Abstract

The present document applies in telecommunication centres and similar installations to the bonding network of the building, the bonding network of the equipment, and the interconnection between these two networks. It contributes to the standardization of telecommunication and datacom equipment installation.
It also co-ordinates with the pre-conditions of the installation to achieve the following targets:
- safety from electrical hazards;
- reliable signal reference;
- satisfactory Electromagnetic Compatibility (EMC) performance.
A defined bonding configuration down to the equipment level shall facilitate the installation, operation and maintenance of telecommunication centres in telecommunication buildings or similar installations independent of the equipment supplier. The specification of telecommunication and datacom equipment and of the pre-conditions of installation are subject to agreement of the parties (e.g. the supplier and the purchaser). Annex A can be used in the procedure to achieve agreement.
The present document does not cover safety and EMC aspects of the equipment. Those aspects are covered by other relevant standards. The present document does not apply to the installation of telecommunication and datacom equipment in locations other than telecommunication centres, e.g.:
- smaller telecommunication equipment inside a subscriber's building;
- subscriber line terminal equipment.
NOTE: Earthing and bonding of equipment installed in locations other than telecommunication building is covered by EN 50310 [8].

Status
Published
Publication Date
31-Jan-2006
Current Stage
6060 - National Implementation/Publication (Adopted Project)
Start Date
01-Feb-2006
Due Date
01-Feb-2006
Completion Date
01-Feb-2006

Buy Documents

Standard

SIST EN 300 253 V2.1.1:2006

English language (21 pages)
Preview
Preview
e-Library read for
×1 day

SIST EN 300 253 V2.1.1:2006 is the Slovenian adoption of ETSI EN 300 253 V2.1.1 for earthing and bonding of telecommunication equipment in telecommunication centres. It specifies how the building bonding network, the equipment bonding network and their interconnection are arranged so that telecommunication and datacom installations support safety from electrical hazards, a reliable signal reference and Electromagnetic Compatibility (EMC) performance. The document is aimed at centres and similar installations where equipment from different suppliers must work within one coordinated bonding concept.

What does SIST EN 300 253 V2.1.1:2006 specify?

SIST EN 300 253 V2.1.1:2006 applies to telecommunication centres and similar installations. It covers the bonding network of the building, the bonding network of the equipment, and the link between them, while excluding equipment safety and EMC design itself and installations outside telecommunication centres, such as smaller equipment inside a subscriber's building and subscriber line terminal equipment.

The document is organized into six clauses and three annexes:

AnnexWhat it covers
Annex ANormative rationale about co-ordination of the Common Bonding Network (CBN)
Annex BInformative rationale about integrating the Direct Current (DC) return conductor into the merged CBN/MESH-BN
Annex CInformative bibliography

Clauses 1 to 3 set out scope, references, definitions and abbreviations. Clauses 4 to 6 set the general requirements, the bonding network requirements, and the power distribution requirements.

What are the key requirements of SIST EN 300 253 V2.1.1:2006?

Safety, reference potential and EMC

Clause 4 ties the installation to safety standards for the equipment and the building wiring. The practical point is that earthing and bonding conductors must be sized and arranged so they can carry fault current and stay low impedance under normal and fault conditions, including induced energy from lightning.

  • Clause 4.1 requires the installation to work with EN 60950, EN 41003, CENELEC HD 384.4.41 and CENELEC HD 384.5.54. In practice, this means the equipment safety design and the building protective conductors have to be matched, not treated as separate tasks.
  • Clause 4.2 requires a System Reference Potential Plane (SRPP) for at least a functional unit or system block. The SRPP may be a metal plane or a mesh such as a bonding mat, and it must keep impedance low up to the highest relevant frequency so signal reference stays stable.
  • Clause 4.3 uses the SRPP to support EMC performance. In practice, filters, cabinets and cable shields need a low-impedance connection path, otherwise emissions and susceptibility can rise.

Building-level and system-level bonding

Clause 5 separates the bonding concept into a building-level Common Bonding Network (CBN) and a system-level MESHed Bonding Network (MESH-BN). This matters because a telecommunication centre needs one building-wide bonding backbone and a dense mesh around the equipment that depends on it.

