Abstract

ISO 7396-1:2016 specifies requirements for design, installation, function, performance, testing, commissioning and documentation of pipeline systems used in healthcare facilities for the following:
- oxygen;
- nitrous oxide;
- medical air;
- carbon dioxide;
- oxygen/nitrous oxide mixtures (see Note 1);
- helium/oxygen mixtures;
- (*) oxygen 93;
- gases and gas mixtures classified as medical device, gases delivered to medical devices or intended for medical purposes or gases and gas mixtures for medicinal use not specified above;
- air for driving surgical tools;
- nitrogen for driving surgical tools;
- vacuum.
NOTE 1 Regional or national regulations may prohibit the distribution of oxygen/nitrous oxide mixtures in medical gas pipeline systems.
NOTE 2 Anaesthetic gas scavenging disposal systems are covered in ISO 7396‑2.
This part of ISO 7396 includes requirements for supply systems, pipeline distribution systems, control systems, monitoring and alarm systems and non-interchangeability between components of different gas/vacuum systems.
This part of ISO 7396 specifies safety requirements for pipeline systems used in healthcare facilities, both public and private. It applies to all facilities providing healthcare services regardless of type, size, location or range of services, including, but not limited to:
a) acute care healthcare facilities;
b) internal patient continuing care healthcare facilities;
c) long-term care facilities;
d) community-based providers;
e) ambulatory and external patient care clinics (e.g. day surgery, endoscopy clinics and doctors' offices).
NOTE 3 This part of ISO 7396 may also be used as reference for pipeline systems for medical gases and vacuum intended to be installed in places other than healthcare facilities.
ISO 7396-1:2016 applies to the following different types of oxygen supply systems:
- supply systems in which all sources of supply deliver oxygen; in this case the concentration of the oxygen will be greater than 99%;
- supply systems in which all sources of supply deliver oxygen 93; in this case the concentration of the oxygen may vary between 90% and 96%;
NOTE 4 A mixture of oxygen 93 and oxygen may be delivered by a medical gas supply system. In this case the concentration of the gas can vary between 90% and >99%.
ISO 7396-1:2016 also applies to:
- extensions of existing pipeline distribution systems;
- modifications of existing pipeline distribution systems;
- modifications or replacement of supply systems or sources of supply.
Oxygen concentrators for domiciliary use are excluded from the scope of this part of ISO 7396.
NOTE 5 Requirements for oxygen concentrators for domiciliary use are specified in ISO 80601‑2-69.
(*) EN 14931 defines additional requirements for hyperbaric application, in particular for flows and pressures of compressed air required to pressurize the hyperbaric chamber and to drive other connected services. Also included are requirements for oxygen and other treatment gases administered to patients.
ISO 7396-1:2016 does not apply to vacuum systems intended to be used in dentistry.
ISO 7396-1:2016 does not apply to filling systems for transportable cylinders and transportable cylinder bundle systems.

Status
Not Published
Public Enquiry End Date
21-Oct-2026
Technical Committee
VAZ - Healthcare
Current Stage
4020 - Public enquire (PE) (Adopted Project)
Start Date
14-Aug-2026
Due Date
01-Jan-2027
Completion Date
02-Nov-2026

Buy Documents

Draft

oSIST prEN ISO 7396-1:2026

English language (203 pages)
Preview
Preview
e-Library read for
×1 day

oSIST prEN ISO 7396-1:2026 is the Slovenian adoption of the ISO draft standard for medical gas pipeline systems. It specifies requirements for the design, installation, function, performance, testing, commissioning and documentation of pipeline systems for compressed medical gases and vacuum in healthcare facilities. It is aimed at manufacturers, installers, healthcare facility managers and the technical and quality staff who specify, build, operate and verify these systems.

What does oSIST prEN ISO 7396-1:2026 specify?

oSIST prEN ISO 7396-1:2026 specifies safety and performance requirements for medical gas pipeline systems in healthcare facilities, both public and private. It covers supply systems, pipeline distribution systems, control systems, monitoring and alarm systems, and the non-interchangeability of components between different gas and vacuum systems.

The scope includes systems for argon, pharmacopeial oxygen, nitrous oxide, medical air, carbon dioxide, oxygen/nitrous oxide mixtures, helium/oxygen mixtures, oxygen 93, nitrogen, vacuum, and other gases or gas mixtures used for medical purposes. It also covers air and nitrogen used for driving surgical tools. Exclusions include anaesthetic gas scavenging disposal systems, oxygen concentrators for domiciliary use, vacuum systems for dentistry, and filling systems for transportable cylinders and transportable cylinder bundle systems.

This document applies to healthcare facilities of any type, size, location or service range, including acute care, continuing care, long-term care, community-based providers, and ambulatory or external patient care clinics. It may also be used as a reference for similar installations outside healthcare facilities.

