Abstract

This document applies to switching device for islanding, hereafter referred to as SDFI, for household and similar uses, primarily intended to be used for energy efficiency (EE) purposes with local production or local storage of energy, or with both.
SDFI are intended to be installed in low voltage prosumer electrical installations (PEI) able to operate in island mode as defined in IEC 60364-8-82, so called islandable PEI.
SDFI are used to disconnect the PEI from the grid to allow operating the PEI in island mode and further reconnect the PEI to the grid.
They are intended to be used in islandable PEI which operate:
– in connected mode (direct feeding mode or reverse feeding mode), and
– in island mode,
as defined in IEC 60364-8-82.
NOTE 1 See definitions 3.10 and 3.13 of island mode and for connected mode respectively.
NOTE 2 Switching of a PEI to island mode can be subject to local regulations (grid codes) or to specific agreement with system operators. Reverse feeding is also usually subject to local regulations (grid codes). SDFI are part of the electrical installation.
This document applies to SDFI for operation in AC single or multiphase main circuits with rated voltages not exceeding 440 V AC, frequencies of 50 Hz, 60 Hz or 50/60 Hz. They are intended to be used in installations with prospective short circuit currents not exceeding 25 000 A.
NOTE 3 DC operations are not covered by this edition and are kept under consideration for a future revision of this document.
The SDFI is composed at least of one switching unit (SU) and a control unit (CU) to monitor its switching operations from grid connected to island mode and reverse wise.
The SDFI can be provided with a communication interface for exchange with external systems such as the Customer Energy Manager (CEM) defined in IEC 63402 series.
According to the intended use, the SDFI can be interlocked with a system referencing conductor switching device (SRCSD) according to IEC 63445 or it can be integrated with a SRCSD in a single unit.
NOTE 4 According to its intended use, the SDFI can also be used as an interface switch with the interface protection (integrated or not). See 3.19 and 3.20.
SDFI are intended for use in circuits where protection against electrical shock and overcurrent is provided according to installation rules for low voltage electrical installations, unless the SDFI already contains such protective function. SDFI are not requested to provide isolation function and overcurrent protection according to IEC 60364-8-82. However, the isolation function can be provided by a SDFI fulfilling the requirements of the relevant product standards.
SDFI are installed by instructed persons (IEC 60050-195:2021, 195-04-02) or skilled persons (IEC 60050-195:2021, 195-04-01). They are intended to be used by ordinary persons (IEC 60005-195:2021, 195-04-03) and do not require maintenance.
It is important to note that the main overcurrent protective device of installations cannot be used as a SDFI in single dwellings or similar islandable PEI (see Clause D.5 of IEC 60364-8-82:2022)

Status
Published
Publication Date
20-Aug-2026
Current Stage
6060 - Document made available - Publishing
Start Date
21-Aug-2026
Due Date
31-Dec-2025
Completion Date
31-Dec-2025

Buy Documents

Standard

EN IEC 63552:2026 - BARVE

English language (35 pages)
Preview
Preview
e-Library read for
×1 day

EN IEC 63552:2026 is a CENELEC/IEC standard for the Switching Device for islanding (SDFI) used in low-voltage prosumer electrical installations (PEI). It specifies the functions, construction features, markings, operating conditions, and type tests for devices that disconnect a PEI from the grid so it can run in island mode and then reconnect it again. The document is aimed at manufacturers, installers, test labs, and designers working with household and similar installations that use local generation and/or storage.

What does EN IEC 63552:2026 specify?

EN IEC 63552:2026 applies to SDFI for household and similar uses, mainly where energy efficiency is supported by local production and/or storage of energy. It covers AC single- or multiphase main circuits up to 440 V AC and prospective short-circuit currents up to 25 000 A.

The standard places the SDFI in the context of islandable PEI, where the device disconnects the installation from the distribution network for island mode and later reconnects it. It is part of the electrical installation, may work with a Customer Energy Manager (CEM), and may be integrated with a System referencing conductor switching device (SRCSD).

The document is organized into:

  • Scope, normative references, terms and definitions
  • Classification
  • Characteristics
  • Markings and product information
  • Standard conditions for operation in service
  • Construction and operation requirements
  • Type tests
  • Bibliography

What are the key requirements of EN IEC 63552:2026?

EN IEC 63552:2026 is built around the idea that the SDFI must switch the PEI safely between grid-connected and islanded operation, while keeping the sequence under control. The most important requirements are in clauses 4 to 9.

