Abstract

IEC 62146-1:2026 is available as IEC 62146-1:2026 RLV which contains the International Standard and its Redline version, showing all changes of the technical content compared to the previous edition.IEC 62146-1:2026 includes generalities of capacitors used on alternating current circuit-breakers and introduces specifications for grading capacitors. Regarding grading capacitors, their function is to control the voltage distribution across the individual interrupter units of a multi-break circuit-breaker.
This document applies to grading capacitors falling into one or both of the following categories for:
- mounting on air-insulated circuit-breakers.
- mounting on enclosed circuit-breakers (for example immersed in insulating gas, in oil, etc.).
The object of this document is:
- to define uniform rules regarding performances, testing and rating;
- to define specific safety rules;
- to provide a guidance for installation and operation.
This document does not apply to capacitors not directly associated with high-voltage alternating current circuit-breakers.

Status
Published
Publication Date
22-Jul-2026
Current Stage
PPUB - Publication issued - 60 Publication
Start Date
23-Jul-2026
Due Date
14-Aug-2026
Completion Date
14-Aug-2026

Buy Documents

Standard

IEC 62146-1:2026 - Capacitors for high-voltage alternating current circuit-breakers - Part 1: General and grading capacitors

ISBN:978-2-8327-1381-5
Release Date:23-Jul-2026
English language (41 pages)
sale 15% off
Preview
sale 15% off
Preview
Standard

REDLINE IEC 62146-1:2026 RLV - Capacitors for high-voltage alternating current circuit-breakers - Part 1: General and grading capacitors

ISBN:978-2-8327-1413-3
Release Date:23-Jul-2026
English language (90 pages)
sale 15% off
Preview
sale 15% off
Preview
Standard

IEC 62146-1:2026 - Condensateurs pour disjoncteurs a courant alternatif haute tension - Partie 1: Généralités et condensateurs de répartition

ISBN:978-2-8327-1381-5
Release Date:23-Jul-2026
French language (44 pages)
sale 15% off
Preview
sale 15% off
Preview

IEC 62146-1:2026 is an International Standard from IEC for capacitors used on high-voltage alternating current circuit-breakers. It specifies the general rules and the grading capacitors used to control voltage distribution across interrupter units in a multi-break circuit-breaker.

The document is written for capacitor manufacturers, circuit-breaker manufacturers, test laboratories, purchasers, and maintenance teams that need to specify, test, install, or inspect these components. It gives a common basis for ratings, construction, testing, safety, marking, and service guidance.

What does IEC 62146-1:2026 specify?

IEC 62146-1:2026 specifies requirements for grading capacitors mounted on air-insulated circuit-breakers and on enclosed circuit-breakers such as units immersed in insulating gas or oil. It also gives generalities for capacitors used on alternating current circuit-breakers and points readers to IEC 62146-2:2023 for Transient Recovery Voltage (TRV) capacitors.

The standard’s stated aim is to set uniform rules for performance, testing, and rating, to define safety rules, and to give guidance for installation and operation. It excludes capacitors that are not directly associated with high-voltage alternating current circuit-breakers.

The document is organized into clauses for scope, references, terms, service conditions, ratings, design and construction, type tests, routine tests, a design aging test, installation and maintenance guidance, safety, and environmental aspects.

AnnexWhat it covers
Annex ACorrosion: service conditions and recommended test requirements
Annex BResonance frequency measurements, including time-domain and frequency-domain methods

What are the key requirements of IEC 62146-1:2026?

IEC 62146-1:2026 focuses on how to rate, build, test, mark, and use grading capacitors so that they match the circuit-breaker they support. In practice, the standard ties the capacitor specification to the breaker design, the insulation environment, and the expected mechanical and electrical stresses.

Service conditions and ratings

Clause 5 aligns normal and special service conditions with IEC 62271-1, with additional points for capacitors. For outdoor use, the normal conditions follow the breaker standard; for immersed capacitors, the surrounding medium can be hotter than ambient air, and the manufacturer is expected to consider the internal operating temperature.

Altitude is treated as a design condition up to 1 000 m, and above that the external insulation withstand level is corrected by an altitude factor. For earthquakes, grading capacitors are treated as breaker accessories and are covered by the seismic qualification rules of IEC 62271-300. This matters because the capacitor rating is not chosen in isolation - it must fit the breaker, the installation site, and the expected environment.

Clause 6 bases the rated voltage of a grading capacitor on the circuit-breaker rated voltage, the number of interrupter units per pole, and the voltage grading factor F, standardized at 1.2. The rated insulation level is derived from the breaker withstand values, using the relevant grading factor and application case. The standard values for rated frequency are 50 Hz and 60 Hz.

Design, materials, and construction

Clause 7 sets the main construction rules. Capacitance tolerance is limited to ±5 % for capacitors for air-insulated circuit-breakers and ±3 % for capacitors in enclosed circuit-breakers. Losses are expressed as tangent of the loss angle (tan δ), and the acceptable loss values are agreed between manufacturer and purchaser.

Partial discharge limits are given for grading capacitors, with different limits for air-insulated and immersed service. The standard also requires grading capacitors to be installable in any direction, and it specifies a minimum mechanical bending load for the relevant mounting cases. This is important because the capacitor is both an electrical component and a structural part of the breaker assembly.

Clause 7 also requires the manufacturer to state the impregnation medium, to specify liquid quality when liquids are used, and to address liquid leakage, gas tightness, corrosion protection, marking, and creepage distance for outdoor capacitors. The nameplate information includes the manufacturer identity, type designation, serial number, rated voltage, rated frequency, rated capacitance and tolerance, test voltage, temperature range, filling quantity or pressure, fluid designation, and the IEC 62146-1 edition reference.

Type tests and design verification

Clause 8 describes type tests that prove the design before series production. These include dielectric tests, switching impulse testing for capacitors installed on breakers rated at 300 kV and above, lightning and chopped lightning impulse tests, low- and high-temperature voltage tests, radio interference voltage (RIV) testing, power-frequency withstand testing for lower rated voltages, short-circuit discharge testing, resonance frequency measurement, mechanical bending, tightness checks, and vibration testing.

The clause also requires clear specimen identification, traceable type-test reports, and repeated type testing after design changes unless the manufacturer shows the change does not affect the result. In practice, this is the clause that links the design drawing to the actual test sample and to the final test evidence.

Routine tests, aging, and operating guidance

Clause 9 requires routine tests on production units, including capacitance and tan δ measurement, power-frequency withstand testing, partial discharge testing, tightness testing where applicable, and final visual and dimensional checks. The acceptance criteria are tied to the measured capacitance change, the permitted loss angle, and the partial discharge limits.

Clause 10 gives an aging test with long-duration voltage stress at elevated temperature, followed by repeat routine checks. Clauses 11 to 13 provide guidance for transport, storage, unpacking, lifting, mounting, connections, operation, maintenance, safety precautions, and environmental aspects. These sections matter because field performance depends on handling and upkeep as much as on the initial test result.

What terms does IEC 62146-1:2026 define?

IEC 62146-1:2026 defines the technical terms used to specify the capacitor, its insulation system, and its test results. The definitions make the electrical and mechanical requirements readable across manufacturers and test houses.

  • grading capacitor - a capacitor installed on a high-voltage circuit-breaker to control the voltage distribution across an individual interrupter unit.
  • capacitor unit - an assembly of one or more capacitor elements in the same container with terminals brought out.
  • rated capacitance of a capacitor - the capacitance value for which the capacitor is designed.
  • rated insulation level - the set of test voltages the insulation is designed to withstand under specified conditions.
  • voltage grading factor of a circuit-breaker (F) - the factor used to define standard rated voltages for the grading capacitor from the breaker voltage distribution.
  • tangent of the loss angle of a capacitor (tan δ) - the ratio used to express capacitor losses at a specified voltage and frequency.
  • resonance frequency - the frequency where the capacitor’s capacitance reactance equals its self-inductance reactance.
  • Transient Recovery Voltage (TRV) - the breaker-related transient voltage for which IEC 62146-2:2023 provides the capacitor application.

Who uses IEC 62146-1:2026?

IEC 62146-1:2026 is used by capacitor manufacturers who design grading capacitors and need a testable specification. It is also used by circuit-breaker manufacturers and switchgear engineers who have to match the capacitor to the interrupter design, insulation level, and mechanical arrangement.

Testing laboratories use it to prepare specimens, run type tests and routine tests, and write the test reports. Purchasers and quality managers use it to state ratings, service conditions, and acceptance expectations in procurement and project documentation. Maintenance and field teams use it for installation, inspection, handling, and periodic condition checks.

What changed in IEC 62146-1:2026 from the previous edition?

IEC 62146-1:2026 is the second edition and replaces the first edition published in 2016. The stated technical changes are clause re-ordering, reworked sentences, and new type and special tests.

Which standards are used with IEC 62146-1:2026?

IEC 62146-1:2026 relies on a set of normative references for test methods, insulation coordination, fluids, and switchgear coordination.

StandardWhat it contributes
IEC 60060-1High-voltage test terminology and test requirements, including impulse waveforms
IEC 60068-2-17:2023Sealing tests used for tightness checks
IEC 60071-2:2023Insulation coordination guidance and altitude correction methods
IEC 60270:2025Partial discharge measurement method
IEC 60296Mineral insulating oils for electrical equipment
IEC 60567Gas sampling and analysis of mineral oils and other insulating liquids
IEC 60815 (all parts)Creepage selection for polluted conditions
IEC 60867Unused synthetic aromatic hydrocarbon insulating liquids
IEC 61099Unused synthetic organic esters for electrical purposes
IEC 61462Composite hollow insulators and related test methods
IEC 62146-2:2023TRV capacitors, including the related application case
IEC 62155:2003Hollow ceramic and glass insulators used for electrical equipment
IEC 62271-1Common specifications for AC switchgear and controlgear
IEC 62271-100AC circuit-breakers
IEC 62271-203AC gas-insulated metal-enclosed switchgear
IEC 62271-205Compact switchgear assemblies above 52 kV
IEC 62271-300Seismic qualification of AC circuit-breakers
IEC 62770Unused natural esters for transformers and similar equipment
IEC 63012Unused modified or blended esters for electrotechnical applications

What does the IEC 62146-1:2026 document contain?

