Start Date
21-Feb-2025
Completion Date
07-Mar-2025
Ref Project

Relations

Standard
IEC 60884-2-3:2025 RLV - Plugs and socket-outlets for household and similar purposes - Part 2-3: Particular requirements for switched socket-outlets without interlock for fixed installations Released:21. 02. 2025 Isbn:9782832702635
English language
35 pages
sale 15% off
Preview
sale 15% off
Preview

Standards Content (Sample)


IEC 60884-2-3 ®
Edition 3.0 2025-02
REDLINE VERSION
INTERNATIONAL
STANDARD
Plugs and socket-outlets for household and similar purposes –
Part 2-3: Particular requirements for switched socket-outlets without interlock
for fixed installations
All rights reserved. Unless otherwise specified, no part of this publication may be reproduced or utilized in any form
or by any means, electronic or mechanical, including photocopying and microfilm, without permission in writing from
either IEC or IEC's member National Committee in the country of the requester. If you have any questions about IEC
copyright or have an enquiry about obtaining additional rights to this publication, please contact the address below or
your local IEC member National Committee for further information.

IEC Secretariat Tel.: +41 22 919 02 11
3, rue de Varembé info@iec.ch
CH-1211 Geneva 20 www.iec.ch
Switzerland
About the IEC
The International Electrotechnical Commission (IEC) is the leading global organization that prepares and publishes
International Standards for all electrical, electronic and related technologies.

About IEC publications
The technical content of IEC publications is kept under constant review by the IEC. Please make sure that you have the
latest edition, a corrigendum or an amendment might have been published.

IEC publications search - webstore.iec.ch/advsearchform IEC Products & Services Portal - products.iec.ch
The advanced search enables to find IEC publications by a Discover our powerful search engine and read freely all the
variety of criteria (reference number, text, technical publications previews, graphical symbols and the glossary.
committee, …). It also gives information on projects, replaced With a subscription you will always have access to up to date
and withdrawn publications. content tailored to your needs.

IEC Just Published - webstore.iec.ch/justpublished
Electropedia - www.electropedia.org
Stay up to date on all new IEC publications. Just Published
The world's leading online dictionary on electrotechnology,
details all new publications released. Available online and once
containing more than 22 500 terminological entries in English
a month by email.
and French, with equivalent terms in 25 additional languages.

Also known as the International Electrotechnical Vocabulary
IEC Customer Service Centre - webstore.iec.ch/csc
(IEV) online.
If you wish to give us your feedback on this publication or need

further assistance, please contact the Customer Service
Centre: sales@iec.ch.
IEC 60884-2-3 ®
Edition 3.0 2025-02
REDLINE VERSION
INTERNATIONAL
STANDARD
Plugs and socket-outlets for household and similar purposes –
Part 2-3: Particular requirements for switched socket-outlets without interlock
for fixed installations
INTERNATIONAL
ELECTROTECHNICAL
COMMISSION
ICS 29.120.30 ISBN 978-2-8327-0263-5

– 2 – IEC 60884-2-3:2025 RLV © IEC 2025
CONTENTS
FOREWORD . 4
1 Scope . 6
2 Normative references . 6
3 Terms and definitions . 6
4 General requirements . 7
5 General notes remarks on tests . 7
6 Ratings . 7
7 Classification . 7
8 Marking . 8
9 Checking of dimensions . 9
10 Protection against electric shock . 9
11 Provision for earthing . 9
12 Terminals and terminations . 10
13 Construction of fixed socket-outlets . 10
14 Construction of plugs and portable socket-outlets . 11
15 Interlocked socket-outlets . 11
16 Resistance to ageing, protection provided by enclosures, and resistance to
humidity . 11
17 Insulation resistance and electric strength . 11
18 Operation of earthing contacts . 12
19 Temperature rise . 12
20 Breaking capacity . 12
21 Normal operation . 14
22 Force necessary to withdraw the plug . 15
23 Flexible cables and their connection . 15
24 Mechanical strength . 16
25 Resistance to heat . 16
26 Screws, current-carrying parts and connections . 16
27 Creepage distances, clearances and distances through sealing compound . 16
28 Resistance of insulating material to abnormal heat, to fire and to tracking . 17
29 Resistance to rusting . 17
30 Additional tests on pins provided with insulating sleeves . 17
31 EMC requirements . 17
32 Electromagnetic fields (EMF) requirements . 17
Annexes . 18
Annex A (normative) Safety-related routine tests for factory-wired portable
accessories (protection against electric shock and correct polarity) . 18
Annex B (informative) Alternative gripping tests . 18
Annex C (normative) Switches incorporated in portable socket-outlets . 18
Annex I (normative) Additional requirements and tests for plugs and socket-outlets for
high-load (HL) application . 18