Classification matters because the device must match the installation

Clause 4 classifies an SDFI by construction, integration with the SRCSD, method of operation, kind of current, number of poles, interlocking means, reclosing mode, islanding means, suitability for isolation, and type of local sources. In practice, this means the manufacturer and buyer need to define the exact variant before selection, testing, and installation.

Clause 4.2 links the switching unit to existing product standards for switches and circuit-breakers. That matters because much of the switching-unit performance is already governed by the underlying device standard.

The control functions must support the intended islanding behavior

Clause 5 states that the control unit and auxiliary circuits are covered by IEC 62991:2022 clause 5.4, with additional characteristics for voltage and frequency deviation limits and any control-circuit ratings. It also requires the declared maximum number of operating cycles.

The preferred operating-cycle values are listed in clause 5, with 4 000 as the requested minimum. For buyers, that figure helps compare endurance and service-life expectations.

Markings and product information must support correct installation

Clause 6 requires identification and documentation based on the classification and Table 1. The required information includes the manufacturer identification, type designation, reference to the product standard, construction method, integration method, operating method, number of poles, reclosing mode, islanding means, suitability for isolation, local-source suitability, ratings, wiring diagram, terminal information, and control-circuit supply data.

This matters in practice because the installer must know how to wire, configure, and commission the SDFI correctly. Markings must also be legible, durable, and indelible.

The device has to work in standard service conditions

Clause 7 sets the standard operating conditions, including ambient temperature, altitude, humidity, mounting position, overvoltage category, pollution degree, frequency tolerance, and harmonic distortion. If the installation is harsher than these conditions, extra requirements may be needed.

For a reader choosing a device, this is where the environmental fit is checked. It tells you whether the standard rating assumptions match the site.

The SDFI must preserve the right switching sequence

Clause 8 requires the SDFI to be safe in use and coordinated with the SRCSD. Open and closed positions must be reliable, contact indication must be dependable, and loss or restoration of control-circuit power must not change the contact position.

Clause 8.2.2 says the SDFI and SRCSD must operate in a coordinated way. If they are not integrated in one device, the SDFI must be supplied with the means and instructions needed for interlocking, and it must work correctly with any declared compatible SRCSD.

Reclosing is controlled either as open transition or closed transition

Clause 8.3 requires the SDFI to be declared either for reclosing without synchronization or with synchronization. For open transition, local sources must be disconnected before reclosing. For closed transition, reclosing is allowed only when voltage, frequency, and phase angle are synchronized within declared limits.

This distinction matters because it affects system behavior during reconnection and the level of control needed from the installation.

Automatic islanding, manual reclosing, and EMC are tested

Clause 8.2.4 covers automatic islanding based on voltage and frequency deviations. The SDFI must open within declared time and deviation limits. Clause 8.2.3 sets different rules for manual reclosing when generators are involved versus inverter-based sources only.

Clause 8.5 requires electrically controlled SDFI with active electronic components to operate correctly in residential, commercial, and light-industrial EMC environments. Clause 9 then turns these requirements into type tests for operation, interlocking, manual reclosing, deviation response, reclosing behavior, and EMC emission and immunity.

What terms does EN IEC 63552:2026 define?

  • Electrical energy management system (EEMS) - a system that monitors, operates, controls, and manages energy resources and loads in an installation.
  • Customer Energy Manager (CEM) - an internal automation function that optimizes energy use, production, and storage in line with customer preferences.
  • Switching device for islanding (SDFI) - the device that changes an islandable PEI between grid-connected mode and island mode.
  • System referencing conductor switching device (SRCSD) - a device connected between the system referencing conductor and the local earthing arrangement.
  • Prosumer’s electrical installation (PEI) - a low-voltage installation with local power supplies and/or storage that can supply loads, storage, or the distribution network.
  • Islandable PEI - a PEI intended to operate either connected to or disconnected from the distribution network.
  • Open transition - a break-before-make reclosing operation.
  • Closed transition - a make-before-break reclosing operation using synchronized sources.

Who uses EN IEC 63552:2026?

EN IEC 63552:2026 is used by manufacturers of SDFI, switching units, control units, and related accessories. It is also used by installers, panel builders, and commissioning teams who need to assemble the device correctly and prove that the switching sequence works.

Test laboratories and certification bodies use it for type testing and verification. Engineers, quality managers, and buyers use it to specify the right operating mode, source type, pole arrangement, interlocking method, and EMC behavior for a PEI project.

Which standards are used with EN IEC 63552:2026?

