(Main)Low-voltage electrical installations - Part 7-701: Requirements for special installations or locations - Locations containing a bath or shower (IEC 60364-7-701:2019)
Low-voltage electrical installations - Part 7-701: Requirements for special installations or locations - Locations containing a bath or shower (IEC 60364-7-701:2019)
IEC 60364-7-701:2019 applies to electrical installations in indoor or outdoor locations where a bath tub and/or a shower is intended to be permanently placed in a specific location.
The extent of the location containing a bath tub and/or a shower is limited by:
– the lowest finished floor level;
– a horizontal plane 3 m above the lowest finished floor level;
– a vertical circumscribing virtual surface at a distance of 4 m from the fixed water outlet for the bath tub or shower; and
– the volume within the walls, floor and ceiling that border the location containing a bath or shower, measured to a depth of 6 cm.
The requirements of this document also apply to fixed electrical installations in mobile applications, for example caravans, mobile homes, shower containers. This document does not apply to emergency facilities, for example emergency showers used in industrial areas or laboratories.
This third edition cancels and replaces the second edition published in 2006. This edition constitutes a technical revision.
This edition includes the following significant technical changes with respect to the previous edition:
– the scope gives precisions relevant to the application of this document;
– the description of zones is improved;
– relevant terms are defined.
Errichten von Niederspannungsanlagen - Teil 7-701: Anforderungen für Betriebsstätten, Räume und Anlagen besonderer Art - Räume mit Badewanne oder Dusche (IEC 60364-7-701:2019)
Installations électriques à basse tension - Partie 7-701: Règles pour les installations et emplacements spéciaux - Emplacements contenant une baignoire ou une douche (IEC 60364-7-701:2019)
IEC 60364-7-701:2019 s’applique aux installations électriques se trouvant dans des emplacements intérieurs ou extérieurs où une baignoire et/ou une douche sont destinées à être installées de façon permanente dans un emplacement spécifique.
L’étendue de l’emplacement contenant une baignoire et/ou une douche est délimitée par:
– le niveau le plus bas du sol fini;
– un plan horizontal situé 3 m au-dessus du niveau le plus bas du sol fini;
– une surface virtuelle verticale se situant à une distance de 4 m de l’arrivée d’eau fixe pour la baignoire ou la douche; et
– le volume entre les murs, sol et plafond qui délimitent l’emplacement contenant une baignoire ou une douche, mesuré à une profondeur de 6 cm.
Les exigences du présent document s’appliquent également aux installations électriques fixes dans des applications mobiles, par exemple les caravanes, mobil-homes, sanitaires mobiles. Le présent document ne s’applique pas aux équipements d’urgence, par exemple les douches d’urgence utilisées dans les installations industrielles ou dans les laboratoires.
Cette édition inclut les modifications techniques majeures suivantes par rapport à l'édition précédente:
– le domaine d’application donne des précisions relatives à l’application du présent document;
– la description des volumes est améliorée;
– les termes pertinents sont définis.
Nizkonapetostne električne inštalacije - 7-701. del: Zahteve za posebne inštalacije ali lokacije - Prostori s kadjo ali prho (IEC 60364-7-701:2019)
Posebne zahteve iz tega dela standarda IEC 60364 se uporabljajo za električne inštalacije v zaprtih prostorih ali na prostem, kjer je predvidena stalna namestitev kopalne kadi in/ali prhe na določenem mestu.
Obseg prostora s kopalno kadjo in/ali prho omejujejo:
– najnižji nivo tal;
– vodoravna ravnina 3 m nad najnižjim nivojem tal;
– navpična obdajajoča navidezna površina na razdalji 4 m od fiksnega odtoka vode za kopalno kad ali prho; ter – prostornina znotraj sten, tal in stropa, ki mejijo na prostor s kadjo ali prho, merjena do globine 6 cm.
OPOMBA 1: Če sta glava prhe in gibljiva cev snemljivi, se šteje, da je fiksni odtok vode na dovodnem koncu gibljive cevi.
