kSIST FprEN 13348-1:2026
(Main)Chimneys - Thermal and fluid dynamic calculation methods - Part 1: Chimneys serving one combustion appliance
- Abstract
This document specifies methods for the calculation of the thermal and fluid dynamic characteristics of chimneys serving one combustion appliance.
The methods in this document are applicable to negative or positive pressure chimneys with wet or dry operating conditions. It is valid for chimneys with combustion appliances for fuels subject to the knowledge of the flue gas characteristics which are needed for the calculation.
The methods in this document are applicable to chimneys with one inlet connected with one combustion appliance. The methods in FprEN 13384-2 are applicable to chimneys with multiple inlets and one inlet with multiple combustion appliances. FprEN 13384-3 describes methods for the development of diagrams and tables for chimneys serving one combustion appliance.
- Status
- Not Published
- Public Enquiry End Date
- 30-Jul-2025
- Technical Committee
- POZ - Požarna varnost
- Current Stage
- 5020 - Formal vote (FV) (Adopted Project)
- Start Date
- 19-Nov-2026
- Due Date
- 07-Jan-2027
- Completion Date
- 20-Nov-2026
kSIST FprEN 13348-1:2026 is a draft European Standard prepared by CEN/TC 166 "Chimneys" and published through SIST. It specifies methods for calculating the thermal and fluid dynamic characteristics of chimneys serving one combustion appliance, so it is used when checking chimney sizing, draught, temperature behaviour, condensation and related operating limits.
What does kSIST FprEN 13348-1:2026 specify?
kSIST FprEN 13348-1:2026 covers calculation methods for chimneys with one inlet connected to one combustion appliance. The methods apply to negative pressure or positive pressure chimneys, and to wet or dry operating conditions, provided the flue gas characteristics needed for the calculation are known.
kSIST FprEN 13348-1:2026 is organized into clauses for scope, normative references, terms, symbols, non-balanced flue chimneys, secondary air, balanced flue chimneys, condensation heat and chimney fans. The annexes then supply calculation aids, default values and reporting examples.
| Annex | What it covers |
|---|---|
| Annex A | Calculation of thermal resistance |
| Annex B | Default values for non-available product information |
| Annex C | Chimney outlet with regard to adjacent buildings |
| Annex D | Determination of the gas constant R considering the condensation |
| Annex E | Example for a report about input and output data of the calculation |
The scope also places this part in the EN 13384 family. Part 2 is for chimneys with multiple inlets or one inlet with multiple combustion appliances, and Part 3 covers methods for diagrams and tables for chimneys serving one combustion appliance.
What are the key requirements of kSIST FprEN 13348-1:2026?
Pressure and temperature checks are the core of the method
kSIST FprEN 13348-1:2026 requires the chimney cross section to satisfy pressure and temperature criteria, not just a geometric size. For negative pressure chimneys, the calculated minimum draught must meet the appliance demand and the air supply resistance, while the maximum draught must stay within the appliance limit. For positive pressure chimneys, the calculated pressures must stay within the appliance and system pressure limits.
In practice, this means the designer must verify both safe operation and safe containment of the flue gases. The document uses one set of external conditions for minimum draught or maximum positive pressure, and another set for maximum draught, minimum positive pressure and outlet surface temperature.
The temperature requirement protects against condensation and icing
kSIST FprEN 13348-1:2026 requires the inner surface temperature at the chimney outlet to be at least the temperature limit. For dry operating conditions, that limit is the flue gas condensing temperature. For wet operating conditions, the limit is 273.15 K to prevent ice formation at the outlet.
If additional insulation is present above the roof, the standard also checks the surface temperature immediately before that insulation. In practice, this matters when a chimney rises through cold zones or when an existing installation is reused with a new appliance. The document also gives cases where the temperature condition can be waived by separate written agreement if fire and operational safety are still maintained.
The calculation uses appliance data plus chimney data
kSIST FprEN 13348-1:2026 requires the user to obtain flue gas data for the combustion appliance and characteristic data for the chimney and connecting flue pipe. Clause 5.5 covers flue gas mass flow, combustion air mass flow, flue gas temperature, and pressure limits for the appliance. Clause 5.6 covers roughness and thermal resistance, and Clause 5.7 provides the basic values such as air temperatures, external air pressure, gas constant, density, specific heat, condensing temperature and safety coefficients.
