Standard Specification for Precast Reinforced Concrete Monolithic Box Sections for Culverts, Storm Drains, and Sewers Designed According to AASHTO LRFD

ABSTRACT
This specification covers single-cell precast reinforced concrete box sections cast monolithically and intended to be used for the construction of culverts and for the conveyance of storm water, industrial wastes and sewage. The reinforced concrete shall consist of cementitious materials, mineral aggregates and water, in which steel has been embedded in such a manner that the steel and concrete act together. The precast reinforced concrete box sections shall be produced with tongue and groove ends. The box section shall be cured using any of the following methods or combinations thereof: steam curing; water curing; and membrane curing. Compression tests for determining concrete compressive strength shall be allowed to be made on either standard rodded concrete cylinders or concrete cylinders compacted and cured in like manner as the box sections, or on cores drilled from the box section.
SCOPE
1.1 This specification covers single-cell precast reinforced concrete box sections cast monolithically and intended to be used for the construction of culverts and for the conveyance of storm water, industrial wastes and sewage.
Note 1—This specification is primarily a manufacturing and purchasing specification. However, standard designs per the AASHTO LRFD Bridge Design Specifications are included and the criteria used to develop these designs are given in Appendix X1. The successful performance of this product depends upon the proper selection of the box section, bedding, backfill, and care that the installation conforms to the construction specifications. The purchaser of the precast reinforced concrete box sections specified herein is cautioned that proper correlation of the loading conditions and the field requirements with the box section specified, and provision for inspection at the construction site, are required.  
1.2 The values stated in inch-pound units are to be regarded as standard. No other units of measurement are included in this standard.

General Information

Status
Historical
Publication Date
31-Oct-2011
Current Stage
Ref Project

Relations

Buy Standard

Technical specification
ASTM C1577-11a - Standard Specification for Precast Reinforced Concrete Monolithic Box Sections for Culverts, Storm Drains, and Sewers Designed According to AASHTO LRFD
English language
17 pages
sale 15% off
Preview
sale 15% off
Preview
Technical specification
REDLINE ASTM C1577-11a - Standard Specification for Precast Reinforced Concrete Monolithic Box Sections for Culverts, Storm Drains, and Sewers Designed According to AASHTO LRFD
English language
17 pages
sale 15% off
Preview
sale 15% off
Preview

Standards Content (Sample)

NOTICE: This standard has either been superseded and replaced by a new version or withdrawn.
Contact ASTM International (www.astm.org) for the latest information
Designation:C1577 −11a
StandardSpecification for
Precast Reinforced Concrete Monolithic Box Sections for
Culverts, Storm Drains, and Sewers Designed According to
1
AASHTO LRFD
This standard is issued under the fixed designation C1577; the number immediately following the designation indicates the year of
original adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. A
superscript epsilon (´) indicates an editorial change since the last revision or reapproval.
1. Scope A615/A615M SpecificationforDeformedandPlainCarbon-
Steel Bars for Concrete Reinforcement
1.1 This specification covers single-cell precast reinforced
C33 Specification for Concrete Aggregates
concrete box sections cast monolithically and intended to be
C150 Specification for Portland Cement
used for the construction of culverts and for the conveyance of
C309 Specification for Liquid Membrane-Forming Com-
storm water, industrial wastes and sewage.
pounds for Curing Concrete
NOTE 1—This specification is primarily a manufacturing and purchas-
C497 Test Methods for Concrete Pipe, Manhole Sections, or
ing specification. However, standard designs per the AASHTO LRFD
Tile
Bridge Design Specifications are included and the criteria used to develop
C595 Specification for Blended Hydraulic Cements
these designs are given in Appendix X1. The successful performance of
C618 Specification for Coal Fly Ash and Raw or Calcined
this product depends upon the proper selection of the box section,
bedding, backfill, and care that the installation conforms to the construc-
Natural Pozzolan for Use in Concrete
tion specifications. The purchaser of the precast reinforced concrete box
C822 Terminology Relating to Concrete Pipe and Related
sectionsspecifiedhereiniscautionedthatpropercorrelationoftheloading
Products
conditions and the field requirements with the box section specified, and
C989 Specification for Slag Cement for Use in Concrete and
provision for inspection at the construction site, are required.
Mortars
1.2 The values stated in inch-pound units are to be regarded
C1116 Specification for Fiber-Reinforced Concrete and
as standard. No other units of measurement are included in this
Shotcrete
standard.
3
2.2 AASHTO Standards:
AASHTO LRFD Bridge Design Specifications
2. Referenced Documents
AASHTO LRFD Bridge Construction Specifications
2
2.1 ASTM Standards: 4
2.3 ASCE Standard:
A82/A82M Specification for Steel Wire, Plain, for Concrete
ASCE 26–97 Standard Practice for Direct Design of Buried
Reinforcement
Precast Concrete Box Sections
A185/A185M Specification for Steel Welded Wire
Reinforcement, Plain, for Concrete 3. Terminology
A496/A496M Specification for Steel Wire, Deformed, for
3.1 Definitions—Fordefinitionsoftermsrelatingtoconcrete
Concrete Reinforcement
pipe, see Terminology C822.
A497/A497M Specification for Steel Welded Wire
4. Designation
Reinforcement, Deformed, for Concrete
4.1 Precast reinforced concrete box sections manufactured
in accordance with this specification shall be legibly marked
1
This specification is under the jurisdiction of ASTM Committee C13 on
Concrete Pipe and is the direct responsibility of Subcommittee C13.07 on with the specification designation, span, rise, and design earth
Acceptance Specifications and Precast Concrete Box Sections.
cover.
Current edition approved Nov. 1, 2011. Published November 2011. Originally
approved in 2005. Last previous edition approved in 2011 as C1577 – 11. DOI:
3
10.1520/C1577-11A. Available from American Association of State Highway and Transportation
2
For referenced ASTM standards, visit the ASTM website, www.astm.org, or Officials (AASHTO), 444 N. Capitol St., NW, Suite 249, Washington, DC 20001,
contact ASTM Customer Service at service@astm.org. For Annual Book of ASTM http://www.transportation.org.
4
Standards volume information, refer to the standard’s Document Summary page on Available from American Society of Civil Engineers (ASCE), 1801 Alexander
the ASTM website. Bell Dr., Reston, VA 20191, http://www.asce.org.
Copyright © ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959. United States
1

