Abstract

This document specifies methods for calculation of the thermal and fluid dynamic characteristics of chimneys serving more than one combustion appliance.
This document is applicable to the following cases:
a)   where the chimney is connected with more than one connecting flue pipe from individual or several combustion appliances in a multi-inlet arrangement;
b)   where the chimney is connected with an individual connecting flue pipe connecting more than one combustion appliance in a cascade arrangement;
c)   where the balanced flue chimney consists of a collective air supply duct serving the combustion air to more than one combustion appliance.
This document is applicable to cases where each combustion appliance is connected to an individual flue duct located inside the collective air supply duct to the outlet, every individual flue duct has a temperature class not exceeding T120, a pressure class of P1, M1 or H1 and a sootfire class of O.
The case of multiple inlet cascade arrangement is covered by the case a).
This document is applicable to chimneys operating under negative pressure conditions (there can be positive pressure condition in the connecting flue pipe) and with chimneys operating under positive pressure conditions and is also applicable for chimneys serving combustion appliances for liquid, gaseous and solid fuels.
For positive pressure chimneys (case a), b) and c)) this document only applies if any combustion appliance which is out of action can be positively isolated to prevent flue gas back flow.
This document does not apply to the following:
—   chimneys with different thermal resistance or different cross-section in the various chimney segments.
This document does not specify a determination of energy gain.
—   chimneys with open fire places, e.g. open fire chimneys or chimney inlets which are normally intended to operate open to the room;
—   chimneys which serve different kinds of combustion appliances regarding natural draught, fan assisted, forced draught or combustion engine;
Fan assisted combustion appliances with draught diverter between the fan and the chimney are considered as natural draught combustion appliances.
—   chimneys with multiple inlets from more than 5 storeys;
This does not apply to balanced flue chimney.
—   chimneys serving combustion appliances with open air supply through ventilation openings or air supply ducts, which are not installed in the same air supply pressure region (e.g. same side of building).

Status
Not Published
Public Enquiry End Date
30-May-2026
Technical Committee
POZ - Požarna varnost
Current Stage
5020 - Formal vote (FV) (Adopted Project)
Start Date
19-Nov-2026
Due Date
07-Jan-2027
Completion Date
20-Nov-2026

Buy Documents

Draft

oSIST prEN 13384-2:2026

English language (105 pages)
Preview
Preview
e-Library read for
×1 day

kSIST FprEN 13384-2:2026 is the Slovenian draft of prEN 13384-2, published by SIST as a European draft for chimney calculations. It specifies thermal and fluid dynamic calculation methods for chimneys serving more than one combustion appliance, so designers and installers can check whether a given chimney arrangement can operate safely under the intended conditions.

This draft is for engineering use. It is a calculation document, not an installation manual, and it supports the execution standards used for chimney systems serving multiple appliances.

What does kSIST FprEN 13384-2:2026 specify?

kSIST FprEN 13384-2:2026 specifies methods for calculating the thermal and fluid dynamic characteristics of chimneys that serve more than one combustion appliance. It covers multi-inlet arrangements, cascade arrangements, and balanced flue chimneys with a collective air supply duct.

The scope also sets out the operating limits. The document applies to negative-pressure chimneys, positive-pressure chimneys, and chimneys serving liquid, gaseous, and solid fuels, with conditions for positive-pressure use where an out-of-action appliance can be positively isolated to prevent flue gas backflow.

The document is organized into clauses on scope, references, terms, symbols, the calculation method, appliance data, chimney and pipe data, basic calculation data, temperature determination, mixing, density and velocity, pressure determination, inner surface temperature, cascade installations, balanced flue chimneys, balanced flue chimneys with more than one individual flue duct in a collective air supply duct, and chimney fans. It ends with three informative annexes.

AnnexWhat it covers
Annex ARecommendations for design choices and connecting flue pipe arrangement
Annex BCharacteristics for the combustion appliance when documentation does not provide the needed flue gas data
Annex CExample report for input data and output data of the calculation

What are the key requirements of kSIST FprEN 13384-2:2026?

kSIST FprEN 13384-2:2026 is built around an iterative calculation that finds a mass flow distribution satisfying pressure equilibrium at each flue gas inlet. Once that balance is found, the document requires checks on mass flow, pressure, and temperature for the relevant operating cases.

Calculation logic and operating cases

Clause 5 states that the calculation uses mass and energy conservation under quasi steady state conditions. In practice, this means the result is not a single closed-form answer but an iterative verification of the whole chimney system.

The validation has to be carried out for the relevant working conditions described in Clause 5.6, including appliances operating at nominal heat output, minimum heat output, and cases where one appliance is operating while the others are out of action. For positive-pressure chimneys, the document also includes a case with one appliance at minimum nominal heat output and the others at maximum nominal heat output.

