Thermal insulation products for building equipment and industrial installations - Factory made cellular glass (CG) products - Specification

This European Standard specifies the requirements for factory made cellular glass products which are used for the thermal insulation of building equipment and industrial installations with an operating temperature range of approximately - 265 °C to + 430 °C.
Below an operating temperature of - 50 °C, special tests regarding the suitability of the product in the intended application are advised (e.g. liquefaction of oxygen). Manufacturer's advice should be heeded in all cases.
The products are manufactured in the form of faced or unfaced boards, pipe sections, segments and prefabricated ware.
This European Standard describes product characteristics and includes procedures for testing, evaluation of conformity, marking and labelling.
Products covered by this standard are also used in prefabricated thermal insulation systems and composite panels; the performance of systems incorporating these products is not covered.
This European Standard does not specify the required level of a given property that should be achieved by a product to demonstrate fitness for purpose in a particular application. The levels required for a given application can be found in regulations and invitations to tender.
Products with a declared thermal conductivity greater than 0,065 W/(m·K) at 10 °C are not covered by this standard.
This European Standard does not cover products for the insulation of the building structure.

Wärmedämmstoffe für die technische Gebäudeausrüstung und für betriebstechnische Anlagen in der Industrie - Werkmäßig hergestellte Produkte aus Schaumglas (CG) - Spezifikation

Diese Europäische Norm legt die Anforderungen an werkmäßig hergestellte Produkte aus Schaumglas fest, die als Wärmedämmstoffe für die technische Gebäudeausrüstung und für betriebstechnische Anlagen in der Industrie in einem Betriebstemperaturbereich von etwa  265 °C bis  430 °C benutzt werden.
Bei einer Betriebstemperatur unterhalb von  50 °C sind besondere Prüfungen bezüglich der Eignung der Produkte für den beabsichtigten Anwendungsfall ratsam (z. B. Sauerstoffverflüssigung). In jedem Fall sollten die Empfehlungen des Herstellers beachtet werden.
Die Produkte werden in Form von kaschierten oder unkaschierten Platten, Rohrschalen, Segmenten und vorgeformter Dämmung hergestellt.
Diese Europäische Norm beschreibt die Produkteigenschaften und enthält Verfahren zur Prüfung, Konformitätsbewertung, Kennzeichnung und Etikettierung.
Die von dieser Norm abgedeckten Produkte werden auch in vorgefertigten Wärmedämmsystemen und Mehr-schicht-Verbundplatten angewendet; die Eigenschaften von Systemen, in die diese Produkte integriert sind, werden nicht behandelt.
Diese Europäische Norm legt für die einzelnen Eigenschaften keine Leistungsstufen fest, die ein Produkt erreichen sollte, um für einen bestimmten Anwendungsfall tauglich zu sein. Die für bestimmte Anwendungen benötigten Stufen können Regelwerken oder Ausschreibungen entnommen werden.
Diese Norm gilt nicht für Produkte mit einem Nennwert der Wärmeleitfähigkeit größer als 0,065 W/(mK) bei 10 °C.
Diese Europäische Norm gilt nicht für Produkte, die zur Dämmung des Bauwerks bestimmt sind.

Produits isolants thermiques pour l'équipement du bâtiment et les installations industrielles - Produits manufacturés en verre cellulaire (CG) - Spécification

La présente Norme européenne spécifie les exigences relatives aux produits manufacturés en verre cellulaire, utilisés pour l’isolation thermique de l’équipement du bâtiment et les installations industrielles, dont la température de service se situe entre – 265 °C et + 430 °C environ.
Pour une température de service inférieure à – 50 °C, des essais particuliers sont recommandés pour s’assurer de l’aptitude à l’emploi du produit dans l’application visée (par exemple, liquéfaction de l’oxygène). Dans de tels cas, il y a lieu de toujours faire appel aux conseils du fabricant.
Les produits sont fabriqués sous la forme de panneaux avec ou sans revêtement, de coquilles, de segments et de marchandise préfabriquée.
La présente Norme européenne décrit les caractéristiques du produit et comprend les modes opératoires pour l’essai, l’évaluation de conformité, le marquage et l’étiquetage.
Les produits couverts par la présente norme sont également utilisés dans des systèmes préfabriqués d’isolation thermique et dans des panneaux composites ; la performance des systèmes incorporant ces produits n’est pas traitée.
La présente Norme européenne ne spécifie pas le niveau requis pour une propriété donnée que doit posséder un produit pour démontrer son aptitude à une application particulière. Les niveaux requis pour une application donnée peuvent être trouvés dans les réglementations et les appels d’offre.
Les produits ayant une conductivité thermique déclarée supérieure à 0,065 W/(m K) à 10 °C ne sont pas couverts par la présente norme.
La présente Norme européenne ne couvre pas les produits destinés à l’isolation de la structure du bâtiment.

