SIST EN 302 099 V1.1.1:2006
(Main)Environmental Engineering (EE); Powering of equipment in access network
- Abstract
The present document describes the principles for powering of telecommunications equipment in access network and contains requirements for the powering systems, laying down:
- the characteristics of the input and output interfaces of the power units;
- the power back-up conditions for TE including a power unit;
- the management data, necessary to guarantee the availability of the service and to ensure the maintenance of the power units.
The present document takes into account the characteristics of access network equipment for which the limits of responsibility in the installation or design of the power plants are very different than for equipment of telecom centre: it goes from "complete integration of the power plant in the TE" till "remote power feeding from a distant power plant". The present document applies for the powering of all equipment of the access network (copper, fiber or radio networks) located outside telecommunications centres. The access network is defined as the part of the telecommunications network, which is comprised between the customer terminal installation and the first exchange (switching unit). The customer terminal and the switching unit are excluded of the application field of the present document.
- Status
- Published
- Publication Date
- 31-Jan-2006
- Current Stage
- 6060 - National Implementation/Publication (Adopted Project)
- Start Date
- 01-Feb-2006
- Due Date
- 01-Feb-2006
- Completion Date
- 01-Feb-2006
SIST EN 302 099 V1.1.1:2006 specifies the principles for powering telecommunications equipment in the access network. The standard covers power interfaces, back-up conditions, and the management data needed to keep service available and to support maintenance. It is written for designers, operators, installers, and others who need to choose or verify how access-network equipment is powered.
What does SIST EN 302 099 V1.1.1:2006 specify?
SIST EN 302 099 V1.1.1:2006 applies to powering of access-network equipment located outside telecommunications centres. It covers copper, fiber, and radio access networks, and it excludes the customer terminal and the first switching unit.
The document is organized around powering configurations and their practical consequences. Clauses 4 to 11 cover powering architectures, the effect of technology on the powering strategy, local and remote powering requirements, power back-up, power management, safety, EMC, protection, bonding and earthing, and environmental conditions.
| Annex | What it covers |
|---|---|
| Annex A | Battery sizing for back-up power |
| Annex B | Bibliography |
What are the key requirements of SIST EN 302 099 V1.1.1:2006?
SIST EN 302 099 V1.1.1:2006 is built around the idea that the location of the mains connection and the location of back-up power drive the whole powering design. In practice, that means the operator or manufacturer must first decide whether the equipment is centrally powered, cluster powered, or locally powered, and then match the interface and back-up arrangement to that choice.
Powering architectures and where they apply
Clause 4 distinguishes centralized powering, cluster powering, and local powering. Centralized powering feeds access-network equipment from a telecommunications centre; cluster powering feeds a group of equipment from a remote source outside the centre; local powering uses a power unit at the same location as the equipment.
Clause 5 links those architectures to network technology. For copper access, centralized powering is suitable when power consumption is low enough, local powering is used when demand is higher, and a local battery can supplement centralized powering during traffic peaks. For fiber and radio access, local powering is generally the normal solution, while cluster powering can be cost-effective when many units are concentrated in one area. For hybrid networks, the same basic logic applies, and customer-home equipment is powered locally.
Local powering requirements
Clause 6 sets the local-power interface conditions. A telecommunications equipment unit with its own power plant uses a nominal 230 V, 50 Hz input, and continuity of service comes from a battery back-up unit. Where a Local Power Unit (LPU) supplies -48 V dc, the input characteristics have to comply with EN 300 132-2.
Clause 6 also allows local power at other dc voltages, but that must be stated in the individual technical specification for the equipment. For equipment powered from a nominal 230 V, 50 Hz local power unit, the LPU may be an uninterruptible power supply. In practice, these clauses tell the designer which voltage and back-up arrangement must be specified at the interface between the power source and the telecom equipment.
Remote powering requirements
Clause 7 defines the input and output conditions for remote powering. In centralized powering, the Remote Power Unit (RPU) is fed from the telecommunications-centre power plant, typically at -48 V dc. In cluster powering, the RPU input is 230 V, 50 Hz.