Figure 101 – Example of apparatus for testing the making and breaking capacity and
the normal operation of switches in switched socket-outlets . 14

Table 101 – Number of operations for normal operation test . 15
Table 102 – Creepage distances, clearances and distances through sealing compound . 16

– 4 – IEC 60884-2-3:2025 RLV © IEC 2025
INTERNATIONAL ELECTROTECHNICAL COMMISSION
____________
PLUGS AND SOCKET-OUTLETS FOR HOUSEHOLD
AND SIMILAR PURPOSES –
Part 2-3: Particular requirements for switched socket-outlets
without interlock for fixed installations

FOREWORD
1) The International Electrotechnical Commission (IEC) is a worldwide organization for standardization comprising
all national electrotechnical committees (IEC National Committees). The object of IEC is to promote international
co-operation on all questions concerning standardization in the electrical and electronic fields. To this end and
in addition to other activities, IEC publishes International Standards, Technical Specifications, Technical Reports,
Publicly Available Specifications (PAS) and Guides (hereafter referred to as “IEC Publication(s)”). Their
preparation is entrusted to technical committees; any IEC National Committee interested in the subject dealt with
may participate in this preparatory work. International, governmental and non-governmental organizations liaising
with the IEC also participate in this preparation. IEC collaborates closely with the International Organization for
Standardization (ISO) in accordance with conditions determined by agreement between the two organizations.
2) The formal decisions or agreements of IEC on technical matters express, as nearly as possible, an international
consensus of opinion on the relevant subjects since each technical committee has representation from all
interested IEC National Committees.
3) IEC Publications have the form of recommendations for international use and are accepted by IEC National
Committees in that sense. While all reasonable efforts are made to ensure that the technical content of IEC
Publications is accurate, IEC cannot be held responsible for the way in which they are used or for any
misinterpretation by any end user.
4) In order to promote international uniformity, IEC National Committees undertake to apply IEC Publications
transparently to the maximum extent possible in their national and regional publications. Any divergence between
any IEC Publication and the corresponding national or regional publication shall be clearly indicated in the latter.
5) IEC itself does not provide any attestation of conformity. Independent certification bodies provide conformity
assessment services and, in some areas, access to IEC marks of conformity. IEC is not responsible for any
services carried out by independent certification bodies.
6) All users should ensure that they have the latest edition of this publication.
7) No liability shall attach to IEC or its directors, employees, servants or agents including individual experts and
members of its technical committees and IEC National Committees for any personal injury, property damage or
other damage of any nature whatsoever, whether direct or indirect, or for costs (including legal fees) and
expenses arising out of the publication, use of, or reliance upon, this IEC Publication or any other IEC
Publications.
8) Attention is drawn to the Normative references cited in this publication. Use of the referenced publications is
indispensable for the correct application of this publication.
9) IEC draws attention to the possibility that the implementation of this document may involve the use of (a)
patent(s). IEC takes no position concerning the evidence, validity or applicability of any claimed patent rights in
respect thereof. As of the date of publication of this document, IEC had not received notice of (a) patent(s), which
may be required to implement this document. However, implementers are cautioned that this may not represent
the latest information, which may be obtained from the patent database available at https://patents.iec.ch. IEC
shall not be held responsible for identifying any or all such patent rights.
This redline version of the official IEC Standard allows the user to identify the changes
made to the previous edition IEC 60884-2-3:2006. A vertical bar appears in the margin
wherever a change has been made. Additions are in green text, deletions are in
strikethrough red text.
IEC 60884-2-3 has been prepared by subcommittee 23B: Plugs, socket-outlets and switches,
of IEC technical committee 23: Electrical accessories. It is an International Standard.
This third edition cancels and replaces the second edition published in 2006. This edition
constitutes a technical revision.
This edition includes the following significant technical changes with respect to the previous
edition:
a) alignment to IEC 60884-1, fourth edition.
The text of this International Standard is based on the following documents:
Draft Report on voting
23B/1546/FDIS 23B/1560/RVD
Full information on the voting for its approval can be found in the report on voting indicated in
the above table.
The language used for the development of this International Standard is English.
This document was drafted in accordance with ISO/IEC Directives, Part 2, and developed in
accordance with ISO/IEC Directives, Part 1 and ISO/IEC Directives, IEC Supplement, available
at www.iec.ch/members_experts/refdocs. The main document types developed by IEC are
described in greater detail at www.iec.ch/publications.
This document is to be used in conjunction with IEC 60884-1:2022.
This document supplements or modifies the corresponding clauses in IEC 60884-1:2022, so as
to convert that publication into the IEC standard: Particular requirements for switched socket-
outlets without interlock for fixed installations.
When a particular subclause of IEC 60884-1:2022 is mentioned in this document, that
subclause applies as far as reasonable. Where this document states "addition", "modification"
or "replacement", the relevant text of IEC 60884-1:2022 is to be adapted accordingly.
In this document the following print types are used:
– requirements proper: in roman type;
– test specification: in italic type;
– explanatory notes: in small roman type.
Subclauses, notes, figures and tables or figures which are additional to those in
IEC 60884-1:2022 are numbered starting from 101.
A list of all parts in the IEC 60884 series, published under the general title Plugs and
socket-outlets for household and similar purposes, can be found on the IEC website.
The committee has decided that the contents of this document will remain unchanged until the
stability date indicated on the IEC website under webstore.iec.ch in the data related to the
specific document. At this date, the document will be
• reconfirmed,
• withdrawn, or
• revised.
– 6 – IEC 60884-2-3:2025 RLV © IEC 2025
PLUGS AND SOCKET-OUTLETS FOR HOUSEHOLD
AND SIMILAR PURPOSES –
Part 2-3: Particular requirements for switched socket-outlets
without interlock for fixed installations

