Abstract

ISO 7396-1:2016 specifies requirements for design, installation, function, performance, testing, commissioning and documentation of pipeline systems used in healthcare facilities for the following:
- oxygen;
- nitrous oxide;
- medical air;
- carbon dioxide;
- oxygen/nitrous oxide mixtures (see Note 1);
- helium/oxygen mixtures;
- (*) oxygen 93;
- gases and gas mixtures classified as medical device, gases delivered to medical devices or intended for medical purposes or gases and gas mixtures for medicinal use not specified above;
- air for driving surgical tools;
- nitrogen for driving surgical tools;
- vacuum.
NOTE 1 Regional or national regulations may prohibit the distribution of oxygen/nitrous oxide mixtures in medical gas pipeline systems.
NOTE 2 Anaesthetic gas scavenging disposal systems are covered in ISO 7396‑2.
This part of ISO 7396 includes requirements for supply systems, pipeline distribution systems, control systems, monitoring and alarm systems and non-interchangeability between components of different gas/vacuum systems.
This part of ISO 7396 specifies safety requirements for pipeline systems used in healthcare facilities, both public and private. It applies to all facilities providing healthcare services regardless of type, size, location or range of services, including, but not limited to:
a) acute care healthcare facilities;
b) internal patient continuing care healthcare facilities;
c) long-term care facilities;
d) community-based providers;
e) ambulatory and external patient care clinics (e.g. day surgery, endoscopy clinics and doctors' offices).
NOTE 3 This part of ISO 7396 may also be used as reference for pipeline systems for medical gases and vacuum intended to be installed in places other than healthcare facilities.
ISO 7396-1:2016 applies to the following different types of oxygen supply systems:
- supply systems in which all sources of supply deliver oxygen; in this case the concentration of the oxygen will be greater than 99%;
- supply systems in which all sources of supply deliver oxygen 93; in this case the concentration of the oxygen may vary between 90% and 96%;
NOTE 4 A mixture of oxygen 93 and oxygen may be delivered by a medical gas supply system. In this case the concentration of the gas can vary between 90% and >99%.
ISO 7396-1:2016 also applies to:
- extensions of existing pipeline distribution systems;
- modifications of existing pipeline distribution systems;
- modifications or replacement of supply systems or sources of supply.
Oxygen concentrators for domiciliary use are excluded from the scope of this part of ISO 7396.
NOTE 5 Requirements for oxygen concentrators for domiciliary use are specified in ISO 80601‑2-69.
(*) EN 14931 defines additional requirements for hyperbaric application, in particular for flows and pressures of compressed air required to pressurize the hyperbaric chamber and to drive other connected services. Also included are requirements for oxygen and other treatment gases administered to patients.
ISO 7396-1:2016 does not apply to vacuum systems intended to be used in dentistry.
ISO 7396-1:2016 does not apply to filling systems for transportable cylinders and transportable cylinder bundle systems.

Status
Not Published
Publication Date
19-Dec-2027
Current Stage
4060 - Closure of enquiry - Enquiry
Start Date
22-Sep-2026
Due Date
22-Sep-2026
Completion Date
22-Sep-2026

Buy Documents

Draft

prEN ISO 7396-1:2026

English language (203 pages)
Preview
Preview
e-Library read for
×1 day

prEN ISO 7396-1 is a CEN draft for medical gas pipeline systems (MGPS) used in healthcare facilities. It specifies requirements for the design, installation, function, performance, testing, commissioning and documentation of pipeline systems for compressed medical gases and vacuum, and it is written for designers, installers, healthcare facility managers and maintenance teams.

What does prEN ISO 7396-1 specify?

prEN ISO 7396-1 covers safety and performance requirements for medical gas pipeline systems in healthcare facilities. It is intended for all healthcare settings, from acute care hospitals to clinics and long-term care, and it can also be used as a reference for installations outside healthcare facilities.

The document applies to supply systems, pipeline distribution systems, control systems, monitoring and alarm systems, and the non-interchangeability of different gas and vacuum systems. It also sets requirements for extensions, modifications and replacement work on existing systems, which matters because many projects are upgrades rather than new builds.

AnnexWhat it covers
Annex ASchematic representations of typical supply systems and area distribution systems
Annex BLocation guidance for cylinder manifolds, cylinder storage areas and stationary cryogenic vessels
Annex CExample procedure for testing and commissioning
Annex DTypical forms for conformity documentation
Annex EPressure and temperature correction example for leak testing
Annex FRationale for air compressor unit hazards
Annex GOperational guidance, roles, procedures and maintenance practice
Annex HRisk management procedure and checklist
Annex IRationale statements for selected requirements
Annex KResponsibilities for medical gas quality and on-site manufacture
Annex LRole allocation across design, installation, testing and maintenance
Annex MExamples of pharmacopeial requirements for on-site production

What are the key requirements of prEN ISO 7396-1?

prEN ISO 7396-1 is built around risk control, continuity of supply and prevention of wrong gas delivery. In practice, the document tells the reader how to design a safe MGPS, how to keep it supplied during failures and maintenance, how to verify gas quality, and how to prove the system was tested and accepted before use.