AnnexWhat it covers
ASchematic representations of typical supply systems and area distribution systems
BLocation guidance for cylinder manifolds, cylinder storage areas and stationary cryogenic vessels
CExample procedure for testing and commissioning
DForms for documenting conformity and test results
EPressure-temperature correction and a worked example
FRationale for air compressor unit hazards
GOperational guidance for management, responsibilities and procedures
HRisk management procedure and checklist
IRationale for selected requirements
KResponsibilities for medical gas quality and on-site manufacture
LRole separation for design, installation, verification and operation
MExamples of pharmacopeial requirements for on-site production

What are the key requirements of oSIST prEN ISO 7396-1:2026?

oSIST prEN ISO 7396-1:2026 requires the whole system to be designed so the correct gas or vacuum reaches the correct terminal point, with risks assessed and controlled across the complete lifecycle. It then sets out the supply redundancy, pressure control, monitoring, installation and testing needed to keep the system safe in use.

Safety, risk management and materials

Clause 4 makes risk management central to the standard. The system has to be assessed as a whole, risks to patients and staff have first priority, and the risk assessment must be documented. In practice, this means design decisions, changes and maintenance work all need a traceable safety rationale, not just a technical layout.

Clause 4 also requires suitable materials for gas-contacting parts, resistance to corrosion, oxygen compatibility where relevant, and compatible lubricants if lubricants are used. This matters because contamination, ignition, corrosion and material incompatibility can affect gas quality and patient safety.

Supply systems and continuity of supply

Clause 5 sets the basic supply architecture. Supply systems for compressed medicinal gases and vacuum are built around multiple sources so the system can keep running during failure or maintenance, and vacuum systems use multiple pumps. Air or nitrogen for driving surgical tools has its own supply arrangements, because those services are operationally important but not the same as medicinal gas supply.

Clause 5 also covers primary, secondary and reserve sources, outlet pressure, pressure relief, maintenance supply assemblies, and line pressure regulators. It means the facility must plan for normal demand, peak demand, and source changeover without interrupting service.

Clause 5 includes several source types: cylinders and cylinder bundles, cryogenic or non-cryogenic vessels, air compressor unit(s), oxygen concentrator unit(s), proportioning unit(s), and systems assembled at site or preassembled in a factory. For buyers and engineers, this is the part that drives selection of the supply concept and the equipment package.

Monitoring and alarms

Clause 6 divides alarm functions into operating alarms, emergency operating alarms, emergency clinical alarms and information signals. The difference matters in practice because each type has a different urgency and different users: technical staff, clinical staff, or both.

Clause 6 also requires visual and auditory signals, alarm initiation on communication failure, and remote alarm extensions where required. Specific alarm conditions include source changeover, low supply, external power failure, gas quality out of range, and unsafe pressure conditions. This helps staff detect loss of supply, contamination or pressure faults early enough to respond.

Distribution pressure, valves and terminal points

Clause 7 requires pipeline distribution systems to withstand 1.2 times the maximum pressure that can occur under single fault condition. It also limits distribution pressure and terminal-unit pressure, including a specific absolute limit for vacuum. In practice, this is what keeps the network from being overstressed and from delivering unsafe pressure to patients or tools.

Clauses 8 to 10 cover shut-off valves, non-return valves, terminal units, pressure regulators, pressure gauges, marking and colour coding. Valves must be identifiable, secure from unauthorized operation, and placed so sections or areas can be isolated for maintenance or emergencies. Terminal units must be gas-specific, and colour coding follows ISO 5359 when used.

Installation, testing and documentation

Clause 11 sets installation rules for routing, supports, joints, protection from damage, and extensions or modifications to existing systems. Metallic joints are brazed except where specific mechanical joints are allowed, and the pipeline is purged during brazing or welding. That reduces leak risk, contamination and installation defects.

Clause 12 requires testing and commissioning before use, with calibrated measuring devices and documented results. It includes tests for leakage, mechanical integrity, cross-connection, obstruction and flow, particulate contamination, gas identity, source performance and monitoring and alarm performance. The standard also requires a written statement of conformance and permanent records for the healthcare facility.

Clause 13 requires documentation for installation, use, operation and maintenance, plus as-installed drawings and test reports. In practice, the facility needs the information needed to run the system safely long after the installer has left.

What terms does oSIST prEN ISO 7396-1:2026 define?

  • Medical gas pipeline system (MGPS) - The installed pipeline system that supplies medical gases and vacuum to terminal units in a healthcare facility.
  • Applicable policy - The set of requirements that apply to a medical device or accessory, including form, fit, function, process or manufacturer information.
  • Air compressor unit - The part of a supply source that compresses or moves ambient air, together with the drive system and required operating components.
  • Air for driving surgical tools - A gas mixture mainly of oxygen and nitrogen, supplied for powering surgical tools.
  • Audio off - A temporary state in which part or all of an alarm system does not produce an audible alarm signal.
  • Booster compressor unit - A compressor unit used to raise an already elevated pressure to a higher pressure.
  • Authorized person (AP) - The person appointed to manage the day-to-day operation of a designated MGPS or section of it.
  • Quality controller (QC) - The person responsible for quality control of the medical gas supply and related verification activities.