This means the calculation is only as good as the declared appliance data and the description of the chimney construction. Annex B is important here because it gives default values when some product information is not available.
Pressure calculations include chimney effect, resistance and wind
kSIST FprEN 13348-1:2026 calculates pressures from chimney effect, pressure resistance, velocity effects and wind velocity pressure. Clause 5.10 covers the pressure at the flue gas inlet, the theoretical draught available due to chimney effect, pressure resistance of the chimney and wind pressure. Clause 5.11 then combines these values to determine the minimum draught required and the maximum allowed draught at the inlet.
In practice, this is where chimney height, diameter, bends, terminal design and weather exposure all matter. Annex C supports the wind assessment by defining when nearby buildings can affect the outlet.
Secondary air can be used to recover temperature or pressure compliance
kSIST FprEN 13348-1:2026 allows secondary air to be considered for negative pressure chimneys when the temperature requirement or the maximum draught requirement is not met. Clause 6 adds secondary air mass flow to the flue gas flow, recalculates the mixture properties and repeats the calculation until the operating requirements are met or the surplus draught is used up.
This is a practical correction method for installations where extra dilution or ventilation changes the flue gas behaviour. The clause also says the minimum draught requirements must already be satisfied without secondary air before this approach is used.
Balanced flue chimneys are treated as coupled flue and air-supply systems
kSIST FprEN 13348-1:2026 gives a separate method for balanced flue chimneys in Clause 7. The chimney and air supply duct are divided into segments, normally with a maximum length of 0.5 m, unless the thermal resistance between them is high enough to avoid segmentation. The same approach applies to the connecting flue pipe and the connecting air supply pipe.
This matters because balanced flues exchange heat between the outgoing flue gas and incoming combustion air. The document therefore calculates temperatures, densities and pressures in both paths together, and the checks are repeated for nominal heat output and the lowest heat output range.
Condensation is handled as a separate extension to the basic method
kSIST FprEN 13348-1:2026 adds a condensation model in Clause 8 for chimneys operating under wet conditions or when outlet temperatures are too low. The method finds where condensation starts, then calculates the effect of latent heat on segment temperatures and condensate mass flow.
The practical point is that condensation can improve heat transfer and change the outlet temperatures, but it does not change the pressure checks in this clause. Annex D can be used when the gas constant needs to reflect condensation more closely.
Chimney fans are only allowed under defined safety conditions
kSIST FprEN 13348-1:2026 lets the user include chimney fans only if their operation is controlled by a safety device that shuts down the appliance on fan failure, or if safe operation on failure is otherwise demonstrated. Clause 9 provides the fan pressure gain model and the checks for inline fans and exhaust fans.
This is important for systems where a fan assists draught or pressure control. The standard also distinguishes between permanent and non-permanent chimney fans, so the calculation must reflect how the fan actually operates.
What terms does kSIST FprEN 13348-1:2026 define?
- Heat output - the amount of heat produced by a combustion appliance per unit of time.
- Nominal heat output - the continuous heat output stated in the combustion appliance documentation for specified fuels.
- Flue gas mass flow - the mass of flue gas leaving the combustion appliance through the connecting flue pipe per unit time.
- Effective height of the chimney - the height difference between the flue gas inlet into the chimney and the chimney outlet.
- Draught - the positive value of the negative pressure in the flue.
- Theoretical draught available due to chimney effect - the pressure difference created by the density difference between the outside air column and the flue gas column.
- Pressure resistance of the chimney - the pressure needed to overcome flow resistance while carrying flue gases through the chimney.
- Wind velocity pressure - the pressure generated on the chimney by wind.
Who uses kSIST FprEN 13348-1:2026?
kSIST FprEN 13348-1:2026 is used by chimney designers, combustion appliance manufacturers, system suppliers, installers and commissioning engineers when they need to size or verify a chimney for one appliance. It is also relevant to testing and conformity assessment people who review input data, calculation reports and operating limits.
In practice, it supports work on heating appliances using solid, liquid or gaseous fuels, including cases where flue gas characteristics, condensation risk, room conditions and terminal position all affect the final design.
