Abstract

The present document contains requirements for:
• the output performance of the power equipment at the interface A3;
• the input of the telecommunications equipment connected to interface A3.
The voltage at interface A3 may be the ac mains, a rectified voltage derived from ac three phase mains, a rectified voltage derived from ac single phase mains or a low voltage derived from a battery. The power supply equipment may incorporate a backup battery.
The present document aims at providing compatibility between the power supply equipment and both the telecommunications equipment, and the different load units connected to the same interface A3 (e.g. datacom equipment).
The requirements at interface A3 apply to:
• the output of the power supply equipment or power supply installation of telecommunications centres;
• the power supply input of telecommunications equipment and the datacom equipment installed at telecommunications centres;
• telecommunications equipment and the datacom equipment, installed in customer's premises, whose power interface A3 is also used by equipment requiring a supply to the present document. The purpose of the present document is:
• to identify a power supply system with the same characteristics for all telecommunications and data communication equipment defined in the area of application;
• to facilitate interworking of different (types of) loads units;
• to facilitate the standardization of power supply systems for telecommunications and datacom equipment;
• to facilitate the installation, operation and maintenance in the same network of equipment and telecommunications and datacom systems from different origins.

Status
Published
Publication Date
31-Jan-2006
Current Stage
6060 - National Implementation/Publication (Adopted Project)
Start Date
01-Feb-2006
Due Date
01-Feb-2006
Completion Date
01-Feb-2006

Buy Documents

Standard

SIST EN 300 132-3 V1.2.1:2006

English language (18 pages)
Preview
Preview
e-Library read for
×1 day

SIST EN 300 132-3 V1.2.1:2006 is the Slovenian adoption of ETSI EN 300 132-3 Version 1.2.1 for the power supply interface at the input to telecommunications equipment. It specifies interface A3 for equipment operated from rectified current, alternating current, or direct current sources up to 400 V, so power systems, telecommunications equipment, and datacom equipment can be matched on the same supply.

What does SIST EN 300 132-3 V1.2.1:2006 specify?

SIST EN 300 132-3 V1.2.1:2006 sets requirements for the output of the power supply equipment at interface A3 and for the input of the telecommunications equipment connected to that interface. It is organized into scope, references, definitions and abbreviations, interface A3, requirements, earthing and bonding, electrical safety requirements, EMC requirements, and informative annexes.

AnnexWhat it covers
APower supply considerations and voltage waveforms
BIdentification of interface A3
CCalculation of extreme voltage nominal values at interface A3
DCalculation of extreme voltage nominal values when other nominal voltages are used
EBibliography

The scope covers telecommunications centres and customer premises where interface A3 is shared by telecommunications equipment and datacom equipment. The document is written to support interoperability, standardization of supply systems, and easier installation, operation, and maintenance across equipment from different origins.

What are the key requirements of SIST EN 300 132-3 V1.2.1:2006?

Clause 4 defines interface A3 as the physical point between the power supply system and the equipment. In practice, this is the point where the supply conditions must be met, even if the exact location is agreed differently during installation.

Voltage and frequency

Clause 5.1 sets the nominal voltage for equipment connected to interface A3 at 230 Vrms. Clause 5.2 defines the normal service voltage range, with a maximum peak voltage of 375 V and a minimum rms voltage of 188 V. Clause 5.3 sets the nominal frequency at 50 Hz for direct ac supply and identifies ripple frequencies of 300 Hz for rectified three-phase supply and 100 Hz for rectified single-phase supply.

Behavior outside normal service

Clause 5.4 requires equipment to survive steady-state abnormal voltages below the normal service range without damage, and to resume normal operation when supply returns to normal. For dips, short interruptions and transients, the document points to the relevant EMC standards and requires the power supply to keep any interruption at interface A3 shorter than 20 ms.

Protection, current and inrush

Clause 5.5 requires supply protection by fuses or circuit breakers for ac, rectified ac, or dc operation, and says the inrush energy must be considered in the supply design. Clause 5.6 limits the current drain at voltages in the normal and abnormal ranges to no more than 1.5 times the current at nominal voltage for periods longer than 1 second. Clause 5.7 then controls surge current on connection: the inrush current ratio is limited, and the measurement uses a defined test circuit with a Line Impedance Stabilization Network (LISN).

Earthing, safety and EMC

Clause 6 states that earthing and bonding follow IEC 60364-4-44 and IEC 60364-5-54. It also allows the battery to be earthed or floating, with additional protection needed for floating operation, and requires the neutral N to be earthed at the source. Clauses 7 and 8 state that safety and EMC are covered by the relevant safety and EMC standards.

What terms does SIST EN 300 132-3 V1.2.1:2006 define?