This matters because a chimney serving several appliances can be safe in one firing pattern and not in another. The designer has to check the worst relevant combinations, not only the normal case.

Appliance data to be used

Clause 6 requires flue gas data that characterise each combustion appliance. The document uses declared or calculated draught or differential pressure, declared flue gas temperature, and flue gas composition data.

For some appliances, Clause 6 uses polynomial relations for calculated draught or differential pressure and an exponential relation for calculated flue gas temperature. It also extends the calculation to CO2 or O2 content of flue gas. In practice, this means the appliance documentation must provide enough data for the chimney calculation, or the fallback values in Annex B are used.

Chimney and pipe data

Clause 7 requires the mean roughness of the inner surface and the thermal resistance for each chimney segment and connecting flue pipe. Clauses 8 and 9 then set the basic calculation data and the temperature calculations, including external and ambient air temperatures, external air pressure, gas constants, density, specific heat capacity, water vapour content, and condensing temperature.

This matters because the same chimney can behave differently depending on geometry, insulation, and ambient conditions. The calculation needs those basic values before any pressure or temperature check can be trusted.

Mixing, density, velocity, and pressures

Clauses 10 to 12 cover gas mixing, density, velocity, and pressure determination. The document calculates the flue gas properties after each confluence, then uses those values to determine pressures in each segment and at each inlet.

The pressure section includes draught available from chimney effect, pressure resistance in chimney segments, pressure resistance of connecting flue pipes, and pressure resistance of the air supply where relevant. In practice, this is the part that tells the designer whether the system will actually move gas in the intended direction.

Temperature requirement

Clause 5.5 and Clause 13 require a temperature check at the inner surface of the chimney segment outlet. For dry operation, the temperature limit is set to the condensing temperature of the flue gas. For wet operation, the limit is the freezing point of water.

That check matters because it is the standard’s way of controlling condensation and freezing risk at the chimney surface. The document also allows specific waiver situations when a combustion appliance is replaced, provided fire and operational safety are not reduced and the parties agree in writing.

Special system types

Clauses 14 and 15 repeat the same overall logic for cascade installations and balanced flue chimneys. Clause 16 then covers a balanced flue chimney with more than one individual flue duct in a collective air supply duct.

These clauses matter because those system types have different airflow paths. The standard gives separate calculation routes so that the pressure and temperature effects in the collector, the air supply, and the flue ducts are handled correctly.

Chimney fans

Clause 17 allows chimney fans to be included only under defined safety conditions. It distinguishes between inline fans and exhaust fans and sets the calculation approach for their pressure gain or flow resistance.

In practice, this means a fan can be part of the design calculation only when its failure is controlled in a safe way or safe operation is otherwise demonstrated.

What terms does kSIST FprEN 13384-2:2026 define?

  • Chimney segment - the part of a chimney between two flue gas connections, or between the last connection and the outlet.
  • Collector segment - the part of a connecting flue pipe between two flue gas connections, or between the last connection and the chimney inlet.
  • Flue gas mass flow - the mass flow leaving the combustion appliance through the connecting flue pipe per unit time.
  • Declared flue gas mass flow - the flue gas mass flow stated in the appliance documentation for the heat output used in the calculation.
  • Calculated flue gas temperature - the flue gas temperature at the appliance outlet as determined from the calculated mass flow.
  • Cascade arrangement - two or more combustion appliances in the same space connected by a common connecting flue pipe to the chimney.
  • Balanced flue chimney - a chimney arrangement where air entry and combustion product discharge are positioned so wind effects are substantially balanced.
  • Pressure equalizing opening - an opening or duct that directly connects the air supply duct with the flue at its base.

Who uses kSIST FprEN 13384-2:2026?

kSIST FprEN 13384-2:2026 is used by chimney designers, heating-system engineers, appliance manufacturers, installers, and commissioning teams working on multi-appliance chimney systems. It is also relevant to quality and compliance staff who need to review whether a proposed installation has been calculated on a defined technical basis.

The document is especially useful for projects involving multi-inlet chimneys, cascade-connected appliances, balanced flue systems, and installations with chimney fans. In practice, users apply it to design checks, system sizing, verification of appliance compatibility, and reporting of calculation inputs and outputs.

What changed in kSIST FprEN 13384-2:2026 from the previous edition?

kSIST FprEN 13384-2:2026 will supersede EN 13384-2:2015+A1:2019. The European foreword states these technical changes:

  • editorial mistakes were corrected;
  • the calculation methods were extended to include O content of the flue gas;
  • pressure requirements for negative-pressure chimneys were modified for possible connection of a positive-pressure combustion appliance with a total or partly positive-pressure connection pipe;
  • remarks were added for the temperature requirement;
  • for concentric duct, the simplified heat transfer calculation based on Srad was deleted and the detailed calculation method from Part 1 was added;
  • a new clause was added for calculating a common balanced flue chimney with more than one flue pipe;
  • the treatment of terminal ζ-values was clarified in relation to static pressure;
  • a new Annex C with an example report for input and output data was added.