Who uses oSIST prEN ISO 7396-1:2026?

oSIST prEN ISO 7396-1:2026 is used by hospitals, long-term care facilities, clinics and other healthcare providers that install or operate medical gas pipeline systems. It is also used by manufacturers, system designers, installers, maintenance contractors and testing personnel who need to build or verify the system against a common technical basis.

In practice, it is used by executive managers, facilities engineering managers, authorized persons, competent persons, quality controllers, designated medical officers and designated nursing officers to assign responsibilities and control changes, maintenance, repairs and emergency actions. Buyers and project teams use it to specify the right supply concept, terminal equipment and documentation package.

What changed in oSIST prEN ISO 7396-1:2026 from the previous edition?

oSIST prEN ISO 7396-1:2026 updates ISO 7396-1:2016.

Which standards are used with oSIST prEN ISO 7396-1:2026?

StandardWhat it contributes
ISO 14971Risk management principles for medical devices
ISO 20417Information to be supplied by the manufacturer
ISO 9170-1Requirements for terminal units for compressed medical gases and vacuum
ISO 10524-2Requirements for manifold and line pressure regulators
ISO 11197Requirements for medical supply units
ISO 5359Low-pressure hose assemblies and colour coding for medical gases
ISO 8573-1Compressed air contaminants and purity classes
ISO 15001:2010Oxygen compatibility of anaesthetic and respiratory equipment
ISO 17672Brazing filler metals
ISO 21969High-pressure flexible connections for medical gas systems
ISO 29463-1High efficiency filter classification, testing and marking
ISO 18562-2Particulate emissions from breathing gas pathways
ISO 3746Sound power and noise measurement method
ISO 4126-1Safety valves for overpressure protection
ISO 5011Performance testing of inlet air cleaning equipment
IEC 60529Degrees of protection provided by enclosures
ISO 7396-2Anaesthetic gas scavenging disposal systems
ISO 80601-2-69Oxygen concentrators for domiciliary use
EN 14931Additional requirements for hyperbaric application

What does the oSIST prEN ISO 7396-1:2026 document contain?

The document contains clauses for scope, normative references, terms, general requirements, supply systems, alarms, distribution systems, valves, terminal units, marking, installation, testing, commissioning and documentation. It also contains tables for pressure limits, alarm conditions and other technical details, plus figures for typical system arrangements.

Annex C provides a worked example of testing and commissioning, including checks before concealment and before use. Annex D gives forms for records, Annex E gives pressure-temperature correction guidance, and Figure 1 in Clause 12 illustrates the particulate contamination test device.

The annexes also include operational guidance, role assignments, risk management checklists and rationale statements. That makes the standard useful not only for design and installation, but also for audits, maintenance planning, training and long-term operation.

Relations

Effective Date
14-Jun-2023
Effective Date
14-Jun-2023

Buy Documents

Draft

oSIST prEN ISO 7396-1:2026

English language (203 pages)
Preview
Preview
e-Library read for
×1 day

Get Certified

Connect with accredited certification bodies for this standard

BSI Group

BSI (British Standards Institution) is the business standards company that helps organizations make excellence a habit.

UKAS United Kingdom Verified

TÜV Rheinland

TÜV Rheinland is a leading international provider of technical services.

DAKKS Germany Verified

TÜV SÜD

TÜV SÜD is a trusted partner of choice for safety, security and sustainability solutions.

