Fixed firefighting systems - Gas extinguishing systems - Part 10: Physical properties and system design of gas extinguishing systems for IG-541 extinguishant

This document gives specific requirements for gaseous fire-extinguishing systems, with respect to the IG-541 extinguishant. It includes details of physical properties, specification, usage and safety aspects and is applicable to systems operating at nominal pressure of 150 bar, 200 bar and 300 bar at 15 °C. This does not preclude the use of other systems; however, design data for other pressures were not available at time of publication.

Ortsfeste Brandbekämpfungsanlagen - Löschanlagen mit gasförmigen Löschmitteln - Teil 10: Physikalische Eigenschaften und Anlagenauslegung für Feuerlöschmittel IG-541

Installations fixes de lutte contre l’incendie - Installations d’extinction à gaz - Partie 10: Propriétés physiques et conception des systèmes pour agent extincteur IG-541

Vgrajeni gasilni sistemi - Sistemi za gašenje s plinom - 10. del: Fizikalne lastnosti in načrtovanje sistema za gašenje s plinom za gasilo IG-541

General Information

Status
Not Published
Public Enquiry End Date
30-Mar-2015
Technical Committee
Current Stage
98 - Abandoned project (Adopted Project)
Start Date
25-Jul-2016
Due Date
30-Jul-2016
Completion Date
25-Jul-2016

Relations

Buy Standard

Draft
prEN 15004-10:2015
English language
12 pages
sale 10% off
Preview
sale 10% off
Preview
e-Library read for
1 day

Standards Content (Sample)

SLOVENSKI STANDARD
oSIST prEN 15004-10:2015
01-marec-2015
9JUDMHQLJDVLOQLVLVWHPL6LVWHPL]DJDãHQMHVSOLQRPGHO)L]LNDOQHODVWQRVWL
LQQDþUWRYDQMHVLVWHPD]DJDãHQMHVSOLQRP]DJDVLOR,*
Fixed firefighting systems - Gas extinguishing systems - Part 10: Physical properties and
system design of gas extinguishing systems for IG-55 extinguishant
Ortsfeste Brandbekämpfungsanlagen - Löschanlagen mit gasförmigen Löschmitteln -
Teil 10: Physikalische Eigenschaften und Anlagenauslegung für Feuerlöschmittel IG-541
Installations fixes de lutte contre l’incendie - Installations d’extinction à gaz - Partie 10:
Propriétés physiques et conception des systèmes pour agent extincteur IG-541
Ta slovenski standard je istoveten z: prEN 15004-10
ICS:
13.220.20 3RåDUQD]DãþLWD Fire protection
oSIST prEN 15004-10:2015 en,fr,de
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.

---------------------- Page: 1 ----------------------
oSIST prEN 15004-10:2015

---------------------- Page: 2 ----------------------
oSIST prEN 15004-10:2015

EUROPEAN STANDARD
DRAFT
prEN 15004-10
NORME EUROPÉENNE

EUROPÄISCHE NORM

December 2014
ICS 13.220.20 Will supersede EN 15004-10:2008
English Version
Fixed firefighting systems - Gas extinguishing systems - Part 10:
Physical properties and system design of gas extinguishing
systems for IG-55 extinguishant
Installations fixes de lutte contre l'incendie - Installations Ortsfeste Brandbekämpfungsanlagen - Löschanlagen mit
d'extinction à gaz - Partie 10: Propriétés physiques et gasförmigen Löschmitteln - Teil 10: Physikalische
conception des systèmes pour agent extincteur IG-541 Eigenschaften und Anlagenauslegung für Feuerlöschmittel
IG-541
This draft European Standard is submitted to CEN members for enquiry. It has been drawn up by the Technical Committee CEN/TC 191.

If this draft becomes a European Standard, CEN members are bound to comply with the CEN/CENELEC Internal Regulations which
stipulate the conditions for giving this European Standard the status of a national standard without any alteration.

This draft European Standard was established by CEN in three official versions (English, French, German). A version in any other language
made by translation under the responsibility of a CEN member into its own language and notified to the CEN-CENELEC Management
Centre has the same status as the official versions.

CEN members are the national standards bodies of Austria, Belgium, Bulgaria, Croatia, Cyprus, Czech Republic, Denmark, Estonia,
Finland, Former Yugoslav Republic of Macedonia, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania,
Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland, Turkey and United
Kingdom.

Recipients of this draft are invited to submit, with their comments, notification of any relevant patent rights of which they are aware and to
provide supporting documentation.

Warning : This document is not a European Standard. It is distributed for review and comments. It is subject to change without notice and
shall not be referred to as a European Standard.


EUROPEAN COMMITTEE FOR STANDARDIZATION
COMITÉ EUROPÉEN DE NORMALISATION

EUROPÄISCHES KOMITEE FÜR NORMUNG

CEN-CENELEC Management Centre: Avenue Marnix 17, B-1000 Brussels
© 2014 CEN All rights of exploitation in any form and by any means reserved Ref. No. prEN 15004-10:2014 E
worldwide for CEN national Members.