1 Scope
IEC 60884-1:2022, Clause 1 is applicable except as follows.
Replacement of the first paragraph:
This part of IEC 60884 applies to switched socket-outlets without interlock, for fixed installation,
for AC only, with or without earthing contact, with a rated voltage not exceeding 440 V and a
rated current not exceeding 32 A, intended for household and similar purposes, either indoors
or outdoors.
NOTE 101 Switched socket-outlets can also be produced by combining a socket-outlet of IEC 60884-1 and a switch
1)
of IEC 60669-1 .
This document applies to socket-outlets controlled by a manually operated mechanical switch.
2 Normative references
The following documents are referred to in the text in such a way that some or all of their content
constitutes requirements of this document. For dated references, only the edition cited applies.
For undated references, the latest edition of the referenced document (including any
amendments) applies.
IEC 60884-1:2022, Clause 2 is applicable except as follows.
Addition:
IEC 60884-1:2022, Plugs and socket-outlets for household and similar purposes – Part 1:
General requirements
3 Terms and definitions
For the purposes of this document, the following terms and definitions apply.
ISO and IEC maintain terminology databases for use in standardization at the following
addresses:
• IEC Electropedia: available at https://www.electropedia.org/
• ISO Online browsing platform: available at https://www.iso.org/obp
IEC 60884-1:2022, Clause 3 is applicable except as follows.
___________
1)
IEC 60669-1, Switches for household and similar fixed-electrical installations - Part 1: General requirements