DAKKS Germany Verified

Sponsored listings

Frequently Asked Questions

oSIST prEN ISO 7396-1:2026 is a draft published by the Slovenian Institute for Standardization (SIST). Its full title is "Medical gas pipeline systems - Part 1: Pipeline systems for compressed medical gases and vacuum (ISO/FDIS 7396-1:2026)". This standard covers: ISO 7396-1:2016 specifies requirements for design, installation, function, performance, testing, commissioning and documentation of pipeline systems used in healthcare facilities for the following: - oxygen; - nitrous oxide; - medical air; - carbon dioxide; - oxygen/nitrous oxide mixtures (see Note 1); - helium/oxygen mixtures; - (*) oxygen 93; - gases and gas mixtures classified as medical device, gases delivered to medical devices or intended for medical purposes or gases and gas mixtures for medicinal use not specified above; - air for driving surgical tools; - nitrogen for driving surgical tools; - vacuum. NOTE 1 Regional or national regulations may prohibit the distribution of oxygen/nitrous oxide mixtures in medical gas pipeline systems. NOTE 2 Anaesthetic gas scavenging disposal systems are covered in ISO 7396‑2. This part of ISO 7396 includes requirements for supply systems, pipeline distribution systems, control systems, monitoring and alarm systems and non-interchangeability between components of different gas/vacuum systems. This part of ISO 7396 specifies safety requirements for pipeline systems used in healthcare facilities, both public and private. It applies to all facilities providing healthcare services regardless of type, size, location or range of services, including, but not limited to: a) acute care healthcare facilities; b) internal patient continuing care healthcare facilities; c) long-term care facilities; d) community-based providers; e) ambulatory and external patient care clinics (e.g. day surgery, endoscopy clinics and doctors' offices). NOTE 3 This part of ISO 7396 may also be used as reference for pipeline systems for medical gases and vacuum intended to be installed in places other than healthcare facilities. ISO 7396-1:2016 applies to the following different types of oxygen supply systems: - supply systems in which all sources of supply deliver oxygen; in this case the concentration of the oxygen will be greater than 99%; - supply systems in which all sources of supply deliver oxygen 93; in this case the concentration of the oxygen may vary between 90% and 96%; NOTE 4 A mixture of oxygen 93 and oxygen may be delivered by a medical gas supply system. In this case the concentration of the gas can vary between 90% and >99%. ISO 7396-1:2016 also applies to: - extensions of existing pipeline distribution systems; - modifications of existing pipeline distribution systems; - modifications or replacement of supply systems or sources of supply. Oxygen concentrators for domiciliary use are excluded from the scope of this part of ISO 7396. NOTE 5 Requirements for oxygen concentrators for domiciliary use are specified in ISO 80601‑2-69. (*) EN 14931 defines additional requirements for hyperbaric application, in particular for flows and pressures of compressed air required to pressurize the hyperbaric chamber and to drive other connected services. Also included are requirements for oxygen and other treatment gases administered to patients. ISO 7396-1:2016 does not apply to vacuum systems intended to be used in dentistry. ISO 7396-1:2016 does not apply to filling systems for transportable cylinders and transportable cylinder bundle systems.

ISO 7396-1:2016 specifies requirements for design, installation, function, performance, testing, commissioning and documentation of pipeline systems used in healthcare facilities for the following: - oxygen; - nitrous oxide; - medical air; - carbon dioxide; - oxygen/nitrous oxide mixtures (see Note 1); - helium/oxygen mixtures; - (*) oxygen 93; - gases and gas mixtures classified as medical device, gases delivered to medical devices or intended for medical purposes or gases and gas mixtures for medicinal use not specified above; - air for driving surgical tools; - nitrogen for driving surgical tools; - vacuum. NOTE 1 Regional or national regulations may prohibit the distribution of oxygen/nitrous oxide mixtures in medical gas pipeline systems. NOTE 2 Anaesthetic gas scavenging disposal systems are covered in ISO 7396‑2. This part of ISO 7396 includes requirements for supply systems, pipeline distribution systems, control systems, monitoring and alarm systems and non-interchangeability between components of different gas/vacuum systems. This part of ISO 7396 specifies safety requirements for pipeline systems used in healthcare facilities, both public and private. It applies to all facilities providing healthcare services regardless of type, size, location or range of services, including, but not limited to: a) acute care healthcare facilities; b) internal patient continuing care healthcare facilities; c) long-term care facilities; d) community-based providers; e) ambulatory and external patient care clinics (e.g. day surgery, endoscopy clinics and doctors' offices). NOTE 3 This part of ISO 7396 may also be used as reference for pipeline systems for medical gases and vacuum intended to be installed in places other than healthcare facilities. ISO 7396-1:2016 applies to the following different types of oxygen supply systems: - supply systems in which all sources of supply deliver oxygen; in this case the concentration of the oxygen will be greater than 99%; - supply systems in which all sources of supply deliver oxygen 93; in this case the concentration of the oxygen may vary between 90% and 96%; NOTE 4 A mixture of oxygen 93 and oxygen may be delivered by a medical gas supply system. In this case the concentration of the gas can vary between 90% and >99%. ISO 7396-1:2016 also applies to: - extensions of existing pipeline distribution systems; - modifications of existing pipeline distribution systems; - modifications or replacement of supply systems or sources of supply. Oxygen concentrators for domiciliary use are excluded from the scope of this part of ISO 7396. NOTE 5 Requirements for oxygen concentrators for domiciliary use are specified in ISO 80601‑2-69. (*) EN 14931 defines additional requirements for hyperbaric application, in particular for flows and pressures of compressed air required to pressurize the hyperbaric chamber and to drive other connected services. Also included are requirements for oxygen and other treatment gases administered to patients. ISO 7396-1:2016 does not apply to vacuum systems intended to be used in dentistry. ISO 7396-1:2016 does not apply to filling systems for transportable cylinders and transportable cylinder bundle systems.

oSIST prEN ISO 7396-1:2026 is classified under the following ICS (International Classification for Standards) categories: 11.040.10 - Anaesthetic, respiratory and reanimation equipment. The ICS classification helps identify the subject area and facilitates finding related standards.

oSIST prEN ISO 7396-1:2026 has the following relationships with other standards: It is inter standard links to SIST EN ISO 7396-1:2016, SIST EN ISO 7396-1:2016/A1:2019. Understanding these relationships helps ensure you are using the most current and applicable version of the standard.

oSIST prEN ISO 7396-1:2026 is associated with the following European legislation: EU Directives/Regulations: 2017/745, 93/42/EEC; Standardization Mandates: M/023, M/575. When a standard is cited in the Official Journal of the European Union, products manufactured in conformity with it benefit from a presumption of conformity with the essential requirements of the corresponding EU directive or regulation.

oSIST prEN ISO 7396-1:2026 is available in PDF format for immediate download after purchase. The document can be added to your cart and obtained through the secure checkout process. Digital delivery ensures instant access to the complete standard document.