  • interface A3 - The physical point where the power supply connects to telecommunications and datacom equipment.
  • normal service voltage range - The steady-state voltage range in which equipment must maintain normal service.
  • abnormal voltage range - A steady-state voltage range outside normal service where the equipment is expected to survive undamaged.
  • load unit - Power-consuming equipment that is part of a system block.
  • system block - A functional group of equipment that depends on the same power supply for operation and performance.
  • Uninterrupted Power Supply (UPS) - A backup power source used when ac input fails.
  • Line Impedance Stabilization Network (LISN) - The network used in the surge-current measurement circuit.

Who uses SIST EN 300 132-3 V1.2.1:2006?

This standard is used by designers of telecommunications power supplies, telecommunications equipment, and datacom equipment. It is also used by installers, integrators, test laboratories, quality managers, and buyers who need the supply interface, voltage range, protection, and inrush behavior to be compatible across mixed equipment in telecommunications centres and customer premises.

Which standards are used with SIST EN 300 132-3 V1.2.1:2006?

  • IEC 60364-4-44 - Provides the protection against voltage disturbances and electromagnetic disturbances referenced for earthing and bonding context.
  • IEC 60364-5-54 - Provides rules for earthing arrangements, protective conductors, and protective bonding conductors.
  • CENELEC HD 472 S1 - Provides the nominal voltage basis for low-voltage public electricity supply systems.
  • CISPR 16-1 - Provides the measuring apparatus and methods referenced for the surge-current test circuit.
  • ETSI EN 300 132-1 - Companion part for equipment operated by alternating current derived from direct current sources.
  • ETSI EN 300 132-2 - Companion part for equipment operated by direct current.

What does the SIST EN 300 132-3 V1.2.1:2006 document contain?

The document gives the interface A3 definition, the nominal voltage and frequency conditions, the normal and abnormal service voltage ranges, and the current and inrush limits. It also includes the measurement approach for surge current, with a defined test circuit and worst-case phase-angle evaluation. Annex A explains possible power supply configurations and waveform types, Annex B shows how interface A3 is identified, and Annexes C and D explain how the voltage limits are derived.

Buy Documents

Standard

SIST EN 300 132-3 V1.2.1:2006

English language (18 pages)
Preview
Preview
e-Library read for
×1 day

Get Certified

Connect with accredited certification bodies for this standard

ANCE

Mexican certification and testing association.

EMA Mexico Verified

IMP NDT d.o.o.

Non-destructive testing services. Radiography, ultrasonic, magnetic particle, penetrant, visual inspection.

SA Slovenia Verified

Inštitut za kovinske materiale in tehnologije

Institute of Metals and Technology. Materials testing, metallurgical analysis, NDT.

SA Slovenia Verified

Sponsored listings

Frequently Asked Questions

SIST EN 300 132-3 V1.2.1:2006 is a standard published by the Slovenian Institute for Standardization (SIST). Its full title is "Environmental Engineering (EE); Power supply interface at the input to telecommunications equipment; Part 3: Operated by rectified current source, alternating current source or direct current source up to 400 V". This standard covers: The present document contains requirements for: • the output performance of the power equipment at the interface A3; • the input of the telecommunications equipment connected to interface A3. The voltage at interface A3 may be the ac mains, a rectified voltage derived from ac three phase mains, a rectified voltage derived from ac single phase mains or a low voltage derived from a battery. The power supply equipment may incorporate a backup battery. The present document aims at providing compatibility between the power supply equipment and both the telecommunications equipment, and the different load units connected to the same interface A3 (e.g. datacom equipment). The requirements at interface A3 apply to: • the output of the power supply equipment or power supply installation of telecommunications centres; • the power supply input of telecommunications equipment and the datacom equipment installed at telecommunications centres; • telecommunications equipment and the datacom equipment, installed in customer's premises, whose power interface A3 is also used by equipment requiring a supply to the present document. The purpose of the present document is: • to identify a power supply system with the same characteristics for all telecommunications and data communication equipment defined in the area of application; • to facilitate interworking of different (types of) loads units; • to facilitate the standardization of power supply systems for telecommunications and datacom equipment; • to facilitate the installation, operation and maintenance in the same network of equipment and telecommunications and datacom systems from different origins.

The present document contains requirements for: • the output performance of the power equipment at the interface A3; • the input of the telecommunications equipment connected to interface A3. The voltage at interface A3 may be the ac mains, a rectified voltage derived from ac three phase mains, a rectified voltage derived from ac single phase mains or a low voltage derived from a battery. The power supply equipment may incorporate a backup battery. The present document aims at providing compatibility between the power supply equipment and both the telecommunications equipment, and the different load units connected to the same interface A3 (e.g. datacom equipment). The requirements at interface A3 apply to: • the output of the power supply equipment or power supply installation of telecommunications centres; • the power supply input of telecommunications equipment and the datacom equipment installed at telecommunications centres; • telecommunications equipment and the datacom equipment, installed in customer's premises, whose power interface A3 is also used by equipment requiring a supply to the present document. The purpose of the present document is: • to identify a power supply system with the same characteristics for all telecommunications and data communication equipment defined in the area of application; • to facilitate interworking of different (types of) loads units; • to facilitate the standardization of power supply systems for telecommunications and datacom equipment; • to facilitate the installation, operation and maintenance in the same network of equipment and telecommunications and datacom systems from different origins.