Toplotnoizolacijski proizvodi za opremo stavb in industrijske inštalacije - Proizvodi iz penjenega stekla (CG) - Specifikacija

Ta evropski standard določa zahteve za proizvode iz penjenega stekla, ki se uporabljajo za toplotno izolacijo opreme stavb in industrijskih inštalacij z razponom delovne temperature približno od –265 °C do 430 °C. Pod delovno temperaturo –50 °C se priporočajo posebni preskusi glede primernosti proizvodov za predvideno vrsto uporabe (npr. utekočinjenje kisika). V vseh primerih naj bi upoštevali napotke proizvajalca. Proizvodi so izdelani v obliki prevlečenih ali neprevlečenih plošč, vodovodnih odsekov, segmentov in montažne opreme. Ta standard opisuje lastnosti proizvodov ter zajema postopke za preskušanje, vrednotenje skladnosti, označevanje in etiketiranje. Proizvodi iz tega standarda se uporabljajo tudi v montažnih sistemih toplotne izolacije in vezanih ploščah; lastnosti sistemov iz teh proizvodov niso opisane. Ta evropski standard ne določa zahtevane ravni določene lastnosti, ki jo mora proizvod doseči, da se dokaže njegova primernost namenu za posamezno vrsto uporabe. Zahtevane ravni za posamezno uporabo je mogoče najti v uredbah in javnih razpisih.  Proizvodi z deklarirano toplotno prevodnostjo, višjo od 0,065 W/mK pri 10 °C, v tem standardu niso zajeti. Ta standard ne zajema proizvodov za izolacijo stavbne strukture.

General Information

Status
Published
Public Enquiry End Date
29-Jul-2015
Publication Date
10-Jan-2016
Technical Committee
Current Stage
6060 - National Implementation/Publication (Adopted Project)
Start Date
17-Dec-2015
Due Date
21-Feb-2016
Completion Date
11-Jan-2016

Relations

Standard
SIST EN 14305:2016
English language
45 pages
sale 10% off
Preview
sale 10% off
Preview
e-Library read for
1 day

Standards Content (Sample)


2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.Toplotnoizolacijski proizvodi za opremo stavb in industrijske inštalacije - Proizvodi iz penjenega stekla (CG) - SpecifikacijaWärmedämmstoffe für die technische Gebäudeausrüstung und für betriebstechnische Anlagen in der Industrie - Werkmäßig hergestellte Produkte aus Schaumglas (CG) - SpezifikationProduits isolants thermiques pour l'équipement du bâtiment et les installations industrielles - Produits manufacturés en verre cellulaire (CG) - SpécificationThermal insulation products for building equipment and industrial installations - Factory made cellular glass (CG) products - Specification91.100.60Thermal and sound insulating materialsICS:Ta slovenski standard je istoveten z:EN 14305:2015SIST EN 14305:2016en,fr,de01-februar-2016SIST EN 14305:2016SLOVENSKI
STANDARDSIST EN 14305:2010+A1:20131DGRPHãþD

EUROPEAN STANDARD NORME EUROPÉENNE EUROPÄISCHE NORM
EN 14305
December
t r s w ICS
{ sä s r rä x r Supersedes EN
s v u r wã t r r { ªA sã t r s uEnglish Version
Thermal insulation products for building equipment and products æ Specification Produits isolants thermiques pour l 5ßquipement du bâtiment et les installations industrielles æ Produits
Wärmedämmstoffe für die technische Gebäudeausrüstung und für betriebstechnische Anlagen in der Industrie æ Werkmäßig hergestellte This European Standard was approved by CEN on
t v October
t r s wä
egulations which stipulate the conditions for giving this European Standard the status of a national standard without any alterationä Upætoædate lists and bibliographical references concerning such national standards may be obtained on application to the CENæCENELEC Management Centre or to any CEN memberä
translation under the responsibility of a CEN member into its own language and notified to the CENæCENELEC Management Centre has the same status as the official versionsä
CEN members are the national standards bodies of Austriaá Belgiumá Bulgariaá Croatiaá Cyprusá Czech Republicá Denmarká Estoniaá Finlandá Former Yugoslav Republic of Macedoniaá Franceá Germanyá Greeceá Hungaryá Icelandá Irelandá Italyá Latviaá Lithuaniaá Luxembourgá Maltaá Netherlandsá Norwayá Polandá Portugalá Romaniaá Slovakiaá Sloveniaá Spainá Swedená Switzerlandá Turkey andUnited Kingdomä
EUROPEAN COMMITTEE FOR STANDARDIZATION COMITÉ EUROPÉEN DE NORMALISATION EUROPÄISCHES KOMITEE FÜR NORMUNG
CEN-CENELEC Management Centre:
Avenue Marnix 17,
B-1000 Brussels
t r s w CEN All rights of exploitation in any form and by any means reserved worldwide for CEN national Membersä Refä Noä EN
s v u r wã t r s w ESIST EN 14305:2016