Addition:
3.101
switched socket-outlet
factory assembled unit accessory consisting of a socket-outlet with a switch controlling the
socket-outlet
3.102
multiple switched socket-outlet
accessory incorporating more than one switched socket-outlet, each socket-outlet being
controlled by its own switch
3.103
switch
device designed to make or break the current in one or more electric circuits
3.104
one operation
transfer of the moving contacts from one operating position to another
4 General requirements
IEC 60884-1:2022, Clause 4 is applicable.
5 General notes remarks on tests
IEC 60884-1:2022, Clause 5 is applicable.
6 Ratings
IEC 60884-1:2022, Clause 6 is applicable except as follows.
Addition:
6.101 Ratings of switched socket-outlets
Switches of switched socket-outlets shall have current and voltage ratings not less than those
of the socket-outlets they control.
7 Classification
IEC 60884-1:2022, Clause 7 is applicable except as follows.
7.2 Socket-outlet classification
Addition:
7.2.101 Switched socket-outlets are classified:
7.2.101.1 According to the method of actuating the switch:
– rotary switches;
– tumbler switches;
– rocker switches;
– 8 – IEC 60884-2-3:2025 RLV © IEC 2025
– push-button switches;
– cord-operated switches.
7.2.101.2 According to the switching of the neutral:
witched neutral;
– s
– unswitched neutral.
8 Marking
IEC 60884-1:2022, Clause 8 is applicable except as follows.
8.1 General
Addition after the seventh dash:
– symbol for mini-gap construction, if applicable.
8.2 Symbols
Addition before Note 1:
– Mini-gap construction m
– Open position (off) O
– Close position (on) I
Addition:
8.101 Identification of line terminals
Terminals intended for the connection of line conductors shall be identified unless the method
of connection is not important, is self-evident or is indicated on a wiring diagram. Such
identification may take the form of a letter L or, in the case of more than one such terminal, the
letters L1, L2, L3, etc., which may be accompanied by an arrow or arrows pointing to the
relevant terminal or terminals.
For two-, three-, and four-pole switches, terminals associated with any one pole shall have
similar identification, if applicable, differing from that of the terminals associated with the other
poles, unless the relationship is self-evident.
These indications shall not be placed on screws or any other easily removable parts.
Compliance is checked by inspection.
8.102 Indication of the actual switch position
Two-, three-, and four-pole switches and switches having a rated voltage exceeding 250 V or a
rated current exceeding 16 A shall be marked such that either the direction of movement of the
actuating member to its different positions or the actual switch position is clearly indicated.
The indications shall be clearly visible on the front of the switched socket-outlet when fitted with
its cover or cover plate. If these indications are placed on the cover or cover plate, it shall not
be possible to fix it in a position such that the indications are incorrect.
For the indication of direction of movement of the operating means, symbols may be used.
The closed position (on) shall be clearly indicated.

Compliance is checked by inspection.
9 Checking of dimensions
IEC 60884-1:2022, Clause 9 is applicable.
10 Protection against electric shock
IEC 60884-1:2022, Clause 10 is applicable except as follows.
Addition:
10.101 Requirements for operating parts
Knobs, operating levers, push-buttons, rockers and the like, for operating switches in switched
socket-outlets, shall be of insulating material, unless their accessible metal parts are separated
from the metal parts of the mechanism by double insulation or reinforced insulation or, as an
alternative, they are reliably connected to earth.
Compliance is checked by inspection and by the tests of Clause 17 and Clause 21.
10.102 Requirements for accessible metal parts
Metal parts of the switch mechanism, such as the spindle or the pivot of the dolly or rocker, that
are not insulated from live parts, shall not protrude from the enclosure.
Compliance is checked by inspection, if necessary, after the actuating member has been
removed or broken. If the actuating member has to be broken, compliance is checked after the
test of Clause 28.
NOTE If the actuating member has to be broken, compliance is checked after the test of Clause 28.
10.103 Requirements for insulation of the mechanism
Metal parts of the switch mechanism, such as the spindle or the pivot of the dolly or rocker shall
not be accessible when the switched socket-outlet is fixed as in normal use.
In addition, these parts shall be insulated from accessible metal parts, including metal frames
supporting the base of flush-type switched socket-outlets, liable to be mounted in a metal box,
and from screws for fixing the base to its support.
The additional requirement does not apply if the metal parts of the mechanism are separated
from live parts in such a way that the creepage distances and clearances have at least twice
the values specified in 27.1 or alternatively, if they are reliably connected to earth.
Compliance is checked by inspection and, if necessary, by measurement and by tests of
Clause 17 and Clause 20.
11 Provision for earthing
IEC 60884-1:2022, Clause 11 is applicable.