  • IEC 60364-8-82:2022 - provides the PEI concepts, operating modes, and the islanding context used throughout the document.
  • IEC 62991:2022 - supplies the broader requirements for source switching equipment and the control unit characteristics.
  • IEC 63445:2025 - provides the SRCSD framework, coordination rules, and several test and inspection methods.
  • IEC 60669-2-4, IEC 60898-1, IEC 60898-2, IEC 60947-2, IEC 60947-3, IEC 60947-10 - define the product requirements for the switching unit used inside the SDFI.
  • IEC 61000-4-2, -4-3, -4-4, -4-5, -4-6, -4-8, -4-11 - define the EMC immunity test methods used for verification.
  • IEC 61000-6-1 - provides the generic immunity performance basis used to set the criteria.
  • CISPR 14-1 - covers conducted and radiated emissions.
  • IEC TS 62786-1:2023 - is referenced for source-deviation context and example operating profiles.

What does the EN IEC 63552:2026 document contain?

The document includes the clause structure, figures, tables, and test methods needed to specify and verify an SDFI. Figures show the PEI architecture, the SDFI functional arrangement, operation principles, and reconnection sequences in both open and closed transition modes.

Table 1 lists the required markings and product information. Table 2 gives the standard service-condition values. Table 3 identifies the EMC immunity tests, and Table 4 gives the performance criteria used for those tests.

The procedures in clause 9 describe how to check operation, interlocking, manual reclosing, source-deviation response, reclosing behavior, and EMC performance. For a project team, this is the part that turns the device description into testable acceptance criteria.

Relations

Effective Date
30-Jun-2026
Effective Date
30-Jun-2026
Effective Date
30-Jun-2026
Effective Date
30-Jun-2026
Effective Date
30-Jun-2026
Effective Date
30-Jun-2026
Effective Date
30-Jun-2026
Effective Date
30-Jun-2026
Effective Date
30-Jun-2026
Effective Date
30-Jun-2026
Effective Date
30-Jun-2026
Effective Date
30-Jun-2026
Effective Date
30-Jun-2026
Effective Date
30-Jun-2026
Effective Date
30-Jun-2026

Buy Documents

Standard

EN IEC 63552:2026 - BARVE

English language (35 pages)
Preview
Preview
e-Library read for
×1 day

Get Certified

Connect with accredited certification bodies for this standard

DNV

DNV is an independent assurance and risk management provider.

NA Norway Verified

Lloyd's Register

Lloyd's Register is a global professional services organisation specialising in engineering and technology.

UKAS United Kingdom Verified

DNV Energy Systems

Energy and renewable energy certification.

NA Norway Verified

Sponsored listings

Frequently Asked Questions

EN IEC 63552:2026 is a standard published by CLC. Its full title is "Switching device for islanding (SDFI)". This standard covers: This document applies to switching device for islanding, hereafter referred to as SDFI, for household and similar uses, primarily intended to be used for energy efficiency (EE) purposes with local production or local storage of energy, or with both. SDFI are intended to be installed in low voltage prosumer electrical installations (PEI) able to operate in island mode as defined in IEC 60364-8-82, so called islandable PEI. SDFI are used to disconnect the PEI from the grid to allow operating the PEI in island mode and further reconnect the PEI to the grid. They are intended to be used in islandable PEI which operate: – in connected mode (direct feeding mode or reverse feeding mode), and – in island mode, as defined in IEC 60364-8-82. NOTE 1 See definitions 3.10 and 3.13 of island mode and for connected mode respectively. NOTE 2 Switching of a PEI to island mode can be subject to local regulations (grid codes) or to specific agreement with system operators. Reverse feeding is also usually subject to local regulations (grid codes). SDFI are part of the electrical installation. This document applies to SDFI for operation in AC single or multiphase main circuits with rated voltages not exceeding 440 V AC, frequencies of 50 Hz, 60 Hz or 50/60 Hz. They are intended to be used in installations with prospective short circuit currents not exceeding 25 000 A. NOTE 3 DC operations are not covered by this edition and are kept under consideration for a future revision of this document. The SDFI is composed at least of one switching unit (SU) and a control unit (CU) to monitor its switching operations from grid connected to island mode and reverse wise. The SDFI can be provided with a communication interface for exchange with external systems such as the Customer Energy Manager (CEM) defined in IEC 63402 series. According to the intended use, the SDFI can be interlocked with a system referencing conductor switching device (SRCSD) according to IEC 63445 or it can be integrated with a SRCSD in a single unit. NOTE 4 According to its intended use, the SDFI can also be used as an interface switch with the interface protection (integrated or not). See 3.19 and 3.20. SDFI are intended for use in circuits where protection against electrical shock and overcurrent is provided according to installation rules for low voltage electrical installations, unless the SDFI already contains such protective function. SDFI are not requested to provide isolation function and overcurrent protection according to IEC 60364-8-82. However, the isolation function can be provided by a SDFI fulfilling the requirements of the relevant product standards. SDFI are installed by instructed persons (IEC 60050-195:2021, 195-04-02) or skilled persons (IEC 60050-195:2021, 195-04-01). They are intended to be used by ordinary persons (IEC 60005-195:2021, 195-04-03) and do not require maintenance. It is important to note that the main overcurrent protective device of installations cannot be used as a SDFI in single dwellings or similar islandable PEI (see Clause D.5 of IEC 60364-8-82:2022)