Zahteve tega dokumenta se uporabljajo tudi za fiksne električne instalacije za mobilno uporabo, npr. v bivalnih prikolicah, mobilnih hišicah, kabinah za prhanje. Ta dokument se ne uporablja za objekte za nujne primere, npr. zasilne prhe, ki se uporabljajo v industrijskih območjih ali laboratorijih.
OPOMBA 2: Za prostore s kadjo ali prho, namenjene za medicinsko zdravljenje, so lahko potrebne dodatne zahteve.
OPOMBA 3: Za montažne kopalne enote in/ali enote za prhanje glej tudi standard IEC 60335-2-105.
General Information
Relations
Standards Content (Sample)
SLOVENSKI STANDARD
01-februar-2025
Nadomešča:
SIST HD 60364-7-701:2007
SIST HD 60364-7-701:2007/A11:2012
SIST HD 60364-7-701:2007/A12:2017
SIST HD 60364-7-701:2007/AC:2011
Nizkonapetostne električne inštalacije - 7-701. del: Zahteve za posebne inštalacije
ali lokacije - Prostori s kadjo ali prho (IEC 60364-7-701:2019)
Low-voltage electrical installations - Part 7-701: Requirements for special installations or
locations - Locations containing a bath or shower (IEC 60364-7-701:2019)
Errichten von Niederspannungsanlagen - Teil 7-701: Anforderungen für Betriebsstätten,
Räume und Anlagen besonderer Art - Räume mit Badewanne oder Dusche (IEC 60364-
7-701:2019)
Installations électriques à basse tension - Partie 7-701: Règles pour les installations et
emplacements spéciaux - Emplacements contenant une baignoire ou une douche (IEC
60364-7-701:2019)
Ta slovenski standard je istoveten z: HD 60364-7-701:2024
ICS:
91.140.50 Sistemi za oskrbo z elektriko Electricity supply systems
91.140.70 Sanitarne naprave Sanitary installations
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.
HARMONIZATION DOCUMENT HD 60364-7-701
DOCUMENT D'HARMONISATION
HARMONISIERUNGSDOKUMENT December 2024
ICS 29.020; 91.140.50 Supersedes HD 60364-7-701:2007; HD 60364-7-
701:2007/A11:2011; HD 60364-7-701:2007/AC:2011
English Version
Low-voltage electrical installations - Part 7-701: Requirements
for special installations or locations - Locations containing a bath
or shower
(IEC 60364-7-701:2019)
Installations électriques à basse tension - Partie 7-701: Errichten von Niederspannungsanlagen - Teil 7-701:
Exigences pour les installations et emplacements spéciaux Anforderungen für Betriebsstätten, Räume und Anlagen
- Emplacements contenant une baignoire ou une douche besonderer Art - Orte mit Badewanne oder Dusche
(IEC 60364-7-701:2019) (IEC 60364-7-701:2019)
This Harmonization Document was approved by CENELEC on 2024-07-29. CENELEC members are bound to comply with the
CEN/CENELEC Internal Regulations which stipulate the conditions for implementation of this Harmonization Document at national level.
Up-to-date lists and bibliographical references concerning such national implementations may be obtained on application to the CEN-
CENELEC Management Centre or to any CENELEC member.
This Harmonization Document exists in three official versions (English, French, German).
CENELEC members are the national electrotechnical committees of Austria, Belgium, Bulgaria, Croatia, Cyprus, the Czech Republic,
Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, the
Netherlands, Norway, Poland, Portugal, Republic of North Macedonia, Romania, Serbia, Slovakia, Slovenia, Spain, Sweden, Switzerland,
Türkiye and the United Kingdom.
European Committee for Electrotechnical Standardization
Comité Européen de Normalisation Electrotechnique
Europäisches Komitee für Elektrotechnische Normung
CEN-CENELEC Management Centre: Rue de la Science 23, B-1040 Brussels
© 2024 CENELEC All rights of exploitation in any form and by any means reserved worldwide for CENELEC Members.