IEC 62146-1:2026 contains rating rules, design limits, and a complete test structure for grading capacitors. It includes the stated limits for capacitance tolerance, partial discharge, losses, resonance frequency, bending load, tightness, and test voltages, plus the acceptance criteria for type tests, routine tests, and the aging test.

The document also contains example figures for dielectric type-test sequencing, routine test sequencing, reduced-scale model geometry, and resonance measurement arrangements. Table 1 gives the partial discharge test voltages and permissible levels, while Annex B explains both time-domain and frequency-domain methods for measuring resonance frequency.

Relations

Effective Date
05-Sep-2023
Effective Date
05-Sep-2023

Buy Documents

Standard

IEC 62146-1:2026 - Capacitors for high-voltage alternating current circuit-breakers - Part 1: General and grading capacitors

ISBN:978-2-8327-1381-5
Release Date:23-Jul-2026
English language (41 pages)
sale 15% off
Preview
sale 15% off
Preview
Standard

REDLINE IEC 62146-1:2026 RLV - Capacitors for high-voltage alternating current circuit-breakers - Part 1: General and grading capacitors

ISBN:978-2-8327-1413-3
Release Date:23-Jul-2026
English language (90 pages)
sale 15% off
Preview
sale 15% off
Preview
Standard

IEC 62146-1:2026 - Condensateurs pour disjoncteurs a courant alternatif haute tension - Partie 1: Généralités et condensateurs de répartition

ISBN:978-2-8327-1381-5
Release Date:23-Jul-2026
French language (44 pages)
sale 15% off
Preview
sale 15% off
Preview

Frequently Asked Questions

IEC 62146-1:2026 is a standard published by the International Electrotechnical Commission (IEC). Its full title is "Capacitors for high-voltage alternating current circuit-breakers - Part 1: General and grading capacitors". This standard covers: IEC 62146-1:2026 is available as IEC 62146-1:2026 RLV which contains the International Standard and its Redline version, showing all changes of the technical content compared to the previous edition.IEC 62146-1:2026 includes generalities of capacitors used on alternating current circuit-breakers and introduces specifications for grading capacitors. Regarding grading capacitors, their function is to control the voltage distribution across the individual interrupter units of a multi-break circuit-breaker. This document applies to grading capacitors falling into one or both of the following categories for: - mounting on air-insulated circuit-breakers. - mounting on enclosed circuit-breakers (for example immersed in insulating gas, in oil, etc.). The object of this document is: - to define uniform rules regarding performances, testing and rating; - to define specific safety rules; - to provide a guidance for installation and operation. This document does not apply to capacitors not directly associated with high-voltage alternating current circuit-breakers.

IEC 62146-1:2026 is available as IEC 62146-1:2026 RLV which contains the International Standard and its Redline version, showing all changes of the technical content compared to the previous edition.IEC 62146-1:2026 includes generalities of capacitors used on alternating current circuit-breakers and introduces specifications for grading capacitors. Regarding grading capacitors, their function is to control the voltage distribution across the individual interrupter units of a multi-break circuit-breaker. This document applies to grading capacitors falling into one or both of the following categories for: - mounting on air-insulated circuit-breakers. - mounting on enclosed circuit-breakers (for example immersed in insulating gas, in oil, etc.). The object of this document is: - to define uniform rules regarding performances, testing and rating; - to define specific safety rules; - to provide a guidance for installation and operation. This document does not apply to capacitors not directly associated with high-voltage alternating current circuit-breakers.

IEC 62146-1:2026 is classified under the following ICS (International Classification for Standards) categories: 31.060.01 - Capacitors in general; 31.060.70 - Power capacitors. The ICS classification helps identify the subject area and facilitates finding related standards.

IEC 62146-1:2026 has the following relationships with other standards: It is inter standard links to IEC 62146-1:2013/AMD1:2016, IEC 62146-1:2013. Understanding these relationships helps ensure you are using the most current and applicable version of the standard.

IEC 62146-1:2026 is available in PDF format for immediate download after purchase. The document can be added to your cart and obtained through the secure checkout process. Digital delivery ensures instant access to the complete standard document.

Standards Content (Sample)

Contents

  • 1 Scope
  • 2 Normative references
  • 3 Terms and definitions
  • 3.1 arcing distance
  • 3.2 capacitor element
  • 3.3 capacitor losses
  • 3.4 capacitor terminals
  • 3.5 capacitance tolerance
  • 3.6 capacitor unit
  • 3.7 completely immersed capacitor
  • 3.8 creepage distance
  • 3.9 dielectric (of a capacitor)
  • 3.10 external insulation
  • 3.11 failure
  • 3.12 flashover
  • 3.13 grading capacitor
  • 3.14 indoor capacitor
  • 3.15 insulating envelope
  • 3.16 outdoor capacitor
  • 3.17 internal insulation
  • 3.18 mechanical stress
  • 3.19 puncture
  • 3.20 rated capacitance of a capacitor
  • 3.21 rated chopped lightning impulse withstand voltage
  • 3.22 rated frequency of a capacitor
  • 3.23 rated insulation level
  • 3.24 rated lightning impulse withstand voltage
  • 3.25 rated short duration power frequency withstand voltage
  • 3.26 rated switching impulse withstand voltage
  • 3.27 rated temperature category (of a capacitor)
  • 3.28 rated voltage of a capacitor
  • 3.29 rated voltage of circuit-breaker
  • 3.30 resonance frequency
  • 3.31 sample
  • 3.32 tangent of the loss angle of a capacitor
  • 3.33 voltage grading factor of a circuit-breaker
  • 4 Abbreviated terms
  • 5 Service conditions
  • 5.1 General
  • 5.2 Normal service conditions
  • 5.3 Special service conditions
  • 6 Ratings
  • 6.1 Rated voltage (U )
  • 6.2 Rated insulation level
  • 6.3 Rated frequency (f )
  • 7 Design and construction
  • 7.1 Capacitance tolerances
  • 7.2 Capacitor loss requirements
  • 7.3 Partial discharge level
  • 7.4 Angle of mounting
  • 7.5 Minimum withstand value of mechanical bending load
  • 7.6 Insulation fluids
  • 7.7 Protection against corrosion
  • 7.8 Marking of the equipment
  • 7.9 Creepage distances for outdoor capacitors
  • 8 Type tests
  • 8.1 Information for identification of specimens
  • 8.2 Information to be included in type-test reports
  • 8.3 Test conditions
  • 8.4 Dielectric type tests
  • 8.5 Voltage test at low and high temperature
  • 8.6 Radio interference voltage (RIV) test
  • 8.7 Power frequency withstand voltage test
  • 8.8 Short-circuit discharge test
  • 8.9 Resonance frequency measurements
  • 8.10 Mechanical bending test
  • 8.11 Tightness test at different temperatures
  • 8.12 Tightness test to check gas ingress from a pressurised environment
  • 8.13 Vibration test
  • 9 Routine tests
  • 9.1 General
  • 9.2 Test conditions
  • 9.3 Capacitance and tan δ (loss angle) measurement at power frequency
  • 9.4 Power frequency withstand voltage test
  • 9.5 Partial discharge test
  • 9.6 Tightness test
  • 9.7 Visual inspection and dimensional check
  • 10 Design test
  • 10.1 Aging test
  • 11 Recommendations for transport, storage, installation, operation and

1 Scope

This part of IEC 62146 includes generalities of capacitors used on alternating current circuitbreakers and introduces specifications for grading capacitors. Regarding grading capacitors, their function is to control the voltage distribution across the individual interrupter units of a multi-break circuit-breaker.

Capacitors can also be used in parallel to the interrupter unit on single break circuit-breakers to modify the Transient Recovery Voltage (TRV). This TRV capacitor application is covered by IEC 62146-2:2023.

Capacitors for high-voltage alternating circuit breakers are sub-components for the circuitbreaker and are specified in accordance with the circuit-breaker specifications according to IEC 62271-1, IEC 62271-100, and if applicable to IEC 62271-203. This document applies to grading capacitors falling into one or both of the following categories for:

− mounting on air-insulated circuit-breakers.

− mounting on enclosed circuit-breakers (for example immersed in insulating gas, in oil, etc.). The testing for each of the above applications is in some cases different. The object of this document is:

− to define uniform rules regarding performances, testing and rating; − to define specific safety rules; − to provide a guidance for installation and operation.

NOTE CIGRÉ TB-368 presents a study about the operating environment of voltage grading capacitors applied to

high-voltage circuit-breakers (see [2] ).

This document does not apply to capacitors not directly associated with high-voltage alternating current circuit-breakers.

2 Normative references

The following documents are referred to in the text in such a way that some or all of their content constitutes requirements of this document. For dated references, only the edition cited applies. For undated references, the latest edition of the referenced document (including any amendments) applies.

IEC 60060-1, High-voltage test techniques - Part 1: General terminology and test requirements IEC 60068-2-17:2023, Environmental testing - Part 2-17: Tests - Test Q: Sealing IEC 60071-2:2023, Insulation co-ordination - Part 2: Application guidelines IEC 60270:2025, High-voltage test techniques - Charge-based measurement of partial discharges IEC 60296, Fluids for electrotechnical applications - Mineral insulating oils for electrical equipment

Numbers in square brackets refer to the Bibliography.