What changed in kSIST FprEN 13348-1:2026 from the previous edition?
kSIST FprEN 13348-1:2026 will supersede EN 13384-1:2015+A1:2019. The draft foreword lists these technical changes:
- editorial mistakes were corrected
- new fuels were added in Table B.1
- the ζ-values of terminals were clarified and linked to static pressure
- the calculation methods were extended to include the O content of the flue gas
- the simplified heat transfer calculation method based on Srad for concentric duct was deleted, and the detailed method was modified
- pressure requirements for negative pressure chimneys were modified for possible connection of a positive pressure combustion appliance with a total or partly positive pressure connection pipe
- remarks were added for the temperature requirement
- a new mass flow factor was introduced for fire places open on all sides
- a new formula was added for thermal resistance of the air gap
- remarks were added for draught regulators for balanced flue chimneys
- a new Annex E was created with an example report for input and output data
Which standards are used with kSIST FprEN 13348-1:2026?
| Standard | What it contributes |
|---|---|
| EN 1443:2019 | General chimney requirements and the base terminology used in this document |
| EN 1749 | Classification of gas appliances by combustion air supply and combustion product evacuation type |
| EN 15287-1:2023 | Design, installation and commissioning rules for chimneys and connecting flue pipes for non-roomsealed combustion appliances |
| EN 15287-2:2023 | Design, installation and commissioning rules for chimneys and connecting flue pipes for roomsealed combustion appliances |
| EN 16475-2 | Requirements and test methods for chimney fans |
| EN 16475-3 | Requirements and test methods for draught regulators, standstill opening devices and combined secondary air devices |
| EN 13384-2 | Calculation methods for chimneys with more than one combustion appliance |
| EN 13384-3 | Methods for developing diagrams and tables for chimneys serving one heating appliance |
What does the kSIST FprEN 13348-1:2026 document contain?
kSIST FprEN 13348-1:2026 contains detailed calculation procedures, formulas, symbols and tables for chimney thermal and fluid dynamic design. Clause 4 defines the symbols and units used throughout the calculations, and the later clauses apply those symbols to pressure, temperature, density and velocity checks.
The document also includes iterative methods for concentric balanced flue systems, segment-by-segment calculations for condensation, and specific procedures for secondary air and chimney fans. Annexes A to E provide thermal resistance calculations, default material and fuel values, outlet positioning near obstacles, a condensation-related gas constant method and a report template for input and output data.
For design and verification work, the most useful parts are the tables of default fuel data in Annex B, the outlet proximity rules in Annex C, and the reporting example in Annex E. Together they support consistent calculation records and make it easier to compare the assumptions, inputs and results used for a chimney calculation.
Relations
- Effective Date
- 15-Feb-2023
Get Certified
Connect with accredited certification bodies for this standard

DIBt (Deutsches Institut für Bautechnik)
German Institute for Building Technology.
DIN CERTCO
DIN Group product certification.

Aboma Certification B.V.
Specialized in construction, metal, and transport sectors.
Sponsored listings
Frequently Asked Questions
kSIST FprEN 13348-1:2026 is a draft published by the Slovenian Institute for Standardization (SIST). Its full title is "Chimneys - Thermal and fluid dynamic calculation methods - Part 1: Chimneys serving one combustion appliance". This standard covers: This document specifies methods for the calculation of the thermal and fluid dynamic characteristics of chimneys serving one combustion appliance. The methods in this document are applicable to negative or positive pressure chimneys with wet or dry operating conditions. It is valid for chimneys with combustion appliances for fuels subject to the knowledge of the flue gas characteristics which are needed for the calculation. The methods in this document are applicable to chimneys with one inlet connected with one combustion appliance. The methods in FprEN 13384-2 are applicable to chimneys with multiple inlets and one inlet with multiple combustion appliances. FprEN 13384-3 describes methods for the development of diagrams and tables for chimneys serving one combustion appliance.