Safety, risk and materials

  • Clause 4 requires risk management to be applied to the system as a whole, with documented risk assessments. This matters because decisions about layout, redundancy, alarms and maintenance have to be justified against patient and staff risk.
  • Clause 4 also covers materials that contact medical gases or vacuum, including corrosion resistance, oxygen compatibility, cleanliness and lubricant compatibility. In practice, the system designer and purchaser need to check that components will not contaminate the gas or fail under pressure.
  • Clause 4 places responsibility on the healthcare facility management for selecting the appropriate pharmacopeia for gases for medical use. That means the gas quality basis has to be chosen before on-site production or acceptance testing starts.

Supply systems and continuity of supply

  • Clause 5 requires redundancy: medicinal gas supply systems need at least three independent sources of supply, air or nitrogen for driving surgical tools need at least two, and vacuum systems need at least three vacuum pumps. This reduces the chance that a single fault stops supply to patients or equipment.
  • Clause 5 also requires capacity and storage to be based on the estimated flow profile and usage, with provision for continuity of supply and planned maintenance. For the facility, that means source sizing is not just a static equipment choice - it must match real demand and maintenance practice.
  • Clause 5 sets special requirements for medical air, proportioning units and oxygen concentrator unit(s), including filtration, monitoring of dew point and carbon monoxide, and continuous analysis of oxygen concentration where relevant. This is important because air quality can affect both patient safety and downstream equipment.
  • Clause 5 includes requirements for pressure relief, maintenance supply assemblies, source changeover, and the location of supply systems. These provisions help staff isolate equipment for service without creating a hazard or interrupting clinical use.
  • Clause 5 separates different supply arrangements, including cylinders, cylinder bundles, high-pressure reservoir(s), cryogenic or non-cryogenic vessels, and systems assembled at site or preassembled in a factory. That distinction matters because the acceptance tests and documentation depend on how the system was built.

Monitoring, alarms and distribution

  • Clause 6 defines four alarm functions: operating alarms, emergency operating alarms, emergency clinical alarms and information signals. In practice, this tells technical and clinical staff what type of abnormal condition has occurred and how urgently it must be handled.
  • Clause 6 requires monitoring and alarm systems to be connected to normal and emergency power, and to alarm on communication failure. This matters because alarm visibility is part of the life-safety function of the MGPS.
  • Clause 6 sets alarm conditions for source changeover, low source pressure or content, compressor malfunction, vacuum malfunction, abnormal oxygen concentration, carbon monoxide conditions and loss of external power. The reader uses this to decide what must be monitored and where alarms must be displayed.
  • Clause 7 requires pipeline distribution systems to withstand pressure in single fault condition and sets limits for distribution pressure and terminal unit pressure. That protects the pipeline from rupture and helps ensure the right pressure reaches the patient or device.
  • Clause 8 covers shut-off valves and non-return valves, including source shut-off valves, main shut-off valves, service valves, riser valves, branch valves and area shut-off valves. This is what allows safe isolation for maintenance, emergencies and zoning.
  • Clause 9 requires gas-specific terminal units, compliance of medical supply units, line pressure regulators and pressure gauges with the named standards. In practice, these requirements reduce misconnection risk and make the system readable and serviceable.
  • Clause 10 requires pipeline marking and, where used, colour coding. This is a simple but critical control against wrong-gas connection and maintenance error.
  • Clause 11 sets installation rules for layout, supports, joints, bonding, protection from damage and extensions or modifications. This matters because a well-designed system can still fail if it is installed badly or altered without control.

Testing, commissioning and records

  • Clause 12 requires inspection, testing and commissioning after installation, with documentation by the manufacturer and supervision by the healthcare facility. The system is not ready for patient use until these checks are complete.
  • Clause 12 includes tests for leakage, mechanical integrity, cross-connection, obstruction, flow rate, particulate contamination, gas identity, pressure relief valves and alarm performance. This is the practical proof that the installed system matches the design and delivers the correct gas.
  • Clause 12 requires a written statement of conformance and permanent test records in the healthcare facility file. That record is important for audits, troubleshooting and later modifications.
  • Clause 13 requires installation, use, operational management, as-installed drawings and test reports to be documented in line with ISO 20417. This supports safe operation after handover and gives the facility traceable evidence of what was installed.

What terms does prEN ISO 7396-1 define?

prEN ISO 7396-1 defines the key terms that shape how the system is specified and operated. These terms matter because the document uses them to separate roles, equipment functions and alarm states.

  • Applicable policy - the set of requirements that apply to the medical device or accessory, including form, function, process and manufacturer information.
  • Air compressor unit - the part of the source of supply that compresses or moves ambient air, including the compressor, drive system and necessary operating components.
  • Air for driving surgical tools - a gas mixture supplied by the MGPS and intended to drive surgical tools, with specified contaminant limits.
  • Audio off - a limited-duration state in which the alarm system does not generate an auditory signal.
  • Booster compressor unit - a compressor unit used to raise an already elevated pressure to a higher pressure.