This document applies to switching device for islanding, hereafter referred to as SDFI, for household and similar uses, primarily intended to be used for energy efficiency (EE) purposes with local production or local storage of energy, or with both. SDFI are intended to be installed in low voltage prosumer electrical installations (PEI) able to operate in island mode as defined in IEC 60364-8-82, so called islandable PEI. SDFI are used to disconnect the PEI from the grid to allow operating the PEI in island mode and further reconnect the PEI to the grid. They are intended to be used in islandable PEI which operate: – in connected mode (direct feeding mode or reverse feeding mode), and – in island mode, as defined in IEC 60364-8-82. NOTE 1 See definitions 3.10 and 3.13 of island mode and for connected mode respectively. NOTE 2 Switching of a PEI to island mode can be subject to local regulations (grid codes) or to specific agreement with system operators. Reverse feeding is also usually subject to local regulations (grid codes). SDFI are part of the electrical installation. This document applies to SDFI for operation in AC single or multiphase main circuits with rated voltages not exceeding 440 V AC, frequencies of 50 Hz, 60 Hz or 50/60 Hz. They are intended to be used in installations with prospective short circuit currents not exceeding 25 000 A. NOTE 3 DC operations are not covered by this edition and are kept under consideration for a future revision of this document. The SDFI is composed at least of one switching unit (SU) and a control unit (CU) to monitor its switching operations from grid connected to island mode and reverse wise. The SDFI can be provided with a communication interface for exchange with external systems such as the Customer Energy Manager (CEM) defined in IEC 63402 series. According to the intended use, the SDFI can be interlocked with a system referencing conductor switching device (SRCSD) according to IEC 63445 or it can be integrated with a SRCSD in a single unit. NOTE 4 According to its intended use, the SDFI can also be used as an interface switch with the interface protection (integrated or not). See 3.19 and 3.20. SDFI are intended for use in circuits where protection against electrical shock and overcurrent is provided according to installation rules for low voltage electrical installations, unless the SDFI already contains such protective function. SDFI are not requested to provide isolation function and overcurrent protection according to IEC 60364-8-82. However, the isolation function can be provided by a SDFI fulfilling the requirements of the relevant product standards. SDFI are installed by instructed persons (IEC 60050-195:2021, 195-04-02) or skilled persons (IEC 60050-195:2021, 195-04-01). They are intended to be used by ordinary persons (IEC 60005-195:2021, 195-04-03) and do not require maintenance. It is important to note that the main overcurrent protective device of installations cannot be used as a SDFI in single dwellings or similar islandable PEI (see Clause D.5 of IEC 60364-8-82:2022)

EN IEC 63552:2026 is classified under the following ICS (International Classification for Standards) categories: 27.015 - Energy efficiency. Energy conservation in general; 29.020 - Electrical engineering in general. The ICS classification helps identify the subject area and facilitates finding related standards.

EN IEC 63552:2026 has the following relationships with other standards: It is inter standard links to EN IEC 61000-4-2:2025, HD 60364-8-82:2025, EN IEC 55014-1:2021, EN 61000-4-5:2014, EN 61000-4-8:2010, EN IEC 61000-4-11:2020, EN IEC 61000-4-3:2020, EN 61000-4-4:2012, EN IEC 63445:2025, EN IEC 60947-3:2021, EN IEC 61000-4-6:2023, EN IEC 60669-2-4:2025, EN IEC 60947-2:2025, EN 60898-2:2021, EN IEC 62991:2025. Understanding these relationships helps ensure you are using the most current and applicable version of the standard.

EN IEC 63552:2026 is available in PDF format for immediate download after purchase. The document can be added to your cart and obtained through the secure checkout process. Digital delivery ensures instant access to the complete standard document.

