SIST EN 50363-4-1:2006
(Main)Insulating, sheathing and covering materials for low voltage energy cables -- Part 4-1: PVC sheathing compounds
Insulating, sheathing and covering materials for low voltage energy cables -- Part 4-1: PVC sheathing compounds
This part of EN 50363 specifies the requirements for the physical properties of the PVC sheathing compounds given in Table 1. The relevant test methods are given in EN 60811 series.
Isolier-, Mantel- und Umhüllungswerkstoffe für Niederspannungskabel und -leitungen -- Teil 4-1: PVC-Mantelmischungen
Dieser Teil der EN 50363 legt die Anforderungen an PVC Mantelmischungen fest, die in Tabelle 1 aufgeführt sind. Die entsprechenden Prüfverfahren sind in den Normen der Reihe EN 60811 beschrieben.
Matériaux pour enveloppe isolante, gainage et revêtement pour les câbles d'énergie basse tension -- Partie 4-1: Mélanges PVC pour gaine
La présente partie de la EN 50363 mentionne les prescriptions pour les mélanges en PVC pour gaine, donnés dans le Tableau 1. Les méthodes d’essais appropriées sont données dans la série EN 60811.
Materiali za izoliranje, oplaščenje in prevleke nizkonapetostnih energetskih kablov – 4-1. del: Polivinilkloridne (PVC) mase za oplaščenje
General Information
- Status
- Published
- Publication Date
- 30-Apr-2006
- Technical Committee
- IEKA - Electric cables
- Current Stage
- 6060 - National Implementation/Publication (Adopted Project)
- Start Date
- 01-May-2006
- Due Date
- 01-May-2006
- Completion Date
- 01-May-2006
Overview
EN 50363-4-1:2005 (CLC) defines the physical property requirements for PVC sheathing compounds used on low voltage energy cables. It is a part of the EN 50363 series and must be read in conjunction with EN 50363-0; the specified test methods are given in the EN 60811 series. The standard classifies PVC sheathing materials into types (TM 1–TM 5) and sets mandatory test criteria for mechanical, thermal and environmental performance.
Key topics and technical requirements
- Scope: Requirements cover the physical properties of PVC sheathing compounds (see Table 1 of the standard).
- Compound types (Table 1):
- TM 1 - 70 °C, general purpose for fixed-installation cables (may oversheath metallic-layer cables up to 80 °C)
- TM 2 - 70 °C, flexible general purpose
- TM 3 - 90 °C, flexible for high-temperature use
- TM 4 - 70 °C, flexible for low-temperature use
- TM 5 - 70 °C, oil-resistant flexible
- Mechanical properties (tensile / elongation):
- Median tensile strength (N/mm²): TM1 = 12.5; TM2–TM5 = 10.0
- Median elongation at break (%): TM1 = 125; TM2–TM5 = 150
- Requirements apply before and after defined ageing cycles (air oven ageing at specified temperatures and durations).
- Ageing and thermal tests:
- Oven ageing with specified temperatures and durations (e.g., TM3 uses 135 °C for 14×24 h).
- Minimum thermal stability at 200 °C is specified for TM3 (240 min).
- Oil immersion (TM5):
- Immersion in mineral oil at 90 °C for 7×24 h; allowable tensile/elongation variations ±30%.
- Degradation and stability tests:
- Loss of mass after ageing (mg/cm²) - e.g., TM3 max 1.5 mg/cm², others typically 2.0 mg/cm².
- Heat shock: 150 °C for 1 h - result: no cracks.
- Pressure test at high temperature: indentation depth median max 50%.
- Low-temperature performance:
- Bending and elongation tests at specified low temperatures (TM4 tested at −30 °C) - elongation without break min 30%.
All test methods are referenced to the EN 60811 series.
Applications and who uses this standard
- Cable manufacturers specifying or qualifying PVC sheathing compounds for low-voltage energy cables.
- Material suppliers and compound formulators ensuring compliance with CLC requirements.
- Independent test laboratories performing EN 60811 test methods against EN 50363-4-1 limits.
- Specifiers, procurement engineers and compliance officers writing product specifications for building, industrial and utility cable systems.
- Designers selecting sheathing types for temperature, oil exposure or low-temperature installations.
Related standards
- EN 50363-0 (general requirements and cross-references)
- EN 60811 series (test methods for cable materials)
- CENELEC / CLC implementation documents
EN 50363-4-1:2005 is essential for ensuring reliable PVC sheaths, consistent test methods, and harmonized performance requirements in low voltage cable production and specification.