Who uses prEN ISO 7396-1?

prEN ISO 7396-1 is used by healthcare facility owners and managers, technical services, installers, manufacturers, suppliers, contractors and quality staff. It is also relevant to pharmacists or equivalent quality controllers, because the document links system operation to gas quality.

Typical users include the executive manager, facilities engineering manager, authorized person, competent person, quality controller, designated medical officer and designated nursing officer described in Annex G. They use the document to assign responsibility, control work on the MGPS, plan maintenance, manage emergencies and keep the gas supply safe for clinical use.

It also matters to design consultants and procurement teams because it defines what needs to be specified, tested and documented before a system is accepted. Buyers use it to check that components, sources of supply and terminal equipment fit the required gas service.

Which standards are used with prEN ISO 7396-1?

prEN ISO 7396-1 uses several standards for specific components, test methods and supporting controls.

  • ISO 14971 - risk management method for the medical gas pipeline system as a whole.
  • ISO 20417 - manufacturer information to be supplied with the product.
  • ISO 5359 - low-pressure hose assemblies and, where used, colour coding.
  • ISO 9170-1 - gas-specific terminal units for compressed medical gases and vacuum.
  • ISO 10524-2 - manifold and line pressure regulators.
  • ISO 11197 - medical supply units such as ceiling pendants, bedhead units and booms.
  • ISO 15001:2010 - oxygen compatibility of anaesthetic and respiratory equipment materials.
  • ISO 17672 - brazing filler metals used for metallic pipeline joints.
  • ISO 21969 - high-pressure flexible connections for medical gas systems.
  • ISO 29463-1 - filter classification and performance for vacuum filtration.
  • ISO 18562-2 - particulate emissions from breathing gas pathways.
  • ISO 8573-1 and ISO 5011 - compressed air purity and inlet air cleaning for compressor-based systems.
  • ISO 3746, ISO 4126-1 and IEC 60529 - noise measurement, safety valves and ingress protection where relevant.
  • ISO 7396-2 - anaesthetic gas scavenging disposal systems.
  • ISO 80601-2-69 - oxygen concentrators for domiciliary use, named as an exclusion reference.
  • EN 14931 - additional requirements for hyperbaric application.
  • EN 1012-1, EN 1254-1 and EN 837-1 - compressor units, copper pipe fittings and pressure gauges.
  • ISO 10637 - dental vacuum, used as the reference point for the dental exclusion.

What does the prEN ISO 7396-1 document contain?

prEN ISO 7396-1 contains clause text, annexes, schematic figures, tables and example procedures that support design, installation, testing and operation. Annex A gives system schematics, Annex C gives an example commissioning procedure, Annex D gives documentation forms, and Annex E gives a temperature-pressure correction example used in leak testing.

The annexes also provide practical context: Annex F explains compressor hazards, Annex G sets out operating practice and responsibilities, Annex H gives a risk management checklist, Annex I gives rationale, Annex K addresses gas quality responsibilities, Annex L separates project roles and Annex M shows examples of pharmacopeial requirements for on-site production.

The body of the document also includes tables and test devices for alarm signalling, pressure ranges, contamination checks and other verification tasks. These are used for design review, installation checks, commissioning, conformity assessment and ongoing audits.

Relations

Effective Date
12-Feb-2026
Effective Date
14-Jun-2023
Effective Date
14-Jun-2023

Buy Documents

Draft

prEN ISO 7396-1:2026

English language (203 pages)
Preview
Preview
e-Library read for
×1 day

Get Certified

Connect with accredited certification bodies for this standard

BSI Group

BSI (British Standards Institution) is the business standards company that helps organizations make excellence a habit.

UKAS United Kingdom Verified

TÜV Rheinland

TÜV Rheinland is a leading international provider of technical services.

DAKKS Germany Verified

TÜV SÜD

TÜV SÜD is a trusted partner of choice for safety, security and sustainability solutions.