  • Clause 5.2 requires each telecommunication building to have a CBN with sufficiently low impedance and high current-carrying capability. The main earthing terminal is extended by a bonding ring conductor along the inside perimeter, or at least by a ring around a system block, so later expansion can be integrated into a three-dimensional grid.
  • Clause 5.3 requires the BN within a telecommunication system to be mesh type. It interconnects shelves, cabinets, rack rows, cable racks, ducts, troughs, distribution frames, cable shields and the bonding mat, and all metallic parts must form one electrically continuous whole.
  • Clause 5.4 connects all BNs and their associated DC return conductors to the CBN. In practice, the MESH-BN is not an isolated island - it augments the CBN through multiple interconnections, including the main earthing terminal.
  • Clause 5.5 controls cabling inside and between BNs. Power and signal cables are to follow the augmented CBN closely, AC mains and signal cable tracks need separation unless shielding is adequate, and cable shields are to be bonded directly to racks, cabinets or the SRPP at each end.

Power distribution interfaces

Clause 6 applies the bonding concept to DC and AC power distribution. For installers and buyers, this is where the standard turns the bonding concept into concrete interface rules.

  • Clause 6.1 requires secondary DC distribution to use close-routed positive and negative conductors, with each DC return conductor bonded to the CBN at the main earthing terminal, at the DC power plant service panel and at least one point of the MESH-BN. It also limits DC voltage drop and requires the return path to carry fault overcurrents.
  • Clause 6.2 requires the reference potential terminal of tertiary power supplies to be connected to the MESH-BN.
  • Clauses 6.3 and 6.4 require indoor AC distribution in the telecommunication building to follow TN-S practice, with no PEN conductor inside the building. Where the outdoor supply is TN-S, TN-C, TT or IT, the indoor bonding and protective conductor arrangement is defined so the building-side earthing rules remain consistent.

What terms does SIST EN 300 253 V2.1.1:2006 define?

  • Common Bonding Network (CBN) - The principal bonding and earthing network inside a telecommunication building, formed by interconnected metallic parts such as structural steel, cable racks and bonding conductors.
  • Bonding Network (BN) - A set of interconnected conductive structures that acts as an electromagnetic shield for electronic systems and personnel from DC to low radio frequency.
  • MESHed Bonding Network (MESH-BN) - A bonding network in which equipment frames, racks and cabinets are bonded together and to the CBN at multiple points.
  • System Reference Potential Plane (SRPP) - A conductive reference plane, approached in practice by a mesh, that helps equipment share a common potential for signalling.
  • Protective conductor (PE) - The conductor used to connect exposed conductive parts, extraneous conductive parts and earthing points for protection against electric shock.
  • PEN conductor - A conductor that combines protective conductor and Neutral conductor functions.
  • DC return conductor - The positive conductor of the -48 V or -60 V secondary DC supply in this document's terminology.

Who uses SIST EN 300 253 V2.1.1:2006?

SIST EN 300 253 V2.1.1:2006 is used by telecom-centre designers, equipment suppliers, purchasers, installers and maintenance teams. It is also relevant to network operators and project teams that have to agree installation pre-conditions between the supplier and the purchaser.

In practice, these users rely on the standard when specifying building bonding, choosing rack and cabinet interconnections, routing cable shields, connecting DC return conductors, and deciding how new equipment fits into existing telecommunication buildings. The foreword also shows that the standard was written to support mixed-vendor installations, structured installation practice and simpler maintenance.

Which standards are used with SIST EN 300 253 V2.1.1:2006?

The document relies on a set of electrical safety, vocabulary and earthing references:

  • CENELEC HD 384.4.41 - provides protection against electric shock.
  • CENELEC HD 384.5.54 - provides rules for earthing arrangements and protective conductors.
  • EN 60950 - provides safety requirements for information technology equipment.
  • EN 41003 - provides particular safety requirements for equipment connected to telecommunication networks.
  • IEC 60050, IEC 60050-604 and IEC 60050-826 - provide the vocabulary used for earthing, bonding and building electrical installations.
  • EN 50310 - is cited for earthing and equipotential bonding in buildings with information technology equipment, especially outside telecommunication centres.
  • IEC 61024-1 - provides lightning protection principles used in the rationale for the CBN.
  • ITU-T Recommendation K.27 and the ITU-T handbook on earthing - provide the building bonding framework that this document tailors for telecommunication centres.
  • ETS 300 132-1, ETS 300 132-2, EG 201 147 and EG 201 212 - are listed in the bibliography as related ETSI documents on power interfaces and safety classification.