– 10 – IEC 60884-2-3:2025 RLV © IEC 2025
12 Terminals and terminations
IEC 60884-1:2022, Clause 12 is applicable.
13 Construction of fixed socket-outlets
IEC 60884-1:2022, Clause 13 is applicable except as follows.
Addition:
13.101 Construction of multiple switched socket-outlets
Multiple switched socket-outlets shall be constructed so that each socket-outlet is controlled by
its own switch.
Compliance is checked by inspection.
13.102 Switch poles
Switches shall be constructed to match the number of poles on the socket-outlet, except that
the neutral pole is not switched in unswitched neutral socket-outlets.
The earthing contact is not considered as a pole and the earth circuit shall not be switched.
The position of the switch-operating member shall be such that it does not prevent, nor shall its
correct operation be prevented by the proper insertion of the corresponding plug or plugs.
NOTE In the following country, the switch shall switch both the line and neutral: ZA.
13.102103 Actuating member
Knobs of rotary switches shall be securely coupled to the shaft or the part operating the
mechanism.
The knob is subjected for 1 min to an axial pull of 100 N.
After this, knobs of switches having only one direction of operation are turned, if possible,
without undue force, 100 times in the reverse direction.
During the test, the knob shall not become detached.
3104 Indication of the position
13.10
The actuating member of a switch, when released, shall automatically take up the position
corresponding to that of the moving contacts, except that, for those switches with a single
push-button, the actuating member may take up a single rest position.
Compliance is checked by inspection and by manual test.
13.104105 Rest and intermediate position
Switches shall be so constructed that the moving contacts can come to rest only in the "on" or
"off" position, an intermediate position being, however, permissible if it corresponds to the
intermediate position of the actuating member, and if the insulation between the fixed and
moving contacts is then adequate.

Compliance is checked by inspection and, if necessary, by the test of 17.2 with the voltage
applied between the fixed and moving contacts when in intermediate position.
13.105106 Undue arcing
Switches shall be constructed so that undue arcing cannot occur when the switch is operated
slowly.
Compliance is checked by actuating the switch, at the end of the test of Clause 21, to break the
circuit a further ten times, the actuating member being, however, moved steadily by hand over
a period of 2 s. If possible, the contacts shall be stopped in an intermediate position, the
actuating member then being released.
During the tests, no sustained arcing shall occur.
13.106107 Making and breaking
Switched socket-outlets with switches operating more than one pole shall make and break all
poles substantially simultaneously, except that for multi-pole switches with switched neutral,
the neutral shall not make after or break before other poles.
Compliance is checked by inspection and by manual test.
f the mechanism without cover or cover plate
13.107108 Action o
The action of the mechanism, if the covers or cover plate are removable for installation
purposes, shall be independent of the presence of the covers or cover plate.
Compliance is checked by connecting the switch, without cover or cover plate fitted, in series
with a lamp and by operating the actuating member without undue force as in normal use.
During the test, the lamp shall not flicker.
14 Construction of plugs and portable socket-outlets
IEC 60884-1:2022, Clause 14 is not applicable.
15 Interlocked socket-outlets
IEC 60884-1:2022, Clause 15 is not applicable.
16 Resistance to ageing, protection provided by enclosures, and resistance to
humidity
IEC 60884-1:2022, Clause 16 is applicable.
17 Insulation resistance and electric strength
IEC 60884-1:2022, Clause 17 is applicable except as follows.