The standard recognizes two remote-powering modes at the RPU output: voltage mode with an RFT-V circuit and current mode with an RFT-C circuit. For voltage mode, the receiver must accept an input range from the nominal output voltage down to half that value. In practice, this matters because line length, line resistance, and the number of receivers affect the voltage that reaches the equipment.
Back-up and battery sizing
Clause 8 requires a back-up system, normally batteries, to keep telephone service running during mains outage or failure of upstream power equipment. For centralized remote powering, the text also allows a standby source such as a turbine or motor-driven generator to supplement back-up.
Annex A gives the battery-sizing method. It ties back-up power to the equipment’s base power, traffic-dependent power, subscriber count, and the service conditions during discharge. It also requires the battery capacity to cover ageing and minimum operating temperature, and it addresses valve regulated lead-acid batteries and end-of-life testing. For a user, this means the battery cannot be sized only for a best-case site - it must be justified for the real load and operating environment.
Power management, alarms, and maintenance
Clause 9 requires the operator to know the status of the power sub-assemblies so maintenance can be planned and service availability protected. The standard groups failure events into three alarm categories, ranging from events that normally do not need immediate intervention to failures that need urgent action.
The alarm duties differ by architecture. Centralized powering leaves power management to the source side. Local powering and cluster powering require the telecom equipment to provide alarm loops, forward alarms from the LPU or RPU, and in some cases monitor the failure events directly. In practical terms, the operator needs enough alarm visibility to know when power conversion, protection devices, monitoring units, or battery conditions need attention.
Safety, EMC, protection, earthing, and environment
Clause 10 points to external standards for product safety and interface classification. It also requires compliance with relevant EMC standards. For mains-fed or UPS-fed equipment, the design has to take overvoltage categories into account, and bonding and earthing have to follow the applicable telecom-centre, customer-premises, remote-site, or national rules.
Clause 11 links the equipment to ETSI environmental classifications for storage and stationary use at weatherprotected, non-weatherprotected, and underground locations. This matters because access-network equipment may be installed in cabinets, buildings, homes, poles, or manholes, and the environment can vary widely from site to site.
What terms does SIST EN 302 099 V1.1.1:2006 define?
- Access network - The part of a telecommunications network between the customer terminal installation and the first switching unit.
- Local powering - A powering principle where a telecommunication equipment unit is supplied by a dedicated power unit at the same location.
- Remote powering - A powering principle where a telecommunication equipment unit is supplied from a remote power circuit.
- Remote Feeding Telecommunication (RFT) circuit - A secondary circuit intended to supply or receive dc power via a telecommunication network at voltages at or above TNV limits.
- RFT-C circuit - An RFT circuit designed so that current stays within defined limits under normal and single-fault conditions.
- RFT-V circuit - An RFT circuit designed so that voltage and accessible contact area stay limited under normal and single-fault conditions.
- Remote Power Unit (RPU) - A power unit that feeds distant telecommunications equipment and is connected to mains or to a centralized power plant.
- Local Power Unit (LPU) - A power supply unit that feeds telecommunications equipment at the same location.
Who uses SIST EN 302 099 V1.1.1:2006?
Telecommunications operators use SIST EN 302 099 V1.1.1:2006 to specify how access-network sites are powered and how alarms are reported for maintenance. Equipment manufacturers and system integrators use it to design the input and output interfaces, backup arrangements, and management functions of power units and telecom equipment.
Installers and site engineers use it when placing equipment in buildings, cabinets, manholes, customer premises, or remote sites, because the standard connects the powering choice to earthing, protection, and environmental conditions. Quality managers and buyers use it to check that a proposed access-network power arrangement matches the intended architecture, voltage interface, and backup strategy.
Which standards are used with SIST EN 302 099 V1.1.1:2006?
- ETSI EN 300 132-2 - Defines the -48 V dc power supply interface at telecom-equipment input.
- ETSI ETS 300 132-1 - Defines the ac interface derived from dc sources and is used for the interface referenced in telecom-centre powering.
- CENELEC EN 60950-1 - Provides general safety requirements and the reference for SELV, TNV, primary circuit, secondary circuit, and hazardous voltage.
