This document specifies the procedure for classification of construction products and building elements using data from fire resistance and/or smoke leakage/control tests and/or mechanical tests which are within the direct field of application of the relevant test method. Classification on the basis of extended application of test results is also included in the scope of this document.
This document deals with:
a) loadbearing elements without a fire separating function:
- walls;
- floors;
- roofs;
- beams;
- columns;
- balconies;
- walkways;
- stairs.
b) loadbearing elements with a fire separating function, with or without glazing, services and fixtures:
- walls;
- floors;
- roofs;
- raised floors.
c) products and systems for protecting elements or parts of the works:
- ceilings with no independent fire resistance;
- fire protective coatings, claddings and screens;
d) non-loadbearing elements or parts of works, with or without glazing, services and fixtures:
- partitions;
- facades (curtain walls) and external walls;
- ceilings with independent fire resistance;
- raised floors;
- fire resisting doorsets, shutter assemblies and openable windows and their closing devices;
- smoke control doorsets and shutter assemblies and their closing devices;
- conveyor systems and their closures;
- penetration seals;
- linear joint seals;
- combined penetration seals;
- service ducts and shafts;
- air transfer grilles.
- chimneys.
e) wall and ceiling coverings with fire protection ability.
f) lift landing doors which are tested according to EN 81-58 are excluded from this document. Lift landing doors which are tested in accordance with EN 1634-1 are classified in accordance with 7.5.5.
Relevant test methods which have been prepared for these construction products are listed in Clauses 2 and 7.
Klassifizierung von Bauprodukten und Bauteilen zu ihrem Brandverhalten - Teil 2: Klassifizierung mit den Ergebnissen aus den Feuerwiderstandsprüfungen und/oder Rauchschutzprüfungen, mit Ausnahme von Lüftungsanlagen
Classement au feu des produits et éléments de construction - Partie 2 : Classement à partir des données d’essais de résistance au feu et/ou de contrôle des fumées à l’exclusion des produits utilisés dans les systèmes de ventilation
Požarna klasifikacija gradbenih proizvodov in elementov stavb - 2. del: Klasifikacija na podlagi podatkov iz preskusov požarne odpornosti in/ali dimotesnosti, izvzete so prezračevalne naprave - Dopolnilo A1
General Information
- Status
- Not Published
- Publication Date
- 21-Nov-2027
- Technical Committee
- CEN/TC 127 - Fire safety in buildings
- Drafting Committee
- CEN/TC 127/WG 7 - Classification
- Current Stage
- 4060 - Closure of enquiry - Enquiry
- Start Date
- 12-Feb-2026
- Due Date
- 28-Sep-2026
- Completion Date
- 12-Feb-2026
Relations
- Effective Date
- 27-Dec-2023
Overview
EN 13501-2:2023/prA1 is a key European standard developed by CEN (European Committee for Standardization) that specifies procedures for the fire classification of construction products and building elements. Focusing on fire resistance and smoke control (excluding ventilation services), this standard plays a critical role in ensuring fire safety in buildings across Europe. It defines how products and building elements are classified based on data from fire resistance, smoke leakage/control, and mechanical tests, as well as the procedure for extended application of test results.
This amendment (prA1) updates important provisions of EN 13501-2:2023, reflecting regulatory, procedural, and terminology changes to keep pace with evolving fire safety best practices.
Key Topics
- Scope of Application: Covers a wide range of construction elements including loadbearing and non-loadbearing walls, floors, roofs, beams, columns, balconies, walkways, stairs, ceilings, partitions, facades, fire resisting doorsets, shutters, smoke control solutions, and fire protective coverings.
- Fire Resistance and Smoke Control: Specifies classification procedures based on fire resistance and smoke leakage/control tests, incorporating updated mechanical and extended application protocols.
- Exclusions: Specifically excludes ventilation services and certain lift landing doors, ensuring the focus remains on building components related to compartmentation, escape, and structural performance in fire.
- Regulatory Update: Incorporates alignment with Commission Delegated Regulation (EU) 2024/1681, ensuring fire resistance classes use consistent and regulated designation letters.
- Testing and Classification:
- References standardized fire testing and smoke control test methods.
- Stipulates procedures for expressing classification results (e.g., EI 60-S200), including aspects of extended and direct application.
- Details the classification of closing devices in fire and/or smoke conditions, and the criteria for “self-closing” (C) performance.
- Offers comprehensive rules for evaluating both single and double element products or assemblies, considering gaps, air flow rates, and the effect of seals at door thresholds.
Applications
EN 13501-2:2023/prA1 is directly applicable to a wide array of stakeholders in the construction and building safety sector:
- Manufacturers of fire-resistant construction products and systems who require harmonized classification for marketing, certification, and regulatory purposes.