IEC 60567, Oil-filled electrical equipment - Sampling of gases and analysis of free and dissolved gases in mineral oils and other insulating liquids - Guidance IEC 60815 (all parts), Selection and dimensioning of high-voltage insulators intended for use in polluted conditions IEC 60867, Insulating liquids - Specifications for unused liquids based on synthetic aromatic hydrocarbons IEC 61099, Insulating liquids - Specifications for unused synthetic organic esters for electrical purposes IEC 61462, Composite hollow insulators - Pressurized and unpressurized insulators for use in electrical equipment with AC rated voltage greater than 1 000 V AC and DC voltage greater than 1 500 V - Definitions, test methods, acceptance criteria and design recommendations IEC 62146-2:2023, Capacitors for high‑voltage alternating current circuit‑breakers - Part 2: TRV capacitors IEC 62155:2003, Hollow pressurized and unpressurized ceramic and glass insulators for use in electrical equipment with rated voltages greater than 1 000 V IEC 62271-1, High-voltage switchgear and controlgear - Part 1: Common specifications for alternating current switchgear and controlgear IEC 62271-100, High-voltage switchgear and controlgear - Part 100: Alternating-current circuitbreakers IEC 62271-203, High-voltage switchgear and controlgear - Part 203: AC gas-insulated metalenclosed switchgear for rated voltages above 52 kV IEC 62271-205, High-voltage switchgear and controlgear - Part 205: Compact switchgear assemblies for rated voltages above 52 kV IEC 62271-300, High-voltage switchgear and controlgear - Part 300: Seismic qualification of alternating current circuit-breakers IEC 62770, Fluids for electrotechnical applications - Unused natural esters for transformers and similar electrical equipment IEC 63012, Insulating liquids - Unused modified or blended esters for electrotechnical applications

3 Terms and definitions

For the purposes of this document, the following terms and definitions apply. ISO and IEC maintain terminology databases for use in standardization at the following addresses:

  • IEC Electropedia: available at https://www.electropedia.org/
  • ISO Online browsing platform: available at https://www.iso.org/obp

3.1 arcing distance

shortest distance in the air external to the insulator between the metallic parts which normally have the operating voltage between them [SOURCE: IEC 60050-471:2007, 471-01-01]

3.2 capacitor element

device consisting essentially of two electrodes separated by a dielectric [SOURCE: IEC 60050-436:1990, 436-01-03]

3.3 capacitor losses

active power dissipated in the capacitor [SOURCE: IEC 60050-436:1990, 436-04-10]

3.4 capacitor terminals

terminals intended for electrical and mechanical connection to the terminals of the interrupter units of circuit-breakers

3.5 capacitance tolerance

permissible difference between the actual capacitance and the rated capacitance under specified conditions Note 1 to entry: The actual capacitance should be measured at, or referred to, the temperature at which the rated capacitance is defined.

[SOURCE: IEC 60050-436:1990, 436-04-01, modified by addition of Note to entry.]

3.6 capacitor unit

assembly of one or more capacitor elements connected together and in the same container with terminals brought out Note 1 to entry: A common type of unit for grading capacitors has a cylindrical housing of insulating material and metal end flanges which serve as terminals.

[SOURCE: IEC 60050-436:1990, 436-01-04, modified by addition of Note to entry]

3.7 completely immersed capacitor

capacitor, both ends of which are intended to be immersed in insulating media other than ambient air (e.g. oil or gas) [SOURCE: IEC 60050-471:2007, 471-02-04, modified - definition originally referred to "bushing" instead of "capacitor".]

3.8 creepage distance

shortest distance along the surface of a solid insulating material between two conductive parts Note 1 to entry: The surface of cement or any other non-insulating jointing material is not considered as forming part of the creepage distance.

Note 2 to entry: If high-resistance coating is applied to parts of the insulating part of an insulator, such parts are considered to be effective insulating surface and the distance over them is included in the creepage distance. [SOURCE: IEC 60050-604:1987, 604-03-61, modified by addition of Notes to entry.]

3.9 dielectric (of a capacitor)

insulating material between the electrodes of the capacitor element Note 1 to entry: The major insulation generally consists of paper, plastic film, or a mixed of paper and plastic film subsequently treated and impregnated with oil or gas at atmospheric pressure or higher.

3.10 external insulation

distance through the air and the surfaces in contact with the air of the grading capacitor that are subjected to dielectric stresses Note 1 to entry: They are also subject to the effects of the atmospheric and other external conditions such as pollution, humidity, ice, vermin, etc.

3.11 failure

termination of the ability of an item to perform a required function Note 1 to entry: After failure the item has a fault.

Note 2 to entry: "Failure" is an event, as distinguished from "fault", which is a state. Note 3 to entry: This concept as defined does not apply to items consisting of software only. [SOURCE: IEC 60050-191:1990, 191-04-01]

3.12 flashover

electric breakdown between conductors in a gas or in a liquid or in a vacuum, at least partly along the surface of solid insulation [SOURCE: IEC 60050-212:2012, 212-11-47]

3.13 grading capacitor

capacitor for installation on high-voltage circuit-breakers to control the voltage distribution across the individual interrupter unit Note 1 to entry: The grading capacitors alone are accessories of the circuit-breaker.

3.14 indoor capacitor

capacitor, both ends of which are intended to be in ambient air at atmospheric pressure but not exposed to outdoor atmospheric conditions [SOURCE: IEC 60050-471:2007, 471-02-05, modified - definition originally referred to "bushing" instead of "capacitor".]

3.15 insulating envelope

insulator which is open from end to end, with or without sheds, including end fittings Note 1 to entry: An insulating envelope can be made from one or more permanently assembled insulating elements. Note 2 to entry: The insulating envelope may be in ceramic, glass or analogous inorganic material, cast or moulded resin, composite insulating material, in one piece or more pieces permanently assembled. [SOURCE: IEC 60050-471:2007, 471-01-08, modified - definition originally referred to a hollow insulator and Note 2 to entry has been added.]

3.16 outdoor capacitor

capacitor, both ends of which are intended to be in ambient air at atmospheric pressure, and exposed to outdoor atmospheric conditions [SOURCE: IEC 60050-471:2007, 471-02-07, modified - definition originally referred to "bushing" instead of "capacitor".]

3.17 internal insulation

internal solid, liquid or gaseous parts of the insulation of the grading capacitor which are protected from the effects of atmospheric conditions Note 1 to entry: The parts are also protected from other external conditions such as pollution, humidity, ice, vermin, etc.

3.18 mechanical stress

any mechanical stress applied to the insulating envelope and to the terminals of the capacitor Note 1 to entry: It is a function of the following main forces:

− forces on the terminals due to the circuit-breaker connection; − forces due to the wind and ice; − seismic forces; − forces due to the operating conditions, opening and closing, of the circuit- breaker; − thermal forces due to the ambient medium conditions; − forces due to the transportation of the circuit-breaker or capacitors.

3.19 puncture

disruptive discharge occurring through a solid insulation material, producing a path of permanent damage Note 1 to entry: The term puncture is also used as a synonym for electrical breakdown in solids. [SOURCE: IEC 60050-212:2010, 212-11-49]

3.20 rated capacitance of a capacitor

C r capacitance value for which the capacitor has been designed

3.21 rated chopped lightning impulse withstand voltage

required peak value of the chopped lightning impulse withstand voltage which characterises the insulation of a capacitor as regards the withstand tests Note 1 to entry: The definitions and the standard parameters applicable to chopped impulses are specified in IEC 60060-1.

3.22 rated frequency of a capacitor

f r frequency for which the capacitor has been designed [SOURCE: IEC 60050-436:1990, 436-01-14, modified by addition of symbol.]

3.23 rated insulation level

test voltages, under specified conditions, that the insulation is designed to withstand Note 1 to entry: These test voltages can be for instance:

a) rated chopped and lightning impulse and short duration power frequency withstand voltages for capacitors installed on circuit-breaker with rated voltage lower than 300 kV. b) rated switching, lightning, chopped impulse and short duration power frequency withstand voltages for capacitors installed on circuit-breaker with rated voltage equal to or greater than 300 kV. Note 2 to entry: The rated insulation levels of the capacitor should be equal to or higher than the relevant requirements for the circuit-breaker interrupting unit.

[SOURCE: IEC 60050-421:1990, 421-09-02, modified Note to entry]

3.24 rated lightning impulse withstand voltage

U C LI required peak value of the lightning impulse withstand voltage which characterises the insulation of an equipment as regards the withstand tests Note 1 to entry: The standard lightning impulse has a front time of 1,2 µs and a time-to-half-value of 50 µs as specified in IEC 60060-1.

3.25 rated short duration power frequency withstand voltage

U C PF required RMS value of sinusoidal power frequency voltage that the equipment withstands during tests made under specified conditions and for a duration of 1 min unless otherwise specified

3.26 rated switching impulse withstand voltage

U C SI required peak value of the switching impulse withstand voltage which characterises the insulation of an equipment as regards the withstand tests Note 1 to entry: The standard switching impulse has a time-to-crest of 250 µs and a time-to-half-value of 2 500 µs as specified in IEC 60060-1.

3.27 rated temperature category (of a capacitor)

range of temperature of the ambient air or other medium in which the capacitor is immersed during the service life and for which it has been designed

3.28 rated voltage of a capacitor

U cr RMS value of the alternating voltage assigned to the capacitor for identification and at which the capacitor is designed to operate continuously

3.29 rated voltage of circuit-breaker

U r indicates the upper limit of the highest voltage of systems for which the circuit-breaker is intended Note 1 to entry: See IEC 62271-1.

Note 2 to entry: U used in IEC 62271-1 series corresponds to Um presented in IEC 60071. r

3.30 resonance frequency

frequency for which the reactance of the intrinsic capacitance of the capacitor is equal to the reactance of the self-inductance of the capacitor

3.31 sample

device for testing Note 1 to entry: Examples of such devices are a complete small capacitor, or the housing of a grading capacitor with metal end flanges filled with impregnating fluid.