DAKKS Germany Verified

Sponsored listings

Frequently Asked Questions

prEN ISO 7396-1 is a draft published by the European Committee for Standardization (CEN). Its full title is "Medical gas pipeline systems - Part 1: Pipeline systems for compressed medical gases and vacuum (ISO/FDIS 7396-1:2026)". This standard covers: ISO 7396-1:2016 specifies requirements for design, installation, function, performance, testing, commissioning and documentation of pipeline systems used in healthcare facilities for the following: - oxygen; - nitrous oxide; - medical air; - carbon dioxide; - oxygen/nitrous oxide mixtures (see Note 1); - helium/oxygen mixtures; - (*) oxygen 93; - gases and gas mixtures classified as medical device, gases delivered to medical devices or intended for medical purposes or gases and gas mixtures for medicinal use not specified above; - air for driving surgical tools; - nitrogen for driving surgical tools; - vacuum. NOTE 1 Regional or national regulations may prohibit the distribution of oxygen/nitrous oxide mixtures in medical gas pipeline systems. NOTE 2 Anaesthetic gas scavenging disposal systems are covered in ISO 7396‑2. This part of ISO 7396 includes requirements for supply systems, pipeline distribution systems, control systems, monitoring and alarm systems and non-interchangeability between components of different gas/vacuum systems. This part of ISO 7396 specifies safety requirements for pipeline systems used in healthcare facilities, both public and private. It applies to all facilities providing healthcare services regardless of type, size, location or range of services, including, but not limited to: a) acute care healthcare facilities; b) internal patient continuing care healthcare facilities; c) long-term care facilities; d) community-based providers; e) ambulatory and external patient care clinics (e.g. day surgery, endoscopy clinics and doctors' offices). NOTE 3 This part of ISO 7396 may also be used as reference for pipeline systems for medical gases and vacuum intended to be installed in places other than healthcare facilities. ISO 7396-1:2016 applies to the following different types of oxygen supply systems: - supply systems in which all sources of supply deliver oxygen; in this case the concentration of the oxygen will be greater than 99%; - supply systems in which all sources of supply deliver oxygen 93; in this case the concentration of the oxygen may vary between 90% and 96%; NOTE 4 A mixture of oxygen 93 and oxygen may be delivered by a medical gas supply system. In this case the concentration of the gas can vary between 90% and >99%. ISO 7396-1:2016 also applies to: - extensions of existing pipeline distribution systems; - modifications of existing pipeline distribution systems; - modifications or replacement of supply systems or sources of supply. Oxygen concentrators for domiciliary use are excluded from the scope of this part of ISO 7396. NOTE 5 Requirements for oxygen concentrators for domiciliary use are specified in ISO 80601‑2-69. (*) EN 14931 defines additional requirements for hyperbaric application, in particular for flows and pressures of compressed air required to pressurize the hyperbaric chamber and to drive other connected services. Also included are requirements for oxygen and other treatment gases administered to patients. ISO 7396-1:2016 does not apply to vacuum systems intended to be used in dentistry. ISO 7396-1:2016 does not apply to filling systems for transportable cylinders and transportable cylinder bundle systems.

ISO 7396-1:2016 specifies requirements for design, installation, function, performance, testing, commissioning and documentation of pipeline systems used in healthcare facilities for the following: - oxygen; - nitrous oxide; - medical air; - carbon dioxide; - oxygen/nitrous oxide mixtures (see Note 1); - helium/oxygen mixtures; - (*) oxygen 93; - gases and gas mixtures classified as medical device, gases delivered to medical devices or intended for medical purposes or gases and gas mixtures for medicinal use not specified above; - air for driving surgical tools; - nitrogen for driving surgical tools; - vacuum. NOTE 1 Regional or national regulations may prohibit the distribution of oxygen/nitrous oxide mixtures in medical gas pipeline systems. NOTE 2 Anaesthetic gas scavenging disposal systems are covered in ISO 7396‑2. This part of ISO 7396 includes requirements for supply systems, pipeline distribution systems, control systems, monitoring and alarm systems and non-interchangeability between components of different gas/vacuum systems. This part of ISO 7396 specifies safety requirements for pipeline systems used in healthcare facilities, both public and private. It applies to all facilities providing healthcare services regardless of type, size, location or range of services, including, but not limited to: a) acute care healthcare facilities; b) internal patient continuing care healthcare facilities; c) long-term care facilities; d) community-based providers; e) ambulatory and external patient care clinics (e.g. day surgery, endoscopy clinics and doctors' offices). NOTE 3 This part of ISO 7396 may also be used as reference for pipeline systems for medical gases and vacuum intended to be installed in places other than healthcare facilities. ISO 7396-1:2016 applies to the following different types of oxygen supply systems: - supply systems in which all sources of supply deliver oxygen; in this case the concentration of the oxygen will be greater than 99%; - supply systems in which all sources of supply deliver oxygen 93; in this case the concentration of the oxygen may vary between 90% and 96%; NOTE 4 A mixture of oxygen 93 and oxygen may be delivered by a medical gas supply system. In this case the concentration of the gas can vary between 90% and >99%. ISO 7396-1:2016 also applies to: - extensions of existing pipeline distribution systems; - modifications of existing pipeline distribution systems; - modifications or replacement of supply systems or sources of supply. Oxygen concentrators for domiciliary use are excluded from the scope of this part of ISO 7396. NOTE 5 Requirements for oxygen concentrators for domiciliary use are specified in ISO 80601‑2-69. (*) EN 14931 defines additional requirements for hyperbaric application, in particular for flows and pressures of compressed air required to pressurize the hyperbaric chamber and to drive other connected services. Also included are requirements for oxygen and other treatment gases administered to patients. ISO 7396-1:2016 does not apply to vacuum systems intended to be used in dentistry. ISO 7396-1:2016 does not apply to filling systems for transportable cylinders and transportable cylinder bundle systems.

prEN ISO 7396-1 is classified under the following ICS (International Classification for Standards) categories: 11.040.10 - Anaesthetic, respiratory and reanimation equipment. The ICS classification helps identify the subject area and facilitates finding related standards.

prEN ISO 7396-1 has the following relationships with other standards: It is inter standard links to ISO 7396-1, EN ISO 7396-1:2016, EN ISO 7396-1:2016/A1:2019. Understanding these relationships helps ensure you are using the most current and applicable version of the standard.

prEN ISO 7396-1 is associated with the following European legislation: EU Directives/Regulations: 2017/745, 93/42/EEC; Standardization Mandates: M/023, M/575, M/575 Amd 2. When a standard is cited in the Official Journal of the European Union, products manufactured in conformity with it benefit from a presumption of conformity with the essential requirements of the corresponding EU directive or regulation.

prEN ISO 7396-1 is available in PDF format for immediate download after purchase. The document can be added to your cart and obtained through the secure checkout process. Digital delivery ensures instant access to the complete standard document.