Factory production control . 24 Annex B (normative)
Determination of minimum service temperature . 27 B.1 Definitions . 27 B.2 Principle . 27 B.3 Apparatus . 27 B.4 Test specimens . 28 B.5 Procedure . 28 B.6 Calculation and expression of results . 29 B.7 Accuracy of measurements . 29 B.8 Test report . 30 Annex C (informative)
Additional properties . 31 C.1 General . 31 C.2 Fire protection . 31 C.3 Compressive strength . 31 C.4 Shear strength . 31 C.5 Dimensional stability under constant normal laboratory conditions . 31 C.6 Coefficient of thermal expansion . 32 C.7 Apparent density . 32 Annex D (informative)
Preparation of the flat test specimens to measure thermal conductivity . 33 D.1 Introduction. 33 D.2 Procedure to get flat test specimen faces: method of the three rulers . 33 Annex ZA (informative)
Clauses of this European Standard addressing the provisions of the EU Construction Products Regulation . 34 ZA.1 Scope and relevant characteristic . 34 ZA.2 Procedures for AVCP of factory made cellular glass products . 35 ZA.3 CE Marking and labelling . 43 Bibliography . 45
is the thermal conductivity W/(m·K) D is the declared thermal conductivity W/(m·K)
is the water vapour diffusion resistance factor — Pd is the deformation under a point load of 1 000 N mm Sb is the deviation from squareness on length and width mm/m Sd is the deviation from squareness on thickness mm sd is the water vapour diffusion equivalent on air layer thickness m Smax is the deviation from flatness mm m is the compressive strength kPa b is the bending strength kPa mt is the tensile strength perpendicular to faces kPa t is the tensile strength parallel to faces kPa v is the deviation from squareness for pipe sections mm Wlp is the long term water absorption by partial immersion kg/m2 Wp is the short-term water absorption kg/m2 Xct is the compressive creep mm Xt is the deformation at time t mm Z is the water vapour resistance m2 h Pa/mg AP is the symbol of the declared level of practical sound absorption coefficient
AW is the symbol of the declared level of weighted sound absorption coefficient
BS is the symbol of the declared level for bending strength
CC(i1/i2 /y) c is the symbol of the declared level for compressive creep
CL is the symbol of the declared level for soluble chlorides
CS(Y) is the symbol of the declared level for compressive strength
F is the symbol of the declared level of soluble fluoride ions
MU is the symbol of the declared value for water vapour diffusion resistance factor
NA is the symbol of the declared level of soluble sodium ions
pH is the symbol of the declared level of the pH-value
PL(P) is the symbol of the declared level for penetration under point load
SI is the symbol of the declared level of soluble silicate ions
ST(+) is the symbol of the declared level for maximum service temperature
ST(–) is the symbol of the declared level for minimum service temperature
TP is the symbol of the declared level for tensile strength parallel to faces
TR is the symbol of the declared level for tensile strength perpendicular to faces
WL(P) is the symbol of the declared level for long term water absorption
WS is the symbol of the declared level for short-term water absorption
Z is the symbol of the declared value for water vapour resistance
3.2.2 Abbreviated terms used in this standard AVCP is Assessment and Verification of Constancy of Performance (previously named attestation of conformity) CG is Cellular Glass DoP is Declaration of Performance FPC is Factory Production Control PTD Product Type Determination (previously named ITT for Initial Type Test) RtF Reaction to Fire ThIBEII is Thermal Insulation for Building Equipment and Industrial Installations VCP is Verification of Constancy of Performance (previously named evaluation of conformity) 4 Requirements 4.1 General Product properties shall be assessed in accordance with Clause 5. To comply with this standard, products shall meet the requirements of 4.2, and the requirements of 4.3 as appropriate. NOTE Information on additional properties is given in Annex C. One test result for a product property is the average of the measured values on the number of test specimens given in Table 6. 4.2 For all applications 4.2.1 Thermal conductivity For flat specimens, thermal conductivity shall be based upon measurements carried out in accordance with EN 12667 or EN 12939 for thick products. For cylindrical specimens EN ISO 8497 shall be used as specified in 5.3.2. SIST EN 14305:2016