- IEC 60950-21 - Covers safety of remote power feeding and is used for RFT-C and RFT-V interface categories.
- CENELEC HD 472 S1 - Gives nominal voltages for low-voltage public electricity supply systems.
- CENELEC HD 625.1 - Provides insulation coordination principles and tests for low-voltage systems.
- CENELEC EN 50310 - Covers equipotential bonding and earthing in buildings with information technology equipment.
- CENELEC EN 60896-2 - Sets requirements and test methods for valve regulated stationary lead-acid batteries.
- ETSI EN 300 019-1-1, EN 300 019-1-3, ETS 300 019-1-4, EN 300 019-1-8 - Define environmental condition classes for storage, weatherprotected, non-weatherprotected, and underground use.
- ETSI EN 300 253 - Covers earthing and bonding inside telecommunications centres.
- ITU-T Recommendation K.35 - Covers bonding configurations and earthing at remote electronic sites.
- ETSI EG 201 212 - Classifies interfaces for equipment connected to telecommunication networks.
- ITU-T Recommendation K.45 - Addresses resistibility of access-network equipment to overvoltages and overcurrents.
What does the SIST EN 302 099 V1.1.1:2006 document contain?
SIST EN 302 099 V1.1.1:2006 includes configuration figures for centralized, cluster, and local powering, plus a technology figure that contrasts copper, optical, hybrid, and radio access networks. It also includes tables for alarm categories, management duties, interface safety categories, and example environmental classes.
Annex A gives the battery-sizing method for telephone-service back-up, including autonomy, ageing, operating temperature, valve regulated lead-acid batteries, and end-of-service-life testing. Annex B is a bibliography.
Get Certified
Connect with accredited certification bodies for this standard

ANCE
Mexican certification and testing association.

IMP NDT d.o.o.
Non-destructive testing services. Radiography, ultrasonic, magnetic particle, penetrant, visual inspection.

Inštitut za kovinske materiale in tehnologije
Institute of Metals and Technology. Materials testing, metallurgical analysis, NDT.
Sponsored listings
Frequently Asked Questions
SIST EN 302 099 V1.1.1:2006 is a standard published by the Slovenian Institute for Standardization (SIST). Its full title is "Environmental Engineering (EE); Powering of equipment in access network". This standard covers: The present document describes the principles for powering of telecommunications equipment in access network and contains requirements for the powering systems, laying down: - the characteristics of the input and output interfaces of the power units; - the power back-up conditions for TE including a power unit; - the management data, necessary to guarantee the availability of the service and to ensure the maintenance of the power units. The present document takes into account the characteristics of access network equipment for which the limits of responsibility in the installation or design of the power plants are very different than for equipment of telecom centre: it goes from "complete integration of the power plant in the TE" till "remote power feeding from a distant power plant". The present document applies for the powering of all equipment of the access network (copper, fiber or radio networks) located outside telecommunications centres. The access network is defined as the part of the telecommunications network, which is comprised between the customer terminal installation and the first exchange (switching unit). The customer terminal and the switching unit are excluded of the application field of the present document.
The present document describes the principles for powering of telecommunications equipment in access network and contains requirements for the powering systems, laying down: - the characteristics of the input and output interfaces of the power units; - the power back-up conditions for TE including a power unit; - the management data, necessary to guarantee the availability of the service and to ensure the maintenance of the power units. The present document takes into account the characteristics of access network equipment for which the limits of responsibility in the installation or design of the power plants are very different than for equipment of telecom centre: it goes from "complete integration of the power plant in the TE" till "remote power feeding from a distant power plant". The present document applies for the powering of all equipment of the access network (copper, fiber or radio networks) located outside telecommunications centres. The access network is defined as the part of the telecommunications network, which is comprised between the customer terminal installation and the first exchange (switching unit). The customer terminal and the switching unit are excluded of the application field of the present document.
SIST EN 302 099 V1.1.1:2006 is classified under the following ICS (International Classification for Standards) categories: 19.040 - Environmental testing; 33.050.01 - Telecommunication terminal equipment in general. The ICS classification helps identify the subject area and facilitates finding related standards.
