Valves for water supply - Fitness for purpose requirements and appropriate verification tests - Part 2: Isolating valves

To correct the test procedure described in C.2 of annex C 'Test method for the operation of valves".

Armaturen für die Wasserversorgung - Anforderungen an die Gebrauchstauglichkeit und deren Prüfung - Teil 2: Absperrarmaturen

Robinetterie pour l'alimentation en eau - Prescriptions d'aptitude à l'emploi et vérifications s'y rapportant - Partie 2: Robinetterie de sectionnement

Ventili za oskrbo z vodo - Zahteve za ustreznost in ustrezni preskusi - 2. del: Zapirni ventili

General Information

Status
Published
Publication Date
27-Apr-2004
Withdrawal Date
30-Oct-2004
Technical Committee
CEN/TC 69 - Industrial valves
Current Stage
6060 - Definitive text made available (DAV) - Publishing
Start Date
28-Apr-2004
Completion Date
28-Apr-2004

Relations

Effective Date
22-Dec-2008

Overview

EN 1074-2:2000/A1:2004 is a CEN amendment addressing valves for water supply - Part 2: Isolating valves. The amendment corrects the test procedure in Annex C (C.2: "Test method for the operation of valves") and clarifies the verification sequence for isolating (shut-off) valves. It focuses on ensuring fitness for purpose through practical verification tests that confirm seat tightness and operational torque under hydrostatic conditions.

Key Topics and Requirements

  • Scope: Applies to verification tests for isolating valves used in water supply systems; the amendment revises the C.2 test method.
  • Test procedure (corrected C.2) - key steps include:
    • Fit a blanking plate with a vent valve to the outlet flange and connect the inlet to a hydrostatic pressure source.
    • Partially open the obturator and the vent valve; fully fill the valve body and vent all air.
    • Close the obturator and apply a torque equal to MOT (the specified test torque).
    • Raise pressure to PFA (the specified test pressure) and maintain it for at least one minute.
    • Check seat tightness while holding pressure.
    • Open and close the valve while ensuring the running torque during operation does not exceed MOT; record the maximum torque observed.
    • Repeat the entire test from the opposite side (bi‑directional verification).
  • Operational checks: Confirms both leak-tightness at the seat and that operating torque remains within acceptable limits during pressurized cycling.
  • Practical notes included: The test procedure highlights that a large volume of water is evacuated through the vent valve during opening.

Applications and Users

This standard and its corrected test method are essential for:

  • Valve manufacturers - type testing, quality control, and design verification for isolating valves.
  • Independent test laboratories - performing hydrostatic and operational torque tests to certify compliance.
  • Water utilities and network operators - specifying procurement and acceptance criteria to ensure reliable isolation under pressure.
  • Specifiers and regulators - incorporating fitness-for-purpose requirements into technical specifications and approvals.
  • Installers and maintenance teams - understanding test expectations for commissioning and troubleshooting.

Related Standards

  • EN 1074 series (other parts covering valves for water supply) and documents produced by CEN/TC 69 (Industrial valves).
  • National adoptions (e.g., SIST EN 1074-2:2001/A1:2004) reflect mandatory implementation timelines across CEN member bodies.

Keywords: EN 1074-2:2000/A1:2004, valves for water supply, isolating valves, fitness for purpose, verification tests, test procedure, hydrostatic pressure, seat tightness, MOT, PFA.

Amendment

EN 1074-2:2001/A1:2004

English language
3 pages
Preview
Preview
e-Library read for
1 day

Frequently Asked Questions

EN 1074-2:2000/A1:2004 is a amendment published by the European Committee for Standardization (CEN). Its full title is "Valves for water supply - Fitness for purpose requirements and appropriate verification tests - Part 2: Isolating valves". This standard covers: To correct the test procedure described in C.2 of annex C 'Test method for the operation of valves".

To correct the test procedure described in C.2 of annex C 'Test method for the operation of valves".

EN 1074-2:2000/A1:2004 is classified under the following ICS (International Classification for Standards) categories: 23.060.01 - Valves in general. The ICS classification helps identify the subject area and facilitates finding related standards.

EN 1074-2:2000/A1:2004 has the following relationships with other standards: It is inter standard links to EN 1074-2:2000. Understanding these relationships helps ensure you are using the most current and applicable version of the standard.

EN 1074-2:2000/A1:2004 is associated with the following European legislation: EU Directives/Regulations: 93/38/EEC; Standardization Mandates: M/BC/CEN/88/15. When a standard is cited in the Official Journal of the European Union, products manufactured in conformity with it benefit from a presumption of conformity with the essential requirements of the corresponding EU directive or regulation.

You can purchase EN 1074-2:2000/A1:2004 directly from iTeh Standards. The document is available in PDF format and is delivered instantly after payment. Add the standard to your cart and complete the secure checkout process. iTeh Standards is an authorized distributor of CEN standards.

Standards Content (Sample)


SLOVENSKI STANDARD
01-september-2004
Ventili za oskrbo z vodo - Zahteve za ustreznost in ustrezni preskusi - 2. del:
Zapirni ventili
Valves for water supply - Fitness for purpose requirements and appropriate verification
tests - Part 2: Isolating valves
Armaturen für die Wasserversorgung - Anforderungen an die Gebrauchstauglichkeit und
deren Prüfung - Teil 2: Absperrarmaturen
Robinetterie pour l'alimentation en eau - Prescriptions d'aptitude a l'emploi et
vérifications s'y rapportant - Partie 2: Robinetterie de sectionnement
Ta slovenski standard je istoveten z: EN 1074-2:2000/A1:2004
ICS:
23.060.01 Ventili na splošno Valves in general
91.140.60 Sistemi za oskrbo z vodo Water supply systems
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.

EUROPEAN STANDARD
EN 1074-2:2000/A1
NORME EUROPÉENNE
EUROPÄISCHE NORM
April 2004
ICS 23.060.01
English version
Valves for water supply - Fitness for purpose requirements and
appropriate verification tests - Part 2: Isolating valves
Robinetterie pour l'alimentation en eau - Prescriptions Armaturen für die Wasserversorgung - Anforderungen an
d'aptitude à l'emploi et vérifications s'y rapportant - Partie 2: die Gebrauchstauglichkeit und deren Prüfung - Teil 2:
Robinetterie de sectionnement Absperrarmaturen
This amendment A1 modifies the European Standard EN 1074-2:2000; it was approved by CEN on 27 February 2004.
CEN members are bound to comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for inclusion of this
amendment into the relevant national standard without any alteration. Up-to-date lists and bibliographical references concerning such
national standards may be obtained on application to the Central Secretariat or to any CEN member.
This amendment exists in three official versions (English, French, German). A version in any other language made by translation under the
responsibility of a CEN member into its own language and notified to the Central Secretariat has the same status as the official versions.
CEN members are the national standards bodies of Austria, Belgium, Cyprus, Czech Republic, Denmark, Estonia, Finland, France,
Germany,
...

Questions, Comments and Discussion

Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.

Loading comments...