Standards Content (Sample)

Contents

  • Introduction
  • 1 Scope
  • 2 Normative references
  • 3 Terms and definitions
  • 3.1 applicable policy
  • 3.2 air compressor unit
  • 3.3 air for driving surgical tools
  • 3.4 audio off
  • 3.5 booster compressor unit
  • 3.6 commissioning
  • 3.7 control equipment
  • 3.8 control system
  • 3.9 cryogenic vessel
  • 3.10 cylinder bundle
  • 3.11 diversity factor
  • 3.12 double-stage pipeline distribution system
  • 3.13 emergency clinical alarm
  • 3.14 emergency operating alarm
  • 3.15 emergency power supply
  • 3.16 feed air unit
  • 3.17 gas-specific
  • 3.18 gas-specific connector
  • 3.19 healthcare facility
  • 3.20 high-dependency patient
  • 3.21 high pressure
  • 3.22 high-pressure reservoir
  • 3.23 information signal
  • 3.24 line pressure regulator
  • 3.25 low pressure
  • 3.26 low-pressure hose assembly
  • 3.27 main line
  • 3.28 maintenance supply assembly
  • 3.29 manifold
  • 3.30 manufacturer
  • 3.31 maximum distribution pressure
  • 3.32 medical air
  • 3.33 medical device gas
  • 3.34 medical gas pipeline system
  • 3.35 nominal distribution pressure
  • 3.36 nominal supply system pressure
  • 3.37 normal condition
  • 3.38 non-return valve
  • 3.39 operating alarm
  • 3.40 pharmacopeial oxygen
  • 3.41 pipeline branch
  • 3.42 pipeline distribution system
  • 3.43 pressure regulator
  • 3.44 pressure relief valve
  • 3.45 primary source of supply
  • 3.46 proportioning unit
  • 3.47 reserve source of supply
  • 3.48 riser
  • 3.49 reservoir
  • 3.50 safety
  • 3.51 Sample port
  • 3.52 secondary source of supply
  • 3.53 shut-off valve
  • 3.54 single fault condition
  • 3.55 single-stage pipeline distribution system
  • 3.56 source of supply
  • 3.57 source of supply with proportioning unit
  • 3.58 source of supply with air compressor unit
  • 3.59 source of supply with oxygen concentrator unit(s)
  • 3.60 supply system
  • 3.61 system design flow
  • 3.62 terminal unit
  • 3.63 vacuum receiver
  • 3.64 vacuum supply system
  • 4 General requirements
  • 4.1 General
  • 4.2 Safety and risk management
  • 4.3 Gases for medical use
  • 4.4 Materials
  • 4.5 System design
  • 5 Supply systems
  • 5.1 Supply system components
  • 5.2 General Requirements for supply systems
  • 5.3 Supply systems with cylinders, cylinder bundles or high pressure reservoir(s)
  • 5.4 Supply systems with cryogenic or non cryogenic vessels
  • 5.5 Supply systems for air

Introduction

Many healthcare facilities use medical gas pipeline systems to deliver medical gases and to provide vacuum to areas where they are used in patient care or to power equipment such as ventilators and surgical tools. This document specifies requirements for medical gas pipeline systems for gases for medicinal use, medical device gases, gases for driving surgical tools and vacuum. It is intended for use by those persons involved in the design, construction, inspection, and operation of healthcare facilities treating human beings. Those persons involved in the design, manufacture and testing of equipment intended to be connected to these medical gas pipeline systems should also be aware of the contents of this document. This document seeks to ensure that medical gas pipelines contain only the specific gas (or vacuum) intended to be supplied. For this reason, gas-specific components are used for terminal units and for other connectors which are intended to be used by the operator. In addition, each system is tested and certified to contain only the specific gas (or vacuum).

The objectives of this document are to ensure the following:

a) non-interchangeability between different medical gas pipeline systems by design, installation and testing; b) continuous supply of gases and vacuum at specified quality, pressures and design flow rates by providing appropriate sources; c) use of suitable materials; d) cleanliness of components; e) correct installation; f) provision of monitoring and alarm systems; g) correct marking of the pipeline system; h) testing and commissioning; i) quality of the gases delivered by the pipeline system; j) correct operational management; k) safety features of the sources to ensure the quality and pressure of the gases delivered to the terminals according to specification.