– 12 – IEC 60884-2-3:2025 RLV © IEC 2025
17.2 Test for measuring the insulation resistance
17.2.1
Replacement of the last sentence:
The insulation resistance shall not be less than 5 MΩ, except for items g) and h) of 17.1.12.2,
where the resistance shall not be less than 2 MΩ.
17.1.12.2
Addition after Note 2 at the end of Subclause 17.2.2:
For switches of switched socket-outlets, the insulation resistance is measured consecutively:
f) between all poles connected together and the body, with the switch in the closed position
(on);
g) between each pole in turn and all others connected to the body, with the switch in the closed
position (on);
h) between the terminals which are electrically connected together when the switch is in the
closed position (on), the switch being in the open position (off).
The term "body" used in f) and g) includes accessible metal parts, metal frames supporting the
base of flush type switched socket-outlets, operating keys, metal foil in contact with the outer
surface of accessible external parts and operating keys of insulation material, the point of
anchorage of the cord, chain or rod for switches operated by such means, fixing screws of
bases or covers and cover plates, external assembly screws, earthing terminals and any metal
part of the mechanism if required to be insulated from live parts (see 10.102).
18 Operation of earthing contacts
IEC 60884-1:2022, Clause 18 is applicable.
19 Temperature rise
IEC 60884-1:2022, Clause 19 is applicable.
20 Breaking capacity
IEC 60884-1:2022, Clause 20 is applicable except as follows.
Addition:
Switches incorporated in switched socket-outlets shall have adequate making and breaking
capacity.
The tests are carried out by means of an apparatus, the principle of which is as shown in
Figure 101 and which is arranged to simulate normal operation.
Switches are fitted with conductors as for the test of Clause 19.
Switches are tested at 1,1 times the rated voltage and 1,25 times the rated current. They are
subjected to 200 operations at a uniform rate of:
– 30 operations per minute, if the rated current does not exceed 10 A;

– 15 operations per minute, if the rated current exceeds 10 A but is less than 25 A;
– 7,5 operations per minute, if the rated current is 25 A or more.
NOTE See definition 3.104 for the definition of “one operation”.
For rotary switches intended to be operated in either direction, the actuating member is turned
in one direction for half the total number of operations, and in the reverse direction for the
remainder.
The test is carried out by using an alternating current (cos φ = 0,6 ± 0,05).
During the test no sustained arcing shall occur.
After the test, the specimen shall show no damage which may impair its further use.

– 14 – IEC 60884-2-3:2025 RLV © IEC 2025

Figure 101 – Example of apparatus for testing the making and breaking capacity and the
normal operation of switches in switched socket-outlets
21 Normal operation
IEC 60884-1:2022, Clause 21 is applicable except as follows.
Addition:
Switches of switched socket-outlets shall withstand, without excessive wear or other harmful
effect, the mechanical, electrical and thermal stresses occurring in normal use.
Compliance is checked by the following test:

The switches are tested at rated voltage and rated current (cos φ = 0,8 ± 0,05) in the apparatus
as specified in Clause 20.
The number of operations is as shown in Table 101.
Table 101 – Number of operations for normal operation test
Rated current Number of
operations
Up to and including 16 A for switches having a rated voltage not 40 000
exceeding 250 V AC
Up to and including 16 A for switches having a rated voltage 20 000
exceeding 250 V AC
Over 16 A up to and including 32 A 10 000