This document specifies methods for the calculation of the thermal and fluid dynamic characteristics of chimneys serving one combustion appliance. The methods in this document are applicable to negative or positive pressure chimneys with wet or dry operating conditions. It is valid for chimneys with combustion appliances for fuels subject to the knowledge of the flue gas characteristics which are needed for the calculation. The methods in this document are applicable to chimneys with one inlet connected with one combustion appliance. The methods in FprEN 13384-2 are applicable to chimneys with multiple inlets and one inlet with multiple combustion appliances. FprEN 13384-3 describes methods for the development of diagrams and tables for chimneys serving one combustion appliance.
kSIST FprEN 13348-1:2026 is classified under the following ICS (International Classification for Standards) categories: 91.060.40 - Chimneys, shafts, ducts. The ICS classification helps identify the subject area and facilitates finding related standards.
kSIST FprEN 13348-1:2026 has the following relationships with other standards: It is inter standard links to SIST EN 13384-1:2015+A1:2019. Understanding these relationships helps ensure you are using the most current and applicable version of the standard.
kSIST FprEN 13348-1:2026 is associated with the following European legislation: EU Directives/Regulations: 305/2011; Standardization Mandates: M/105. When a standard is cited in the Official Journal of the European Union, products manufactured in conformity with it benefit from a presumption of conformity with the essential requirements of the corresponding EU directive or regulation.
kSIST FprEN 13348-1:2026 is available in PDF format for immediate download after purchase. The document can be added to your cart and obtained through the secure checkout process. Digital delivery ensures instant access to the complete standard document.
Standards Content (Sample)
Contents
- 1 Scope
- 2 Normative references
- 3 Terms and definitions
- 3.1 heat output
- 3.1.1 nominal heat output
- 3.1.2 heat output range
- 3.2 heat input
- 3.3 efficiency of the combustion appliance
- 3.4 flue gas mass flow
- 3.5 effective height of the chimney
- 3.6 effective height of the connecting flue pipe
- 3.7 draught
- 3.8 theoretical draught available due to chimney effect
- 3.9 pressure resistance of the chimney
- 3.10 wind velocity pressure
- 3.11 minimum draught at the flue gas inlet into the chimney
- 3.12 maximum draught at the flue gas inlet into the chimney
- 3.13 minimum draught for the combustion appliance
- 3.14 maximum draught for the combustion appliance
- 3.15 effective pressure resistance of the connecting flue pipe
- 3.16 effective pressure resistance of the air supply
- 3.17 minimum draught required at the flue gas inlet into the chimney
- 3.18 maximum allowed draught at the flue gas inlet into the chimney
- 3.19 maximum positive pressure at the flue gas inlet into the chimney
- 3.20 minimum positive pressure at the flue gas inlet into the chimney
- 3.21 maximum differential pressure of the combustion appliance
- 3.22 minimum differential pressure of the combustion appliance
- 3.23 maximum differential pressure at the flue gas inlet into the chimney
- 3.24 secondary air
- 3.25 minimum differential pressure at the flue gas inlet into the chimney
- 3.26 secondary air device
- 3.27 draught regulator
- 3.28 draught diverter
- 3.29 temperature limit of the inner surface
- 3.30 air-supply duct
- 3.31 balanced flue chimney
- 3.32 chimney segment
- 3.33 condensate mass flow
- 3.34 connecting air supply pipe
- 3.35 condensation factor
- 3.36 chimney fan
- 3.36.1 exhaust fan
- 3.36.2 inline fan
- 4 Symbols and abbreviations
- 5 Calculation method for non-balanced flue chimneys
- 5.1 General principles
- 5.2 Pressure requirements
- 5.3 Temperature requirement
- 5.4 Calculation procedure
- 5.5 Flue gas data characterising the combustion appliance
- 5.6 Characteristic data for the calculation
- 5.7 Basic values for the calculation
- 5.8 Determination of the temperatures
- 5.9 Determination of the density of the flue gas and the velocity of the flue gas
- 5.10 Determination of the pressures
- 5.11 Minimum draught required at the flue gas inlet into the chimney and maximum
- 5.12 Calculation of the inner surface temperature at the chimney outlet (T )
- 6 Secondary air for negative pressure chimneys
- 6.1 General
- 6.2 Calculation method
- 6.3 Basic values for the calculation of secondary air
- 2 NL L 2 NL
- 2 NL L 2 NL
- 6.4 Pressures
- 6.5 Temperature requirement with secondary air
- 7 Calculation method for balanced flue chimneys
- 7.1 General principles
- 7.2 Pressure requirements
- 7.3 Temperature requirements
- 7.4 Calculation procedure
- 7.5 Flue gas data characterizing the combustion appliance
- 7.6 Characteristic data for the calculation
- 7.7 Basic values for the calculation
- 7.8 Determination of the temperatures
- 7.9 Determination of densities and velocities
- 7.10 Determination of pressures
- 7.11 Calculation of the inner surface temperature at the flue duct outlet (T )
- 8 Consideration of the condensation heat of the flue gas water vapour
- 8.1 General
- 8.2 Onset of condensation
1 Scope
This document specifies methods for the calculation of the thermal and fluid dynamic characteristics of chimneys serving one combustion appliance.