Standards Content (Sample)

Contents

  • Introduction
  • 1 Scope
  • 2 Normative references
  • 3 Terms and definitions
  • 3.1 applicable policy
  • 3.2 air compressor unit
  • 3.3 air for driving surgical tools
  • 3.4 audio off
  • 3.5 booster compressor unit
  • 3.6 commissioning
  • 3.7 control equipment
  • 3.8 control system
  • 3.9 cryogenic vessel
  • 3.10 cylinder bundle
  • 3.11 diversity factor
  • 3.12 double-stage pipeline distribution system
  • 3.13 emergency clinical alarm
  • 3.14 emergency operating alarm
  • 3.15 emergency power supply
  • 3.16 feed air unit
  • 3.17 gas-specific
  • 3.18 gas-specific connector
  • 3.19 healthcare facility
  • 3.20 high-dependency patient
  • 3.21 high pressure
  • 3.22 high-pressure reservoir
  • 3.23 information signal
  • 3.24 line pressure regulator
  • 3.25 low pressure
  • 3.26 low-pressure hose assembly
  • 3.27 main line
  • 3.28 maintenance supply assembly
  • 3.29 manifold
  • 3.30 manufacturer
  • 3.31 maximum distribution pressure
  • 3.32 medical air
  • 3.33 medical device gas
  • 3.34 medical gas pipeline system
  • 3.35 nominal distribution pressure
  • 3.36 nominal supply system pressure
  • 3.37 normal condition
  • 3.38 non-return valve
  • 3.39 operating alarm
  • 3.40 pharmacopeial oxygen
  • 3.41 pipeline branch
  • 3.42 pipeline distribution system
  • 3.43 pressure regulator
  • 3.44 pressure relief valve
  • 3.45 primary source of supply
  • 3.46 proportioning unit
  • 3.47 reserve source of supply
  • 3.48 riser
  • 3.49 reservoir
  • 3.50 safety
  • 3.51 Sample port
  • 3.52 secondary source of supply
  • 3.53 shut-off valve
  • 3.54 single fault condition
  • 3.55 single-stage pipeline distribution system
  • 3.56 source of supply
  • 3.57 source of supply with proportioning unit
  • 3.58 source of supply with air compressor unit
  • 3.59 source of supply with oxygen concentrator unit(s)
  • 3.60 supply system
  • 3.61 system design flow
  • 3.62 terminal unit
  • 3.63 vacuum receiver
  • 3.64 vacuum supply system
  • 4 General requirements
  • 4.1 General
  • 4.2 Safety and risk management
  • 4.3 Gases for medical use
  • 4.4 Materials
  • 4.5 System design
  • 5 Supply systems
  • 5.1 Supply system components
  • 5.2 General Requirements for supply systems
  • 5.3 Supply systems with cylinders, cylinder bundles or high pressure reservoir(s)
  • 5.4 Supply systems with cryogenic or non cryogenic vessels
  • 5.5 Supply systems for air

Introduction

Many healthcare facilities use medical gas pipeline systems to deliver medical gases and to provide vacuum to areas where they are used in patient care or to power equipment such as ventilators and surgical tools. This document specifies requirements for medical gas pipeline systems for gases for medicinal use, medical device gases, gases for driving surgical tools and vacuum. It is intended for use by those persons involved in the design, construction, inspection, and operation of healthcare facilities treating human beings. Those persons involved in the design, manufacture and testing of equipment intended to be connected to these medical gas pipeline systems should also be aware of the contents of this document. This document seeks to ensure that medical gas pipelines contain only the specific gas (or vacuum) intended to be supplied. For this reason, gas-specific components are used for terminal units and for other connectors which are intended to be used by the operator. In addition, each system is tested and certified to contain only the specific gas (or vacuum).

The objectives of this document are to ensure the following:

a) non-interchangeability between different medical gas pipeline systems by design, installation and testing; b) continuous supply of gases and vacuum at specified quality, pressures and design flow rates by providing appropriate sources; c) use of suitable materials; d) cleanliness of components; e) correct installation; f) provision of monitoring and alarm systems; g) correct marking of the pipeline system; h) testing and commissioning; i) quality of the gases delivered by the pipeline system; j) correct operational management; k) safety features of the sources to ensure the quality and pressure of the gases delivered to the terminals according to specification.