What does the SIST EN 300 253 V2.1.1:2006 document contain?

The document contains six clauses, two technical figures for the CBN/MESH-BN arrangement, and two figures for AC supply transition modes. Clause 4 focuses on safety, signal reference and EMC; clause 5 describes the building and system bonding networks; and clause 6 covers DC and AC power distribution interfaces.

Annex A explains the rationale for building a CBN that can support EMC and lightning protection coordination. Annex B explains why the DC return conductor may be integrated into the merged CBN/MESH-BN or, in existing installations, treated differently by agreement. Annex C gives the bibliography used to support the terminology and installation concepts.

Buy Documents

Standard

SIST EN 300 253 V2.1.1:2006

English language (21 pages)
Preview
Preview
e-Library read for
×1 day

Get Certified

Connect with accredited certification bodies for this standard

ANCE

Mexican certification and testing association.

EMA Mexico Verified

IMP NDT d.o.o.

Non-destructive testing services. Radiography, ultrasonic, magnetic particle, penetrant, visual inspection.

SA Slovenia Verified

Inštitut za kovinske materiale in tehnologije

Institute of Metals and Technology. Materials testing, metallurgical analysis, NDT.

SA Slovenia Verified

Sponsored listings

Frequently Asked Questions

SIST EN 300 253 V2.1.1:2006 is a standard published by the Slovenian Institute for Standardization (SIST). Its full title is "Environmental Engineering (EE); Earthing and bonding of telecommunication equipment in telecommunication centres". This standard covers: The present document applies in telecommunication centres and similar installations to the bonding network of the building, the bonding network of the equipment, and the interconnection between these two networks. It contributes to the standardization of telecommunication and datacom equipment installation. It also co-ordinates with the pre-conditions of the installation to achieve the following targets: - safety from electrical hazards; - reliable signal reference; - satisfactory Electromagnetic Compatibility (EMC) performance. A defined bonding configuration down to the equipment level shall facilitate the installation, operation and maintenance of telecommunication centres in telecommunication buildings or similar installations independent of the equipment supplier. The specification of telecommunication and datacom equipment and of the pre-conditions of installation are subject to agreement of the parties (e.g. the supplier and the purchaser). Annex A can be used in the procedure to achieve agreement. The present document does not cover safety and EMC aspects of the equipment. Those aspects are covered by other relevant standards. The present document does not apply to the installation of telecommunication and datacom equipment in locations other than telecommunication centres, e.g.: - smaller telecommunication equipment inside a subscriber's building; - subscriber line terminal equipment. NOTE: Earthing and bonding of equipment installed in locations other than telecommunication building is covered by EN 50310 [8].

The present document applies in telecommunication centres and similar installations to the bonding network of the building, the bonding network of the equipment, and the interconnection between these two networks. It contributes to the standardization of telecommunication and datacom equipment installation. It also co-ordinates with the pre-conditions of the installation to achieve the following targets: - safety from electrical hazards; - reliable signal reference; - satisfactory Electromagnetic Compatibility (EMC) performance. A defined bonding configuration down to the equipment level shall facilitate the installation, operation and maintenance of telecommunication centres in telecommunication buildings or similar installations independent of the equipment supplier. The specification of telecommunication and datacom equipment and of the pre-conditions of installation are subject to agreement of the parties (e.g. the supplier and the purchaser). Annex A can be used in the procedure to achieve agreement. The present document does not cover safety and EMC aspects of the equipment. Those aspects are covered by other relevant standards. The present document does not apply to the installation of telecommunication and datacom equipment in locations other than telecommunication centres, e.g.: - smaller telecommunication equipment inside a subscriber's building; - subscriber line terminal equipment. NOTE: Earthing and bonding of equipment installed in locations other than telecommunication building is covered by EN 50310 [8].