The methods in this part of this document are applicable to negative or positive pressure chimneys with wet or dry operating conditions. It is valid for chimneys with combustion appliances for fuels subject to the knowledge of the flue gas characteristics which are needed for the calculation. The methods in this part of this document are applicable to chimneys with one inlet connected with one combustion appliance.
2 Normative references
The following documents are referred to in the text in such a way that some or all of their content constitutes requirements of this document. For dated references, only the edition cited applies. For undated references, the latest edition of the referenced document (including any amendments) applies. EN 1443:2019, Chimneys - General requirements EN 1749, Classification of gas appliances according to the method of supplying combustion air and of evacuation of the combustion products (types) EN 15287-1:2023, Chimneys - Design, installation and commissioning - Part 1: Chimneys and connecting flue pipes for non-roomsealed combustion appliances EN 15287-2:2023, Chimneys - Design, installation and commissioning - Part 2: Chimneys and connecting flue pipes for roomsealed combustion appliances
EN 16475-2:—, Chimneys - Accessories - Part 2: Chimney fans - Requirements and test methods
EN 16475-3:—, Chimneys - Accessories - Part 3: Draught regulators, standstill opening devices and combined secondary air devices - Requirements and test methods
3 Terms and definitions
For the purposes of this document, the terms and definitions given in EN 1443:2019, EN 15287-1:2023, EN 15287-2:2023 and the following apply.
ISO and IEC maintain terminological databases for use in standardization at the following addresses:
- IEC Electropedia: available at http://www.electropedia.org/
- ISO Online browsing platform: available at http://www.iso.org/obp
3.1 heat output
Q amount of heat produced by a combustion appliance per unit of time
Under preparation. Stage at time of publication: prEN 16475-2:2025
Under preparation. Stage at time of publication: prEN 16475-3:2025
oSIST prEN 13348-1:2025 prEN 13384-1:2025 (E)
3.1.1 nominal heat output
Q N continuous heat output specified in the documentation of the combustion appliance related to specified fuels
3.1.2 heat output range
range of output below the nominal heat output specified in the documentation over which the combustion appliance can be used
3.2 heat input
Q F amount of heat in unit time which is supplied to the combustion appliance by the fuel based on its net caloric value H u
3.3 efficiency of the combustion appliance
ηW ratio of the heat output (Q) from the combustion appliance to the heat input (Q ) F
3.4 flue gas mass flow
𝒎𝒎̇ mass of flue gas leaving the combustion appliance through the connecting flue pipe per time unit
3.5 effective height of the chimney
H difference in height between the axis of the flue gas inlet into the chimney and the outlet of the chimney
3.6 effective height of the connecting flue pipe
H V difference in height between the axis of the flue gas chimney outlet of the combustion appliance and the axis of the flue gas inlet into the chimney Note 1 to entry In the case of open fire chimneys, H is the difference in height between the height of the V upper frame of the furnace and the axis of the flue gas inlet into the chimney.