Ref. No. HD 60364-7-701:2024 E
European foreword
The text of document 64/2382/FDIS, future edition 3 of IEC 60364-7-701, prepared by IEC/TC 64
"Electrical installations and protection against electric shock" was submitted to the IEC-CENELEC
parallel vote and approved by CENELEC as HD 60364-7-701:2024.
The following dates are fixed:
• latest date by which the document has to be implemented at national (dop) 2025-06-06
level by publication of an identical national standard or by endorsement
• latest date by which the national standards conflicting with the (dow) 2027-12-06
document have to be withdrawn
This document supersedes HD 60364-7-701:2007 and all of its amendments and corrigenda (if any).
Attention is drawn to the possibility that some of the elements of this document may be the subject of
patent rights. CENELEC shall not be held responsible for identifying any or all such patent rights.
Any feedback and questions on this document should be directed to the users’ national committee. A
complete listing of these bodies can be found on the CENELEC website.
Endorsement notice
The text of the International Standard IEC 60364-7-701:2019 was approved by CENELEC as a
European Standard without any modification.
In the official version, for Bibliography, the following notes have to be added for the standard indicated:
IEC 60335 (series) NOTE Approved as EN IEC 60335 (series)
IEC 60335-2-105 NOTE Approved as EN IEC 60335-2-105
IEC 61558-2-5 NOTE Approved as EN 61558-2-5
IEC 60364-7-701 ®
Edition 3.0 2019-10
INTERNATIONAL
STANDARD
NORME
INTERNATIONALE
Low-voltage electrical installations –
Part 7-701: Requirements for special installations or locations – Locations
containing a bath or shower
Installations électriques à basse tension –
Partie 7-701: Exigences pour les installations et emplacements spéciaux –
Emplacements contenant une baignoire ou une douche
INTERNATIONAL
ELECTROTECHNICAL
COMMISSION
COMMISSION
ELECTROTECHNIQUE
INTERNATIONALE
ICS 29.020; 91.140.50 ISBN 978-2-8322-7414-9
– 2 – IEC 60364-7-701:2019 IEC 2019
CONTENTS
FOREWORD . 3
INTRODUCTION . 5
701 Locations containing a bath or shower . 6
701.1 Scope . 6
701.2 Normative references . 6
701.3 Terms and definitions . 6
701.30 Assessment of general characteristics . 7
701.4 Protection for safety . 8
701.41 Protection against electric shock . 8
701.411 Protective measure: automatic disconnection of supply . 9
701.414 Protective measure: extra-low-voltage provided by SELV and PELV . 9
701.415 Additional protection . 9
701.5 Selection and erection of electrical equipment. 10
701.51 Common rules . 10
701.512 Operational conditions and external influences . 10
701.52 Wiring systems . 11
701.522 Selection and erection of wiring systems in relation to external
influences . 11
701.53 Devices for protection for safety, isolation, switching, control and
monitoring . 12
701.531 Devices for protection against indirect contact by automatic
disconnection of supply . 12
Annex A (informative) List of notes concerning certain countries . 21
Bibliography . 27
Figure 1 – Remaining wall thickness behind zones . 12
Figure 2 – Dimensions of zones: side view of a bath tub . 13
Figure 3 – Dimensions of zones: top view of a bath tub without partition . 14
Figure 4 – Dimensions of zones: top view of a bath tub with fixed partition . 15
Figure 5 – Dimensions of zones 0 and 1: side view of a shower . 16
Figure 6 – Dimensions of zones 0 and 1: side view of a shower with fixed partition . 17
Figure 7 – Dimensions of zones 0 and 1: top view of a shower with fixed water outlet
close to a corner . 18
Figure 8 – Dimensions of zones 0 and 1: top view of a shower with fixed water outlet at
a distance from a corner . 18
Figure 9 – Dimensions of zones 0 and 1: top view of a shower with a fixed partition . 19
Figure 10 – Example of zone for shower with doors . 20
Figure 11 – Dimensions of zones in locations containing a shower with a basin . 26
IEC 60364-7-701:2019 IEC 2019 – 3 –
INTERNATIONAL ELECTROTECHNICAL COMMISSION
____________
LOW-VOLTAGE ELECTRICAL INSTALLATIONS –
Part 7-701: Requirements for special installations or locations –
Locations containing a bath or shower
FOREWORD
1) The International Electrotechnical Commission (IEC) is a worldwide organization for standardization comprising
all national electrotechnical committees (IEC National Committees). The object of IEC is to promote
international co-operation on all questions concerning standardization in the electrical and electronic fields. To
this end and in addition to other activities, IEC publishes International Standards, Technical Specifications,
Technical Reports, Publicly Available Specifications (PAS) and Guides (hereafter referred to as “IEC
Publication(s)”). Their preparation is entrusted to technical committees; any IEC National Committee interested
in the subject dealt with may participate in this preparatory work. International, governmental and non-
governmental organizations liaising with the IEC also participate in this preparation. IEC collaborates closely
with the International Organization for Standardization (ISO) in accordance with conditions determined by
agreement between the two organizations.