3.32 tangent of the loss angle of a capacitor

tan δ ratio between the equivalent series resistance and the capacitive reactance of a capacitor at specified sinusoidal alternating voltage and frequency [SOURCE: IEC 60050-436:1990, 436-04-11]

3.33 voltage grading factor of a circuit-breaker

F VG value that defines the standard values of rated voltages for the grading capacitor Note 1 to entry: This factor is the ratio between the actual maximum power frequency voltage fraction across one interrupter unit of a multi-break circuit-breaker and the calculated linear power frequency voltage distribution per interrupting unit.

Note 2 to entry: It is dependent on the circuit-breaker design, of the capacitance value of the grading capacitor and its tolerance and of the safety margin.

4 Abbreviated terms

TRV Transient Recovery Voltage Rated capacitance of a capacitor C r f Rated frequency of a capacitor r U Rated voltage of a capacitor cr U Rated voltage of circuit-breaker r tan δ Tangent of the loss angle of a capacitor F Voltage grading factor of a circuit-breaker VG

U Rated short-duration power frequency withstand voltage for the grading capacitor C PF U Rated short-duration power frequency withstand voltage across the open circuit- PF breaker U Rated lightning impulse withstand voltage for the grading capacitor C LI U Combined lightning and power frequency withstand voltage for the circuit-breaker (LI + PF) U Rated switching impulse withstand voltage for the grading capacitor C SI U Combined switching and power frequency withstand voltage for the circuit-breaker (SI + PF) U Chopped lightning impulse voltage for the grading capacitor C LIC RIV Radio interference voltage ESR Equivalent series resistance

5 Service conditions

5.1 General

The capacitors mentioned in this document are intended to be installed on circuit-breakers, for which the normal and special service conditions are described in IEC 62271-1. Additional service conditions specific to the capacitors are given in 5.2.3.

5.2 Normal service conditions

5.2.1 Ambient temperature

For outdoor application the normal service conditions of the grading capacitor are given in IEC 62271-1.

For an immersed capacitor, the temperature around the capacitor can be higher than the ambient air around the breaker. The preferred values of maximum surrounding temperature to be specified should be: 60 °C, 70 °C, 80 °C.

The internal operating temperature of the capacitor is higher than the maximum temperature around the capacitor and should be considered by the capacitor manufacturer.

5.2.2 Altitude

The altitude does not exceed 1 000 m.

5.2.3 Mechanical stress and vibrations

Mechanical stress and vibrations can be due to:

  • forces due to wind and ice according to IEC 62271-1;
  • forces on the terminals due to the circuit-breaker connection which value shall be defined by agreement between purchaser and capacitor manufacturer;
  • forces due to the operations consequent to vibrations, such as opening and closing, of the circuit-breaker.
5.2.4 Additional service conditions for indoor and completely immersed capacitor

The completely immersed capacitors are subjected to the following other conditions:

  • the influence of the insulating gas pressure;
  • the resistance of the capacitor materials against the decomposition products of the insulating gas.

5.3 Special service conditions

5.3.1 General

The special service conditions are given in IEC 62271-1; if they are required, the purchaser will specify it to the capacitor manufacturer.

5.3.2 Altitude correction

The coordination withstand voltages are considered valid up to an altitude of 1 000 m. To consider the reduced withstand capability of the air at an installation site with an altitude above 1 000 m, the required type test insulation withstand level of external insulation at standard reference atmospheric conditions shall be determined by multiplying the withstand voltage required on site by an altitude correction factor K . The correction factor shall not be applied a for routine tests, because a routine test validates the quality of the internal insulation only. For AC applications, the altitude correction factor shall be determined in accordance with IEC 60071-2:2023, 7.2.2, using Formula H.13 from IEC 60071-2:2023 as follows:

(H−1 000) m 8 150 K = e a where H is the altitude above sea level (in metres); m is as follows:

m = 1,0 for co-ordination lightning impulse withstand voltages; m = 1,0 for power-frequency withstand voltages in case of wet tests; m is in accordance with Figure 1 for coordination switching impulse withstand voltages. NOTE 1 To determine the value of m for the switching impulse shown in Figure 1, use the switching impulse value applicable to normal service conditions.

Figure 1 – Factor m for the switching impulse withstand test To verify the withstand voltages corrected for altitude, the arcing distance of the capacitor needs to be increased. If increasing the arcing distance is based on a verified arcing distance of a similar product, it can be considered valid without further testing. If the withstand voltages corrected for altitude cannot be validated by an increased arcing distance of a similar product, external insulation shall be tested in accordance with IEC 60071-2:2023, 8.3.7.

NOTE 2 It is considered that the altitude does not affect the internal insulation.

5.3.3 Earthquakes

For earthquake stress, the grading capacitors shall be considered as accessories of the circuitbreaker and in this way, they shall satisfy the seismic qualification rules according to IEC 62271-300.

NOTE Assuming that the mechanical stresses on circuit-breakers due to seismic activity are covered by the relevant standards, the stressing of the grading capacitor is low in comparison to transport or operation stressing.

6 Ratings

6.1 Rated voltage (U )

cr The rated voltage U of a grading capacitor is based on the following formula:

...

Contents

  • 1 Scope
  • 2 Normative references
  • 3 Terms and definitions
  • 3.1 arcing distance
  • 3.2 capacitor element
  • 3.3 capacitor losses
  • 3.4 capacitor terminals
  • 3.5 capacitance tolerance
  • 3.6 capacitor unit
  • 3.7 completely immersed capacitor
  • 3.8 creepage distance
  • 3.9 dielectric (of a capacitor)
  • 3.10 external insulation
  • 3.11 failure
  • 3.12 flashover
  • 3.13 grading capacitor
  • 3.14 indoor capacitor
  • 3.15 insulating envelope
  • 3.16 outdoor capacitor
  • 3.17 internal insulation
  • 3.18 major failure (of a grading capacitor)
  • 3.18 mechanical stress
  • 3.20 minor failure (of a grading capacitor)
  • 3.19 puncture
  • 3.20 rated capacitance of a capacitor
  • 3.21 rated chopped lightning impulse withstand voltage
  • 3.22 rated frequency of a capacitor
  • 3.23 rated insulation level
  • 3.24 rated lightning impulse withstand voltage
  • 3.25 rated short duration power frequency withstand voltage
  • 3.26 rated switching impulse withstand voltage
  • 3.27 rated temperature category (of a capacitor)
  • 3.28 rated voltage of a capacitor
  • 3.29 rated voltage of circuit-breaker
  • 3.30 resonance frequency
  • 3.31 sample
  • 3.32 tangent of the loss angle of a capacitor
  • 3.33 voltage grading factor of a circuit-breaker
  • 4 Abbreviated terms
  • 5 Normal and special Service conditions
  • 5.1 General
  • 5.2 Normal service conditions
  • 5.3 Special service conditions
  • 6 Ratings
  • 6.1 Rated voltage (U )
  • 6.2 Rated insulation level
  • 6.3 Rated frequency (f )
  • 7 Design and construction
  • 7.1 Capacitance tolerances
  • 7.2 Capacitor loss requirements
  • 7.3 Partial discharge level
  • 7.4 Angle of mounting
  • 7.5 Minimum withstand value of mechanical bending load
  • 7.6 Requirements for impregnation medium in capacitor Insulation fluids
  • 7.7 Protection against corrosion
  • 7.8 Nameplates Marking of the equipment
  • 7.9 Creepage distances for outdoor insulators capacitors
  • 8 Type tests
  • 8.1 Information for identification of specimens
  • 8.2 Information to be included in type-test reports
  • 8.3 Test conditions
  • 8.4 Dielectric type tests
  • 8.5 Voltage test at low and high temperature
  • 8.6 Radio interference voltage (RIV) test
  • 8.7 Power frequency withstand voltage test
  • 8.8 Short-circuit discharge test
  • 8.9 Resonance frequency measurements
  • 8.10 Mechanical bending test
  • 8.11 Tightness test at different temperatures
  • 8.12 Tightness test to check gas ingress from a pressurised environment
  • 8.13 Vibration test
  • 9 Routine tests
  • 9.1 General
  • 9.2 Test conditions
  • 9.3 Capacitance and tan δ (loss angle) measurement at power frequency
  • 9.4 Power frequency withstand voltage test
  • 9.5 Partial discharge test
  • 9.6 Tightness test
  • 9.7 Visual inspection and dimensional check
  • 10 Design test

1 Scope

This part of IEC 62146 is applicable to grading includes generalities of capacitors used on alternating current circuit-breakers and introduces specifications for grading capacitors. Regarding grading capacitors, their function is to control the voltage distribution across the individual interrupter units of a multi-break circuit-breaker. Grading Capacitors can also be used in parallel to the interrupter unit on single break circuitbreakers to modify the Transient Recovery Voltage (TRV). This TRV capacitor application is covered by IEC 62146-2:2023.

The grading capacitor is a sub-component for the circuit-breaker and shall be specified in accordance with the circuit-breaker specifications.

Capacitors for high-voltage alternating circuit breakers are sub-components for the circuitbreaker and are specified in accordance with the circuit-breaker specifications according to IEC 62271-1, IEC 62271-100, and if applicable to IEC 62271-203. This document applies to grading capacitors falling into one or both of the following categories for:

− mounting on air-insulated circuit-breakers.

− mounting on enclosed circuit-breakers (for example immersed in SF insulating gas, in oil,

etc.).

The testing for each of the above applications is in some cases different. The object of this document is:

− to define uniform rules regarding performances, testing and rating; − to define specific safety rules; − to provide a guidance for installation and operation.

NOTE CIGRÉ TB-368 presents a study about the operating environment of voltage grading capacitors applied to

high-voltage circuit-breakers (see [2] ).

