Abstract

The present document defines the classes of environmental conditions and their severities to which telecommunications equipment may be exposed. The severities specified are those which will have a low probability of being exceeded; generally less than 1 %. The present document applies to equipment installed for stationary use at underground locations during:
- normal operation;
- on site installation and lining up;
- repair, maintenance and restoration of functions failed.

Status
Published
Publication Date
31-Jan-2006
Current Stage
6060 - National Implementation/Publication (Adopted Project)
Start Date
01-Feb-2006
Due Date
01-Feb-2006
Completion Date
01-Feb-2006

Buy Documents

Standard

SIST EN 300 019-1-8 V2.1.2:2006

English language (11 pages)
Preview
Preview
e-Library read for
×1 day

SIST EN 300 019-1-8 V2.1.2:2006 is a SIST standard in the ETSI Environmental Engineering (EE) series for telecommunications equipment. It specifies the class of environmental conditions and severities for stationary use at underground locations. In practice, it helps users describe the underground site environment that equipment may face during operation, installation, maintenance, and repair.

What does SIST EN 300 019-1-8 V2.1.2:2006 specify?

SIST EN 300 019-1-8 V2.1.2:2006 defines environmental condition classes for telecommunications equipment used in underground locations, with one main class: class 8.1 for partly weatherprotected underground locations. It is organized into Scope, References, Definitions and abbreviations, Environmental class, and Environmental conditions.

The scope covers stationary equipment during normal operation, on-site installation and lining up, repair, maintenance, and restoration of failed functions. The standard is therefore aimed at site conditions, not portable use.

The body then sets out:

  • class 8.1 and its relationship to IEC 60721 classes
  • climatic conditions
  • biological conditions
  • chemically active substances
  • mechanically active substances
  • mechanical conditions
  • earthquake conditions

Figure 1 gives the climatogram for class 8.1, and figure 2 gives the earthquake response spectrum.

What are the key requirements of SIST EN 300 019-1-8 V2.1.2:2006?

Environmental class

Clause 4 defines class 8.1 as partly weatherprotected underground locations. The site is protected from direct weather influences, but those influences are not completely excluded. In practice, this tells the reader which underground installations fit the class, such as footway boxes, manholes, and some tunnels.

Clause 4 also notes that the climate in this class is based on measurements at typical underground telecommunications locations, because the IEC 60721 series has no dedicated underground class. That matters when selecting equipment or site profiles for testing.

Climatic, biological and chemical conditions

Clause 5.1 sets the climatic envelope for class 8.1. It covers moderate to warm temperatures, high humidity, condensation, icing, limited air movement, and the possibility of dripping water, condensed water, and soil water. For the user, this means equipment may need protection against moisture ingress and temperature cycling more than against direct sun or wind-driven rain.

Clause 5.2 allows mould, fungus, rodents, and other harmful animals, while excluding termites. This is relevant for enclosure design, material choice, and maintenance planning.

Clause 5.3 covers airborne contaminants such as sea salts, road salts, sulphur compounds, chlorine, hydrogen chloride, hydrogen fluoride, ammonia, ozone, and nitrogen oxides. It also notes that special class 3C3 values may be selected for individual parameters where needed, which helps when the installation is near stronger industrial emissions.

Mechanical and earthquake conditions

Clause 5.4 covers sand and dust, and clause 5.5 covers vibration and shock. The class includes stationary sinusoidal vibration and non-stationary vibration including shock, with a more severe special mechanical option 3M5. This matters when equipment is exposed to traffic vibration, nearby machinery, or similar mechanical disturbance.

Clause 5.6 addresses earthquake conditions. It uses a response spectrum approach and explains Zero Period Acceleration (ZPA), with assumptions for rigid foundations or high-rigidity structures. In practice, this is the part to use when the installation must be checked for seismic movement as well as ordinary vibration.

What terms does SIST EN 300 019-1-8 V2.1.2:2006 define?

  • Absolute humidity - the mass of water vapour in a given volume of dry air.
  • Relative humidity - the ratio of water vapour pressure in moist air to saturation pressure at the same temperature.
  • Stationary use - equipment permanently placed at a site.
  • Weatherprotected location - a location where equipment is protected from direct weather influences.
  • Partly weatherprotected location - a location where direct weather influences are not completely excluded.
  • RS - Response Spectrum, used to describe expected seismic motion at the mounting point.
  • ZPA - Zero Period Acceleration, the high-frequency asymptotic acceleration level of a response spectrum.