Which standards are used with kSIST FprEN 13384-2:2026?

  • EN 1443:2019 - provides general chimney requirements and the base terms and definitions used with this part.
  • prEN 13384-1:2025 - provides the calculation principles, general symbols and abbreviations, and many property and heat-transfer methods used by this part.
  • EN 15287-1:2023 - gives design, installation and commissioning requirements for chimneys for non-roomsealed combustion appliances.
  • EN 15287-2:2023 - gives design, installation and commissioning requirements for chimneys and connecting flue pipes for roomsealed combustion appliances.

What does the kSIST FprEN 13384-2:2026 document contain?

The document contains a full calculation framework with formulas, figures, and tables for multi-appliance chimney systems. It includes the procedure for iterative pressure balance, the calculation of temperatures, gas mixing, densities, velocities, and pressure losses, plus the special treatment of cascade systems, balanced flue chimneys, and chimney fans.

It also contains informative annexes with practical recommendations, fallback combustion-appliance characteristics, and an example calculation report. Annex C is particularly useful for documenting design reviews, technical files, commissioning records, or software output in a consistent format.

Relations

Effective Date
15-Feb-2023

Buy Documents

Draft

oSIST prEN 13384-2:2026

English language (105 pages)
Preview
Preview
e-Library read for
×1 day

Get Certified

Connect with accredited certification bodies for this standard

DIBt (Deutsches Institut für Bautechnik)

German Institute for Building Technology.

DAKKS Germany Verified

DIN CERTCO

DIN Group product certification.

DAKKS Germany Verified

Aboma Certification B.V.

Specialized in construction, metal, and transport sectors.

RVA Netherlands Verified

Sponsored listings

Frequently Asked Questions

kSIST FprEN 13384-2:2026 is a draft published by the Slovenian Institute for Standardization (SIST). Its full title is "Chimneys - Thermal and fluid dynamic calculation methods - Part 2: Chimneys serving more than one combustion appliance". This standard covers: This document specifies methods for calculation of the thermal and fluid dynamic characteristics of chimneys serving more than one combustion appliance. This document is applicable to the following cases: a) where the chimney is connected with more than one connecting flue pipe from individual or several combustion appliances in a multi-inlet arrangement; b) where the chimney is connected with an individual connecting flue pipe connecting more than one combustion appliance in a cascade arrangement; c) where the balanced flue chimney consists of a collective air supply duct serving the combustion air to more than one combustion appliance. This document is applicable to cases where each combustion appliance is connected to an individual flue duct located inside the collective air supply duct to the outlet, every individual flue duct has a temperature class not exceeding T120, a pressure class of P1, M1 or H1 and a sootfire class of O. The case of multiple inlet cascade arrangement is covered by the case a). This document is applicable to chimneys operating under negative pressure conditions (there can be positive pressure condition in the connecting flue pipe) and with chimneys operating under positive pressure conditions and is also applicable for chimneys serving combustion appliances for liquid, gaseous and solid fuels. For positive pressure chimneys (case a), b) and c)) this document only applies if any combustion appliance which is out of action can be positively isolated to prevent flue gas back flow. This document does not apply to the following: — chimneys with different thermal resistance or different cross-section in the various chimney segments. This document does not specify a determination of energy gain. — chimneys with open fire places, e.g. open fire chimneys or chimney inlets which are normally intended to operate open to the room; — chimneys which serve different kinds of combustion appliances regarding natural draught, fan assisted, forced draught or combustion engine; Fan assisted combustion appliances with draught diverter between the fan and the chimney are considered as natural draught combustion appliances. — chimneys with multiple inlets from more than 5 storeys; This does not apply to balanced flue chimney. — chimneys serving combustion appliances with open air supply through ventilation openings or air supply ducts, which are not installed in the same air supply pressure region (e.g. same side of building).