SIST EN 302 099 V1.1.1:2006 is available in PDF format for immediate download after purchase. The document can be added to your cart and obtained through the secure checkout process. Digital delivery ensures instant access to the complete standard document.
Standards Content (Sample)
Contents
- 1 Scope
- 2 References
- 6 ETSI EN 302 099 V1.1.1 (2002-01)
- 3 Definitions and abbreviations
- 3.1 Definitions
- 7 ETSI EN 302 099 V1.1.1 (2002-01)
- 3.2 Abbreviations
- 4 Powering configurations
- 8 ETSI EN 302 099 V1.1.1 (2002-01)
- 4.1 Remote powering
- 9 ETSI EN 302 099 V1.1.1 (2002-01)
- 10 ETSI EN 302 099 V1.1.1 (2002-01)
- 4.2 Local powering
- 11 ETSI EN 302 099 V1.1.1 (2002-01)
- 5 Effect of the technologies on the powering strategy
- 12 ETSI EN 302 099 V1.1.1 (2002-01)
- 5.1 Powering strategy of family 1: metallic links
- 5.2 Powering strategy of family 2: non-metallic links
- 13 ETSI EN 302 099 V1.1.1 (2002-01)
- 6 Requirements for local powering
- 6.1 TE including the power plant
- 6.2 TE powered by a dc voltage nominal -48 V local power unit
- 6.3 TE powered by a LPU with a dc voltage other than -48 V
- 6.4 TE powered by a nominal ac voltage
- 7 Requirements for remote powering
- 7.1 Input of the Remote Power Unit
- 7.2 Output of the Remote Power Unit
- 14 ETSI EN 302 099 V1.1.1 (2002-01)
- 7.3 Input characteristics of remote powered receiver in the
- 7.4 Input characteristics of remote powered receiver in the
- 8 Power back-up
- 9 Power management
- 15 ETSI EN 302 099 V1.1.1 (2002-01)
- 16 ETSI EN 302 099 V1.1.1 (2002-01)
- 10 Safety, EMC, protection
- 10.1 Product Safety
- 10.2 EMC
- 10.3 Protection/resistibility
- 10.4 Bonding and earthing
- 17 ETSI EN 302 099 V1.1.1 (2002-01)
- 11 Environmental conditions
- 18 ETSI EN 302 099 V1.1.1 (2002-01)
- 19 ETSI EN 302 099 V1.1.1 (2002-01)
- 20 ETSI EN 302 099 V1.1.1 (2002-01)
- Bibliography
- 21 ETSI EN 302 099 V1.1.1 (2002-01)
1 Scope
The present document describes the principles for powering of telecommunications equipment in access network and contains requirements for the powering systems, laying down:
- the characteristics of the input and output interfaces of the power units;
- the power back-up conditions for TE including a power unit;
- the management data, necessary to guarantee the availability of the service and to ensure the maintenance of the power units.
The present document takes into account the characteristics of access network equipment for which the limits of responsibility in the installation or design of the power plants are very different than for equipment of telecom centre: it goes from "complete integration of the power plant in the TE" till "remote power feeding from a distant power plant". The present document applies for the powering of all equipment of the access network (copper, fiber or radio networks) located outside telecommunications centres. The access network is defined as the part of the telecommunications network, which is comprised between the customer terminal installation and the first exchange (switching unit). The customer terminal and the switching unit are excluded of the application field of the present document.
2 References
The following documents contain provisions which, through reference in this text, constitute provisions of the present document.
- References are either specific (identified by date of publication and/or edition number or version number) or non-specific.
- For a specific reference, subsequent revisions do not apply.
- For a non-specific reference, the latest version applies.
[1] ETSI ETS 300 132-1: "Equipment Engineering (EE); Power supply interface at the input to telecommunications equipment; Part 1: Operated by alternating current (ac) derived from direct current (dc) sources".
[2] ETSI EN 300 132-2: "Environmental Engineering (EE); Power supply interface at the input to telecommunications equipment; Part 2: Operated by direct current (dc)". [3] Void.