It is normal practice to assign responsibility for the quality of the medical gas supplied to a nominated person within the healthcare facility such as the head pharmacist. Where the healthcare facility manufactures the medical gas on site the healthcare facility is responsible for all aspects of the medical gas quality. Vacuum for medical suction is also the responsibility of the healthcare facility. [37] EN 14931:2006 defines additional requirements for hyperbaric application, in particular for flow rates and pressures of compressed air required to pressurize hyperbaric chambers and to drive other connected services. Also included are requirements for oxygen and other treatment gases administered to patients during hyperbaric therapies. Annex G, J and K provides guidance for the assignment of responsibility for production and quality control of the gases and vacuum.

Annexes G and H provide some guidance as to how the quality of the gas should be managed to maintain patient safety at the highest level.

Annex I contains rationale statements for some of the requirements of this document. It is included to provide additional insight into the reasoning that led to the requirements and recommendations that have been incorporated into this document.

oSIST prEN ISO 7396-1:2026 FINAL DRAFT International Standard ISO/FDIS 7396-1:2026(en) Medical gas pipeline systems — Part 1:

Pipeline systems for compressed medical gases and vacuum

1 Scope

This document specifies requirements for design, installation, function, performance, testing, commissioning and documentation of medical gas pipeline systems used in healthcare facilities for the following:

  • argon;
  • pharmacopeial oxygen;
  • nitrous oxide;
  • medical air;
  • carbon dioxide;
  • oxygen/nitrous oxide mixtures;
  • helium/oxygen mixtures;
  • gases and gas mixtures classified as medical device, gases delivered to medical devices or intended for medical purposes or gases and gas mixtures for medicinal use not specified above;
  • air for driving surgical tools;
  • nitrogen;
  • vacuum.

NOTE 1 A rationale for this is contained in Annex I.2 [6] NOTE 2 Anaesthetic gas scavenging disposal systems are covered in ISO 7396-2 . This document includes requirements for supply systems, medical gas pipeline distribution systems, control system(s), monitoring and alarm systems and non-interchangeability between different gas/vacuum systems.

This document specifies safety requirements for medical gas pipeline systems used in healthcare facilities. It applies to all facilities providing healthcare services regardless of type, size, location or range of services, including, but not limited to:

a) acute care healthcare facilities; b) internal patient continuing care healthcare facilities; c) long-term care facilities; d) community-based providers; e) ambulatory and external patient care clinics (e.g. day surgery, endoscopy clinics and doctors’ offices). This document may also be used as reference for medical gas pipeline systems intended to be installed in places other than healthcare facilities.

oSIST prEN ISO 7396-1:2026 ISO/FDIS 7396-1:2026(en) This document applies to the following different types of oxygen supply systems:

  • supply systems in which all sources of supply deliver oxygen produced off-site;
  • supply systems in which some or all sources of supply deliver oxygen produced on-site; in this case the concentration of the oxygen may vary, depending on the pharmacopeial specification selected by the healthcare facility Oxygen concentrators for domiciliary use are excluded from the scope of this document. This document also applies to:
  • extensions of existing pipeline distribution systems;
  • modifications of existing pipeline distribution systems;
  • modifications or replacement of supply systems or sources of supply. This document does not apply to vacuum systems intended to be used in dentistry (A rationale is discussed in Annex I.2) This document does not apply to filling systems for transportable cylinders and transportable cylinder bundle systems.

This document does not apply to cryogenic pipeline systems conveying liquified gases.

2 Normative references

The following documents are referred to in the text in such a way that some or all of their content constitutes requirements of this document. For dated references, only the edition cited applies. For undated references, the latest edition of the referenced document (including any amendments) applies. ISO 3746, Acoustics — Determination of sound power levels and sound energy levels of noise sources using sound pressure — Survey method using an enveloping measurement surface over a reflecting plane ISO 4126-1, Safety devices for protection against excessive pressure — Part 1: Safety valves ISO 5011, Inlet air cleaning equipment for internal combustion engines and compressors — Performance testing ISO 5359, Anaesthetic and respiratory equipment — Low-pressure hose assemblies for use with medical gases ISO 8573-1, Compressed air — Part 1: Contaminants and purity classes ISO 9170-1, Terminal units for medical gas pipeline systems — Part 1: Terminal units for use with compressed medical gases and vacuum ISO 10524-2, Pressure regulators for use with medical gases — Part 2: Manifold and line pressure regulators ISO 11197, Medical supply units ISO 14971, Medical devices — Application of risk management to medical devices ISO 15001:2010, Anaesthetic and respiratory equipment — Compatibility with oxygen ISO 17672, Brazing — Filler metals ISO 20417, Medical devices — Information to be supplied by the manufacturer ISO 21969, High-pressure flexible connections for use with medical gas systems ISO 29463-1, High efficiency filters and filter media for removing particles in air — Part 1: Classification, performance, testing and marking ISO 18562-2, Biocompatibility evaluation of breathing gas pathways in healthcare applications — Part 2: Tests for emissions of particulate matter