It is normal practice to assign responsibility for the quality of the medical gas supplied to a nominated person within the healthcare facility such as the head pharmacist. Where the healthcare facility manufactures the medical gas on site the healthcare facility is responsible for all aspects of the medical gas quality. Vacuum for medical suction is also the responsibility of the healthcare facility. [37] EN 14931:2006 defines additional requirements for hyperbaric application, in particular for flow rates and pressures of compressed air required to pressurize hyperbaric chambers and to drive other connected services. Also included are requirements for oxygen and other treatment gases administered to patients during hyperbaric therapies. Annex G, J and K provides guidance for the assignment of responsibility for production and quality control of the gases and vacuum.

Annexes G and H provide some guidance as to how the quality of the gas should be managed to maintain patient safety at the highest level.

Annex I contains rationale statements for some of the requirements of this document. It is included to provide additional insight into the reasoning that led to the requirements and recommendations that have been incorporated into this document.

oSIST prEN ISO 7396-1:2026 FINAL DRAFT International Standard ISO/FDIS 7396-1:2026(en) Medical gas pipeline systems — Part 1:

Pipeline systems for compressed medical gases and vacuum

1 Scope

This document specifies requirements for design, installation, function, performance, testing, commissioning and documentation of medical gas pipeline systems used in healthcare facilities for the following:

  • argon;
  • pharmacopeial oxygen;
  • nitrous oxide;
  • medical air;
  • carbon dioxide;
  • oxygen/nitrous oxide mixtures;
  • helium/oxygen mixtures;
  • gases and gas mixtures classified as medical device, gases delivered to medical devices or intended for medical purposes or gases and gas mixtures for medicinal use not specified above;
  • air for driving surgical tools;
  • nitrogen;
  • vacuum.

NOTE 1 A rationale for this is contained in Annex I.2 [6] NOTE 2 Anaesthetic gas scavenging disposal systems are covered in ISO 7396-2 . This document includes requirements for supply systems, medical gas pipeline distribution systems, control system(s), monitoring and alarm systems and non-interchangeability between different gas/vacuum systems.

This document specifies safety requirements for medical gas pipeline systems used in healthcare facilities. It applies to all facilities providing healthcare services regardless of type, size, location or range of services, including, but not limited to:

a) acute care healthcare facilities; b) internal patient continuing care healthcare facilities; c) long-term care facilities; d) community-based providers; e) ambulatory and external patient care clinics (e.g. day surgery, endoscopy clinics and doctors’ offices). This document may also be used as reference for medical gas pipeline systems intended to be installed in places other than healthcare facilities.

oSIST prEN ISO 7396-1:2026 ISO/FDIS 7396-1:2026(en) This document applies to the following different types of oxygen supply systems:

  • supply systems in which all sources of supply deliver oxygen produced off-site;
  • supply systems in which some or all sources of supply deliver oxygen produced on-site; in this case the concentration of the oxygen may vary, depending on the pharmacopeial specification selected by the healthcare facility Oxygen concentrators for domiciliary use are excluded from the scope of this document. This document also applies to:
  • extensions of existing pipeline distribution systems;
  • modifications of existing pipeline distribution systems;
  • modifications or replacement of supply systems or sources of supply. This document does not apply to vacuum systems intended to be used in dentistry (A rationale is discussed in Annex I.2) This document does not apply to filling systems for transportable cylinders and transportable cylinder bundle systems.

This document does not apply to cryogenic pipeline systems conveying liquified gases.

2 Normative references

The following documents are referred to in the text in such a way that some or all of their content constitutes requirements of this document. For dated references, only the edition cited applies. For undated references, the latest edition of the referenced document (including any amendments) applies. ISO 3746, Acoustics — Determination of sound power levels and sound energy levels of noise sources using sound pressure — Survey method using an enveloping measurement surface over a reflecting plane ISO 4126-1, Safety devices for protection against excessive pressure — Part 1: Safety valves ISO 5011, Inlet air cleaning equipment for internal combustion engines and compressors — Performance testing ISO 5359, Anaesthetic and respiratory equipment — Low-pressure hose assemblies for use with medical gases ISO 8573-1, Compressed air — Part 1: Contaminants and purity classes ISO 9170-1, Terminal units for medical gas pipeline systems — Part 1: Terminal units for use with compressed medical gases and vacuum ISO 10524-2, Pressure regulators for use with medical gases — Part 2: Manifold and line pressure regulators ISO 11197, Medical supply units ISO 14971, Medical devices — Application of risk management to medical devices ISO 15001:2010, Anaesthetic and respiratory equipment — Compatibility with oxygen ISO 17672, Brazing — Filler metals ISO 20417, Medical devices — Information to be supplied by the manufacturer ISO 21969, High-pressure flexible connections for use with medical gas systems ISO 29463-1, High efficiency filters and filter media for removing particles in air — Part 1: Classification, performance, testing and marking ISO 18562-2, Biocompatibility evaluation of breathing gas pathways in healthcare applications — Part 2: Tests for emissions of particulate matter