[4] CENELEC EN 60950-1: "Information technology equipment - Safety - Part 1: General requirements".
[5] IEC 60950-21: "Safety of information technology equipment - Part 21: Remote power feeding". [6] CENELEC HD 472 S1 (1989): "Nominal voltages for low-voltage public electricity supply systems".
[7] CENELEC HD 625.1: "Insulation coordination for equipment within low-voltage systems - Part 1: Principles requirements and tests".
[8] CENELEC EN 50310: "Application of equipotential bonding and earthing in buildings with information technology equipment".
[9] CENELEC EN 60896-2: "Stationary lead-acid batteries - General requirements and method of test - Part 2: Valve regulated types".
[10] ETSI EN 300 019-1-1: "Environmental Engineering (EE); Environmental conditions and environmental tests for telecommunications equipment; Part 1-1: Classification of environmental conditions; Storage".
ETSI
SIST EN 302 099 V1.1.1:2006
6 ETSI EN 302 099 V1.1.1 (2002-01)
[11] ETSI EN 300 019-1-3: "Environmental Engineering (EE); Environmental conditions and environmental tests for telecommunications equipment; Part 1-3: Classification of environmental conditions; Stationary use at weatherprotected locations".
[12] ETSI ETS 300 019-1-4: "Equipment Engineering (EE); Environmental conditions and environmental tests for telecommunications equipment; Part 1-4: Classification of environmental conditions; Stationary use at non-weatherprotected locations". [13] ETSI EN 300 019-1-8: "Environmental Engineering (EE); Environmental conditions and environmental tests for telecommunications equipment; Part 1-8: Classification of environmental conditions; Stationary use at underground locations".
[14] ETSI EN 300 253: "Environmental Engineering (EE); Earthing and bonding configuration inside telecommunications centres".
[15] ITU-T Recommendation K.35: "Bonding configurations and earthing at remote electronic sites". [16] ETSI EG 201 212: "Electrical safety; Classification of interfaces for equipment to be connected to telecommunication networks".
[17] ITU-T Recommendation K.45: "Resistibility of access network equipment to overvoltages and overcurrents".
3 Definitions and abbreviations
3.1 Definitions
For the purposes of the present document the following terms and definitions apply:
access network: part of a telecommunications network between the customer terminal installation and the first switching unit local powering: powering principle of a telecommunications equipment by a (dedicated) power unit implemented in the same location remote powering: power feeding of a telecommunications equipment by a remote power circuit NOTE: Such a circuit consists of a remote power unit, distribution wiring, and fed receivers. Remote Feeding Telecommunication (RFT) circuit: secondary circuit within the equipment, intended to supply or receive dc power via a telecommunication network at voltages equal to or exceeding the limits for TNV circuits, and on which overvoltages from telecommunication networks are possible RFT-C circuit: RFT circuit which is so designed and protected that under normal operating conditions and single fault conditions the currents in the circuit do not exceed defined values RFT-V circuit: RFT circuit which is so designed and protected that under normal operating conditions and single fault conditions the voltages are limited and the accessible area of contact is limited centralized powering: remote powering in which the remote feeding source is located in a telecommunications centre cluster powering: remote powering of a cluster of equipment (1 to n items of equipment), in which the remote feeding source is located outside a telecommunications centre Remote Power Unit (RPU): power unit, connected to the mains or from a centralized power plant, which supplies distant telecommunications equipment distant power receiver: power equipment electrically connected to a Remote Power Unit NOTE: Its function is to supply telecommunications equipment situated at the same location. It may be combined with the item of telecommunications equipment itself.
ETSI
SIST EN 302 099 V1.1.1:2006
7 ETSI EN 302 099 V1.1.1 (2002-01)
Local Power Unit (LPU): power supply equipment whose function is to supply a telecommunication equipment situated at the same location NOTE: It is generally locally connected to the mains and provides dc or ac voltage output to feed telecommunication equipment.
SELV circuit: See EN 60950-1 [4].