oSIST prEN ISO 7396-1:2026 ISO/FDIS 7396-1:2026(en) IEC 60529, Degrees of protection provided by enclosures (IP Code) IEC 60601-1-8, Medical electrical equipment — Part 1-8: General requirements for basic safety and essential performance — Collateral standard: General requirements, tests and guidance for alarm systems in medical electrical equipment and medical electrical systems IEC 62304, Medical device software — Software life cycle processes EN 286-1, Simple unfired pressure vessels designed to contain air or nitrogen — Part 1: Pressure vessels for general purposes EN 837-1, Pressure gauges, Bourdon tube pressure gauges, Dimensions, metrology, requirements and testing EN 1254-1, Copper and copper alloys - Plumbing fittings - Fittings with ends for capillary soldering or capillary brazing to copper tubes EN 1012-1, Compressors and vacuum pumps - Safety requirements - Part 1: Air Compressors EN 1012-2, Compressors and vacuum pumps - Safety requirements - Part 2: Vacuum Pumps EN 13348, Copper and copper alloys — Seamless, round copper tubes for medical gases or vacuum EN 13445-1, Unfired pressure vessels - Part 1: General

3 Terms and definitions

For the purposes of this document, the following terms and definitions apply. ISO and IEC maintain terminology databases for use in standardization at the following addresses:

  • ISO Online browsing platform: available at https:// www .iso .org/ obp
  • IEC Electropedia: available at https:// www .electropedia .org/

3.1 applicable policy

set of requirements relating to the medical device or accessory and its attributes such as form, fit, function, process or information to be supplied by the manufacturer Note 1 to entry: The applicable policy can be established by the authority having jurisdiction. Note 2 to entry: The applicable policy can include specification for the format of the information to be supplied by the manufacturer.

3.2 air compressor unit

the portion of the source of supply including the device for compressing or moving ambient air (typical examples are compressors and blowers). The air compressor unit comprises the compressor, a drive system and any component or device which is necessary for operation

3.3 air for driving surgical tools

natural or synthetic mixture of gases, mainly composed of oxygen and nitrogen in specified proportions, with defined limits for the concentration of contaminants, supplied by a medical gas pipeline system and intended for driving surgical tools Note 1 to entry: Different names or symbols are used for air for driving surgical tools, such as instrument air, surgical air, air motor, air - 700 and air - 800.

Note 2 to entry: Nitrogen can also be used to drive surgical tools.

oSIST prEN ISO 7396-1:2026 ISO/FDIS 7396-1:2026(en)

3.4 audio off

state of limited duration in which the alarm system or part of the alarm system does not generate an auditory alarm signal Note 1 to entry: This is sometimes referred to as silencing.

[SOURCE: IEC 60601-1-8 2006 3.12]

3.5 booster compressor unit

compressor unit used to raise an elevated pressure to a higher pressure Note 1 to entry: As used herein, the term applies to compressors used to fill high-pressure reservoir(s).

3.6 commissioning

proof of function to verify that the agreed system specification is met and is accepted by the responsible organization

3.7 control equipment

items necessary to maintain a medical gas pipeline system within the specified operating parameters Note 1 to entry: Examples of control equipment are pressure regulators, pressure relief valves, sensors, manual or automatic valves and non-return valves.

3.8 control system

device or set of devices to manage, command, direct or regulate the behaviour of other device(s) or system(s)

3.9 cryogenic vessel

vacuum jacketed vessel intended for application at low temperature involving liquefied gases

3.10 cylinder bundle

pack or pallet of cylinders linked together with one or more connectors for filling and emptying

3.11 diversity factor

number which represents the maximum proportion of terminal units in a defined clinical area which will be used at the same time, at flow rates defined in agreement with the management of the healthcare facility

3.12 double-stage pipeline distribution system

pipeline distribution system in which gas is initially distributed from the supply system at a pressure higher than the nominal distribution pressure, and is then reduced to the nominal distribution pressure by line pressure regulator(s) Note 1 to entry: This initial higher pressure is the nominal supply system pressure (see 3.38).

3.13 emergency clinical alarm

alarm to indicate to medical and technical staff that there is a deviation from a monitored parameter which requires an immediate response

3.14 emergency operating alarm

alarm to indicate to technical staff that there is a deviation from a monitored parameter which requires an immediate response

oSIST prEN ISO 7396-1:2026 ISO/FDIS 7396-1:2026(en)

3.15 emergency power supply

an emergency power supply is an independent source of electrical power that supports important electrical systems on loss of normal power supply. An emergency power supply may include a standby generator, batteries and other apparatus

3.16 feed air unit

means of compressing ambient air (e.g.: air compressor unit, air blower unit).

3.17 gas-specific

having characteristics which prevent connections between different gas services or vacuum services

3.18 gas-specific connector

connector with dimensional characteristics which prevent connections between different gas services Note 1 to entry: Examples of gas-specific connectors are quick connectors, screw-threaded connectors, diameterindexed safety system (DISS) connectors, non-interchangeable screw-threaded (NIST) connectors and sleeve indexed system (SIS) connectors.