This document specifies methods for calculation of the thermal and fluid dynamic characteristics of chimneys serving more than one combustion appliance. This document is applicable to the following cases: a) where the chimney is connected with more than one connecting flue pipe from individual or several combustion appliances in a multi-inlet arrangement; b) where the chimney is connected with an individual connecting flue pipe connecting more than one combustion appliance in a cascade arrangement; c) where the balanced flue chimney consists of a collective air supply duct serving the combustion air to more than one combustion appliance. This document is applicable to cases where each combustion appliance is connected to an individual flue duct located inside the collective air supply duct to the outlet, every individual flue duct has a temperature class not exceeding T120, a pressure class of P1, M1 or H1 and a sootfire class of O. The case of multiple inlet cascade arrangement is covered by the case a). This document is applicable to chimneys operating under negative pressure conditions (there can be positive pressure condition in the connecting flue pipe) and with chimneys operating under positive pressure conditions and is also applicable for chimneys serving combustion appliances for liquid, gaseous and solid fuels. For positive pressure chimneys (case a), b) and c)) this document only applies if any combustion appliance which is out of action can be positively isolated to prevent flue gas back flow. This document does not apply to the following: — chimneys with different thermal resistance or different cross-section in the various chimney segments. This document does not specify a determination of energy gain. — chimneys with open fire places, e.g. open fire chimneys or chimney inlets which are normally intended to operate open to the room; — chimneys which serve different kinds of combustion appliances regarding natural draught, fan assisted, forced draught or combustion engine; Fan assisted combustion appliances with draught diverter between the fan and the chimney are considered as natural draught combustion appliances. — chimneys with multiple inlets from more than 5 storeys; This does not apply to balanced flue chimney. — chimneys serving combustion appliances with open air supply through ventilation openings or air supply ducts, which are not installed in the same air supply pressure region (e.g. same side of building).

kSIST FprEN 13384-2:2026 is classified under the following ICS (International Classification for Standards) categories: 91.060.40 - Chimneys, shafts, ducts. The ICS classification helps identify the subject area and facilitates finding related standards.

kSIST FprEN 13384-2:2026 has the following relationships with other standards: It is inter standard links to SIST EN 13384-2:2015+A1:2019. Understanding these relationships helps ensure you are using the most current and applicable version of the standard.

kSIST FprEN 13384-2:2026 is associated with the following European legislation: EU Directives/Regulations: 305/2011; Standardization Mandates: M/105. When a standard is cited in the Official Journal of the European Union, products manufactured in conformity with it benefit from a presumption of conformity with the essential requirements of the corresponding EU directive or regulation.

kSIST FprEN 13384-2:2026 is available in PDF format for immediate download after purchase. The document can be added to your cart and obtained through the secure checkout process. Digital delivery ensures instant access to the complete standard document.

Standards Content (Sample)

Contents

  • Introduction
  • 1 Scope
  • 2 Normative references
  • 3 Terms and definitions
  • 3.1 chimney segment
  • 3.2 collector segment
  • 3.3 flue gas mass flow
  • 3.3.1 declared flue gas mass flow
  • 3.3.2 calculated flue gas mass flow
  • 3.4 calculated flue gas temperature
  • 3.5 calculated draught of the flue gas of the combustion appliance
  • 3.6 flue damper
  • 3.7 balanced flue chimney
  • 3.8 cascade arrangement
  • 3.9 multi inlet arrangement
  • 3.10 air supply duct
  • 3.11 pressure equalizing opening
  • 4 Symbols and abbreviations
  • 5 Calculation method
  • 5.1 General principles
  • 5.2 Pressure equilibrium condition
  • 5.3 Mass flow requirement
  • 5.4 Pressure requirements
  • 5.5 Temperature requirement
  • 5.6 Calculation procedure
  • 6 Flue gas data characterising the combustion appliance
  • 2 W,j
  • 2 Wc,j
  • 2 Wc,j
  • 2 W,j
  • 2 Wc,j 2 W,j 2 Wc,j 2 W,j
  • 7 Data for chimney and connecting flue pipes
  • 8 Basic data for the calculation
  • 8.1 General
  • 8.2 Air temperatures
  • 8.3 External air pressure (pL)
  • 8.4 Gas constant
  • 8.5 Density of external air (ρ )
  • 8.6 Specific heat capacity of the flue gas (cp)
  • 8.7 Water vapour content (σ(H2O),j) and condensing temperature (Tsp)
  • 8.8 Correction factor for temperature instability (SH)
  • 8.9 Flow safety coefficient (SE)
  • 8.10 External coefficient of heat transfer
  • 9 Determination of temperatures
  • 10 Mixing calculations
  • 10.1 General
  • 10.2 Flue gas mass flow (𝒎𝒎̇) and temperature (T ) at the inlet of chimney segment j
  • 2 V,j 2 Wc,j
  • 2 V,j 2 Wc,j
  • 2 V,j
  • 10.4 Flue gas data
  • 11 Density and velocity of the flue gas
  • 12 Determination of the pressures
  • 12.1 Pressures at each inlet of the chimney segments
  • 12.2 Minimum draught required at the flue gas inlet into the chimney and maximum
  • 13 Inner surface temperature
  • 14 Cascade installations
  • 14.1 Principle of the calculation method
  • 14.2 Pressure equilibrium condition
  • 14.3 Mass flow requirement
  • 14.4 Pressure requirements
  • 14.5 Temperature requirement
  • 14.6 Calculation procedure
  • 14.7 Pressures at the outlet of the connecting flue pipe and pressures at the inlet of the
  • 14.8 Inner surface temperature (TiobC,j,l)
  • 15 Calculation method for balanced flue chimneys
  • 15.1 General principles
  • 15.2 Pressure equilibrium condition
  • 15.3 Mass flow requirement
  • 15.4 Pressure requirements
  • 15.5 Temperature requirements
  • 15.6 Calculation procedure for balanced flue chimneys
  • 15.7 Mass flow of the combustion air
  • 15.8 Determination of the temperatures in balanced flue chimneys
  • 15.9 Determination of densities and velocities
  • 15.10 Determination of pressures
  • 15.11 Calculation of the inner surface temperature at the flue duct outlet (Tiob)
  • 16 Calculation method for a balanced flue chimney with more than one
  • 17 Consideration of chimney fans
  • 17.1 General