- Architects, Engineers, Designers specifying compliant products for new buildings or renovations, particularly where fire compartmentation and smoke control are critical.
- Testing Laboratories and notified bodies performing fire and smoke control testing and subsequent performance classification in line with current European legislation.
- Building Regulators and Inspectors enforcing fire safety requirements in building codes and approving products for use within fire-resistant building designs.
- Specifiers and Procurement Professionals selecting products with verified fire and smoke performance credentials in line with European standards for public and private procurement.
Related Standards
EN 13501-2:2023/prA1 references and is complemented by several important related European fire and smoke test standards, including:
- EN 1634-1 & EN 1634-3: Test methods for assessing fire resistance and smoke control of doors, shutters, and windows.
- EN 15269 series: Extended application (EXAP) standards covering fire resistance and smoke control extensions for door and shutter assemblies.
- EN 17020 series: Durability for self-closing mechanisms.
- EN 12605: Mechanical test methods for industrial, commercial, and garage doors and gates.
Other relevant standards within the EN 13501 family address reaction to fire, classification of building materials, and additional aspects of fire behavior, supporting a holistic approach to fire safety in the built environment.
Keywords: fire classification, fire resistance, EN 13501-2, smoke control, building safety, construction products, fire doors, fire testing, smoke leakage, European standards, CEN, fire safety certification.
Get Certified
Connect with accredited certification bodies for this standard
CIS Institut d.o.o.
Personal Protective Equipment (PPE) certification body. Notified Body NB-2890 for EU Regulation 2016/425 PPE.

Kiwa BDA Testing
Building and construction product certification.
Kmetijski inštitut Slovenije
Agricultural Institute of Slovenia. Soil testing, plant health, agricultural product analysis.
Sponsored listings
Frequently Asked Questions
EN 13501-2:2023/prA1 is a draft published by the European Committee for Standardization (CEN). Its full title is "Fire classification of construction products and building elements - Part 2: Classification using data from fire resistance and/or smoke control tests, excluding ventilation services". This standard covers: This document specifies the procedure for classification of construction products and building elements using data from fire resistance and/or smoke leakage/control tests and/or mechanical tests which are within the direct field of application of the relevant test method. Classification on the basis of extended application of test results is also included in the scope of this document. This document deals with: a) loadbearing elements without a fire separating function: - walls; - floors; - roofs; - beams; - columns; - balconies; - walkways; - stairs. b) loadbearing elements with a fire separating function, with or without glazing, services and fixtures: - walls; - floors; - roofs; - raised floors. c) products and systems for protecting elements or parts of the works: - ceilings with no independent fire resistance; - fire protective coatings, claddings and screens; d) non-loadbearing elements or parts of works, with or without glazing, services and fixtures: - partitions; - facades (curtain walls) and external walls; - ceilings with independent fire resistance; - raised floors; - fire resisting doorsets, shutter assemblies and openable windows and their closing devices; - smoke control doorsets and shutter assemblies and their closing devices; - conveyor systems and their closures; - penetration seals; - linear joint seals; - combined penetration seals; - service ducts and shafts; - air transfer grilles. - chimneys. e) wall and ceiling coverings with fire protection ability. f) lift landing doors which are tested according to EN 81-58 are excluded from this document. Lift landing doors which are tested in accordance with EN 1634-1 are classified in accordance with 7.5.5. Relevant test methods which have been prepared for these construction products are listed in Clauses 2 and 7.
This document specifies the procedure for classification of construction products and building elements using data from fire resistance and/or smoke leakage/control tests and/or mechanical tests which are within the direct field of application of the relevant test method. Classification on the basis of extended application of test results is also included in the scope of this document. This document deals with: a) loadbearing elements without a fire separating function: - walls; - floors; - roofs; - beams; - columns; - balconies; - walkways; - stairs. b) loadbearing elements with a fire separating function, with or without glazing, services and fixtures: - walls; - floors; - roofs; - raised floors. c) products and systems for protecting elements or parts of the works: - ceilings with no independent fire resistance; - fire protective coatings, claddings and screens; d) non-loadbearing elements or parts of works, with or without glazing, services and fixtures: - partitions; - facades (curtain walls) and external walls; - ceilings with independent fire resistance; - raised floors; - fire resisting doorsets, shutter assemblies and openable windows and their closing devices; - smoke control doorsets and shutter assemblies and their closing devices; - conveyor systems and their closures; - penetration seals; - linear joint seals; - combined penetration seals; - service ducts and shafts; - air transfer grilles. - chimneys. e) wall and ceiling coverings with fire protection ability. f) lift landing doors which are tested according to EN 81-58 are excluded from this document. Lift landing doors which are tested in accordance with EN 1634-1 are classified in accordance with 7.5.5. Relevant test methods which have been prepared for these construction products are listed in Clauses 2 and 7.