2) The formal decisions or agreements of IEC on technical matters express, as nearly as possible, an international
consensus of opinion on the relevant subjects since each technical committee has representation from all
interested IEC National Committees.
3) IEC Publications have the form of recommendations for international use and are accepted by IEC National
Committees in that sense. While all reasonable efforts are made to ensure that the technical content of IEC
Publications is accurate, IEC cannot be held responsible for the way in which they are used or for any
misinterpretation by any end user.
4) In order to promote international uniformity, IEC National Committees undertake to apply IEC Publications
transparently to the maximum extent possible in their national and regional publications. Any divergence
between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in
the latter.
5) IEC itself does not provide any attestation of conformity. Independent certification bodies provide conformity
assessment services and, in some areas, access to IEC marks of conformity. IEC is not responsible for any
services carried out by independent certification bodies.
6) All users should ensure that they have the latest edition of this publication.
7) No liability shall attach to IEC or its directors, employees, servants or agents including individual experts and
members of its technical committees and IEC National Committees for any personal injury, property damage or
other damage of any nature whatsoever, whether direct or indirect, or for costs (including legal fees) and
expenses arising out of the publication, use of, or reliance upon, this IEC Publication or any other IEC
Publications.
8) Attention is drawn to the Normative references cited in this publication. Use of the referenced publications is
indispensable for the correct application of this publication.
9) Attention is drawn to the possibility that some of the elements of this IEC Publication may be the subject of
patent rights. IEC shall not be held responsible for identifying any or all such patent rights.
International Standard IEC 60364-7-701 has been prepared by IEC technical committee 64:
Electrical installations and protection against electric shock.
This third edition cancels and replaces the second edition published in 2006. This edition
constitutes a technical revision.
This edition includes the following significant technical changes with respect to the previous
edition:
– the scope gives precisions relevant to the application of this document;
– the description of zones is improved;
– relevant terms are defined.
– 4 – IEC 60364-7-701:2019 IEC 2019
The text of this International Standard is based on the following documents:
FDIS Report on voting
64/2382/FDIS 64/2395/RVD
Full information on the voting for the approval of this International Standard can be found in
the report on voting indicated in the above table.
This document has been drafted in accordance with the ISO/IEC Directives, Part 2.
A list of all parts in the IEC 60364 series, published under the general title Low voltage
electrical installations can be found on the IEC website.
The reader's attention is drawn to the fact that Annex A lists all of the “in-some-country”
clauses on differing practices of a less permanent nature relating to the subject of this
document.
The committee has decided that the contents of this document will remain unchanged until the
stability date indicated on the IEC website under "http://webstore.iec.ch" in the data related to
the specific document. At this date, the document will be
• reconfirmed,
• withdrawn,
• replaced by a revised edition, or
• amended.