Introduction

The calculation described in this document is complex and is intended to be solved by using a computer program. The general principles of the calculation method of prEN 13384-1:2025 also apply to this document.

This document is in support of the execution standards for a chimney installation serving more than one combustion appliance.

The execution standards in conjunction with installation instructions identify limitations and safety considerations associated with the design, installation, commissioning and maintenance of a chimney serving more than one combustion appliance (not dealt within the calculation method).

oSIST prEN 13384-2:2026 prEN 13384-2:2026 (E)

1 Scope

This document specifies methods for calculation of the thermal and fluid dynamic characteristics of chimneys serving more than one combustion appliance.

This part of prEN 13384 covers the following cases:

a) where the chimney is connected with more than one connecting flue pipe from individual or several combustion appliances in a multi-inlet arrangement; b) where the chimney is connected with an individual connecting flue pipe connecting more than one combustion appliance in a cascade arrangement; or c) where the balanced flue chimney consists of a collective air supply duct serving the combustion air to more than one combustion appliance. Each combustion appliance is connected to an individual flue duct located inside the collective air supply duct to the outlet. Every individual flue duct has a temperature class not exceeding T120, a pressure class of P1, M1 or H1 and a sootfire class of O. The case of multiple inlet cascade arrangement is covered by the case a). This part of prEN 13384 deals with chimneys operating under negative pressure conditions (there can be positive pressure condition in the connecting flue pipe) and with chimneys operating under positive pressure conditions and is valid for chimneys serving combustion appliances for liquid, gaseous and solid fuels.

For positive pressure chimneys (case a), b) and c)) this part only applies if any combustion appliance which is out of action can be positively isolated to prevent flue gas back flow. This part of EN 13384 does not apply to:

  • chimneys with different thermal resistance or different cross-section in the various chimney segments. This part does not apply to calculate energy gain;
  • chimneys with open fire places, e.g. open fire chimneys or chimney inlets which are normally intended to operate open to the room;
  • chimneys which serve different kinds of combustion appliances regarding natural draught, fan assisted, forced draught or combustion engine. Fan assisted combustion appliances with draught diverter between the fan and the chimney are considered as natural draught combustion appliances;
  • chimneys with multiple inlets from more than 5 storeys. (This does not apply to balanced flue chimney.);
  • chimneys serving combustion appliances with open air supply through ventilation openings or air supply ducts, which are not installed in the same air supply pressure region (e.g. same side of building).

2 Normative references

The following documents are referred to in the text in such a way that some or all of their content constitutes requirements of this document. For dated references, only the edition cited applies. For undated references, the latest edition of the referenced document (including any amendments) applies. EN 1443:2019, Chimneys — General requirements

oSIST prEN 13384-2:2026 prEN 13384-2:2026 (E) prEN 13384-1:2025, Chimneys — Thermal and fluid dynamic calculation methods — Part 1: Chimneys serving one combustion appliance EN 15287-1:2023, Chimneys — Design, installation and commissioning — Part 1: Chimneys for nonroomsealed combustion appliances EN 15287-2:2023, Chimneys — Design, installation and commissioning — Part 2: Chimneys and connecting flue pipes for roomsealed combustion appliances

3 Terms and definitions

For the purposes of this document, the terms and definitions given in EN 1443:2019, prEN 13384-1:2025, EN 15287-1:2023, EN 15287-2:2023 and the following apply.

3.1 chimney segment

part of a chimney between two consecutive flue gas connections or between the last flue gas connection and the chimney outlet

3.2 collector segment

part of a connecting flue pipe between two consecutive flue gas connections or between the last flue gas connection and the chimney inlet

3.3 flue gas mass flow

𝒎𝒎̇ mass of the flue gas leaving the combustion appliance through the connecting flue pipe per unit of time Note 1 to entry: In case of a chimney serving more than one combustion appliance, the air being transported through a combustion appliance which is out of action is also given the term flue gas mass flow.