Standards Content (Sample)

Contents

  • 1 Distribution network 8 Non-sheddable loads (sensitive loads)
  • 2 Point of connection (POC) 9 Sheddable loads (adjustable loads)
  • 3 Main switching device 10 Solar generator
  • 4 Switching device for islanding (SDFI) 11 Electrical energy storage system
  • 5 System referencing conductor switching device 12 Other generator (wind, etc.)
  • 6 Source switching device 13 Main distribution board
  • 7 Load switching device
  • 1 Scope
  • 2 Normative references
  • 3 Terms and definitions
  • 3.1 electrical energy management system
  • 3.2 Customer Energy Manager
  • 3.3 Energy Management Gateway
  • 3.4 switching device for islanding
  • 3.5 system referencing conductor switching devices
  • 3.6 source switching equipment
  • 3.7 prosumer
  • 3.8 prosumer's electrical installation
  • 3.9 islandable PEI
  • 3.10 island mode
  • 3.11 direct feeding mode
  • 3.12 reverse feeding mode
  • 3.13 connected mode
  • 3.14 interlock
  • 3.15 synchronization
  • 3.16 open transition
  • 3.17 closed transition
  • 3.18 isolation
  • 3.19 interface protection
  • 3.20 interface switch
  • 3.21 voltage source deviation
  • 3.22 frequency source deviation
  • 3.23 point of connection
  • 3.24 control unit
  • 4 Classification
  • 4.1 General
  • 1 Switching device for islanding (SDFI) 6 Electrical Energy Management (EEM) or the
  • 2 Control unit (CU)
  • 7 Grid
  • 3 Switching unit (SU)
  • 8 Local source(s)
  • 4 System referencing conductor switching device
  • 5 Interlock (of the SRCSD with SDFI) 10 Earth
  • 4.2 According to the construction
  • 4.3 According to the method of integration of SRCSD
  • 4.4 According to the method of operation
  • 4.5 According to kind of current
  • 4.6 According to the number of switched poles
  • 4.7 According to SRCSD interlocking means
  • 4.8 According to the reclosing mode
  • 4.9 According to islanding means
  • 4.10 According to the type of isolation
  • 4.11 According to the type of local sources
  • 5 Characteristics
  • 6 Markings and product information
  • 7 Standard conditions for operation in service
  • 8 Requirements for construction and operation
  • 8.1 General requirements
  • 8.2 Construction requirements
  • 8.3 Reclosing operations (reconnection to grid connected mode)
  • 8.4 Operational endurance
  • 8.5 EMC
  • 9 Type tests
  • 9.1 General
  • 9.2 SDFI operation and interlocking
  • 9.3 Tests for manual reclosing
  • 9.4 Verification of operations upon deviations
  • 9.5 Test for reclosing operations
  • 9.6 EMC tests
  • 9.17.3.3 Short interruptions IEC 61000-4-11 IEC 63445:2025, B
  • 9.17.3.3 Surges IEC 61000-4-5 IEC 63445:2025, B
  • 9.17.3.4 Fast transients (burst) IEC 61000-4-4 IEC 63445:2025, B
  • 9.17.3.6 Radiated radio-frequency IEC 61000-4-3 IEC 63445:2025, A
  • Bibliography

INTRODUCTION IEC 60364-8-82 aims to ensure that low-voltage electrical installations are compatible with both current and future methods for safely and effectively delivering electrical energy to currentusing equipment, regardless of whether the energy comes from Distribution System Operator (DSO) or local generation. IEC 60364-8-82 provides requirements and recommendations for to low-voltage electrical installations, whether or not they are connected to a distribution network, and are capable of operating:

  • with either local power supplies,
  • or with local storage units,
  • or with both, and that monitors and controls the energy from the locally connected sources delivering it to:
  • either current-using equipment,
  • or local storage units,
  • or distribution networks.

Such electrical installations are designated as prosumer's electrical installations (PEIs) by IEC 60364-8-82 which defines specific devices (or functions) to ensure the correct and safe operation of PEI depending on their operating mode. In the case of an islandable PEI, IEC 60364-8-82 defines a "Switching Device For islanding (SDFI)", identified as device 4 in Figure 1.

SIST EN IEC 63552:2026

Key

1 Distribution network 8 Non-sheddable loads (sensitive loads)

2 Point of connection (POC) 9 Sheddable loads (adjustable loads)

3 Main switching device 10 Solar generator

4 Switching device for islanding (SDFI) 11 Electrical energy storage system

5 System referencing conductor switching device 12 Other generator (wind, etc.)

6 Source switching device 13 Main distribution board

7 Load switching device

SOURCE: IEC 60364-8-82:2022, Figure 4.

Figure 1 – Example of islandable PEI architecture The objectives of this document is to define the functions, requirements and tests of a SDFI in line with the requirements stated in IEC 60364-8-82.