IEC 60364-7-701:2019 IEC 2019 – 5 –
INTRODUCTION
For the purpose of this part of IEC 60364 (IEC 60364-7-701) the requirements of the general
Parts 1 to 6 and Parts 8 of IEC 60364 apply.
The IEC 60364-7-7XX parts of IEC 60364 contain particular requirements for special
installations or locations which are based on the requirements of the general parts of
IEC 60364 (IEC 60364-1 to IEC 60364-6 and IEC 60364-8). These IEC 60364-7-7XX parts are
considered in conjunction with the requirements of the general parts.
The particular requirements of this part of IEC 60364 supplement, modify or replace certain of
the requirements of the general parts of IEC 60364 being valid at the time of publication of
this part. The absence of reference to the exclusion of a part or a clause of a general part
means that the corresponding clauses of the general part are applicable (undated reference).
Requirements of other 7XX parts being relevant for installations covered by this part also
apply. This part may therefore also supplement, modify or replace certain of these
requirements valid at the time of publication of this part.
The clause numbering of this part follows the pattern and corresponding references of
IEC 60364. The numbers following the particular number of this part are those of the
corresponding parts, or clauses of the other parts of the IEC 60364 series, valid at the time of
publication of this part, as indicated in the normative references of this document (dated
reference).
If requirements or explanations additional to those of the other parts of the IEC 60364 series
are needed, the numbering of such items appears as 701.101, 701.102, 701.103, etc.
In the case where new or amended general parts with modified numbering were published
after this part was issued, the clause numbers referring to a general part in this Part 701 may
no longer align with the latest edition of the general part. Dated references should be
observed.
– 6 – IEC 60364-7-701:2019 IEC 2019
LOW-VOLTAGE ELECTRICAL INSTALLATIONS –
Part 7-701: Requirements for special installations or locations –
Locations containing a bath or shower
701 Locations containing a bath or shower
701.1 Scope
The particular requirements of this part of IEC 60364 apply to electrical installations in indoor
or outdoor locations where a bath tub and/or a shower is intended to be permanently placed in
a specific location.
The extent of the location containing a bath tub and/or a shower is limited by:
– the lowest finished floor level;
– a horizontal plane 3 m above the lowest finished floor level;
– a vertical circumscribing virtual surface at a distance of 4 m from the fixed water outlet for
the bath tub or shower; and
– the volume within the walls, floor and ceiling that border the location containing a bath or
shower, measured to a depth of 6 cm.
NOTE 1 Where the shower head and flexible hose are detachable, the fixed water outlet is taken to be at the
supply end of the flexible hose.
The requirements of this document also apply to fixed electrical installations in mobile
applications, for example caravans, mobile homes, shower containers. This document does
not apply to emergency facilities, for example emergency showers used in industrial areas or
laboratories.
NOTE 2 For locations containing a bath or shower for medical treatment, special requirements can be necessary.
NOTE 3 For prefabricated bath and/or shower units, see also IEC 60335-2-105.
701.2 Normative references
The following documents are referred to in the text in such a way that some or all of their
content constitutes requirements of this document. For dated references, only the edition
cited applies. For undated references, the latest edition of the referenced document (including
any amendments) applies.
IEC 60364-4-41:2005, Low-voltage electrical installations – Part 4-41: Protection for safety –
Protection against electric shock
IEC 60364-4-41:2005/AMD1:2017
701.3 Terms and definitions
For the purposes of this document, the following terms and definitions apply.
ISO and IEC maintain terminological databases for use in standardization at the following
addresses:
• IEC Electropedia: available at http://www.electropedia.org/
• ISO Online browsing platform: available at http://www.iso.org/obp
IEC 60364-7-701:2019 IEC 2019 – 7 –
701.3.1
location
particular place or position
EXAMPLE A dedicated room, an area of a room (e.g. area in a loft), an outdoor area.
701.3.2
bath tub
basin for the total or substantial immersion of the human body in water, which is intended to
be drained after every use
701.3.3
shower
defined place intended for personal cleaning activity under a spray of water without intentional
retention of the water
701.3.4
fixed partition
solid barrier or enclosure, including any integrated doors, with some portion attached to the
building structure that will deflect water directed against its surface
Note 1 to entry: Integrated doors are considered to be closed.