SIST EN 300 253 V2.1.1:2006 is classified under the following ICS (International Classification for Standards) categories: 19.040 - Environmental testing; 33.050.01 - Telecommunication terminal equipment in general. The ICS classification helps identify the subject area and facilitates finding related standards.

SIST EN 300 253 V2.1.1:2006 is available in PDF format for immediate download after purchase. The document can be added to your cart and obtained through the secure checkout process. Digital delivery ensures instant access to the complete standard document.

Standards Content (Sample)

Contents

  • Introduction
  • 6 ETSI EN 300 253 V2.1.1 (2002-04)
  • 1 Scope
  • 2 References
  • 7 ETSI EN 300 253 V2.1.1 (2002-04)
  • 3 Definitions and abbreviations
  • 3.1 Definitions
  • 8 ETSI EN 300 253 V2.1.1 (2002-04)
  • 9 ETSI EN 300 253 V2.1.1 (2002-04)
  • 3.2 Abbreviations
  • 4 General requirements
  • 4.1 Safety from electrical hazards
  • 4.2 Signal reference
  • 4.3 EMC performance
  • 10 ETSI EN 300 253 V2.1.1 (2002-04)
  • 5 Requirements on bonding networks
  • 5.1 Bonding configurations
  • 5.2 CBN within a telecommunication building
  • 5.3 BN within a telecommunication system
  • 11 ETSI EN 300 253 V2.1.1 (2002-04)
  • 12 ETSI EN 300 253 V2.1.1 (2002-04)
  • 13 ETSI EN 300 253 V2.1.1 (2002-04)
  • 5.4 Merging of CBN and MESH-BNs
  • 5.5 Cabling within and between BNs
  • 6 Requirements for power distribution
  • 6.1 DC power distribution of secondary supply
  • 6.2 DC power distribution of tertiary supplies
  • 14 ETSI EN 300 253 V2.1.1 (2002-04)
  • 6.3 AC mains distribution and bonding of the protective
  • 6.4 AC power distribution from tertiary power supply
  • 15 ETSI EN 300 253 V2.1.1 (2002-04)
  • 16 ETSI EN 300 253 V2.1.1 (2002-04)
  • 17 ETSI EN 300 253 V2.1.1 (2002-04)
  • 18 ETSI EN 300 253 V2.1.1 (2002-04)
  • 19 ETSI EN 300 253 V2.1.1 (2002-04)
  • 20 ETSI EN 300 253 V2.1.1 (2002-04)
  • Bibliography
  • 21 ETSI EN 300 253 V2.1.1 (2002-04)

Introduction

The present document addresses earthing and bonding of telecommunication equipment in telecommunication centres in relation to safety, functional performance and EMC.

Information regarding the general principles on earthing for telecommunication sites has been published by the ITU-T in the handbook on "Earthing of telecommunication installations" (see bibliography). ITU-T Recommendation K.27 deals with bonding configurations and earthing inside a telecommunication building. One bonding configuration only is selected from ITU-T Recommendation K.27 (CBN/MESH-BN) and tailored to the present document. ETSI

SIST EN 300 253 V2.1.1:2006

6 ETSI EN 300 253 V2.1.1 (2002-04)

1 Scope

The present document applies in telecommunication centres and similar installations to the bonding network of the building, the bonding network of the equipment, and the interconnection between these two networks. It contributes to the standardization of telecommunication and datacom equipment installation. It also co-ordinates with the pre-conditions of the installation to achieve the following targets:

  • safety from electrical hazards;
  • reliable signal reference;
  • satisfactory Electromagnetic Compatibility (EMC) performance. A defined bonding configuration down to the equipment level shall facilitate the installation, operation and maintenance of telecommunication centres in telecommunication buildings or similar installations independent of the equipment supplier.

The specification of telecommunication and datacom equipment and of the pre-conditions of installation are subject to agreement of the parties (e.g. the supplier and the purchaser). Annex A can be used in the procedure to achieve agreement.

The present document does not cover safety and EMC aspects of the equipment. Those aspects are covered by other relevant standards.

The present document does not apply to the installation of telecommunication and datacom equipment in locations other than telecommunication centres, e.g.:

  • smaller telecommunication equipment inside a subscriber's building;
  • subscriber line terminal equipment.