3.7 draught
positive value of the negative pressure in the flue
3.8 theoretical draught available due to chimney effect
P H pressure difference caused by the difference in weight between the column of air equal to the effective height outside a chimney and the column of flue gas equal to the effective height inside the chimney
oSIST prEN 13348-1:2025 prEN 13384-1:2025 (E)
3.9 pressure resistance of the chimney
P R pressure which is necessary to overcome the resistance of the flue gas mass flow which exists when carrying the flue gases through the chimney
3.10 wind velocity pressure
P L pressure generated on the chimney due to wind
3.11 minimum draught at the flue gas inlet into the chimney
P Z difference between the minimum theoretical draught and the sum of the maximum pressure resistance of the chimney and the wind velocity pressure
3.12 maximum draught at the flue gas inlet into the chimney
PZmax difference between the maximum theoretical draught and the minimum pressure resistance in the chimney
3.13 minimum draught for the combustion appliance
P W difference between the static air pressure of the room of installation of the combustion appliance and the static pressure of the flue gas at the chimney outlet of the combustion appliance which is necessary to maintain the correct operation of the combustion appliance
3.14 maximum draught for the combustion appliance
P Wmax difference between the static air pressure of the room of installation of the combustion appliance and the static pressure of the flue gas at the outlet of the combustion appliance which is the maximum allowed to maintain the correct operation of the combustion appliance
3.15 effective pressure resistance of the connecting flue pipe
P FV static pressure difference between the axis of the inlet of the connecting flue pipe and the axis of the chimney outlet due to the theoretical draught and pressure resistance
3.16 effective pressure resistance of the air supply
P B difference between the static pressure in the open air and the static air pressure in the room of installation of the combustion appliance at the same height
oSIST prEN 13348-1:2025 prEN 13384-1:2025 (E)
3.17 minimum draught required at the flue gas inlet into the chimney
P Ze sum of the minimum draught required for the combustion appliance and the draught required to overcome the effective pressure resistance of the connecting flue pipe and the effective pressure resistance of the air supply
3.18 maximum allowed draught at the flue gas inlet into the chimney
P Zemax sum of the maximum draught allowed for the combustion appliance and the draught required to overcome the effective pressure resistance of the connecting flue pipe and the effective pressure resistance of the air supply
3.19 maximum positive pressure at the flue gas inlet into the chimney
P ZO difference of the maximum pressure resistance and the minimum theoretical draught of the chimney added by the wind velocity pressure
3.20 minimum positive pressure at the flue gas inlet into the chimney
P ZOmin difference of the minimum pressure resistance and the maximum theoretical draught of the chimney
3.21 maximum differential pressure of the combustion appliance
P WO maximum difference between the static pressure of the flue gas at the chimney outlet of the combustion appliance and the static pressure of the air at the inlet to the combustion appliance specified for its correct operation
3.22 minimum differential pressure of the combustion appliance
P WOmin minimum difference between the static pressure of the flue gas at the outlet of the combustion appliance and the static pressure of the air at the inlet to the combustion appliance specified for its correct operation. This can be a negative value.
3.23 maximum differential pressure at the flue gas inlet into the chimney
PZOe difference between the maximum differential pressure of the combustion appliance and the sum of the effective pressure resistance of the connecting flue pipe and the effective pressure resistance of the air supply
3.24 secondary air
ambient air added to the flue gas in addition to the nominal flue gas mass flow
oSIST prEN 13348-1:2025 prEN 13384-1:2025 (E)
3.25 minimum differential pressure at the flue gas inlet into the chimney
P ZOemin difference between the minimum differential pressure of the combustion appliance and the sum of the effective pressure resistance of the connecting flue pipe and the effective pressure resistance of the air supply
3.26 secondary air device
draught regulator or a draught diverter
3.27 draught regulator
component which automatically supplies ambient air to the chimney, the connecting flue pipe or the combustion appliance
3.28 draught diverter
device, placed in the combustion products passage of the combustion appliance, that is intended to maintain the quality of combustion within certain limits and to keep the combustion stable under certain conditions of up draught and down draught
3.29 temperature limit of the inner surface
T g allowed minimum temperature of the inner surface of the chimney outlet
3.30 air-supply duct
component or components parallel to the chimney (separate or concentric) that conveys combustion air from the outside atmosphere to the inlet of the connecting air supply pipe
3.31 balanced flue chimney
chimney where the point of air entry to the air supply duct is adjacent to the point of discharge of combustion products from the flue, the inlet and outlet being so positioned that wind effects are substantially balanced
3.32 chimney segment
calculation part of a chimney
3.33 condensate mass flow
𝜟𝜟𝒎𝒎̇ 𝐃𝐃 mass of water vapour of the flue gas condensed in the combustion appliance, connecting flue pipe or the chimney per time unit
3.34 connecting air supply pipe
component or components connecting the air supply duct outlet with the room-sealed combustion appliance combustion air inlet
oSIST prEN 13348-1:2025 prEN 13384-1:2025 (E)
3.35 condensation factor
f K proportion of the theoretical maximum condensation mass flow usable in the calculation
3.36 chimney fan
exhaust fan or inline fan
3.36.1 exhaust fan
fan positioned on the outlet of the chimney
3.36.2 inline fan
fan positioned as a section of the connecting flue
4 Symbols and abbreviations
The symbols given in this clause can be completed by one or more indices to indicate location or materials if necessary.