---------------------- Page: 1 ----------------------
C1577−11a
TABLE 1 Design Requirements for Precast Concrete Box Sections Under Earth, Dead and HL-93 Live Load Conditions
NOTE 1—Design earth loads and reinforcement areas are based on the weight of a column of earth over the width of the box section multiplied by a
soil structure interaction factor as defined in Appendix X1.
NOTE 2—Concrete design strength 5000 psi.
NOTE3—SteelareasarebasedonanHL-93liveloadwithoutthelaneloadaspermittedbyAASHTO,usingeitherthedesigntruckorthedesigntandem
and taking the controlling case.
NOTE 4—The design earth cover indicated is the height of fill above the top of the box s
...

This document is not anASTM standard and is intended only to provide the user of anASTM standard an indication of what changes have been made to the previous version. Because
it may not be technically possible to adequately depict all changes accurately, ASTM recommends that users consult prior editions as appropriate. In all cases only the current version
of the standard as published by ASTM is to be considered the official document.
Designation:C1577–11 Designation: C1577 – 11a
Standard Specification for
Precast Reinforced Concrete Monolithic Box Sections for
Culverts, Storm Drains, and Sewers Designed According to
1
AASHTO LRFD
This standard is issued under the fixed designation C1577; the number immediately following the designation indicates the year of
original adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. A
superscript epsilon (´) indicates an editorial change since the last revision or reapproval.
1. Scope
1.1 This specification covers single-cell precast reinforced concrete box sections cast monolithically and intended to be used for
the construction of culverts and for the conveyance of storm water, industrial wastes and sewage.
NOTE 1—This specification is primarily a manufacturing and purchasing specification. However, standard designs per the AASHTO LRFD Bridge
Design Specifications are included and the criteria used to develop these designs are given inAppendix X1. The successful performance of this product
depends upon the proper selection of the box section, bedding, backfill, and care that the installation conforms to the construction specifications. The
purchaser of the precast reinforced concrete box sections specified herein is cautioned that proper correlation of the loading conditions and the field
requirements with the box section specified, and provision for inspection at the construction site, are required.
1.2 The values stated in inch-pound units are to be regarded as standard. No other units of measurement are included in this
standard.
2. Referenced Documents
2
2.1 ASTM Standards:
A82/A82M Specification for Steel Wire, Plain, for Concrete Reinforcement
A185/A185M Specification for Steel Welded Wire Reinforcement, Plain, for Concrete
A496/A496M Specification for Steel Wire, Deformed, for Concrete Reinforcement
A497/A497M Specification for Steel Welded Wire Reinforcement, Deformed, for Concrete
A615/A615M Specification for Deformed and Plain Carbon-Steel Bars for Concrete Reinforcement
C33 Specification for Concrete Aggregates
C150 Specification for Portland Cement
C309 Specification for Liquid Membrane-Forming Compounds for Curing Concrete
C497 Test Methods for Concrete Pipe, Manhole Sections, or Tile
C595 Specification for Blended Hydraulic Cements
C618 Specification for Coal Fly Ash and Raw or Calcined Natural Pozzolan for Use in Concrete
C822 Terminology Relating to Concrete Pipe and Related Products
C989 Specification for Slag Cement for Use in Concrete and Mortars
C1116 Specification for Fiber-Reinforced Concrete and Shotcrete
3
2.2 AASHTO Standards:
AASHTO LRFD Bridge Design Specifications
AASHTO LRFD Bridge Construction Specifications
4
2.3 ASCE Standard:
ASCE 26–97 Standard Practice for Direct Design of Buried Precast Concrete Box Sections
3. Terminology
3.1 Definitions—For definitions of terms relating to concrete pipe, see Terminology C822.
1
This specification is under the jurisdiction of ASTM Committee C13 on Concrete Pipe and is the direct responsibility of Subcommittee C13.07 on Acceptance
Specifications and Precast Concrete Box Sections.
Current edition approved Sept. 15,Nov. 1, 2011. Published SeptemberNovember 2011. Originally approved in 2005. Last previous edition approved in 20102011 as
C1577 – 101. DOI: 10.1520/C1577-11A.
2
For referencedASTM standards, visit theASTM website, www.astm.org, or contactASTM Customer Service at service@astm.org. For Annual Book of ASTM Standards
volume information, refer to the standard’s Document Summary page on the ASTM website.
3
Available from American Association of State Highway and Transportation Officials (AASHTO), 444 N. Capitol St., NW, Suite 249, Washington, DC 20001,
http://www.transportation.org.
4
Available from American Society of Civil Engineers (ASCE), 1801 Alexander Bell Dr., Reston, VA 20191, http://www.asce.org.
Copyright © ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959, United States.
1

---------------------- Page: 1 ----------------------
C1577 – 11a
4. Designation
4.1 Precast reinforced concrete box sections manufactured in accordance with this specification shall be legibly marked with
the specification designation, span, rise, and design earth cover.
TABLE 1 Design Requirements for Precast Concrete Box Sections Under Earth, Dead and HL-93 Live Load Conditions
NOTE 1—Design earth loads and reinforcement areas are based on the weight of a column of earth over the width of the box section multiplied by a
soil st
...