oSIST prEN ISO 7396-1:2026 ISO/FDIS 7396-1:2026(en) IEC 60529, Degrees of protection provided by enclosures (IP Code) IEC 60601-1-8, Medical electrical equipment — Part 1-8: General requirements for basic safety and essential performance — Collateral standard: General requirements, tests and guidance for alarm systems in medical electrical equipment and medical electrical systems IEC 62304, Medical device software — Software life cycle processes EN 286-1, Simple unfired pressure vessels designed to contain air or nitrogen — Part 1: Pressure vessels for general purposes EN 837-1, Pressure gauges, Bourdon tube pressure gauges, Dimensions, metrology, requirements and testing EN 1254-1, Copper and copper alloys - Plumbing fittings - Fittings with ends for capillary soldering or capillary brazing to copper tubes EN 1012-1, Compressors and vacuum pumps - Safety requirements - Part 1: Air Compressors EN 1012-2, Compressors and vacuum pumps - Safety requirements - Part 2: Vacuum Pumps EN 13348, Copper and copper alloys — Seamless, round copper tubes for medical gases or vacuum EN 13445-1, Unfired pressure vessels - Part 1: General

3 Terms and definitions

For the purposes of this document, the following terms and definitions apply. ISO and IEC maintain terminology databases for use in standardization at the following addresses:

  • ISO Online browsing platform: available at https:// www .iso .org/ obp
  • IEC Electropedia: available at https:// www .electropedia .org/

3.1 applicable policy

set of requirements relating to the medical device or accessory and its attributes such as form, fit, function, process or information to be supplied by the manufacturer Note 1 to entry: The applicable policy can be established by the authority having jurisdiction. Note 2 to entry: The applicable policy can include specification for the format of the information to be supplied by the manufacturer.

3.2 air compressor unit

the portion of the source of supply including the device for compressing or moving ambient air (typical examples are compressors and blowers). The air compressor unit comprises the compressor, a drive system and any component or device which is necessary for operation

3.3 air for driving surgical tools

natural or synthetic mixture of gases, mainly composed of oxygen and nitrogen in specified proportions, with defined limits for the concentration of contaminants, supplied by a medical gas pipeline system and intended for driving surgical tools Note 1 to entry: Different names or symbols are used for air for driving surgical tools, such as instrument air, surgical air, air motor, air - 700 and air - 800.

Note 2 to entry: Nitrogen can also be used to drive surgical tools.

oSIST prEN ISO 7396-1:2026 ISO/FDIS 7396-1:2026(en)

3.4 audio off

state of limited duration in which the alarm system or part of the alarm system does not generate an auditory alarm signal Note 1 to entry: This is sometimes referred to as silencing.

[SOURCE: IEC 60601-1-8 2006 3.12]

3.5 booster compressor unit

compressor unit used to raise an elevated pressure to a higher pressure Note 1 to entry: As used herein, the term applies to compressors used to fill high-pressure reservoir(s).

3.6 commissioning

proof of function to verify that the agreed system specification is met and is accepted by the responsible organization

3.7 control equipment

items necessary to maintain a medical gas pipeline system within the specified operating parameters Note 1 to entry: Examples of control equipment are pressure regulators, pressure relief valves, sensors, manual or automatic valves and non-return valves.

3.8 control system

device or set of devices to manage, command, direct or regulate the behaviour of other device(s) or system(s)

3.9 cryogenic vessel

vacuum jacketed vessel intended for application at low temperature involving liquefied gases

3.10 cylinder bundle

pack or pallet of cylinders linked together with one or more connectors for filling and emptying

3.11 diversity factor

number which represents the maximum proportion of terminal units in a defined clinical area which will be used at the same time, at flow rates defined in agreement with the management of the healthcare facility

3.12 double-stage pipeline distribution system

pipeline distribution system in which gas is initially distributed from the supply system at a pressure higher than the nominal distribution pressure, and is then reduced to the nominal distribution pressure by line pressure regulator(s) Note 1 to entry: This initial higher pressure is the nominal supply system pressure (see 3.38).

3.13 emergency clinical alarm

alarm to indicate to medical and technical staff that there is a deviation from a monitored parameter which requires an immediate response

3.14 emergency operating alarm

alarm to indicate to technical staff that there is a deviation from a monitored parameter which requires an immediate response

oSIST prEN ISO 7396-1:2026 ISO/FDIS 7396-1:2026(en)

3.15 emergency power supply

an emergency power supply is an independent source of electrical power that supports important electrical systems on loss of normal power supply. An emergency power supply may include a standby generator, batteries and other apparatus

3.16 feed air unit

means of compressing ambient air (e.g.: air compressor unit, air blower unit).

3.17 gas-specific

having characteristics which prevent connections between different gas services or vacuum services

3.18 gas-specific connector

connector with dimensional characteristics which prevent connections between different gas services Note 1 to entry: Examples of gas-specific connectors are quick connectors, screw-threaded connectors, diameterindexed safety system (DISS) connectors, non-interchangeable screw-threaded (NIST) connectors and sleeve indexed system (SIS) connectors.