Table 1 — Symbols, terminology and units Symbol Terminology Unit
A cross sectional area m c specific heat capacity J/(kg · K) c specific heat capacity of flue gas J/(kg · K) p d thickness of the section m D diameter m D hydraulic diameter m h E heat flux ratio –
g acceleration due to gravity m/s H effective height of the chimney m
k coefficient for heat transmission W/(m · K) K coefficient of cooling – L length m l proportion of condensation surface – C 𝑚𝑚̇ flue gas mass flow kg/s flue gas mass flow of combustion appliance reduced by condensed 𝑚𝑚̇ kg/s 𝑊𝑊 water 𝑚𝑚̇ condensate mass flow kg/s 𝐷𝐷 N Nusselt number – u
oSIST prEN 13348-1:2025 prEN 13384-1:2025 (E) Symbol Terminology Unit N number of segments – seg p static pressure Pa p external air pressure Pa L P effective pressure resistance of the air supply Pa B P pressure resistance due to friction and form resistance of the chimney Pa E P effective pressure resistance of the connecting flue pipe Pa FV difference in pressure caused by change of velocity of flue gas in the P Pa G chimney P theoretical draught available due to chimney effect Pa H theoretical draught available due to chimney effect of the connecting P Pa HV flue pipe P wind velocity pressure Pa L P draught required for secondary air devices Pa NL P pressure resistance of the chimney Pa R P pressure resistance of the connecting flue pipe Pa RV P minimum draught for the combustion appliance Pa W P maximum draught for the combustion appliance Pa Wmax P maximum differential pressure of the combustion appliance Pa WO P minimum differential pressure of the combustion appliance Pa WOmin P minimum draught at the flue gas inlet into the chimney Pa Z P maximum draught at the flue gas inlet into the chimney Pa Zmax P minimum draught required at the flue gas inlet into the chimney Pa Ze P maximum allowed draught at the flue gas inlet into the chimney Pa Zemax P maximum positive pressure at the flue gas inlet into the chimney Pa ZO P minimum positive pressure at the flue gas inlet into the chimney Pa ZOmin P maximum differential pressure at the flue gas inlet into the chimney Pa ZOe P minimum differential pressure at the flue gas inlet into the chimney Pa ZOemin P maximum allowed pressure from the designation of the chimney Pa Zexcess maximum allowed pressure from the designation of the connecting flue P Pa ZVexcess pipe Pr Prandtl number – q heat transfer from the flue to the outer surface W C q condensation heat W K Q heat output kW Q heat input kW F
oSIST prEN 13348-1:2025 prEN 13384-1:2025 (E) Symbol Terminology Unit Q nominal heat output kW N r mean value for roughness of the inner surface m R gas constant of the flue gas J/(kg · K) R gas constant of the air J/(kg · K) L Re Reynolds number – s cross section m SE flow safety coefficient – S correction factor for temperature instability – H
t temperature °C T temperature, absolute K T flue gas temperature at the chimney inlet K e T temperature limit K g T inner surface temperature at chimney outlet K io inner surface temperature at the chimney outlet at temperature T K iob equilibrium T flue gas temperature immediately before the additional insulation K irb T external air temperature K L T mean temperature of the flue gas K m T flue gas temperature at the chimney outlet K o T water dew point K p T condensing temperature K sp T ambient air temperature K u T ambient air temperature of the boiler room K ub T ambient air temperature for heated areas K uh T ambient air temperature for areas external to the building K ul T ambient air temperature at the chimney outlet K uo the ambient air temperature immediately before the additional T K ur insulation T ambient air temperature for unheated areas inside the house K uu T flue gas temperature of the combustion appliance K W flue gas temperature of the combustion appliance at nominal heat T K WN output flue gas temperature of the combustion appliance at the lowest possible T K Wmin heat output
oSIST prEN 13348-1:2025 prEN 13384-1:2025 (E) Symbol Terminology Unit U internal chimney segment parameter m w mean velocity within a cross section m/s w mean velocity over a defined length m/s m y form value – z height above sea level m
α coefficient of heat transfer W/(m · K) β ratio of the combustion air mass flow to the flue gas mass flow – γ angle between flow directions ° δ wall thickness m ε proportion of black body radiation emitted by a surface – coefficient of flow resistance due to a directional and/or ζ – cross sectional and/or mass flow change in the flue