Note 2 to entry: A curtain is not a fixed partition.
701.30 Assessment of general characteristics
701.30.101 General
When applying this document, the zones specified in 701.30.102, 701.30.103, and 701.30.104
shall be taken into account. For fixed prefabricated bath or shower units, the zones are
applied to the situation when the bath or shower basin is in its intended configuration.
Fixed partitions including horizontal or inclined ceilings, walls with or without windows, doors,
floors, may limit the extent of locations containing a bath or shower as well as their zones.
Where the dimensions of fixed partitions are smaller than the dimensions of the relevant
zones, for example partitions having a height lower than 225 cm, the minimum distance in
horizontal and vertical direction shall be taken into account (see Figure 2 to Figure 9).
Shower curtains or equivalent flexible material shall not be used for limiting the zones.
Where a shower is located in zone 1 of a bath tub, the zones for a bath tub apply.
Where for showers there is more than one fixed water outlet, the limit of the zones to be
considered are those given by the combination of the zones.
701.30.102 Description of zone 0
Zone 0 is limited:
a) by the interior of a bath tub, see Figure 2 to Figure 4;
b) for showers:
– from the lowest finished floor level up to a horizontal plane at the height of 10 cm
above; and
– by a vertical circumscribing virtual surface at a distance of 120 cm from the centre of
the fixed shower head(s) and/or water outlet(s) limited by fixed partitions restricting the
water to enter into the area on the other side of the partition (see Figure 5, Figure 6,
Figure 7, Figure 8 and Figure 9).
– 8 – IEC 60364-7-701:2019 IEC 2019
– Shower doors intended to be closed when taking a shower are delimiting the zone 0,
(see Figure 10).
701.30.103 Description of zone 1
Zone 1 is limited:
a) for a bath tub by:
– the floor level below the bath tub;
– a horizontal plane lying 225 cm above the floor level below the bath tub or a horizontal
plane corresponding to the highest fixed shower head, if any, or fixed water outlet,
whichever is higher;
– the vertical virtual surface circumscribing the bath tub (see Figure 2 to Figure 4); and
– excluding zone 0;
b) for showers by:
– the lowest finished floor level;
– a horizontal plane corresponding to the highest fixed shower head or fixed water
outlet or the horizontal plane lying 225 cm above the lowest finished floor level,
whichever is higher;
– the vertical circumscribing virtual surface at a distance of 120 cm from the centre of
the fixed shower head(s) and/or fixed water outlet(s) limited by fixed partitions
restricting the water to enter into the area on the other side of the partition;
– shower doors intended to be closed when taking a shower, if any, see Figure 10; and
– excluding zone 0.
701.30.104 Description of zone 2
Zone 2 is limited:
a) for a bath tub by:
– the finished floor level;
– the horizontal plane corresponding to the highest fixed shower head or fixed water
outlet or the horizontal plane lying 225 cm above the finished floor level, whichever is
higher; and
– the vertical virtual surface at the boundary of zone 1 and the parallel vertical virtual
surface at a distance of 60 cm from the zone 1 border (see Figure 2 to Figure 4);
b) for showers, there is no zone 2. (see Figure 5 to Figure 10).
701.4 Protection for safety
701.41 Protection against electric shock
701.410.3 General requirements
701.410.3.4
Replace the existing text by the following:
The protective measure electrical separation shall only be used for:
– circuits supplying one item of current-using equipment; or
– one single socket-outlet.
The protective measure electrical separation for the supply shall not be applied for heating cables
and embedded heating systems.
IEC 60364-7-701:2019 IEC 2019 – 9 –
701.410.3.5
Replace the existing text by the following:
The protective measures of obstacles and placing out of reach, as specified in
IEC 60364-4-41:2005, Annex B shall not be applied.
701.410.3.6
Replace the existing text by the following:
The protective measures of non-con
...