---------------------- Page: 3 ----------------------
oSIST prEN 15004-10:2015
prEN 15004-10:2014 (E)
Contents
Page
Foreword .3
1 Scope .3
2 Normative references .3
3 Terms and definitions .3
4 Characteristics and uses .4
4.1 General .4
4.2 Use of IG-541 systems .5
5 Safety of personnel. 10
6 System design . 10
6.1 Fill pressure . 10
6.2 Superpressurization . 11
6.3 Extinguishant quantity . 11
7 Environmental Properties . 12

2

---------------------- Page: 4 ----------------------
oSIST prEN 15004-10:2015
prEN 15004-10:2014 (E)
Foreword
This document (prEN 15004-10:2014) has been prepared by Technical Committee CEN/TC 191 “Fixed
firefighting systems”, the secretariat of which is held by BSI.
This document is currently submitted to the CEN Enquiry.
This document will supersede EN 15004-10:2008.
EN 15004 consists of the following parts, under the general title Fixed firefighting systems – Gas extinguishing
systems:
 Part 1: Design, installation and maintenance”
 Part 2: Physical properties and system design of gas extinguishing systems for FK-5-1-12 extinguishant”
 Part 3: Physical properties and system design of gas extinguishing systems for HCFC Blend A
extinguishant”
 Part 4: Physical properties and system design of gas extinguishing systems for HFC 125 extinguishant”
 Part 6: Physical properties and system design of gas extinguishing systems for HFC 23 extinguishant”
 Part 7: Physical properties and system design of gas extinguishing systems for IG-01 extinguishant “
 Part 8: Physical properties and system design of gas extinguishing systems for IG-100 extinguishant”
 Part 9: Physical properties and system design of gas extinguishing systems for IG-55 extinguishant”
 Part 10: Physical properties and system design of gas extinguishing systems for IG-541 extinguishant”
1 Scope
1.1 This part of EN 15004 contains specific requirements for gaseous fire-extinguishing systems, with
respect to the IG-541 extinguishant. It includes details of physical properties, specification, usage and safety
aspects.
1.2 This part of EN 15004 covers systems operating at nominal pressures of 150 bar, 200 bar and 300 bar
at 15 °C. This does not preclude the use of other systems, although design data for other pressures are not
available at this time.
2 Normative references
The following documents, in whole or in part, are normatively referenced in this document and are
indispensable for its application. For dated references, only the edition cited applies. For undated references,
the latest edition of the referenced document (including any amendments) applies.
EN 15004-1, Gaseous fire-extinguishing systems — Physical properties and system design — Part 1: General
requirements.
3 Terms and definitions
For the purposes of this part of EN 15004, the terms and definitions given in EN 15004-1 apply.
3

---------------------- Page: 5 ----------------------
oSIST prEN 15004-10:2015
prEN 15004-10:2014 (E)
4 Characteristics and uses
4.1 General
IG-541 is a colourless, odourless, electrically non-conductive gas with a density approximately the same as
that of air.
It is an inert gas mixture consisting nominally of 52 % nitrogen, 40 % argon and 8 % carbon dioxide. The
mixture specification for IG-541 (based on 8 % carbon dioxide with tolerance of ± 5 %) is as follows:
a) carbon dioxide percentage range 7,6 % to 8,4 %;
b) argon  percentage range 37,2 % to 42,8 %;
c) nitrogen  percentage range 48,8 % to 55,2 %.
Individual container or batch analysis is based on carbon dioxide measurement only.
Extinguishant IG-541 shall comply with the specification shown in Table 1.
4

---------------------- Page: 6 ----------------------
oSIST prEN 15004-10:2015
prEN 15004-10:2014 (E)
The physical properties are shown in Table 2.
IG-541 extinguishes fires mainly by a reduction of oxygen concentration in the atmosphere of the hazard
enclosure.
Table 1 — Component gas specification for IG-541
Argon Nitrogen Carbon dioxide
Purity 99,997 % by 99,99 % by 99,5 % by volume,
volume, min. volume, min. min.
–6 –6 –6
Moisture
4 × 10 by mass, 5 × 10 by mass, 10 × 10 by mass,
max. max. max.
–6 –6 –6
Oxygen
3 × 10 by mass, 3 × 10 by mass, 10 × 10 by mass,
max. max. max.
NOTE Only principal contaminants are shown. Other measurements may include
–6
hydrocarbons, CO, NO, NO , CO , O , etc. Most are < 20 × 10 .
2 2 2

Table 2 — Physical properties of IG-541
Property Units Value
Molecular mass — 34,0
Boiling point at 1,013 bar (absolute) –196
°C
Freezing point –78,5
°C
Critical temperature —
°C
Critical pressure bar abs —
3
Critical volume cm /mol —
3
Critical density kg/m —
Vapour pressure 20 °C bar abs 152
3
Liquid density 20 °C kg/m —
3
Saturated vapour density 20 °C kg/m —
3
Specific volume of superheated vapour m /kg 0,706
at 1,013 bar and 20 °C
Components N  52 % by volume
2
Ar  40 % by volume
CO 8 % by volume
2
Chemical name Nitrogen/argon/carbon dioxide

4.2 Use of IG-541 systems
IG-541 total flooding systems may be used for extinguishing fires of all classes within the limits specifie
...

Questions, Comments and Discussion

Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.