3.19 healthcare facility

dedicated setting where health care professionals deliver services for patient care

3.20 high-dependency patient

patient with a continual need of a medical gas/vacuum supply, who will be adversely affected by a medical gas/vacuum supply failure to such a degree that his/her clinical condition or safety can be compromised

3.21 high pressure

pressures greater than 3 000 kPa

3.22 high-pressure reservoir

permanently installed container(s) with nominal working pressures greater than 3 000 kPa and up to 25 000 kPa at 15 °C Note 1 to entry: installed container include cylinders and cylinders bundles, intended to be permanent in the healthcare facility

3.23 information signal

signal that is not an alarm signal or a reminder signal

3.24 line pressure regulator

pressure regulator used in a pipeline distribution system to reduce the nominal supply system pressure to the nominal distribution pressure

3.25 low pressure

pressures lower than 1 400 kPa

3.26 low-pressure hose assembly

assembly consisting of a flexible hose with permanently attached gas-specific inlet and outlet connectors and designed to conduct a medical gas at pressures less than 1 400 kPa

oSIST prEN ISO 7396-1:2026 ISO/FDIS 7396-1:2026(en)

3.27 main line

portion of the pipeline distribution system connecting the supply system to risers and/or pipeline branches

3.28 maintenance supply assembly

source of supply intended to supply the system during maintenance

3.29 manifold

device for connecting the outlet(s) of one or more cylinders, cylinder bundles or high-pressure reservoir(s) of the same gas to the pipeline system using a high-pressure flexible connection

3.30 manufacturer

natural or legal person with responsibility for the design, manufacture, packaging and labelling of a device before it is placed on the market under his own name, regardless of whether these operations are carried out by that person or on their behalf by a third party Note 1 to entry: See also Annex L.

3.31 maximum distribution pressure

pressure at any terminal unit when the medical gas pipeline system isoperating at zero flow

3.32 medical air

natural or synthetic mixture of gases, mainly composed of oxygen and nitrogen in specified proportions, with defined limits for the concentration of contaminants, supplied by a medical gas pipeline system and intended for administration to patients Note 1 to entry: Medical air can be produced by supply systems with air compressor sources of supply or by supply systems with proportioning units on site or by a manufacturer off site. Medical air produced by air compressor systems is called “medicinal air”, and medical air produced by proportioning systems is called “synthetic medicinal air” by the European Pharmacopoeia

3.33 medical device gas

gas or mixture of gases intended by the manufacturer to be used for human beings for the purpose of:

  • diagnosis, prevention, monitoring, treatment or alleviation of disease;
  • investigation, replacement or modification of the anatomy or of a physiological process;
  • control of conception; and that does not achieve its principal intended action in or on the human body by pharmacological, immunological or metabolic means, but which may be assisted in its function by such means.

3.34 medical gas pipeline system

complete system which comprises a supply system, a monitoring and alarm system and a distribution system with terminal units at the points where medical gases or vacuum are required

3.35 nominal distribution pressure

pressure which the medical gas pipeline system is intended to deliver at the terminal units

3.36 nominal supply system pressure

pressure which the supply system is intended to deliver at the inlet to the line pressure regulator when flowing at the design flow rate for the medical gas pipeline.

oSIST prEN ISO 7396-1:2026 ISO/FDIS 7396-1:2026(en)

3.37 normal condition

condition in which all means provided for protection against hazards are intact

3.38 non-return valve

valve which permits flow in one direction only

3.39 operating alarm

alarm to indicate to technical staff that it is necessary to replenish the gas supply or to correct a malfunction

3.40 pharmacopeial oxygen

oxygen conforming to the pharmacopeia required by the regulatory authority having jurisdiction or the pharmacopeia selected by the healthcare facility

3.41 pipeline branch

portion of the pipeline distribution system which supplies one or more areas on the same floor of the healthcare facility

3.42 pipeline distribution system

portion of a medical gas or vacuum pipeline system linking the sources of supply of the supply system to the terminal units

3.43 pressure regulator

device which reduces the inlet pressure and maintains the set outlet pressure within specified limits

3.44 pressure relief valve

device intended to relieve excess pressure at a pre-set pressure

3.45 primary source of supply

portion of the supply system which is the first to be drawn upon to supply the medical gas pipeline distribution system

3.46 proportioning unit

device in which gases are mixed in a specified ratio

3.47 reserve source of supply

that source of supply which supplies the pipeline distribution system (or part(s) thereof) in the event both the primary and secondary sources of supply fail, are exhausted or under maintenance.

3.48 riser

portion of the pipeline distribution system traversing one or more floors and connecting the main line with pipeline branch lines on various levels

3.49 reservoir

permanently installed container(s) designed for storing gas at pressures up to 3 000 kPa Note 1 to entry: See also vacuum receiver (3.62)

oSIST prEN ISO 7396-1:2026 ISO/FDIS 7396-1:2026(en)

3.50 safety

freedom from unacceptable risk

3.51 Sample port

A designated port on a medical gas pipeline system intended to allow the safe and controlled taking of a gas sample.

...