TNV circuit: See EN 60950-1 [4].
hazardous voltage: See EN 60950-1 [4].
primary circuit: See EN 60950-1 [4].
secondary circuit: See EN 60950-1 [4].
3.2 Abbreviations
For the purposes of the present document, the following abbreviations apply:
ac alternating current CH Customer's Home dc direct current FTTB Fibre To The Building FTTC Fibre To The Curb FTTCab Fibre To The Cabinet FTTH Fibre To The Home LPU Local Power Unit ONU Optical Network Unit RFT Remote Feeding Telecommunication RPU Remote Power Unit TC Telecommunication's Centre TE Telecom Equipment TNV Telecommunication Network Voltage UPS Uninterruptible Power Supply
4 Powering configurations
The main characteristic feature of the different powering architectures of access network equipment is the location of the following two functions:
- the point of connection to the mains; and
- the place of power back-up.
The total network can be divided in three main parts:
1) the Telecommunication Centre (TC); 2) the field (the undefined area between the Telecom Centre and the Customer's Home); 3) the Customer's Home (CH).
Powering architectures Equipment of access network can be powered remotely from a telecommunications centre (centralized powering) or from a power supply node (cluster powering), or locally from the mains (local powering). Inside these three main powering architectures, several configurations of powering are used. They are summarized in the clauses 4.1 to 4.2 and in the figures 1, 2 and 3 by the acronyms PW1 to PW 9 (for powering). ETSI
SIST EN 302 099 V1.1.1:2006
8 ETSI EN 302 099 V1.1.1 (2002-01)
Power back-up For the telephone service, which needs to provide an available service even in the case of a mains outage, a power back-up unit is located either in the remote power source or in the equipment powered. The clauses 4.1 to 4.2 detail the different installation configurations.
Location of the Telecom Equipment (TE) On the figures 1, 2 and 3 of the following clauses, the TE in access network is schematically represented in the field. These figures mean that the TE can be implemented in different types of locations:
- in a customer's office;
- in a building, public or private;
- in an indoor cabinet;
- in a street cabinet;
- on a pole cabinet;
- in a telecommunications manhole, etc.
The TE provides services for several customers or for one professional customer. On figure 3, the TE can be located at customer's home and provides services for only one private customer. Power interfaces Six power-feeding interfaces are mentioned in the following clauses: They are as follows:
I = Power interface between a -48 V power plant and the fed equipment in a telecom centre. It fits with the
interface "A" according to EN 300 132-2 [2].
I = Power interface between the public mains (commercial ac) and the fed equipment. It fits with the voltage
defined in HD 472 [6].
I = Power interface at the output of a remote power source.
I = Power interface at the input of a distant power receiver interface, in remote powering.
I = Power interface between a local power unit and the fed equipment, in local powering. It fits with the interface
"A" according to EN 300 132-2 [2] or with the interface defined in clauses 6.2 to 6.4. I = Power interface between the public mains (commercial ac) or emergency power (UPS, diesel generator) or
interface "A" according to ETS 300 132-1 [1] and the fed equipment in a telecom centre. It fits with the voltage defined in HD 472 [6].
4.1 Remote powering
4.1.1 Centralized powering
The different power supply configurations are detailed in figure 1. The output of the power source is defined at interface I . It comes from a TE (PW1a) or from a specific remote power unit (RPU in PW1b). Interface I corresponds to the 2 0 input of the RPU. The remote power unit consists of protection and distribution devices and, possibly, power conversion equipment. Interface I corresponds to Interface I and is located in the telecommunication centre. 5 1 In some cases, the TE of the access network may be equipped with a battery providing additional power in periods of heavy traffic (PW3). This battery is recharged by the remote power supply during periods of light traffic. ETSI
SIST EN 302 099 V1.1.1:2006
9 ETSI EN 302 099 V1.1.1 (2002-01)
Customer
terminal
TE TE PW1a
Remote TE PW1b Power Unit
Central TE TE PW2a Power Supply
Remote TE PW2b Power Unit 2 3 TE PW3 Ad Customer's Access network equipment Telecommunications centre home Additional power source (for traffic) Ad
Figure 1: Centralized powering
...