SIST EN IEC 63552:2026

1 Scope

This document applies to switching device for islanding, hereafter referred to as SDFI, for household and similar uses, primarily intended to be used for energy efficiency (EE) purposes with local production or local storage of energy, or with both. SDFI are intended to be installed in low voltage prosumer electrical installations (PEI) able to operate in island mode as defined in IEC 60364-8-82, so called islandable PEI. SDFI are used to disconnect the PEI from the grid to allow operating the PEI in island mode and further reconnect the PEI to the grid.

They are intended to be used in islandable PEI which operate:

  • in connected mode (direct feeding mode or reverse feeding mode), and
  • in island mode, as defined in IEC 60364-8-82.

NOTE 1 See definitions 3.10 and 3.13 of island mode and for connected mode respectively. NOTE 2 Switching of a PEI to island mode can be subject to local regulations (grid codes) or to specific agreement with system operators. Reverse feeding is also usually subject to local regulations (grid codes). SDFI are part of the electrical installation.

This document applies to SDFI for operation in AC single or multiphase main circuits with rated voltages not exceeding 440 V AC, frequencies of 50 Hz, 60 Hz or 50/60 Hz. They are intended to be used in installations with prospective short circuit currents not exceeding 25 000 A. NOTE 3 DC operations are not covered by this edition and are kept under consideration for a future revision of this document.

The SDFI is composed at least of one switching unit (SU) and a control unit (CU) to monitor its switching operations from grid connected to island mode and reverse wise. The SDFI can be provided with a communication interface for exchange with external systems such as the Customer Energy Manager (CEM) defined in IEC 63402 series. According to the intended use, the SDFI can be interlocked with a system referencing conductor switching device (SRCSD) according to IEC 63445 or it can be integrated with a SRCSD in a single unit.

NOTE 4 According to its intended use, the SDFI can also be used as an interface switch with the interface protection (integrated or not). See 3.19 and 3.20.

SDFI are intended for use in circuits where protection against electrical shock and overcurrent is provided according to installation rules for low voltage electrical installations, unless the SDFI already contains such protective function. SDFI are not requested to provide isolation function and overcurrent protection according to IEC 60364-8-82. However, the isolation function can be provided by a SDFI fulfilling the requirements of the relevant product standards. SDFI are installed by instructed persons (IEC 60050-195:2021, 195-04-02) or skilled persons (IEC 60050-195:2021, 195-04-01). They are intended to be used by ordinary persons (IEC 60005-195:2021, 195-04-03) and do not require maintenance. It is important to note that the main overcurrent protective device of installations cannot be used as a SDFI in single dwellings or similar islandable PEI (see Clause D.5 of IEC 60364-8-82:2022)

SIST EN IEC 63552:2026

2 Normative references

The following documents are referred to in the text in such a way that some or all of their content constitutes requirements of this document. For dated references, only the edition cited applies. For undated references, the latest edition of the referenced document (including any amendments) applies.

IEC 60364-8-82:2022, Low-voltage electrical installations - Part 8-82: Functional aspects - Prosumer's low-voltage electrical installations IEC 60669-2-4, Switches for household and similar fixed electrical installations - Part 2-4:

Particular requirements - Isolating switches IEC 60898-1:2015, Electrical accessories - Circuit-breakers for overcurrent protection for household and similar installations - Part 1: Circuit-breakers for a.c. operation IEC 60898-2, Electrical accessories - Circuit-breakers for overcurrent protection for household and similar installations - Part 2: Circuit-breakers for AC and DC operation IEC 60947-2, Low-voltage switchgear and controlgear - Part 2: Circuit-breakers IEC 60947-3, Low-voltage switchgear and controlgear - Part 3: Switches, disconnectors, switchdisconnectors and fuse-combination units IEC 60947-10, Low-voltage switchgear and controlgear - Part 10: Semiconductor circuit-

breakers IEC 61000-4-2, Electromagnetic compatibility (EMC) - Part 4-2: Testing and measurement techniques - Electrostatic discharge immunity test IEC 61000-4-3, Electromagnetic compatibility (EMC) - Part 4-3: Testing and measurement techniques - Radiated, radio-frequency, electromagnetic field immunity test IEC 61000-4-4, Electromagnetic compatibility (EMC) - Part 4-4: Testing and measurement techniques - Electrical fast transient/burst immunity test IEC 61000-4-5, Electromagnetic compatibility (EMC) - Part 4-5: Testing and measurement techniques - Surge immunity test IEC 61000-4-6, Electromagnetic compatibility (EMC) - Part 4-6: Testing and measurement techniques - Immunity to conducted disturbances, induced by radio-frequency fields IEC 61000-4-8, Electromagnetic compatibility (EMC) - Part 4-8: Testing and measurement techniques - Power frequency magnetic field immunity test IEC 61000-4-11, Electromagnetic compatibility (EMC) - Part 4-11: Testing and measurement techniques - Voltage dips, short interruptions and voltage variations immunity tests for equipment with input current up to 16 A per phase IEC 61000-6-1, Electromagnetic compatibility (EMC) - Part 6-1: Generic standards - Immunity standard for residential, commercial and light-industrial environments