The rate of operations is according to Clause 20.
For rotary switches intended to be operated in either direction, three-quarters of the total
number of operations shall be in the clockwise direction and the remainder in the reverse
direction.
During the test, the specimens shall function correctly.
After the test, the specimens shall withstand an electric strength test as specified in Clause 17,
and a temperature rise test as specified in Clause 19, the test current however being reduced
to the rated current.
The specimens shall then not show:
– wear impairing their further use;
– discrepancy between the position of the actuating member and that of the moving contacts,
if the position of the actuating member is indicated;
– deterioration of enclosures, insulating linings or barriers to such an extent that the switch
cannot be further operated or that the requirements of Clause 10 are no longer complied
with;
– loosening of electrical or mechanical connections;
– seepage of sealing compound;
– relative displacement of the moving contacts of switches.
The humidity treatment according to 16.3 is not repeated before the dielectric strength test of
this Clause 21.
During the test, the specimens are not lubricated.
22 Force necessary to withdraw the plug
IEC 60884-1:2022, Clause 22 is applicable.
23 Flexible cables and their connection
IEC 60884-1:2022, Clause 23 is not applicable.

– 16 – IEC 60884-2-3:2025 RLV © IEC 2025
24 Mechanical strength
IEC 60884-1:2022, Clause 24 is applicable.
25 Resistance to heat
IEC 60884-1:2022, Clause 25 is applicable.
26 Screws, current-carrying parts and connections
IEC 60884-1:2022, Clause 26 is applicable.
27 Creepage distances, clearances and distances through sealing compound
IEC 60884-1:2022, Clause 27 is applicable except as follows.
Addition:
27.101 Additional requirement for switched socket-outlets
For switches incorporated in switched socket-outlets, creepage distances, clearances and
distances through sealing compound shall not be less than the values shown in Table 102.
Table 102 – Creepage distances, clearances and distances through sealing compound
Description mm
Creepage distance
1) Between live parts which are separated when the contacts are open 3
2) Between live parts and:
– metal parts of the mechanism, if required to be insulated from live parts (see 10.102) 3
3) Between metal parts of the mechanism, if required to be insulated from accessible metal parts
(see 10.103) and:
– screws or devices for fixing bases, covers or cover plates
– metal frames supporting the base of flush-type switched socket-outlets
– accessible metal parts 3
Clearance
4) Between live parts which are separated when the contacts are open 3*
5) Between live parts and metal parts of the mechanism, if required to be insulated from live parts 3
(see 10.102)
6) Between metal parts of the mechanism, if required to be insulated from accessible metal parts (see
10.103) and:
– screws or devices for fixing bases, covers or cover plates
– metal frames supporting the base of flush-type switched socket-outlets
– accessible metal parts 3
* This value is reduced to 1,2 mm when the contacts are open, for live parts of switches of mini-gap construction
which are moved during the separation of the contacts.

Compliance is checked by measurement.

28 Resistance of insulating material to abnormal heat, to fire and to tracking
IEC 60884-1:2022, Clause 28 is applicable.
29 Resistance to rusting
IEC 60884-1:2022, Clause 29 is applicable.
30 Additional tests on pins provided with insulating sleeves
IEC 60884-1:2022, Clause 30 is not applicable.
31 EMC requirements
IEC 60884-1:2022, Clause 31 is applicable.
32 Electromagnetic fields (EMF) requirements
IEC 60884-1:2022, Clause 32 is applicable.

– 18 – IEC 60884-2-3:2025 RLV © IEC 2025
Annexes
The annexes of IEC 60884-1:2022 are applicable except as follows:

Annex A
(normative)
Safety-related routine tests for factory-wired portable accessories
(protection against electric shock and correct polarity)
IEC 60884-1:2022, Annex A is not applicable.

Annex B
(informative)
Alternative gripping tests
IEC 60884-1:2022, Annex B is not applicable.

Annex C
(normative)
Switches incorporated in portable socket-outlets
IEC 60884-1:2022, Annex C is not applicable.

Annex I
(normative)
Additional requirements and tests for plugs and
socket-outlets for high-load (HL) application
IEC 60884-1:2022, Annex I is not applicable.