This document does not apply to phase-to-earth capacitors installed on the circuit-breaker to modify the Transient Recovery Voltage capacitors not directly associated with high-voltage alternating current circuit-breakers.

2 Normative references

The following documents are referred to in the text in such a way that some or all of their content constitutes requirements of this document. For dated references, only the edition cited applies. For undated references, the latest edition of the referenced document (including any amendments) applies.

IEC 60050 (all parts), International electrotechnical vocabulary (available at http://www.electropedia.org) IEC 60060-1:2010, High-voltage test techniques - Part 1: General terminology and test requirements

Numbers in square brackets refer to the Bibliography.

IEC 60068-2-17:19942023, Official version in Russian – Basic Environmental testing procedures - Part 2-17: Tests - Test Q: Sealing IEC 60071-1:2006, Insulation co-ordination – Part 1: Definitions, principles and rules IEC 60071-2:2023, Insulation co-ordination - Part 2: Application guidelines IEC 60270:20002025, High-voltage test techniques - Charge-based measurement of partial discharges measurements IEC 60296, Fluids for electrotechnical applications - Mineral insulating oils for electrical equipment IEC 60376:2005, Specification of technical grade sulfur hexafluoride (SF ) for use in electrical

equipment IEC 60507-1:1991, Artificial pollution tests on high-voltage insulators to be used on a.c. systems IEC 60567:2011, Oil-filled electrical equipment - Sampling of gases and analysis of free and dissolved gases in mineral oils and other insulating liquids - Guidance IEC 60721-1:2002, Classification of environmental conditions – Part 1: Environmental parameters and their severities IEC 60815 (all parts), Selection and dimensioning of high-voltage insulators intended for use in polluted conditions IEC 60867, Insulating liquids - Specifications for unused liquids based on synthetic aromatic hydrocarbons IEC 61099, Insulating liquids - Specifications for unused synthetic organic esters for electrical purposes IEC 61462:2007, Composite hollow insulators - Pressurized and unpressurized insulators for use in electrical equipment with AC rated voltage greater than 1 000 V AC and DC voltage greater than 1 500 V – Definitions, test methods, acceptance criteria and design recommendations IEC 62146-2:2023, Capacitors for high‑voltage alternating current circuit‑breakers - Part 2: TRV capacitors IEC 62155:2003, Hollow pressurized and unpressurized ceramic and glass insulators for use in electrical equipment with rated voltages greater than 1 000 V IEC 62271-1:2007, High-voltage switchgear and controlgear - Part 1: Common specifications for alternating current switchgear and controlgear IEC 62271-100:2008, High-voltage switchgear and controlgear - Part 100: Alternating-current circuit-breakers IEC 62271-203:2003, High-voltage switchgear and controlgear - Part 203: AC gas-insulated metal-enclosed switchgear for rated voltages above 52 kV IEC 62271-205, High-voltage switchgear and controlgear - Part 205: Compact switchgear assemblies for rated voltages above 52 kV

IEC 62271-300:2006, High-voltage switchgear and controlgear - Part 300: Seismic qualification of alternating current circuit-breakers IEC 62770, Fluids for electrotechnical applications - Unused natural esters for transformers and similar electrical equipment IEC 63012, Insulating liquids - Unused modified or blended esters for electrotechnical applications IEC Guide 109, Environmental aspects – Inclusion in electrotechnical product standards CISPR 18-2:1986, Radio interference characteristics of overhead power lines and high-voltage equipment – Part 2: Methods of measurement and procedure for determining limits

3 Terms and definitions

For the purposes of this document, the following terms and definitions apply. ISO and IEC maintain terminology databases for use in standardization at the following addresses:

  • IEC Electropedia: available at https://www.electropedia.org/
  • ISO Online browsing platform: available at https://www.iso.org/obp

3.1 arcing distance

shortest distance in the air external to the insulator between the metallic parts which normally have the operating voltage between them [SOURCE: IEC 60050-471:2007, 471-01-01]

3.2 capacitor element

device consisting essentially of two electrodes separated by a dielectric [SOURCE: IEC 60050-436:1990, 436-01-03]

3.3 capacitor losses

active power dissipated in the capacitor [SOURCE: IEC 60050-436:1990, 436-04-10]

3.4 capacitor terminals

terminals intended for electrical and mechanical connection to the terminals of the interrupter units of circuit-breakers

3.5 capacitance tolerance

permissible difference between the actual capacitance and the rated capacitance under specified conditions Note 1 to entry: The actual capacitance should be measured at, or referred to, the temperature at which the rated capacitance is defined.

[SOURCE: IEC 60050-436:1990, 436-04-01, modified by addition of Note to entry.]

3.6 capacitor unit

assembly of one or more capacitor elements connected together and in the same container with terminals brought out Note 1 to entry: A common type of unit for grading capacitors has a cylindrical housing of insulating material and metal end flanges which serve as terminals.

[SOURCE: IEC 60050-436:1990, 436-01-04, modified by addition of Note to entry]

3.7 completely immersed capacitor

capacitor, both ends of which are intended to be immersed in insulating media other than ambient air (e.g. oil or gas) [SOURCE: IEC 60050-471:2007, 471-02-04, modified - definition originally referred to "bushing" instead of "capacitor".]

3.8 creepage distance

shortest distance along the surface of a solid insulating material between two conductive parts Note 1 to entry: The surface of cement or any other non-insulating jointing material is not considered as forming part of the creepage distance.

Note 2 to entry: If high-resistance coating is applied to parts of the insulating part of an insulator, such parts are considered to be effective insulating surface and the distance over them is included in the creepage distance. [SOURCE: IEC 60050-604:1987, 604-03-61, modified by addition of Notes to entry.]

3.9 dielectric (of a capacitor)

insulating material between the electrodes of the capacitor element Note 1 to entry: The major insulation generally consists of paper, plastic film, or a mixed of paper and plastic film subsequently treated and impregnated with oil or gas at atmospheric pressure or higher.

3.10 external insulation

distance in through the air and the surfaces in contact with open the air of insulation of the grading capacitor that are subjected to dielectric stresses Note 1 to entry: They are also subject to the effects of the atmospheric and other external conditions such as pollution, humidity, ice, vermin, etc.

3.11 failure

termination of the ability of an item to perform a required function Note 1 to entry: After failure the item has a fault.

Note 2 to entry: "Failure" is an event, as distinguished from "fault", which is a state. Note 3 to entry: This concept as defined does not apply to items consisting of software only. [SOURCE: IEC 60050-191:1990, 191-04-01]

3.12 flashover

electric breakdown between conductors in a gas or in a liquid or in a vacuum, at least partly along the surface of solid insulation

[SOURCE: IEC 60050-212:2012, 212-11-47]

3.13 grading capacitor

capacitor for installation on high-voltage circuit-breakers to control the voltage distribution across the individual interrupter unit Note 1 to entry: The grading capacitors alone are accessories of the circuit-breaker.

3.14 indoor capacitor

capacitor, both ends of which are intended to be in ambient air at atmospheric pressure but not exposed to outdoor atmospheric conditions [SOURCE: IEC 60050-471:2007, 471-02-05, modified - definition originally referred to "bushing" instead of "capacitor".]

3.15 insulating envelope

insulator which is open from end to end, with or without sheds, including end fittings Note 1 to entry: An insulating envelope can be made from one or more permanently assembled insulating elements. Note 2 to entry: The insulating envelope may be in ceramic, glass or analogous inorganic material, cast or moulded resin, composite insulating material, in one piece or more pieces permanently assembled. [SOURCE: IEC 60050-471:2007, 471-01-08, modified - definition originally referred to a hollow insulator and Note 2 to entry has been added.]

3.16 outdoor capacitor

capacitor, both ends of which are intended to be in ambient air at atmospheric pressure, and exposed to outdoor atmospheric conditions [SOURCE: IEC 60050-471:2007, 471-02-07, modified - definition originally referred to "bushing" instead of "capacitor".]

3.17 internal insulation

internal solid, liquid or gaseous parts of the insulation of the grading capacitor which are protected from the effects of atmospheric conditions Note 1 to entry: The parts are also protected from other external conditions such as pollution, humidity, ice, vermin, etc.

3.18 major failure (of a grading capacitor)

failure of a grading capacitor which causes the cessation of its fundamental function. Note 1 to entry: A major failure will result in a mandatory removal from service within 30 min for unscheduled maintenance.

3.18 mechanical stress

any mechanical stress applied to the insulating envelope and to the terminals of the grading capacitor Note 1 to entry: It is a function of the following main forces:

− forces on the terminals due to the circuit-breaker connection; − forces due to the wind and ice;

− seismic forces; − forces due to the operating conditions, opening and closing, of the circuit- breaker; − thermal forces due to the ambient medium conditions; − forces due to the transportation of the circuit-breaker or grading capacitors.

3.20 minor failure (of a grading capacitor)

any failure of a grading capacitor which does not cause a major failure of the grading capacitor

3.19 puncture

disruptive discharge occurring through a solid insulation material, producing a path of permanent damage Note 1 to entry: The term puncture is also used as a synonym for electrical breakdown in solids. [SOURCE: IEC 60050-212:2010, 212-11-49]

3.20 rated capacitance of a capacitor

C r capacitance value for which the capacitor has been designed

3.21 rated chopped lightning impulse withstand voltage

required peak value of the chopped lightning impulse withstand voltage which characterises the insulation of a grading capacitor as regards the withstand tests Note 1 to entry: The definitions and the standard parameters applicable to chopped impulses are specified in IEC 60060-1.

3.22 rated frequency of a capacitor

f r frequency for which the capacitor has been designed [SOURCE: IEC 60050-436:1990, 436-01-14, modified by addition of symbol.]