values below 0,1 W/(m·K) and in 0,001 W/(m·K) for
values above 0,1 W/(m·K). This shall be used as a reference for the verification of the declaration. When thermal conductivity is declared as a table derived from the equation, the rounding upwards to the next 0,001 W/(m·K) has to be done for the full range of the thermal conductivity. NOTE Determinations of the declared thermal conductivity of pipe sections, following EN ISO 8497, having joints in the metering area, include the effects of these joints as defined in EN ISO 23993. 4.2.2 Dimensions and tolerances 4.2.2.1 Linear dimensions The length, l, width, b, and thickness, d, of flat products shall be determined in accordance with EN 822 and EN 823. Length, thickness, and inside diameter Di, of pipe sections, segments and prefabricated ware shall be determined in accordance with EN 13467. No test result shall deviate from the declared values by more than the tolerances given in Table 1. Table 1 — Dimensional tolerances Dimensions in millimetres Form of
delivery Length Width Thickness Inside diameter Squareness Flatness Pipe section linearity Length and width Thickness Unfaced board ±2 ±2 ±2
±5 mm/m ±2 ±2
Faced board ±5 ±2 ±2 a
±5 mm/m ±2 ±2
Pipe section ±2
±2 – 0 to + 4 ±3
±2 a The tolerances apply only to unfaced boards. The thickness of any facing exceeding 3 mm shall be indicated in the manufacturer's literature. 4.2.2.2 Squareness Deviation from squareness, Sb, of boards and slabs shall be determined in accordance with EN 824. Deviation from squareness, v, of pipe sections shall be determined in accordance with EN 13467. No test result shall exceed the corresponding tolerance given in Table 1. 4.2.2.3 Flatness Deviation from flatness, Smax, of boards and slabs shall be determined in accordance with EN 825. SIST EN 14305:2016

· 400 CS(Y)500
· 500 CS(Y)600
· 600 CS(Y)700
· 700 CS(Y)800
· 800 CS(Y)900
· 900 CS(Y)1000
· 1 000 CS(Y)1200
· 1 200 CS(Y)1400
· 1 400 CS(Y)1600
· 1 600 CS(Y)1800
· 1 800 CS(Y)2000
· 2 000 CS(Y)2200
· 2 200 CS(Y)2400
· 2 400 CS(Y)2500
· 2 500 CS(Y)2750
· 2 750 CS(Y)3000
· 3 000 SIST EN 14305:2016
· 200 BS 250
· 250 BS 300
· 300 BS 350
· 350 BS 400
· 400 BS 450
· 450 BS 500
· 500 BS 550
· 550 BS 600
· 600 BS 700
· 700 BS 800
· 800 BS 900
· 900 BS 1000
· 1 000 BS 1100
· 1 100 BS 1200
· 1 200 BS 1300
· 1 300 BS 1400
· 1 400 4.3.6 Point load Deformation under a point load of 1 000 N, Pd, of boards and slabs, shall be determined in accordance with EN 12430. No test result shall exceed the value, given in Table 5, for the declared level. Table 5 — Levels for deformation under point load Level Requirement mm PL(P)2
¶ 2,0 PL(P)1,5
¶ 1,5 PL(P)1
¶ 1,0 PL(P)0,5
¶ 0,5 4.3.7 Tensile strength parallel to faces Tensile strength parallel to faces, t, shall be determined in accordance with EN 1608. The level of tensile strength parallel to faces shall be declared in levels, TP, with steps of 50 kPa. No test result shall be less than the declared level. SIST EN 14305:2016

¶ i CC(i1/i2/25) c 304 25 c i1/i2
¶ i CC(i1/i2/50) c 608 50 c i1/i2
¶ i a The creep of the bitumen used for the facings is not taken into account in these values. NOTE 2 Referring to the designation code CC(i1/i2/y)c, according to Clause 6, a declared level CC(1,5/1/10)450, as for example, indicates a value not exceeding 1 mm for compressive creep and 1,5 mm for total thickness reduction after extrapolation at 10 years (i.e. 30 times one hundred and 22 days of testing) under a declared stress of 450 kPa. 4.3.10 Water absorption 4.3.10.1
Short-term water absorption Short-term water absorption by par
...

Questions, Comments and Discussion

Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.