EN 13501-2:2023/prA1 is classified under the following ICS (International Classification for Standards) categories: 13.220.50 - Fire-resistance of building materials and elements. The ICS classification helps identify the subject area and facilitates finding related standards.
EN 13501-2:2023/prA1 has the following relationships with other standards: It is inter standard links to EN 13501-2:2023. Understanding these relationships helps ensure you are using the most current and applicable version of the standard.
EN 13501-2:2023/prA1 is associated with the following European legislation: EU Directives/Regulations: 305/2011; Standardization Mandates: M/117. When a standard is cited in the Official Journal of the European Union, products manufactured in conformity with it benefit from a presumption of conformity with the essential requirements of the corresponding EU directive or regulation.
EN 13501-2:2023/prA1 is available in PDF format for immediate download after purchase. The document can be added to your cart and obtained through the secure checkout process. Digital delivery ensures instant access to the complete standard document.
Standards Content (Sample)
SLOVENSKI STANDARD
01-januar-2026
Požarna klasifikacija gradbenih proizvodov in elementov stavb - 2. del:
Klasifikacija na podlagi podatkov iz preskusov požarne odpornosti in/ali
dimotesnosti, izvzete so prezračevalne naprave - Dopolnilo A1
Fire classification of construction products and building elements - Part 2: Classification
using data from fire resistance and/or smoke control tests, excluding ventilation services
Klassifizierung von Bauprodukten und Bauteilen zu ihrem Brandverhalten - Teil 2:
Klassifizierung mit den Ergebnissen aus den Feuerwiderstandsprüfungen und/oder
Rauchschutzprüfungen, mit Ausnahme von Lüftungsanlagen
Classement au feu des produits et éléments de construction - Partie 2 : Classement à
partir des données d’essais de résistance au feu et/ou de contrôle des fumées à
l’exclusion des produits utilisés dans les systèmes de ventilation
Ta slovenski standard je istoveten z: EN 13501-2:2023/prA1
ICS:
13.220.50 Požarna odpornost Fire-resistance of building
gradbenih materialov in materials and elements
elementov
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.
DRAFT
EUROPEAN STANDARD
EN 13501-2:2023
NORME EUROPÉENNE
EUROPÄISCHE NORM
prA1
November 2025
ICS
English Version
Fire classification of construction products and building
elements - Part 2: Classification using data from fire
resistance and/or smoke control tests, excluding
ventilation services
Classement au feu des produits et éléments de Klassifizierung von Bauprodukten und Bauteilen zu
construction - Partie 2 : Classement à partir des ihrem Brandverhalten - Teil 2: Klassifizierung mit den
données d'essais de résistance au feu et/ou de contrôle Ergebnissen aus den Feuerwiderstandsprüfungen
des fumées à l'exclusion des produits utilisés dans les und/oder Rauchschutzprüfungen, mit Ausnahme von
systèmes de ventilation Lüftungsanlagen
This draft amendment is submitted to CEN members for enquiry. It has been drawn up by the Technical Committee CEN/TC 127.
This draft amendment A1, if approved, will modify the European Standard EN 13501-2:2023. If this draft becomes an
amendment, CEN members are bound to comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for
inclusion of this amendment into the relevant national standard without any alteration.
This draft amendment was established by CEN in three official versions (English, French, German). A version in any other
language made by translation under the responsibility of a CEN member into its own language and notified to the CEN-CENELEC
Management Centre has the same status as the official versions.
CEN members are the national standards bodies of Austria, Belgium, Bulgaria, Croatia, Cyprus, Czech Republic, Denmark, Estonia,
Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway,
Poland, Portugal, Republic of North Macedonia, Romania, Serbia, Slovakia, Slovenia, Spain, Sweden, Switzerland, Türkiye and
United Kingdom.
Recipients of this draft are invited to submit, with their comments, notification of any relevant patent rights of which they are
aware and to provide supporting documentation.
Warning : This document is not a European Standard. It is distributed for review and comments. It is subject to change without
notice and shall not be referred to as a European Standard.
EUROPEAN COMMITTEE FOR STANDARDIZATION
COMITÉ EUROPÉEN DE NORMALISATION
EUROPÄISCHES KOMITEE FÜR NORMUNG
CEN-CENELEC Management Centre: Rue de la Science 23, B-1040 Brussels
© 2025 CEN All rights of exploitation in any form and by any means reserved Ref. No. EN 13501-2:2023/prA1:2025 E
worldwide for CEN national Members.