3.3.1 declared flue gas mass flow

𝒎𝒎̇ W,j flue gas mass flow given in the documentation of the combustion appliance j with respect to the heat output used in the calculation

3.3.2 calculated flue gas mass flow

𝒎𝒎̇ Wc,j flue gas mass flow calculated with respect to calculated draught and the working conditions of the combustion appliance j

3.4 calculated flue gas temperature

𝑻𝑻 Wc,j flue gas temperature at the outlet of the combustion appliance j depending on the calculated flue gas mass flow

oSIST prEN 13384-2:2026 prEN 13384-2:2026 (E)

3.5 calculated draught of the flue gas of the combustion appliance

𝑷𝑷 Wc,j draught at the flue gas outlet of the combustion appliance j depending on the calculated flue gas mass flow

3.6 flue damper

device to close or partially close the flue

3.7 balanced flue chimney

chimney where the point of air entry to the air supply duct is adjacent to the point of discharge of combustion products from the flue, the inlet and outlet being so positioned that wind effects are substantially balanced

3.8 cascade arrangement

arrangement where two or more combustion appliances situated in the same space are connected by a common connecting flue pipe to the chimney

3.9 multi inlet arrangement

arrangement where two or more combustion appliances are connected to the chimney by individual connecting flue pipes

3.10 air supply duct

independent duct in a building or a structural part of a flue terminal conveying combustion air to a roomsealed combustion appliance

3.11 pressure equalizing opening

opening or duct that directly connects the air supply duct with the flue at its base

4 Symbols and abbreviations

Symbols, terminology and units are given to make the text of this document understandable. A list of general symbols and abbreviations is given in prEN 13384-1:2025, Clause 4. Indices added to symbols for purposes of the calculation method for chimneys serving more than one combustion appliance relate to one chimney segment and connecting flue pipe section. An example of an indices numbering scheme is given in Figures 1 and 2. Indices numbering begins at the lowest, farthest combustion appliance connection. For more than one cascade system/connection, the indices numbering scheme for the calculation formula should be adopted in a similar manner to that for a single cascade scheme. Symbols assigned to a specific section will be indicated by the number of the section after the comma (e. g. H is ,1 the effective height of a section of a chimney segment between the outlet of the connecting flue pipe of the combustion appliance in the lowest position and the outlet of the connecting flue pipe of the next combustion appliance).

Each symbol and abbreviation is explained at the formula where it is used.

oSIST prEN 13384-2:2026 prEN 13384-2:2026 (E)

5 Calculation method

5.1 General principles

Key 1 chimney 2 connecting flue pipe j 3 combustion appliance j 4 connecting flue pipe 2 5 combustion appliance 2 6 connecting flue pipe 1 7 combustion appliance 1 8 chimney segment 1 9 chimney segment j Figure 1 — Example of multiple inlet arrangement and numbering pressure values and temperature values of a chimney serving more than one combustion appliance The calculation is based upon determining the mass flow distribution in the chimney which fulfils the pressure equilibrium condition (Formula (1) or (4)) at each flue gas inlet to the chimney (see Figure 1). After such a distribution has been found four requirements shall be verified:

a) the mass flow requirement (Formulae (7) and (8)); b) the pressure requirement for minimum draught (Formula (9) and, if appropriate, Formulae (10), (11), (12) or (13)), or for maximum positive pressure (Formulae (15) and (16)); c) the pressure requirement for maximum draught (Formula (14)) or for minimum positive pressure (Formula (17));

oSIST prEN 13384-2:2026 prEN 13384-2:2026 (E) d) the temperature requirement (Formula (18)).

NOTE The calculation is affected by the specific installation design. For recommendations for the installation of combustion appliance and connection flue pipes, see Annex A. The pressure requirements for maximum draught or minimum positive pressure are only required if there is a limit for the maximum draught for the negative pressure combustion appliance or a minimum differential pressure of the positive pressure combustion appliance. In order to verify the criteria, two sets of external conditions are used:

  • the calculation of the minimum draught and maximum positive pressure is made with conditions for which the capacity of the chimney is minimal (i.e. high outside temperature); and also
  • the calculation of the maximum draught and minimum positive pressure and of the inner surface temperature with conditions for which the inside temperature of the chimney is minimal (i.e. low outside temperature).

The validation of the mass flow requirement and pressure requirement shall be done at following working conditions, using the external and ambient air temperatures specified in prEN 13384-1:2025:

  • all combustion appliances are simultaneously operating at nominal heat output;
  • all combustion appliances are simultaneously operating at minimum heat output;
  • a single combustion appliance operating at nominal heat output and all other combustion appliances out of action (all possible cases);
  • a single combustion appliance operating at minimum heat output and all other combustion appliances out of action (all possible cases);
  • for positive pressure chimneys a single combustion appliance operating at minimum nominal heat output and all other combustion appliances operating at maximum nominal heat output (all possible cases).