3.23 rated insulation level

test voltages, under specified conditions, that the insulation is designed to withstand Note 1 to entry: These test voltages can be for instance:

a) rated chopped and lightning impulse and short duration power frequency withstand voltages for capacitors installed on circuit-breaker with rated voltage lower than 300 kV. b) rated switching, lightning, chopped impulse and short duration power frequency withstand voltages for capacitors installed on circuit-breaker with rated voltage equal to or greater than 300 kV. Note 2 to entry: The rated insulation levels of the grading capacitor should be equal to or higher than the relevant requirements for the circuit-breaker interrupting unit.

[SOURCE: IEC 60050-421:1990, 421-09-02, modified Note to entry]

3.24 rated lightning impulse withstand voltage

U C LI required peak value of the lightning impulse withstand voltage which characterises the insulation of an equipment as regards the withstand tests

Note 1 to entry: The standard lightning impulse has a front time of 1,2 µs and a time-to-half-value of 50 µs as specified in IEC 60060-1.

3.25 rated short duration power frequency withstand voltage

U C PF required RMS value of sinusoidal power frequency voltage that the equipment withstands during tests made under specified conditions and for a duration of 1 min unless otherwise specified

3.26 rated switching impulse withstand voltage

U C SI required peak value of the switching impulse withstand voltage which characterises the insulation of an equipment as regards the withstand tests Note 1 to entry: The standard switching impulse has a time-to-crest of 250 µs and a time-to-half-value of 2 500 µs as specified in IEC 60060-1.

3.27 rated temperature category (of a capacitor)

range of temperature of the ambient air or other medium in which the capacitor is immersed during the service life and for which it has been designed

3.28 rated voltage of a capacitor

U cr RMS value of the alternating voltage assigned to the capacitor for identification and at which the capacitor is designed to operate continuously

3.29 rated voltage of circuit-breaker

U r indicates the upper limit of the highest voltage of systems for which the circuit-breaker is intended Note 1 to entry: See IEC 62271-1.

Note 2 to entry: U used in IEC 62271-1 series corresponds to Um presented in IEC 60071. r

3.30 resonance frequency

frequency for which the reactance of the intrinsic capacitance of the capacitor is equal to the reactance of the self-inductance of the capacitor

3.31 sample

device for testing Note 1 to entry: Examples of such devices are a complete small capacitor, or the housing of a grading capacitor with metal end flanges filled with impregnating fluid.

3.32 tangent of the loss angle of a capacitor

tan δ ratio between the equivalent series resistance and the capacitive reactance of a capacitor at specified sinusoidal alternating voltage and frequency [SOURCE: IEC 60050-436:1990, 436-04-11]

3.33 voltage grading factor of a circuit-breaker

F VG value that defines the standard values of rated voltages for the grading capacitor Note 1 to entry: This factor is the ratio between the actual maximum power frequency voltage fraction across one interrupter unit of a multi-break circuit-breaker and the calculated linear power frequency voltage distribution per interrupting unit.

Note 2 to entry: It is dependent on the circuit-breaker design, of the capacitance value of the grading capacitor and its tolerance and of the safety margin.

4 Abbreviated terms

TRV Transient Recovery Voltage Rated capacitance of a capacitor C r f Rated frequency of a capacitor r U Rated voltage of a capacitor cr U Rated voltage of circuit-breaker r tan δ Tangent of the loss angle of a capacitor F Voltage grading factor of a circuit-breaker VG U Rated short-duration power frequency withstand voltage for the grading C PF capacitor U Rated short-duration power frequency withstand voltage across the open PF circuit-breaker U U Rated lightning impulse withstand voltage for the grading capacitor CLIWL C LI U Combined lightning and power frequency withstand voltage for the circuit- (LIWL LI + PF) breaker U U Rated switching impulse withstand voltage for the grading capacitor CSIWL C SI U Combined switching and power frequency withstand voltage for the circuit- (SIWL SI + PF) breaker U U Chopped lightning impulse voltage for the grading capacitor CCHOPPED C LIC BIL Bushings insulated level SIL Standard insulation level RIV Radio interference voltage ESR Equivalent series resistance

5 Normal and special Service conditions

5.1 General

The grading capacitors mentioned in this document are intended to be installed on circuitbreakers, for which the normal and special service conditions are described in IEC 62271-1. Additional service conditions specific to the capacitors are given in 5.2.3.

5.2 Normal service conditions

5.2.1 Ambient temperature

For outdoor application the normal service conditions of the grading capacitor are given in IEC 62271-1.

For an immersed capacitor, the temperature around the capacitor can be higher than the ambient air around the breaker. The preferred values of maximum surrounding temperature to be specified should be: 60 °C, 70 °C, 80 °C.

The internal operating temperature of the capacitor is higher than the maximum temperature around the capacitor and should be considered by the capacitor manufacturer.

5.2.2 Altitude

The altitude does not exceed 1 000 m.

5.2.3 Mechanical stress and vibrations

Mechanical stress and vibrations can be due to:

  • forces due to wind and ice according to IEC 62271-1;
  • forces on the terminals due to the circuit-breaker connection which value shall be defined by agreement between purchaser and capacitor manufacturer;
  • forces due to the operations consequent to vibrations, such as opening and closing, of the circuit-breaker.

Vibrations due to earthquakes are not considered for normal service conditions.

5.2.4 Additional service conditions for indoor and completely immersed grading

capacitor The completely immersed grading capacitors are subjected to the following other conditions:

  • the influence of SF the insulating gas pressure;
  • the resistance of the capacitor materials against the decomposition products of SF the

insulating gas.

5.3 Special service conditions

5.3.1 General

The special service conditions are given in IEC 62271-1; if they are required, the purchaser will specify it to the capacitor manufacturer.

5.3.2 Altitude correction

The coordination withstand voltages are considered valid up to an altitude of 1 000 m. To consider the reduced withstand capability of the air at an installation site with an altitude above 1 000 m, the required type test insulation withstand level of external insulation at standard reference atmospheric conditions shall be determined by multiplying the withstand voltage required on site by an altitude correction factor K . The correction factor shall not be applied a for routine tests, because a routine test validates the quality of the internal insulation only.

...

Contents

  • 1 Domaine d’application
  • 2 Références normatives
  • 3 Termes et définitions
  • 3.1 distance d’arc
  • 3.2 élément de condensateur
  • 3.3 pertes d’un condensateur
  • 3.4 bornes de condensateur
  • 3.5 tolérance de capacité
  • 3.6 unité de condensateur
  • 3.7 condensateur immergé totalement
  • 3.8 ligne de fuite
  • 3.9 diélectrique (d’un condensateur)
  • 3.10 isolation externe
  • 3.11 défaillance
  • 3.12 contournement
  • 3.13 condensateur de répartition
  • 3.14 condensateur d'intérieur
  • 3.15 enveloppe isolante
  • 3.16 condensateur d'extérieur
  • 3.17 isolation interne
  • 3.18 contrainte mécanique
  • 3.19 perforation
  • 3.20 capacité assignée d'un condensateur
  • 3.21 tension de tenue coupée assignée aux chocs de foudre
  • 3.22 fréquence assignée d'un condensateur
  • 3.23 niveau d’isolement assigné
  • 3.24 tension de tenue assignée aux chocs de foudre
  • 3.25 tension de tenue assignée de courte durée à fréquence industrielle
  • 3.26 tension de tenue assignée aux chocs de manœuvre
  • 3.27 catégorie de température assignée (d'un condensateur)
  • 3.28 tension assignée d'un condensateur
  • 3.29 tension assignée d'un disjoncteur
  • 3.30 fréquence de résonance
  • 3.31 échantillon
  • 3.32 tangente de l'angle de perte d'un condensateur
  • 3.33 facteur de répartition de la tension d'un disjoncteur
  • 4 Abréviations
  • 5 Conditions de service
  • 5.1 Généralités
  • 5.2 Conditions normales de service
  • 5.3 Conditions spéciales de service
  • 6 Caractéristiques assignées
  • 6.1 Tension assignée (U )
  • 6.2 Niveau d’isolement assigné
  • 6.3 Fréquence assignée (f )
  • 7 Conception et construction
  • 7.1 Tolérances de capacité
  • 7.2 Exigences concernant les pertes d’un condensateur
  • 7.3 Niveau de décharges partielles
  • 7.4 Angle d’installation
  • 7.5 Valeur de tenue minimale de la charge de flexion mécanique
  • 7.6 Fluides isolants
  • 7.7 Protection contre la corrosion
  • 7.8 Marquage du matériel
  • 7.9 Lignes de fuite pour les condensateurs d’extérieur
  • 8 Essais de type
  • 8.1 Informations pour l’identification des éprouvettes
  • 8.2 Informations à inclure dans les rapports d’essai de type
  • 8.3 Conditions d’essai
  • 8.4 Essais de type diélectriques
  • 8.5 Essai de tension à basse et haute températures
  • 8.6 Essais de tension de perturbation radioélectrique (RIV)
  • 8.7 Essai de tension de tenue à fréquence industrielle
  • 8.8 Essai de décharge en court-circuit
  • 8.9 Mesurages de la fréquence de résonance
  • 8.10 Essai de flexion mécanique
  • 8.11 Essai d’étanchéité à des températures différentes
  • 8.12 Essai d'étanchéité permettant de vérifier la pénétration de gaz
  • 8.13 Essai de vibrations
  • 9 Essais individuels de série
  • 9.1 Généralités
  • 9.2 Conditions d’essai
  • 9.3 Mesurage de la capacité et de tan δ (angle de perte) à fréquence industrielle
  • 9.4 Essai de tension de tenue à fréquence industrielle
  • 9.5 Essai de décharges partielles
  • 9.6 Essai d’étanchéité
  • 9.7 Inspection visuelle et vérification dimensionnelle
  • 10 Essai de conception
  • 10.1 Essai de vieillissement
  • 11.1 Généralités

1 Domaine d’application

La présente partie de l’IEC 62146 expose des généralités concernant les condensateurs utilisés sur les disjoncteurs à courant alternatif et présente des spécifications relatives aux condensateurs de répartition. Les condensateurs de répartition ont pour fonction de contrôler la répartition de la tension entre chaque interrupteur d'un disjoncteur à coupure multiple.