Contents Page
European foreword . 3
1 Modification to “Introduction” . 4
2 Modification to Clause 2, "Normative References" . 4
3 Modification to Clause 4, "Fire Scenarios" . 4
4 Modification to Clause 5, "Resistance to fire performance characteristics" . 4
5 Modification to Clause 6, "Classification of characteristics related to fire resistance
performance”. 5
6 Modification to Clause 7, "Classification procedure for fire resistance” . 5
7 Modification to Clause A.1, “A.1 General” . 8
8 Modification to Clause A.2, “A.2 Content and Format”. 8
9 Modification to Table B.2, “Table B.2 – Example of tabulated data”. 9
European foreword
This document (EN 13501-2:2023/prA1:2025) has been prepared by Technical Committee CEN/TC 127
“Fire safety in buildings”, the secretariat of which is held by BSI.
This document is currently submitted to the CEN Enquiry.
1 Modification to “Introduction”
Replace
“CEN, CENELEC and EOTA committees preparing technical specifications which contain performance
requirements against fire resistance tests are expected to refer to the fire resistance classification given
in this document and not refer directly to any specific fire test method.”
with
“Commission delegated regulation (EU) 2024/1681 of 6 March 2024 specifies performance and classes
regarding fire resistance. These classes are identified by designation letters, each of which refers to an
important characteristic of fire resistance behaviour.”
2 Modification to Clause 2, "Normative References"
Replace
“EN 12604, Industrial, commercial and garage doors and gates — Mechanical aspects — Requirements and
test methods”
with
“EN 12605: 2000, Industrial, commercial and garage doors and gates —Mechanical aspects — Test
methods”
3 Modification to Clause 4, "Fire Scenarios"
Replace the word “doors” with “doorsets” throughout Clause 4.
In clause 4.6 bullet point 1 replace “leakage” with “air flow”.
In clause 4.6 bullet point 2 replace “leakage” with “air flow”.
At end of section 4.6 add the following note:
“NOTE Instead of air flow rate, the term leakage rate was used to describe the evaluation of ambient and medium
temperature for smoke control doorsets in former versions of this document.”
4 Modification to Clause 5, "Resistance to fire performance characteristics"
In clause 5.1, at end of second sentence, add “/control” after “smoke leakage”.
In clause 5.2.2.1 in second sentence of first paragraph replace “may” with “can”
In clause 5.2.3.3 replace the word “doorsests” with “doorsets”.
In clause 5.2.4 in the last sentence replace “thermal insulation” with “radiation”
In clause 5.2.7, after the first sentence, delete all text and replace with the following:
“S is the classification related to the air flow rate at ambient temperature and in the case the doorset
a3
was tested with the bottom gap taped over.
S is the classification related to the air flow rate at ambient temperature and in the case the doorset was
a4
tested without the bottom gap taped over.
S is the classification for the air flow rate at both ambient temperature and at 200°C.
S is the classification for the air flow rate at both ambient temperature and at 200°C and may be used
200L
for large industrial doorsets only. Large industrial doorsets have an overall door leaf area of more than
9m .
NOTE 1 The classification S is defined in previous versions of this document.
a
NOTE 2 The classification S is defined in previous versions of this document.”
m
5 Modification to Clause 6, "Classification of characteristics related to fire
resistance performance”
In clause 6.6.2 replace the text for S definition with the following:
“for elements with particular limitations on smoke leakage/control;
For fire resistant elements the S shall be added to the fire resistance classification (e.g. EI 60-
S ). Where no fire resistance classification is relevant, the element shall simply be classified S
as defined in this document for the particular product and classification;”
6 Modification to Clause 7, "Classification procedure for fire resistance”
In clause 7.1.1 a) “load level (see 3.26)” is to be a separate bullet point
In clause 7.1.1 c) replace the word “doorsests” with “doorsets”.
In clause 7.1.1 d) add “/control” after “smoke leakage” and “/air flow” after “limiting leakage” and before
“rate”.
In clause 7.2.2.3 replace the word “both” with “one”.
In section 7.3.2.4 move “With external fire exposure, the classification shall be given as REI 30-ef, or
REI 60-ef (o→i).” to the end of the paragraph above.
nd
In table 4 in clause 7.3.4.4 delete the 10-minute classification column (2 column) for both RE and REI.
In clause 7.5.2.1 delete “EN 15254-6 and”.
In clause 7.5.2.2 delete “and EN 15254- 6” and insert “EN 15254-3” between “EN 15254-2” and “EN 15254-
4”, and insert “and” between “EN 15254-4” and “EN 15254
...