NOTE: Earthing and bonding of equipment installed in locations other than telecommunication building is covered by EN 50310 [8].

2 References

The following documents contain provisions which, through reference in this text, constitute provisions of the present document.

  • References are either specific (identified by date of publication and/or edition number or version number) or non-specific.
  • For a specific reference, subsequent revisions do not apply.
  • For a non-specific reference, the latest version applies.

[1] CENELEC HD 384.4.41: "Electrical installation of buildings - Part 4: Protection for safety - Chapter 41: Protection against electric shock".

[2] CENELEC HD 384.5.54: "Electrical installation of buildings - Part 5: Selection and erection of electrical equipment - Chapter 54: Earthing arrangements and protective conductors". [3] EN 60950: "Safety of information technology equipment".

[4] EN 41003: "Particular safety requirements for equipment to be connected to telecommunication networks".

[5] IEC 60050: "International Electrotechnical Vocabulary".

[6] IEC 60050-604: "International Electrotechnical Vocabulary. Chapter 604: Generation, transmission and distribution of electricity - Operation".

ETSI

SIST EN 300 253 V2.1.1:2006

7 ETSI EN 300 253 V2.1.1 (2002-04)

[7] IEC 60050-826: "International Electrotechnical Vocabulary. Electrical installations of buildings". [8] EN 50310: "Application of equipotential bonding and earthing in buildings with information technology equipment".

[9] IEC 61024-1: "Protection of structures against lightning - Part 1: General principles".

3 Definitions and abbreviations

3.1 Definitions

For the purposes of the present document, the following terms and definitions apply. The following definitions with respect to earthing and bonding are introduced by the IEC 60050 [5] and are used within the present document to maintain conformity.

3.1.1 IEC definitions (by IEC 60050 numbers)

NOTE: IEC 60050 [5] references are given in parentheses (see IEC 60050-604 [6] and IEC 60050-826 [7]). earth (826-04-01): conductive mass of earth, whose electric potential at any point is conventionally taken as equal to zero earthing conductor (826-04-07): protective conductor connecting the main earthing terminal or bar to the earth electrode earth electrode (826-04-02): conductive part or a group of conductive parts in intimate contact with and providing an electrical connection with earth earthing network (604-04-07): part of an earthing installation that is restricted to the earth electrodes and their interconnections equipotential bonding (826-04-09): electrical connection putting various exposed conductive parts and extraneous conductive parts at a substantially equal potential equipotential bonding conductor (826-04-10): protective conductor for ensuring equipotential bonding IT: See IEC 60364-3.

main earthing terminal (826-04-08): terminal or bar provided for the connection of protective conductors, including equipotential bonding conductors and conductors for functional earthing if any, to the means of earthing Neutral conductor (N) (826-01-03): conductor connected to the neutral point of a system and capable of contributing to the transmission of electrical energy PEN conductor (826-04-06): earthed conductor combining the functions of both protective conductor and neutral conductor Protective conductor (PE) (826-04-05): conductor required by some measures for protection against electric shock by electrically connecting any of the following parts:

  • exposed conductive parts;
  • extraneous conductive parts;
  • main earthing terminal;
  • earth electrode;
  • earthed point of the source or artificial neutral.

TN-C: See IEC 60364-3.

ETSI

SIST EN 300 253 V2.1.1:2006

8 ETSI EN 300 253 V2.1.1 (2002-04)

TN-S: See IEC 60364-3.

TT: See IEC 60364-3.

3.1.2 Telecommunication definitions

The following definitions, specific to telecommunication installations and not covered by the IEC 60050 [5], are used within the present document. Correspondence to ITU-T Recommendation K.27 (see bibliography) is indicated as appropriate.

bonding mat: essential means to provide a SRPP by a discernible, nearly regular mesh structure NOTE: The bonding mat may be located either below or above a collection of equipment constituting a system block.

Bonding Network (BN), (ITU-T Recommendation K.27): set of interconnected conductive structures that provides an "electromagnetic shield" for electronic systems and personnel at frequencies from Direct Current (DC) to low Radio Frequency (RF) NOTE: The term "electromagnetic shield" denotes any structure used to divert, block or impede the passage of electromagnetic energy. In general, a BN need not be connected to earth but all BNs considered in the present document will have an earth connection.