dynamic viscosity η N ⋅ s/m η efficiency of the combustion appliance – W η efficiency of the combustion appliance at nominal heat output – WN λ coefficient of thermal conductivity W/(m · K)
ρ density kg/m
ρ density of the external air kg/m L mean density of flue gas averaged over a defined length and over the
ρ kg/m m cross section σ(CO ) volume-concentration of CO % 2 2 σ(O ) volume-concentration of O % 2 2 σ(H O) volume-concentration of H O (vapour) % 2 2 2 4 σ black body radiation number W/(m · K ) rad ψ coefficient of flow resistance due to friction of the flue –
thermal resistance
m · K/W
𝛬𝛬
oSIST prEN 13348-1:2025 prEN 13384-1:2025 (E) Table 2 — Additional subscripts Subscript Terminology Unit a outside – A flue gas – b equilibrium temperature condition – B combustion air – D water vapour – e inlet – F open fire place – G change in velocity – i inside – K condensation – L open air (outside) – m mean value – M mixture – n counting index – N nominal value – NL secondary air – o chimney outlet – O positive pressure – tot totalized over all sections (segments) – u ambient air – V connecting flue pipe – W combustion appliance –
5 Calculation method for non-balanced flue chimneys
5.1 General principles
The calculation of inside dimensions (cross section) of negative pressure chimneys is based on the following four criteria:
- the minimum draught at the flue gas inlet into the chimney shall be equal to or greater than the minimum draught required at the flue gas inlet into the chimney;
- the minimum draught at the flue gas inlet to the chimney shall be equal to or greater than the effective pressure resistance of the air supply;
- the maximum draught at the flue gas inlet into the chimney shall be equal to or less than the maximum allowed draught at the flue gas inlet into the chimney;
oSIST prEN 13348-1:2025 prEN 13384-1:2025 (E) - the temperature of the inner surface at the outlet of the chimney shall be equal to or greater than the temperature limit.
The calculation of inside dimensions (cross section) of positive pressure is based on the following four criteria:
- the maximum positive pressure at the flue gas inlet into the chimney shall be equal or less than the maximum differential pressure at the flue gas inlet into the chimney;
- the maximum positive pressure in the connecting flue pipe and in the chimney shall not be higher than the excess pressure for which both are designated;
- the minimum positive pressure at the flue gas inlet into the chimney shall be equal or greater than the minimum differential pressure at the flue gas inlet into the chimney;
- the temperature of the inner surface at the chimney outlet of the chimney shall be equal to greater than the temperature limit.
NOTE The pressure requirements for maximum draught or minimum positive pressure are only required if there is a limit for the maximum draught for the negative pressure combustion appliance or a minimum differential pressure of the positive pressure combustion appliance.
In order to verify the criteria two sets of external conditions are used:
- the calculation of the minimum draught and maximum positive pressure is made with conditions for which the capacity of the chimney is minimal (i.e. high outside temperature); and also
- the calculation of the maximum draught and minimum positive pressure and of the inner surface temperature with conditions for which the inside temperature of the chimney is minimal (i.e. low outside temperature.
The input data and results of the calculation shall be reported. An example of the content is given in Annex E.
5.2 Pressure requirements
5.2.1 Negative pressure chimneys
The following relationships shall be verified:
P = P − P − P ≥ P + P + P = P , in Pa (1) Z H R L W FV B Ze P ≥ P , in Pa (2) Z B and if P < 0 Pa and the connecting flue pipe is designated for negative pressure (N):
W P ≥ P + P , in Pa (3) Z B FV or if P < 0 Pa and the connecting flue pipe is designated for positive pressure (P, M or H):
W P – P ≤ P , in Pa (4) FV Z ZVexcess or if P < 0 Pa and only the first part of the connecting flue pipe is designated for positive pressure:
W P ≥ P + P , in Pa (5) Z B FV2 P + P – P ≤ P , in Pa (6) FV1 FV2 Z ZVexcess
...