Under preparation. Stage at the time of publication: IEC FDIS 60947-10:2025.

SIST EN IEC 63552:2026

IEC 62991:2022, Particular requirements for source switching equipment (SSE) IEC 63445:2025, System referencing conductor switching device CISPR 14-1, Electromagnetic compatibility - Requirements for household appliances, electric tools and similar apparatus - Part 1: Emission

3 Terms and definitions

For the purposes of this document, the following terms and definitions apply. ISO and IEC maintain terminology databases for use in standardization at the following addresses:

  • IEC Electropedia: available at https://www.electropedia.org/
  • ISO Online browsing platform: available at https://www.iso.org/obp

3.1 electrical energy management system

EEMS system monitoring, operating, controlling and managing energy resources and loads of the installations Note 1 to entry: The EEMS can be a dedicated system or part of an integrated system, such as a home and building electronic system (HBES) or building management system (BMS or BACS) or other similar management system. [SOURCE: IEC 60364-8-82:2022, 82.3.7]

3.2 Customer Energy Manager

CEM internal automation function for optimizing the energy consumption, production and storage within the premises according to the preferences of the customer using internal flexibilities and typically based on external information received through the Energy Management Gateway and possibly other data sources Note 1 to entry: A EEMS as defined in 3.1 of this document and in 3.2.1 of IEC 60364-8-1:2019 provides the same function as a CEMS except that the EEMS is limited to electrical energy management. [SOURCE: IEC 63402-1:2025, 3.1.1, modified – Note 1 to entry added.]

3.3 Energy Management Gateway

EMG access point (functional entity) sending and receiving smart grid related information and commands between an actor in the grid and the CEM, letting the CEM decide how to process the events Note 1 to entry: The communication is often ensured through an internet connection. [SOURCE: IEC 63402-1:2025, 3.1.3]

SIST EN IEC 63552:2026

3.4 switching device for islanding

SDFI device dedicated to the change from grid connected mode to island mode and from island mode to connected mode for an islandable PEI, functionally speaking, to separate/link the local sources from/to the distribution network Note 1 to entry: See also 3.20.

[SOURCE: IEC 60364-8-82:2022, 1st paragraph of 82.6.3.4.3]

3.5 system referencing conductor switching devices

SRCSD device connected between the system referencing conductor and the local earthing arrangement of the PEI [SOURCE: IEC 63445:2025, 3.3]

3.6 source switching equipment

SSE equipment able to select (power) sources when certain conditions are met or following human intervention Note 1 to entry: For example, SSE for back-up applications may contain one or more switching devices and all associated control means for disconnecting load circuits from one source and reconnecting them to another source when certain conditions are met.

Note 2 to entry: For example, SSE for grid connected PEI defined in IEC 60364-8-82:2022 may contain one or more switching devices and associated control means for switching load circuits from one normal source to another source, when certain conditions are met, maintaining the loads always energized. [SOURCE: IEC 62991:2022, 3.1.28]

3.7 prosumer

<of electricity> entity or party which can be both a producer and a consumer of electrical energy [SOURCE: IEC 60364-8-82:2022, 82.3.5]

3.8 prosumer's electrical installation

PEI low-voltage electrical installation connected or not to a distribution network able to operate:

  • with local power supplies, and/or
  • with local storage units, and that monitors and controls the energy from the connected sources delivering it to:
  • current-using equipment, and/or
  • local storage units, and/or
  • distribution network.

[SOURCE: IEC 60364-8-82:2022, 82.3.6]

SIST EN IEC 63552:2026

3.9 islandable PEI

PEI intended for operating either being connected to a distribution network or being disconnected from the distribution network Note 1 to entry: An islandable PEI is in a connected mode or an intentionally island mode. [SOURCE: IEC 60364-8-82:2022, 82.3.15]

3.10 island mode

operating mode in which the PEI is disconnected from the distribution network Note 1 to entry: An island mode can be either the result of the action of automatic protections or the result of a deliberate action.