Common Bonding Network (CBN), (ITU-T Recommendation K.27): principal means for effective bonding and earthing inside a telecommunication building NOTE: It is the set of metallic components that are intentionally or incidentally interconnected to form the principal BN in a building. These components include: structural steel or reinforcing rods, metallic plumbing, Alternating Current (AC) power conduit, PE conductors, cable racks and bonding conductors. The CBN always has a mesh topology and is connected to the earthing network. DC return conductor: (+) conductor of the -48 V or -60 V secondary DC supply MESHed Bonding Network (MESH-BN), (ITU-T Recommendation K.27): bonding network in which all associated equipment frames, racks and cabinets and usually the DC power return conductor, are bonded together as well as at multiple points to the CBN NOTE 1: Consequently, the MESH-BN augments the CBN NOTE 2: See figure 1 of the present document.

MESHed Isolated Bonding Network (MESH-IBN), (ITU-T Recommendation K.27): type of IBN in which the components of the IBN (e.g. equipment frames) are interconnected to form a mesh-like structure NOTE: This may, for example, be achieved by multiple interconnections between cabinet rows, or by connecting all equipment frames to a metallic grid (a "bonding mat") extending beneath the equipment. The bonding mat is, of course, insulated from the adjacent CBN. If necessary the bonding mat could include vertical extensions, resulting in an approximation to a Faraday cage. The spacing of the grid is chosen according to the frequency range of the electromagnetic environment.

power supply:

  • primary supply: public mains or, under emergency conditions, a locally generated AC supply
  • secondary supply: supply to the telecommunication equipment, racks or system block, derived from the primary supply
  • tertiary supplies: supplies to the telecommunication equipment, derived from the secondary supply system: regularly interacting or interdependent group of items forming a unified whole system block: functional group of equipment depending in its operation and performance on its connection to the same system reference potential plane, inherent to a MESH-BN ETSI

SIST EN 300 253 V2.1.1:2006

9 ETSI EN 300 253 V2.1.1 (2002-04)

System Reference Potential Plane (SRPP): conductive solid plane, as an ideal goal in potential equalizing, is approached in practice by horizontal or vertical meshes NOTE 1: The mesh width thereof is adapted to the frequency range to be considered. Horizontal and vertical meshes may be interconnected to form a grid structure approximating to a Faraday cage. NOTE 2: The SRPP facilitates signalling with reference to a common potential.

3.2 Abbreviations

For the purposes of the present document, the following abbreviations apply:

AC Alternating Current BN Bonding Network CBN Common Bonding Network DC Direct Current EMC ElectroMagnetic Compatibility LPS Lightning Protection System MESH-BN MESHed Bonding Network MESH-IBN MESHed Isolated Bonding Network N Neutral conductor PE Protective conductor PEN combined Protective conductor and Neutral conductor RF Radio Frequency SRPP System Reference Potential Plane

4 General requirements

4.1 Safety from electrical hazards

To achieve safety it is required to design equipment to the standards EN 60950 [3], EN 41003 [4] and CENELEC HD 384.4.41 [1] and to perform the installation of PEs and equipotential bonding conductors, according to CENELEC HD 384.5.54 [2].

The conductors involved shall provide sufficiently high current conducting capability and low impedance according to the relevant safety standards to avoid electric shock, risk of fire, or damage to the equipment under normal or faulty operating conditions within an equipment or the distribution network, or due to the impact of induced voltage and current, e.g. by lightning.

4.2 Signal reference

Reliable signal reference shall be provided by a SRPP dedicated at least to a functional unit or a system block. To avoid undue functional distortion or risk of component failure, the SRPP shall provide sufficiently low impedance up to the highest frequency to be regarded by using a metal plane or a meshed configuration having adequate mesh dimensions, e.g. a bonding mat. The frequency band to be covered shall include the spectral components of transients caused by switching, short circuits and atmospheric discharges.

NOTE: Signal reference to the SRPP does not always imply signal return via the SRPP.

...