Frequently Asked Questions
SIST EN 50363-4-1:2006 is a standard published by the Slovenian Institute for Standardization (SIST). Its full title is "Insulating, sheathing and covering materials for low voltage energy cables -- Part 4-1: PVC sheathing compounds". This standard covers: This part of EN 50363 specifies the requirements for the physical properties of the PVC sheathing compounds given in Table 1. The relevant test methods are given in EN 60811 series.
This part of EN 50363 specifies the requirements for the physical properties of the PVC sheathing compounds given in Table 1. The relevant test methods are given in EN 60811 series.
SIST EN 50363-4-1:2006 is classified under the following ICS (International Classification for Standards) categories: 29.035.20 - Plastics and rubber insulating materials; 29.060.20 - Cables. The ICS classification helps identify the subject area and facilitates finding related standards.
SIST EN 50363-4-1:2006 is associated with the following European legislation: EU Directives/Regulations: 2006/95/EC, 2014/35/EU, 73/23/EEC. When a standard is cited in the Official Journal of the European Union, products manufactured in conformity with it benefit from a presumption of conformity with the essential requirements of the corresponding EU directive or regulation.
SIST EN 50363-4-1:2006 is available in PDF format for immediate download after purchase. The document can be added to your cart and obtained through the secure checkout process. Digital delivery ensures instant access to the complete standard document.
Standards Content (Sample)
SLOVENSKI SIST EN 50363-4-1:2006
STANDARD
maj 2006
Materiali za izoliranje, oplaščenje in prevleke nizkonapetostnih energetskih
kablov – 4-1. del: Polivinilkloridne (PVC) mase za oplaščenje
Insulating, sheathing and covering materials for low voltage energy cables – Part 4-
1: PVC sheathing compounds
ICS 29.035.20; 29.060.20 Referenčna številka
© Standard je založil in izdal Slovenski inštitut za standardizacijo. Razmnoževanje ali kopiranje celote ali delov tega dokumenta ni dovoljeno
EUROPEAN STANDARD EN 50363-4-1
NORME EUROPÉENNE
EUROPÄISCHE NORM November 2005
ICS 29.035.20
English version
Insulating, sheathing and covering materials
for low voltage energy cables
Part 4-1: PVC sheathing compounds
Matériaux pour enveloppe isolante, Isolier-, Mantel- und
gainage et revêtement pour les câbles Umhüllungswerkstoffe für
d'énergie basse tension Niederspannungskabel und -leitungen
Partie 4-1: Mélanges PVC pour gaine Teil 4-1: PVC-Mantelmischungen
This European Standard was approved by CENELEC on 2005-11-01. CENELEC members are bound to
comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this European
Standard the status of a national standard without any alteration.
Up-to-date lists and bibliographical references concerning such national standards may be obtained on
application to the Central Secretariat or to any CENELEC member.
This European Standard exists in three official versions (English, French, German). A version in any other
language made by translation under the responsibility of a CENELEC member into its own language and
notified to the Central Secretariat has the same status as the official versions.
CENELEC members are the national electrotechnical committees of Austria, Belgium, Cyprus, Czech
Republic, Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia,
Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Slovakia, Slovenia, Spain, Sweden,
Switzerland and United Kingdom.
CENELEC
European Committee for Electrotechnical Standardization
Comité Européen de Normalisation Electrotechnique
Europäisches Komitee für Elektrotechnische Normung
Central Secretariat: rue de Stassart 35, B - 1050 Brussels
© 2005 CENELEC - All rights of exploitation in any form and by any means reserved worldwide for CENELEC members.
Ref. No. EN 50363-4-1:2005 E
Foreword
This European Standard was prepared by the Technical Committee CENELEC TC 20, Electric cables.
The text of the draft was submitted to the formal vote and was approved by CENELEC as
EN 50363-4-1 on 2005-11-01.
EN 50363 (in all its parts) supersedes the equivalent information at present in HD 21.1 S4,
HD 21.14 S1, HD 22.1 S4, HD 22.10 S1, HD 22.14 S2 and prHD 21.15 S1. The existing information
in these HDs will be deleted at the next maintenance review.
EN 50363-4-1 should be read in conjunction with EN 50363-0.
The following dates were fixed:
– latest date by which the EN has to be implemented
at national level by publication of an identical
national standard or by endorsement (dop) 2006-11-01
– latest date by which the national standards conflicting
with the EN have to be withdrawn (dow) 2007-11-01
– 3 – EN 50363-4-1:2005
Contents
1 Scope.4
2 Normative references.4
3 Definitions.4
4 Properties.4
Table 1 – Types of PVC sheathing compound.4
Table 2 – Requirements for the tests for PVC sheathing compounds .5
1 Scope
This part of EN 50363 specifies the requirements for the physical properties of the PVC sheathing
compounds given in Table 1. The relevant test methods are given in EN 60811 series.
NOTE This part of EN 50363 is to be read in conjunction with EN
...