[SOURCE: IEC 60050-692:2017, 692-02-11, modified – The term "electric island" has been replaced with "island mode", the definition has been adapted to the PEI and Note 2 to entry has been deleted.]

3.11 direct feeding mode

operating mode in which the distribution network supplies the PEI Note 1 to entry: Local storage units can supply current-using equipment or be charged by local power supplies and/or the distribution system.

[SOURCE: IEC 60364-8-82:2022, 82.3.9]

3.12 reverse feeding mode

operating mode in which the PEI supplies the distribution network Note 1 to entry: Local storage units can supply current-using equipment and/or the distribution system or be charged by local power supplies.

[SOURCE: IEC 60364-8-82:2022, 82.3.10]

3.13 connected mode

operating mode in which the PEI is connected to the distribution network EXAMPLE Direct feeding mode, reverse feeding mode or no feeding mode (i.e. without any energy exchange between the PEI and the distribution network).

[SOURCE: IEC 60364-8-82:2022, 82.3.11]

3.14 interlock

<of an SDFI with an SRCSD> means to prevent simultaneous closing of SRCSD and SDFI, under all conditions [SOURCE: IEC 63445:2025, 3.11]

SIST EN IEC 63552:2026

3.15 synchronization

condition of an electrical system intentionally allowing the connection of two voltage sources in parallel for a short duration Note 1 to entry: The local power source when set in grid forming mode is a voltage source. [SOURCE: IEC 62991:2022, 3.1.17, modified – Replacing "different power" with "voltage", addition of "condition of an" in the definition and addition of Note 1 to entry.]

3.16 open transition

break before make transfer operation that intentionally breaks the load current from one source for a period of time prior to making it to the other source Note 1 to entry: SSE with open transition may operate with a time delay e.g. for power backup application. [SOURCE: IEC 60947-6-1:2021, 3.4.7, modified – Note 1 to entry has been added.]

3.17 closed transition

make before break transfer operation that intentionally makes the load current of a second synchronized source for a short period of time before breaking it from the first source [SOURCE: IEC 60947-6-1:2021, 3.4.9]

3.18 isolation

isolating function function intended to cut off the supply from all or a discrete section of the installation by separating the installation from every source of electrical energy for reasons of safety [SOURCE: IEC 60898-1:2015, 3.6.10]

3.19 interface protection

combination of protection relay functions which open the interface switch of a generating unit and prevents its closure, whichever is appropriate, in the case of:

  • a fault on the electric power distribution network;
  • an unintentional islanding situation;
  • voltage and/or frequency being outside the tolerance of their operating ranges for continuous operation.

[SOURCE: IEC TS 62786-1:2023, 3.1.14, modified - "distribution" added in the first indent.]

3.20 interface switch

switch (circuit breaker, switch or contactor) installed in the prosumer's electrical installation, for separating the part(s) of the prosumer's electrical installation that contains at least one generation unit from the network Note 1 to entry: See also Figure 1 of IEC TS 62786-1:2023.

Note 2 to entry: In some situations, the interface switch can be used to enable island operation of part of the prosumer's electrical installation, if technically feasible.

[SOURCE: IEC TS 62786-1:2023, 3.1.33, modified - Reference to the IEC standard adding and replaced "producer's network" by "prosumer's electrical installation".]

SIST EN IEC 63552:2026

3.21 voltage source deviation

change in voltage level from the nominal voltage of the monitored source Note 1 to entry: In this document, the term is often used stating only the term "source deviation". [SOURCE: IEC 60947-6-1:2021, 3.4.3, modified – Replacing "supply" by "source" and adding the note.]

3.22 frequency source deviation

change in frequency from the nominal operating frequency of the monitored source Note 1 to entry: In this document, the term is often used stating only the term "source". [SOURCE: IEC 60947-6-1:2021, 3.4.4, modified – Replacing "supply" by "source" and adding the note.]

3.23 point of connection

POC reference point where the prosumer's electrical installation is connected to the distribution network Note 1 to entry: A PEI can have several points of connection for resilience. Note 2 to entry: In IEC 60364 (all parts), the concept of origin of the installation is also used, origin of the installation meaning the point at which energy is delivered to the electrical installation. The POC is a specific origin of the installation, the one connected to the distribution network. Other origins of the installation can be the connection to the local power supply, to the storage system.

Note 3 to entry: Connection or disconnection of the prosumer electrical installation from the distribution network generally occurs at the POC.

[SOURCE: IEC 60050-617:2009, 617-04-01 modified – The definition has been adapted to the PEI and the notes to entry have been added.]

...