Who uses SIST EN 300 019-1-8 V2.1.2:2006?

Telecommunications equipment manufacturers use this standard to describe the expected underground environment for enclosures and installed equipment. Test engineers use it to select environmental severities for qualification and type testing.

Site planners, installers, and maintenance teams use it when specifying conditions for manholes, footway boxes, tunnels, and similar underground locations. Quality managers and buyers use it to check whether a product is suited to the intended site environment.

What changed in SIST EN 300 019-1-8 V2.1.2:2006 from the previous edition?

The document history shows the earlier ETS 300 019-1-8 publication, a V2.1.0 approval step, and this V2.1.2 publication. The history records this version as the April 2002 publication of the standard.

Which standards are used with SIST EN 300 019-1-8 V2.1.2:2006?

The standard references these documents:

  • IEC 60721-3-3 - provides the general classification of environmental groups and severities for stationary use at weatherprotected locations.
  • IEC 60068-2-27 - provides shock test guidance used for the mechanical discussion.
  • IEC 60721-2-6 - provides earthquake vibration and shock conditions in nature, used for the seismic class.
  • IEC 60068-3-3 - provides seismic test methods and the response spectrum guidance used in clause 5.6.

The foreword also places this part in the wider ETSI series:

  • Part 1-0 - general overview
  • Part 1-1 to Part 1-7 - storage, transportation, stationary use at weatherprotected and non-weatherprotected locations, ground vehicles, ship environments, and portable/non-stationary use
  • Part 2 - specification of environmental tests

What does the SIST EN 300 019-1-8 V2.1.2:2006 document contain?

SIST EN 300 019-1-8 V2.1.2:2006 contains one climate profile, one biological description, one chemical contamination table, one mechanical condition table, and one earthquake section with a response spectrum and coordinate points. These are used to describe site conditions for design, test planning, and equipment selection.

It also includes a climatogram for class 8.1 and a seismic response spectrum figure. The tables and figures give the practical profile of the underground environment without turning the document into a test method standard.

Buy Documents

Standard

SIST EN 300 019-1-8 V2.1.2:2006

English language (11 pages)
Preview
Preview
e-Library read for
×1 day

Get Certified

Connect with accredited certification bodies for this standard

ANCE

Mexican certification and testing association.

EMA Mexico Verified

IMP NDT d.o.o.

Non-destructive testing services. Radiography, ultrasonic, magnetic particle, penetrant, visual inspection.

SA Slovenia Verified

Inštitut za kovinske materiale in tehnologije

Institute of Metals and Technology. Materials testing, metallurgical analysis, NDT.

SA Slovenia Verified

Sponsored listings

Frequently Asked Questions

SIST EN 300 019-1-8 V2.1.2:2006 is a standard published by the Slovenian Institute for Standardization (SIST). Its full title is "Environmental Engineering (EE); Environmental conditions and environmental tests for telecommunications equipment; Part 1-8: Classification of environmental conditions; Stationary use at underground locations". This standard covers: The present document defines the classes of environmental conditions and their severities to which telecommunications equipment may be exposed. The severities specified are those which will have a low probability of being exceeded; generally less than 1 %. The present document applies to equipment installed for stationary use at underground locations during: - normal operation; - on site installation and lining up; - repair, maintenance and restoration of functions failed.

The present document defines the classes of environmental conditions and their severities to which telecommunications equipment may be exposed. The severities specified are those which will have a low probability of being exceeded; generally less than 1 %. The present document applies to equipment installed for stationary use at underground locations during: - normal operation; - on site installation and lining up; - repair, maintenance and restoration of functions failed.

SIST EN 300 019-1-8 V2.1.2:2006 is classified under the following ICS (International Classification for Standards) categories: 19.040 - Environmental testing; 33.050.01 - Telecommunication terminal equipment in general. The ICS classification helps identify the subject area and facilitates finding related standards.

SIST EN 300 019-1-8 V2.1.2:2006 is available in PDF format for immediate download after purchase. The document can be added to your cart and obtained through the secure checkout process. Digital delivery ensures instant access to the complete standard document.