Les condensateurs peuvent également être utilisés parallèlement à l'interrupteur de disjoncteurs à coupure unique afin de modifier la tension transitoire de rétablissement (TTR). Cette application des condensateurs TTR est couverte par l’IEC 62146-2:2023. Les condensateurs pour disjoncteurs à courant alternatif haute tension sont des sous-composants du disjoncteur et sont spécifiés conformément aux spécifications des disjoncteurs de l’IEC 62271-1, l’IEC 62271-100 et, le cas échéant, l’IEC 62271-203. Le présent document s'applique aux condensateurs de répartition relevant de l'une des catégories suivantes, ou des deux:

− condensateurs montés sur des disjoncteurs isolés dans l’air; − condensateurs montés sur des disjoncteurs protégés (par exemple, immergés dans du gaz isolant, dans l'huile, etc.).

L'essai applicable à chacune des applications susmentionnées est différent dans certains cas. Le présent document a pour objet:

− de définir des règles uniformes concernant les performances, les essais et les caractéristiques assignées; − de définir des règles de sécurité spécifiques; − de fournir des recommandations pour l’installation et le fonctionnement. NOTE Le document CIGRÉ TB-368 présente une étude sur l'environnement de fonctionnement des condensateurs

de répartition de la tension dans les applications de disjoncteurs à haute tension (voir [2] ). Le présent document ne s’applique pas aux condensateurs qui ne sont pas directement associés aux disjoncteurs à courant alternatif haute tension.

2 Références normatives

Les documents suivants sont cités dans le texte de sorte qu’ils constituent, pour tout ou partie de leur contenu, des exigences du présent document. Pour les références datées, seule l’édition citée s’applique. Pour les références non datées, la dernière édition du document de référence s’applique (y compris les éventuels amendements). IEC 60060-1, Technique des essais à haute tension - Partie 1: Terminologie générale et exigences d’essai IEC 60068-2-17:2023, Essais d’environnement - Partie 2-17: Essais - Essai Q: Étanchéité IEC 60071-2:2023, Coordination de l’isolement - Partie 2: Lignes directrices en matière d'application

Les chiffres entre crochets renvoient à la Bibliographie.

IEC 60270:2025, Techniques des essais à haute tension - Mesurages des décharges partielles fondés sur les charges IEC 60296, Fluides pour applications électrotechniques - Huiles minérales isolantes pour matériel électrique IEC 60567,Matériels électriques immergés - Échantillonnage de gaz libres et analyse des gaz libres et dissous dans les huiles minérales et d’autres liquides isolants - Recommandations IEC 60815 (toutes les parties), Selection and dimensioning of high-voltage insulators intended for use in polluted conditions (disponible en anglais seulement) IEC 60867, Isolants liquides - Spécifications pour les liquides neufs à base d'hydrocarbures aromatiques de synthèse IEC 61099, Liquides isolants - Spécifications relatives aux esters organiques de synthèse neufs destinés aux matériels électriques IEC 61462, Isolateurs composites creux - Isolateurs avec ou sans pression interne pour utilisation dans des appareillages électriques de tensions alternatives assignées supérieures à 1 000 V et de tensions continues supérieures à 1 500 V - Définitions, méthodes d’essai, critères d’acceptation et recommandations de conception IEC 62146-2:2023, Condensateurs pour disjoncteurs à courant alternatif haute tension - Partie 2: Condensateurs TTR IEC 62155:2003, Isolateurs creux avec ou sans pression interne, en matière céramique ou en verre, pour utilisation dans des appareillages électriques prévus pour des tensions nominales supérieures à 1 000 V IEC 62271-1, Appareillage à haute tension - Partie 1: Spécifications communes pour appareillage à courant alternatif IEC 62271-100, Appareillage à haute tension - Partie 100: Disjoncteurs à courant alternatif IEC 62271-203, Appareillage à haute tension - Partie 203: Appareillage sous enveloppe métallique à isolation gazeuse et à courant alternatif de tensions assignées supérieures à 52 kV IEC 62271-205, Appareillage à haute tension - Partie 205: Ensembles d’appareillages compacts de tensions assignées supérieures à 52 kV IEC 62271-300, Appareillage à haute tension - Partie 300: Qualification sismique des disjoncteurs à courant alternatif IEC 62770, Fluides pour applications électrotechniques - Esters naturels neufs pour transformateurs et matériels électriques analogues IEC 63012, Isolants liquides - Esters neufs modifiés ou mélangés pour applications électrotechniques

3 Termes et définitions

Pour les besoins du présent document, les termes et définitions suivants s’appliquent. L’ISO et l’IEC tiennent à jour des bases de données terminologiques destinées à être utilisées en normalisation, consultables aux adresses suivantes:

  • IEC Electropedia: disponible à l’adresse https://www.electropedia.org/
  • ISO Online browsing platform: disponible à l’adresse https://www.iso.org/obp

3.1 distance d’arc

plus courte distance dans l’air à l’extérieur de l’isolateur entre les parties métalliques sur lesquelles on applique normalement la tension de service [SOURCE: IEC 60050-471:2007, 471-01-01]

3.2 élément de condensateur

dispositif constitué essentiellement par deux électrodes séparées par un diélectrique [SOURCE: IEC 60050-436:1990, 436-01-03]

3.3 pertes d’un condensateur

puissance active dissipée dans le condensateur [SOURCE: IEC 60050-436:1990, 436-04-10]

3.4 bornes de condensateur

bornes destinées à être connectées électriquement et mécaniquement aux bornes des interrupteurs des disjoncteurs

3.5 tolérance de capacité

différence admise entre la valeur réelle de la capacité et la valeur assignée dans des conditions spécifiées Note 1 à l’article: Il convient de mesurer la capacité réelle à, ou en référence à, la température à laquelle la capacité assignée est définie.

[SOURCE: IEC 60050-436:1990, 436-04-01, modifié par l'ajout de la Note 1 à l'article]

3.6 unité de condensateur

ensemble d’un ou plusieurs éléments de condensateurs placés dans une même enveloppe et reliés à des bornes de sortie Note 1 à l’article: Un type courant d'unité de condensateurs de répartition comprend un boîtier cylindrique en matériau isolant et des talons d'extrémité métalliques servant de bornes. [SOURCE: IEC 60050-436:1990, 436-01-04, modifié par l'ajout de la Note 1 à l'article]

3.7 condensateur immergé totalement

condensateur dont les deux extrémités sont destinées à l’immersion dans des milieux isolants autres que l'air (par exemple huile ou gaz) [SOURCE: IEC 60050-471:2007, 471-02-04, modifié - La définition faisait initialement référence à des "traversées" en lieu et place des "condensateurs"]

3.8 ligne de fuite

distance la plus courte, le long de la surface d’un isolant solide, entre deux parties conductrices Note 1 à l’article: La surface du ciment ou de toute autre matière de scellement non isolante n’est pas considérée comme faisant partie de la ligne de fuite.

Note 2 à l’article: Si un revêtement à haute résistance est appliqué sur certaines parties isolantes d’un isolateur, ces parties sont considérées comme surfaces isolantes effectives et la distance mesurée à la surface de ces parties est incluse dans la ligne de fuite.

[SOURCE: IEC 60050-604:1987, 604-03-61, modifié par l'ajout des Notes 1 et 2 à l'article]

3.9 diélectrique (d’un condensateur)

matériau isolant entre les électrodes de l'élément de condensateur Note 1 à l’article: La principale isolation est généralement constituée de papier, d’un film en matière plastique ou d’un mélange de papier et de film en matière plastique qui est ensuite traité et imprégné d’huile ou de gaz à pression atmosphérique ou supérieure.

3.10 isolation externe

distance dans l'air et sur les surfaces du condensateur de répartition en contact avec l'air, qui sont soumises aux contraintes diélectriques Note 1 à l’article: Elles sont également soumises à l'influence des conditions atmosphériques ou d'autres conditions externes telles que la pollution, l'humidité, la glace, les animaux, etc.

3.11 défaillance

cessation de l’aptitude d’une entité à accomplir une fonction exigée Note 1 à l’article: Après une défaillance, l’appareil présente une panne. Note 2 à l’article: Une défaillance est un passage d’un état à un autre, par opposition à une panne, qui est un état. Note 3 à l’article: La notion de défaillance, telle qu’elle est définie, ne s’applique pas à une entité constituée seulement de logiciel.

[SOURCE: IEC 60050-191:1990, 191-04-01]

3.12 contournement

claquage électrique entre des conducteurs dans un gaz, un liquide ou le vide, au moins en partie le long de la surface d'une isolation solide [SOURCE: IEC 60050-212:2012, 212-11-47]

3.13 condensateur de répartition

condensateur destiné à être installé sur des disjoncteurs haute tension afin de contrôler la répartition de la tension sur chaque interrupteur Note 1 à l’article: Les condensateurs de répartition seuls constituent des accessoires du disjoncteur.

3.14 condensateur d'intérieur

condensateur dont les deux extrémités sont destinées à être dans l'air ambiant à la pression atmosphérique mais non soumises aux conditions atmosphériques extérieures [SOURCE: IEC 60050-471:2007, 471-02-05, modifié - La définition faisait initialement référence à des "traversées" en lieu et place des "condensateurs"]

3.15 enveloppe isolante

isolateur creux, ouvert de part en part, équipé ou non d’ailettes, incluant les armatures d’extrémité Note 1 à l’article: Une enveloppe isolante peut être constituée d’un ou plusieurs éléments d’isolateurs assemblés d’une façon permanente.