If the control of the installation guarantees that not all combustion appliances will be in operation simultaneously, the validation of the mass flow requirement and pressure requirement may be done with the maximum number of combustion appliances which will be in operation under the most adverse condition.

The validation for the mass flow requirement and pressure requirement for working conditions with combustion appliances at minimum heat output is not required in the following cases:

  • the combustion appliances do not have any heat output range;
  • the combustion appliances have a heat output which is limited to a fixed value as specified on a label on the combustion appliance. In this case the nominal heat output is the given heat output on the label;
  • combustion appliances heated with solid fuels without fan and combustion appliances with regulated air supply.

The validation of the mass flow requirement for working conditions with combustion appliances at nominal heat output is not required in the following case:

  • the combustion appliances have a flue gas mass flow at minimum heat output higher than or equal to the flue gas mass flow at nominal heat output.

oSIST prEN 13384-2:2026 prEN 13384-2:2026 (E) The temperature requirement shall be validated for the following relevant working condition, using the ambient and external air temperatures as specified in prEN 13384-1:2025:

  • combustion appliances for solid fuels without fan and combustion appliances with regulated air supply are in operation at nominal heat output;
  • combustion appliances with a draught diverter which provide domestic hot water only are out of action. These combustion appliances operate with a considerable secondary air (these operate only a short time and therefore it can be assumed that condensation will not cause damage or a lack in safety);
  • combustion appliances with a fixed output range are in operation at this (nominal) heat output;
  • all other combustion appliances are in operation at minimum heat output. When chimneys suitable for operating under wet conditions are located inside a building, the check of the temperature requirement is necessary only for the top of the chimney. The validation of the temperature requirement is not necessary when the chimney serves only domestic gas fired water heaters with instantaneous production and domestic gas fired storage water heaters. If the chimney system includes a draught regulator, the system is handled as a cascade system. The input data and results of the calculation shall be reported. An example of the content is given in Annex C.

5.2 Pressure equilibrium condition

5.2.1 Negative pressure chimneys

The following formulae shall be fulfilled for each chimney segment j at all relevant working conditions:

�𝑃𝑃 −𝑃𝑃 �≤ 0,1, in Pa (1) 𝑍𝑍,𝑗𝑗 Ze,𝑗𝑗 𝑁𝑁 𝑃𝑃 =−𝑃𝑃 +� �𝑃𝑃 −𝑃𝑃 � , in Pa (2) Z,𝑗𝑗 𝐿𝐿 H,k R,k 𝑘𝑘=𝑗𝑗 𝑃𝑃 =𝑃𝑃 +𝑃𝑃 +𝑃𝑃 , in Pa (3) Ze,j Wc,j V,j Bc,j where P is the draught at the flue gas inlet to the chimney segment j, in Pa; Z,j P is the theoretical draught available due to chimney effect in chimney segment k, in Pa; H,k P is the pressure resistance of the chimney segment k, in Pa; R,k P is the calculated draught of the combustion appliance, in Pa; Wc,j P is the calculated pressure resistance of the connecting flue pipe j, in Pa; V,j P is the calculated pressure resistance of the air supply for the combustion appliance j, in Pa; Bc,j P is the required draught at the flue gas inlet to the chimney segment j, in Pa; Ze,j P is the wind velocity pressure, in Pa; L N is the number of combustion appliances.

oSIST prEN 13384-2:2026 prEN 13384-2:2026 (E)

5.2.2 Positive pressure chimneys

The following formulae shall be fulfilled for each chimney segment j at all relevant working conditions:

�𝑃𝑃 −𝑃𝑃 �≤ 0,1 , in Pa (4) ZOe,𝑗𝑗 ZO,𝑗𝑗 𝑁𝑁 𝑃𝑃 =𝑃𝑃 +� 𝑃𝑃 −𝑃𝑃 , in Pa (5)

Z,O𝑗𝑗 𝐿𝐿 R,k H,k 𝑘𝑘=𝑗𝑗 𝑃𝑃 =𝑃𝑃 −𝑃𝑃 −𝑃𝑃 , in Pa (6) ZOe,𝑗𝑗 WOc,j V,j Bc,j where P is the positive pressure at the flue gas inlet to the chimney segment j, in Pa; ZO,j P is the theoretical draught available due to chimney effect in chimney segment k, in Pa; H,k P is the pressure resistance of the chimney segment k, in Pa; R,k P is the calculated positive differential pressure of the combustion appliance j, in Pa; WOc,j P is the calculated pressure resistance of the connecting flue pipe j, in Pa; Vj P is the calculated pressure resistance of the air supply for the combustion appliance j, in Pa; Bc,j P is the maximum differential pressure at the flue gas inlet to the chimney segment j, in Pa; ZOe,j P is the wind velocity pressure; L N is the number of combustion appliances.