___________
IEC 60884-2-3 ®
Edition 3.0 2025-02
INTERNATIONAL
STANDARD
Plugs and socket-outlets for household and similar purposes –
Part 2-3: Particular requirements for switched socket-outlets without interlock
for fixed installations
– 2 – IEC 60884-2-3:2025 © IEC 2025
CONTENTS
FOREWORD . 4
1 Scope . 6
2 Normative references . 6
3 Terms and definitions . 6
4 General requirements . 7
5 General remarks on tests . 7
6 Ratings . 7
7 Classification . 7
8 Marking . 8
9 Checking of dimensions . 8
10 Protection against electric shock . 9
11 Provision for earthing . 9
12 Terminals and terminations . 9
13 Construction of fixed socket-outlets . 10
14 Construction of plugs and portable socket-outlets . 11
15 Interlocked socket-outlets . 11
16 Resistance to ageing, protection provided by enclosures, and resistance to
humidity . 11
17 Insulation resistance and electric strength . 11
18 Operation of earthing contacts . 12
19 Temperature rise . 12
20 Breaking capacity . 12
21 Normal operation . 14
22 Force necessary to withdraw the plug . 15
23 Flexible cables and their connection . 15
24 Mechanical strength . 15
25 Resistance to heat . 15
26 Screws, current-carrying parts and connections . 15
27 Creepage distances, clearances and distances through sealing compound . 15
28 Resistance of insulating material to abnormal heat, to fire and to tracking . 16
29 Resistance to rusting . 16
30 Additional tests on pins provided with insulating sleeves . 16
31 EMC requirements . 16
32 Electromagnetic fields (EMF) requirements . 16
Annexes . 17
Annex A (normative) Safety-related routine tests for factory-wired portable
accessories (protection against electric shock and correct polarity) . 17
Annex B (informative) Alternative gripping tests . 17
Annex C (normative) Switches incorporated in portable socket-outlets . 17
Annex I (normative) Additional requirements and tests for plugs and socket-outlets for
high-load (HL) application . 17

Figure 101 – Example of apparatus for testing the making and breaking capacity and
the normal operation of switches in switched socket-outlets . 13

Table 101 – Number of operations for normal operation test . 14
Table 102 – Creepage distances, clearances and distances through sealing compound . 16

– 4 – IEC 60884-2-3:2025 © IEC 2025
INTERNATIONAL ELECTROTECHNICAL COMMISSION
____________
PLUGS AND SOCKET-OUTLETS FOR HOUSEHOLD
AND SIMILAR PURPOSES –
Part 2-3: Particular requirements for switched socket-outlets
without interlock for fixed installations

FOREWORD
1) The International Electrotechnical Commission (IEC) is a worldwide organization for standardization comprising
all national electrotechnical committees (IEC National Committees). The object of IEC is to promote international
co-operation on all questions concerning standardization in the electrical and electronic fields. To this end and
in addition to other activities, IEC publishes International Standards, Technical Specifications, Technical Reports,
Publicly Available Specifications (PAS) and Guides (hereafter referred to as “IEC Publication(s)”). Their
preparation is entrusted to technical committees; any IEC National Committee interested in the subject dealt with
may participate in this preparatory work. International, governmental and non-governmental organizations liaising
with the IEC also participate in this preparation. IEC collaborates closely with the International Organization for
Standardization (ISO) in accordance with conditions determined by agreement between the two organizations.
2) The formal decisions or agreements of IEC on technical matters express, as nearly as possible, an international
consensus of opinion on the relevant subjects since each technical committee has representation from all
interested IEC National Committees.
3) IEC Publications have the form of recommendations for international use and are accepted by IEC National
Committees in that sense. While all reasonable efforts are made to ensure that the technical content of IEC
Publications is accurate, IEC cannot be held responsible for the way in which they are used or for any
misinterpretation by any end user.
4) In order to promote international uniformity, IEC National Committees undertake to apply IEC Publications
transparently to the maximum extent possible in their national and regional publications. Any divergence between
any IEC Publication and the corresponding national or regional publication shall be clearly indicated in the latter.
5) IEC itself does not provide any attestation of conformity. Independent certification bodies provide conformity
assessment services and, in some areas, access to IEC marks of conformity. IEC is not respon
...

Questions, Comments and Discussion

Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.

Loading comments...