Note 2 à l’article: L'enveloppe isolante peut être constituée d'un matériau céramique, de verre ou d'un matériau inorganique analogue, de résine coulée ou moulée, d'un matériau isolant composite, en une ou plusieurs pièces assemblées d'une façon permanente.

[SOURCE: IEC 60050-471:2007, 471-01-08, modifié - La définition faisait initialement référence à un "isolateur creux" et une Note 2 à l’article a été ajoutée]

3.16 condensateur d'extérieur

condensateur dont les deux extrémités sont destinées à être dans l'air ambiant à la pression atmosphérique et soumises aux conditions atmosphériques extérieures [SOURCE: IEC 60050-471:2007, 471-02-07, modifié - La définition faisait initialement référence à des "traversées" en lieu et place des "condensateurs"]

3.17 isolation interne

éléments internes solides, liquides ou gazeux de l'isolation du condensateur de répartition qui sont à l'abri de l'influence des conditions atmosphériques Note 1 à l’article: Ces éléments sont également à l’abri de l’influence d’autres conditions externes telles que la pollution, l’humidité, la glace, les animaux, etc.

3.18 contrainte mécanique

toute contrainte mécanique appliquée à l'enveloppe isolante et aux bornes du condensateur Note 1 à l’article: La contrainte mécanique est fonction des principales forces suivantes:

− les forces exercées sur les bornes produites par la connexion du disjoncteur; − les forces produites par le vent et la glace; − les forces sismiques; − les forces produites par les conditions de fonctionnement, à savoir ouverture et fermeture, du disjoncteur; − les forces thermiques produites par les conditions ambiantes; − les forces produites par le transport du disjoncteur ou des condensateurs.

3.19 perforation

décharge disruptive se produisant à travers un matériau d’isolation solide, créant un chemin de destruction permanente Note 1 à l’article: Ce terme est aussi utilisé comme synonyme de claquage électrique dans les solides. [SOURCE: IEC 60050-212:2010, 212-11-49]

3.20 capacité assignée d'un condensateur

C r valeur de la capacité pour laquelle le condensateur a été conçu

3.21 tension de tenue coupée assignée aux chocs de foudre

valeur de crête exigée de la tension de tenue coupée aux chocs de foudre qui caractérise l'isolation d'un condensateur eu égard aux essais de tenue Note 1 à l’article: Les définitions et les paramètres normalisés applicables aux chocs coupés sont spécifiés dans l’IEC 60060-1.

3.22 fréquence assignée d'un condensateur

f r fréquence pour laquelle le condensateur a été conçu [SOURCE: IEC 60050-436:1990, 436-01-14, modifié par l'ajout du symbole]

3.23 niveau d’isolement assigné

tensions d'essai que l'isolation doit pouvoir supporter dans des conditions spécifiées Note 1 à l’article: Ces tensions d'essai peuvent être par exemple:

a) des tensions de tenue coupées assignées aux chocs de foudre et des tensions de tenue de courte durée à fréquence industrielle pour les condensateurs installés sur un disjoncteur de tension assignée inférieure à 300 kV; b) des tensions de tenue assignées aux chocs de manœuvre et aux chocs de foudre, des tensions de tenue aux chocs coupés et des tensions de tenue de courte durée à fréquence industrielle pour les condensateurs installés sur un disjoncteur de tension assignée supérieure ou égale à 300 kV. Note 2 à l’article: Il convient que les niveaux d'isolement assignés du condensateur soient supérieurs ou égaux aux exigences pertinentes concernant l'interrupteur du disjoncteur. [SOURCE: IEC 60050-421:1990, 421-09-02 - Les notes à l’article ont été modifiées]

3.24 tension de tenue assignée aux chocs de foudre

U C LI valeur de crête exigée de la tension de tenue aux chocs de foudre qui caractérise l'isolation d'un matériel eu égard aux essais de tenue Note 1 à l’article: La tension de choc de foudre normalisée a un temps de montée de 1,2 µs et une durée jusqu’à la mi-valeur de 50 µs comme spécifié dans l’IEC 60060-1.

3.25 tension de tenue assignée de courte durée à fréquence industrielle

U C PF valeur efficace exigée de la tension sinusoïdale à fréquence industrielle à laquelle le matériel peut résister au cours des essais réalisés dans des conditions spécifiées et pendant une durée de 1 min sauf spécification contraire

3.26 tension de tenue assignée aux chocs de manœuvre

U C SI valeur de crête exigée de la tension de tenue aux chocs de manœuvre qui caractérise l'isolation d'un matériel eu égard aux essais de tenue Note 1 à l’article: La tension de choc de manœuvre normalisée a une durée jusqu’à la crête de 250 µs et une durée jusqu’à la mi-valeur 2 500 µs comme spécifié dans l’IEC 60060-1.

3.27 catégorie de température assignée (d'un condensateur)

plage de température de l'air ambiant ou d'un autre milieu dans lequel le condensateur est immergé pendant la durée de vie en service et pour laquelle il a été conçu

3.28 tension assignée d'un condensateur

U cr valeur efficace de la tension alternative attribuée au condensateur pour identification et à laquelle ce dernier est conçu pour fonctionner de manière continue

3.29 tension assignée d'un disjoncteur

U r indique la limite supérieure de la tension maximale des systèmes pour lesquels le disjoncteur est destiné Note 1 à l’article: Voir l’IEC 62271-1.

Note 2 à l’article: U utilisée dans la série IEC 62271-1 correspond à la valeur Um présentée dans l’IEC 60071. r

3.30 fréquence de résonance

fréquence pour laquelle la réactance de la capacité intrinsèque du condensateur est égale à la réactance de l'inductance propre du condensateur

3.31 échantillon

dispositif pour essai Note 1 à l’article: Un condensateur complet de petite dimension ou le boîtier d'un condensateur de répartition avec des talons d'extrémité métalliques remplis de fluide d'imprégnation constituent des exemples de ce type de dispositifs.

3.32 tangente de l'angle de perte d'un condensateur

tan δ rapport entre la résistance-série équivalente et la réactance capacitive du condensateur dans des conditions spécifiées de fréquence et de tension alternative sinusoïdale [SOURCE: IEC 60050-436:1990, 436-04-11]

3.33 facteur de répartition de la tension d'un disjoncteur

F VG valeur qui définit les valeurs normalisées des tensions assignées du condensateur de répartition Note 1 à l’article: Ce facteur est le rapport entre la fraction réelle de tension maximale à fréquence industrielle aux bornes d’un interrupteur d'un disjoncteur à coupure multiple et la répartition calculée linéairement de la tension à fréquence industrielle par interrupteur.

Note 2 à l’article: Ce facteur dépend de la conception du disjoncteur, de la valeur de capacité du condensateur de répartition et sa tolérance, ainsi que de la marge de sécurité.

4 Abréviations

TTR Tension Transitoire de Rétablissement C Capacité assignée d'un condensateur r f Fréquence assignée d'un condensateur r U Tension assignée d'un condensateur cr U Tension assignée d’un disjoncteur r tan δ Tangente de l'angle de perte d'un condensateur F Facteur de répartition de la tension d'un disjoncteur VG U Tension assignée de tenue de courte durée à fréquence industrielle pour C PF le condensateur de répartition U Tension assignée de tenue de courte durée à fréquence industrielle aux bornes PF du disjoncteur ouvert U Tension de tenue assignée aux chocs de foudre pour le condensateur de répartition C LI U Tension combinée de tenue aux chocs de foudre et à fréquence industrielle (LI + PF) pour le disjoncteur U Tension de tenue assignée aux chocs de manœuvre pour le condensateur C SI de répartition U Tension combinée de tenue aux chocs de manœuvre et à fréquence industrielle (SI + PF) pour le disjoncteur U Tension de tenue aux chocs de foudre coupés pour le condensateur de répartition C LIC RIV Tension de perturbation radioélectrique RSE Résistance-Série Équivalente

5 Conditions de service

5.1 Généralités

Les condensateurs mentionnés dans le présent document sont destinés à être installés sur des disjoncteurs, pour lesquels les conditions normales et spéciales de service sont décrites dans l’IEC 62271-1.

Les conditions de service supplémentaires spécifiques aux condensateurs sont définies en 5.2.3.

5.2 Conditions normales de service

5.2.1 Température ambiante

Pour une application en extérieur, les conditions normales de service du condensateur de répartition sont données dans l’IEC 62271-1.

Pour un condensateur immergé, la température environnante du condensateur peut être supérieure à l'air ambiant autour du disjoncteur. Il convient que les valeurs préférentielles de la température environnante maximale à spécifier soient les suivantes: 60 °C, 70 °C, 80 °C. La température de fonctionnement interne du condensateur est supérieure à la température maximale environnante du condensateur et il convient qu’elle soit prise en compte par le constructeur du condensateur.

5.2.2 Altitude

L’altitude ne dépasse pas 1 000 m.

5.2.3 Contraintes et vibrations mécaniques

Les contraintes et vibrations mécaniques peuvent être engendrées par:

  • les forces produites par l'action du vent et de la glace selon l’IEC 62271-1;
  • les forces exercées sur les bornes produites par la connexion des disjoncteurs dont la valeur doit être définie par accord entre l'acheteur et le constructeur du condensateur;
  • les forces produites par les opérations conséquentes aux vibrations, à savoir ouverture et fermeture, du disjoncteur.
5.2.4 Conditions de service supplémentaires pour un condensateur utilisé en

intérieur et immergé totalement Les condensateurs immergés totalement sont soumis aux autres conditions suivantes:

  • l'influence de la pression du gaz isolant;
  • la résistance des matériaux constitutifs du condensateur aux produits de décomposition du gaz isolant.

...