5.3 Mass flow requirement

Formulae (7) and (8) shall be verified for all relevant working conditions (see 5.6). For each combustion appliance in operation at nominal or minimum heat output:

𝑚𝑚̇≥𝑚𝑚̇, in kg/s (7) Wc,j W,j and for each combustion appliance out of action:

𝑚𝑚̇≥ 0, in kg/s (8) Wc,j where 𝑚𝑚̇ is the calculated mass flow of the combustion appliance, in kg/s; Wc,j 𝑚𝑚̇ is the declared mass flow of the combustion appliance, in kg/s. W,j Where a totally closed mechanically driven flue damper (Type 2 in accordance with EN 16475-4) is applied, mass flow of a combustion appliance out of action shall be taken as 0. Otherwise as flow resistance for a flue damper of a combustion appliance out of action shall be taken as 0 unless additional data are available.

5.4 Pressure requirements

5.4.1 Negative pressure chimneys

For negative pressure chimneys, it has to be additionally checked that the minimum draught (negative pressure) in the chimney (P ) is more than or equal to the negative pressure in the room where the Z,j combustion appliance is placed at calculated draught conditions for air supply. The check on this

oSIST prEN 13384-2:2026 prEN 13384-2:2026 (E) pressure requirement shall be done using the same conditions as specified for the check on the mass flow requirement (see 5.3 and 5.6). The following relationships shall be verified:

𝑃𝑃 ≥𝑃𝑃 , in Pa (9) Z,j Bc,j and if P < 0 Pa and the connecting flue pipe j is designated for negative pressure (N):

W,j P ≥ P + P , in Pa (10) Z,j Bc,j V,j or if P < 0 Pa and the connecting flue pipe j is designated for positive pressure (P, M or H):

W,j P – P ≤ P , in Pa (11) V,j Z,j ZVexcess, j or if P < 0 Pa and only the first part of the connecting flue pipe j is designated for positive pressure:

W,j P ≥ P + P , in Pa (12) Z,j Bc,j V2,j P + P – P ≤ P , in Pa (13) V1,j V2,j Z,j ZVexcess,j where P is the draught at the inlet to the chimney segment j, in Pa; Z,j P is the calculated pressure resistance of the air supply for the combustion appliance j, in Pa; Bc,j P is the minimum draught for the combustion appliance j, in Pa; W,j P is the calculated pressure resistance of the connecting flue pipe j, in Pa; V,j P is the calculated pressure resistance of a first, positive pressure part of the connecting flue V1,j pipe j, in Pa; P is the calculated pressure resistance of a second, negative pressure part of the connecting V2,j flue pipe j, in Pa; P is the maximum allowed pressure from the designation of the connecting flue pipe j, in Pa. ZVexcess,j If required, it has to be additionally checked that the draught in the chimney (P ) is less than or equal Zmax,j to the maximum allowed draught (P ) caused by the combustion appliance. The Formula (14) shall Zemax,j be verified for all relevant working conditions (see 5.6). The check of this pressure requirement shall be done with a separate calculation using the newly calculated flue mass flows that fulfil the pressure equilibrium conditions at an external air temperature of T = 258,15 K (t = -15 °C, see prEN 13384- L L 1:2025, 5.7.1.2).

𝑁𝑁 𝑃𝑃 =� �𝑃𝑃 −𝑃𝑃 � ≤𝑃𝑃 +𝑃𝑃 +𝑃𝑃 =𝑃𝑃 , in Pa (14) Zmax,𝑗𝑗 H,k R,k Wmax,j V,j Bc,j Zemax,j 𝑘𝑘=𝑗𝑗 where PZmax,j is the maximum draught at the flue gas inlet into the chimney segment j, in Pa; P is the maximum allowed draught at the flue gas inlet into the chimney segment j, in Zemax,j Pa; P is the theoretical draught available due to chimney effect in chimney segment k, in H,k Pa; P is the pressure resistance of the chimney segment k, in Pa; R,k

oSIST prEN 13384-2:2026 prEN 13384-2:2026 (E) P is the maximum draught for the combustion appliance j, in Pa; Wmax,j P is the calculated pressure resistance of the connecting flue pipe j, in Pa; V,j P is the calculated pressure resistance of the air supply for the combustion appliance j, Bc,j in Pa.

NOTE The values of PH,k, PR,k, PV,j and PBc,j in Formulae (2) and (14) are normally different because the conditions are different.

5.4.2 Positive pressure chimneys

For positive pressure chimneys it has to be additionally checked that the maximum positive pressure in the connecting flue pipe (P + P ) and in the chimney (P ) is not higher than the excess pressure for ZO,j V,j ZO,j which both are designated (PZVexcess and PZexcess). The check on the pressure requirement shall be done using the same conditions as specified for the check on the mass flow requirement (see 5.3 and 5.6). The following relationships shall be verified:

...