3.19 healthcare facility

dedicated setting where health care professionals deliver services for patient care

3.20 high-dependency patient

patient with a continual need of a medical gas/vacuum supply, who will be adversely affected by a medical gas/vacuum supply failure to such a degree that his/her clinical condition or safety can be compromised

3.21 high pressure

pressures greater than 3 000 kPa

3.22 high-pressure reservoir

permanently installed container(s) with nominal working pressures greater than 3 000 kPa and up to 25 000 kPa at 15 °C Note 1 to entry: installed container include cylinders and cylinders bundles, intended to be permanent in the healthcare facility

3.23 information signal

signal that is not an alarm signal or a reminder signal

3.24 line pressure regulator

pressure regulator used in a pipeline distribution system to reduce the nominal supply system pressure to the nominal distribution pressure

3.25 low pressure

pressures lower than 1 400 kPa

3.26 low-pressure hose assembly

assembly consisting of a flexible hose with permanently attached gas-specific inlet and outlet connectors and designed to conduct a medical gas at pressures less than 1 400 kPa

oSIST prEN ISO 7396-1:2026 ISO/FDIS 7396-1:2026(en)

3.27 main line

portion of the pipeline distribution system connecting the supply system to risers and/or pipeline branches

3.28 maintenance supply assembly

source of supply intended to supply the system during maintenance

3.29 manifold

device for connecting the outlet(s) of one or more cylinders, cylinder bundles or high-pressure reservoir(s) of the same gas to the pipeline system using a high-pressure flexible connection

3.30 manufacturer

natural or legal person with responsibility for the design, manufacture, packaging and labelling of a device before it is placed on the market under his own name, regardless of whether these operations are carried out by that person or on their behalf by a third party Note 1 to entry: See also Annex L.

3.31 maximum distribution pressure

pressure at any terminal unit when the medical gas pipeline system isoperating at zero flow

3.32 medical air

natural or synthetic mixture of gases, mainly composed of oxygen and nitrogen in specified proportions, with defined limits for the concentration of contaminants, supplied by a medical gas pipeline system and intended for administration to patients Note 1 to entry: Medical air can be produced by supply systems with air compressor sources of supply or by supply systems with proportioning units on site or by a manufacturer off site. Medical air produced by air compressor systems is called “medicinal air”, and medical air produced by proportioning systems is called “synthetic medicinal air” by the European Pharmacopoeia

3.33 medical device gas

gas or mixture of gases intended by the manufacturer to be used for human beings for the purpose of:

  • diagnosis, prevention, monitoring, treatment or alleviation of disease;
  • investigation, replacement or modification of the anatomy or of a physiological process;
  • control of conception; and that does not achieve its principal intended action in or on the human body by pharmacological, immunological or metabolic means, but which may be assisted in its function by such means.

3.34 medical gas pipeline system

complete system which comprises a supply system, a monitoring and alarm system and a distribution system with terminal units at the points where medical gases or vacuum are required

3.35 nominal distribution pressure

pressure which the medical gas pipeline system is intended to deliver at the terminal units

3.36 nominal supply system pressure

pressure which the supply system is intended to deliver at the inlet to the line pressure regulator when flowing at the design flow rate for the medical gas pipeline.

oSIST prEN ISO 7396-1:2026 ISO/FDIS 7396-1:2026(en)

3.37 normal condition

condition in which all means provided for protection against hazards are intact

3.38 non-return valve

valve which permits flow in one direction only

3.39 operating alarm

alarm to indicate to technical staff that it is necessary to replenish the gas supply or to correct a malfunction

3.40 pharmacopeial oxygen

oxygen conforming to the pharmacopeia required by the regulatory authority having jurisdiction or the pharmacopeia selected by the healthcare facility

3.41 pipeline branch

portion of the pipeline distribution system which supplies one or more areas on the same floor of the healthcare facility

3.42 pipeline distribution system

portion of a medical gas or vacuum pipeline system linking the sources of supply of the supply system to the terminal units

3.43 pressure regulator

device which reduces the inlet pressure and maintains the set outlet pressure within specified limits

3.44 pressure relief valve

device intended to relieve excess pressure at a pre-set pressure

3.45 primary source of supply

portion of the supply system which is the first to be drawn upon to supply the medical gas pipeline distribution system

3.46 proportioning unit

device in which gases are mixed in a specified ratio

3.47 reserve source of supply

that source of supply which supplies the pipeline distribution system (or part(s) thereof) in the event both the primary and secondary sources of supply fail, are exhausted or under maintenance.

3.48 riser

portion of the pipeline distribution system traversing one or more floors and connecting the main line with pipeline branch lines on various levels

3.49 reservoir

permanently installed container(s) designed for storing gas at pressures up to 3 000 kPa Note 1 to entry: See also vacuum receiver (3.62)

oSIST prEN ISO 7396-1:2026 ISO/FDIS 7396-1:2026(en)

3.50 safety

freedom from unacceptable risk

3.51 Sample port

A designated port on a medical gas pipeline system intended to allow the safe and controlled taking of a gas sample.

...