Standards Content (Sample)

Contents

  • 1 Scope
  • 2 References
  • 3 Definitions and abbreviations
  • 3.1 Definitions
  • 6 ETSI EN 300 019-1-8 V2.1.2 (2002-04)
  • 3.2 Abbreviations
  • 4 Environmental class
  • 4.1 Class 8.1: partly weatherprotected underground locations
  • 7 ETSI EN 300 019-1-8 V2.1.2 (2002-04)
  • 5 Environmental conditions
  • 5.1 Climatic conditions
  • 8 ETSI EN 300 019-1-8 V2.1.2 (2002-04)
  • 5.2 Biological conditions
  • 5.3 Chemically active substances
  • 5.4 Mechanically active substances
  • 9 ETSI EN 300 019-1-8 V2.1.2 (2002-04)
  • 5.5 Mechanical conditions
  • 5.6 Earthquake conditions
  • 10 ETSI EN 300 019-1-8 V2.1.2 (2002-04)
  • 11 ETSI EN 300 019-1-8 V2.1.2 (2002-04)

1 Scope

The present document defines the classes of environmental conditions and their severities to which telecommunications equipment may be exposed. The severities specified are those which will have a low probability of being exceeded; generally less than 1 %.

The present document applies to equipment installed for stationary use at underground locations during:

  • normal operation;
  • on site installation and lining up;
  • repair, maintenance and restoration of functions failed.

2 References

The following documents contain provisions which, through reference in this text, constitute provisions of the present document.

  • References are either specific (identified by date of publication and/or edition number or version number) or non-specific.
  • For a specific reference, subsequent revisions do not apply.
  • For a non-specific reference, the latest version applies.

[1] IEC 60721-3-3: "Classification of environmental conditions - Part 3: Classification of groups of environmental parameters and their severities - Section 3: Stationary use at weatherprotected locations".

[2] IEC 60068-2-27: "Environmental testing. Part 2: Tests. Test Ea and guidance: Shock". [3] IEC 60721-2-6: "Classification of environmental conditions. Part 2: Environmental conditions appearing in nature. Earthquake vibration and shock".

[4] IEC 60068-3-3: "Environmental testing. Part 3: Guidance. Seismic test methods for equipment".

3 Definitions and abbreviations

3.1 Definitions

For the purposes of the present document, the following terms and definitions apply:

absolute humidity: mass of water vapour in grammes which is associated with one cubic metre of dry air in an air/watervapourmixture NOTE: It is not intended for portable use but short periods of handling during erection work, down time, maintenance and repair at the location are accepted.

relative humidity: ratio of the partial pressure of the water vapour in moist air at a given temperature, to the partial pressure of the water vapour in saturated air at the same temperature stationary use: equipment permanently placed at a certain site weatherprotected location: location at which the equipment is protected from direct weather influences NOTE 1: Totally weatherprotected location: direct weather influences are totally excluded. NOTE 2: Partly weatherprotected location: direct weather influences are not completely excluded. ETSI

SIST EN 300 019-1-8 V2.1.2:2006

6 ETSI EN 300 019-1-8 V2.1.2 (2002-04)

3.2 Abbreviations

For the purposes of the present document, the following abbreviations apply:

RS Response Spectrum ZPA Zero Period Acceleration

4 Environmental class

4.1 Class 8.1: partly weatherprotected underground locations

At present no underground classes in IEC 60721 Publication series exist. This class is a combination of classes 3Z7/3B2/3C2(3C3)/3S3/3M3(3M5) in IEC 60721-3-3 [1]. As no IEC 60721-3-3 [1] climatic class is applicable, climatic conditions are described in clause 4 based on measurements conducted at typical underground telecommunications locations. Seismic environment: zone 4 as defined in IEC 60721-2-6 [3].

Option zone 4 (modified Mercalli scale ≥ 9): if earthquake conditions are specified by the customer, the conditions stated in clause 5.6 apply.

This class applies to partly weatherprotected underground locations. The location has no temperature or humidity control, but the variations in the temperature are limited due to the stabilizing influence of the surroundings. The climatogram is shown in figure 1.

This class applies to locations:

- where the installed equipment is normally protected from direct weather influences; - where the surrounding medium is normally air, but the equipment may be immersed in water during exceptional conditions; - where mould growth or attacks by animals, except termites, may occur; - with normal levels of contaminants experienced in urban areas with industrial activities scattered over the whole area and/or with heavy traffic; NOTE 1: At locations in the immediate neighbourhood of industrial sources with chemical emissions either special precautions shall be taken or the special chemical class 3C3 shall be chosen. - in close proximity to sources of sand and dust; - with vibration and shock of low significance.

...