SIST EN 300 132-3 V1.2.1:2006 is classified under the following ICS (International Classification for Standards) categories: 19.040 - Environmental testing; 33.050.01 - Telecommunication terminal equipment in general. The ICS classification helps identify the subject area and facilitates finding related standards.

SIST EN 300 132-3 V1.2.1:2006 is available in PDF format for immediate download after purchase. The document can be added to your cart and obtained through the secure checkout process. Digital delivery ensures instant access to the complete standard document.

Standards Content (Sample)

Contents

  • 1 Scope
  • 2 References
  • 6 ETSI EN 300 132-3 V1.2.1 (2003-08)
  • 3 Definitions and abbreviations
  • 3.1 Definitions
  • 3.2 Abbreviations
  • 7 ETSI EN 300 132-3 V1.2.1 (2003-08)
  • 5 Requirements
  • 5.1 Nominal voltage
  • 8 ETSI EN 300 132-3 V1.2.1 (2003-08)
  • 5.3 Nominal frequencies
  • 9 ETSI EN 300 132-3 V1.2.1 (2003-08)
  • 5.5 Supply protection
  • 5.6 Maximum current drain
  • 10 ETSI EN 300 132-3 V1.2.1 (2003-08)
  • 11 ETSI EN 300 132-3 V1.2.1 (2003-08)
  • 6 Earthing and bonding
  • 7 Electrical safety requirements
  • 8 EMC requirements
  • 12 ETSI EN 300 132-3 V1.2.1 (2003-08)
  • 13 ETSI EN 300 132-3 V1.2.1 (2003-08)
  • 14 ETSI EN 300 132-3 V1.2.1 (2003-08)
  • 15 ETSI EN 300 132-3 V1.2.1 (2003-08)
  • 16 ETSI EN 300 132-3 V1.2.1 (2003-08)
  • 17 ETSI EN 300 132-3 V1.2.1 (2003-08)
  • Bibliography
  • 18 ETSI EN 300 132-3 V1.2.1 (2003-08)

1 Scope

The present document contains requirements for:

  • the output performance of the power equipment at the interface A3;
  • the input of the telecommunications equipment connected to interface A3. The voltage at interface A3 may be the ac mains, a rectified voltage derived from ac three phase mains, a rectified voltage derived from ac single phase mains or a low voltage derived from a battery. The power supply equipment may incorporate a backup battery.

The present document aims at providing compatibility between the power supply equipment and both the telecommunications equipment, and the different load units connected to the same interface A3 (e.g. datacom equipment). The requirements at interface A3 apply to:

  • the output of the power supply equipment or power supply installation of telecommunications centres;
  • the power supply input of telecommunications equipment and the datacom equipment installed at telecommunications centres;
  • telecommunications equipment and the datacom equipment, installed in customer's premises, whose power interface A3 is also used by equipment requiring a supply to the present document. The purpose of the present document is:
  • to identify a power supply system with the same characteristics for all telecommunications and data communication equipment defined in the area of application;
  • to facilitate interworking of different (types of) loads units;
  • to facilitate the standardization of power supply systems for telecommunications and datacom equipment;
  • to facilitate the installation, operation and maintenance in the same network of equipment and telecommunications and datacom systems from different origins.

2 References

The following documents contain provisions which, through reference in this text, constitute provisions of the present document.

  • References are either specific (identified by date of publication and/or edition number or version number) or non-specific.
  • For a specific reference, subsequent revisions do not apply.
  • For a non-specific reference, the latest version applies.

Referenced documents which are not found to be publicly available in the expected location might be found at http://docbox.etsi.org/Reference.

[1] IEC 60364-4-44: "Electrical installations of buildings - Part 4-44: Protection for safety - Protection against voltage disturbances and electromagnetic disturbances". [2] IEC 60364-5-54: "Electrical installations of buildings - Part 5-54: Selection and erection of electrical equipment - Earthing arrangements, protective conductors and protective bonding conductors".

[3] CENELEC HD 472 S1: "Nominal voltage for low-voltage public electricity supply systems". ETSI

SIST EN 300 132-3 V1.2.1:2006

6 ETSI EN 300 132-3 V1.2.1 (2003-08)

[4] CISPR 16-1: "Specification for radio disturbance and immunity measuring apparatus and methods Part 1: Radio disturbance and immunity measuring apparatus".

3 Definitions and abbreviations

3.1 Definitions

For the purposes of the present document, the following terms and definitions apply:

abnormal voltage range: range of steady-state voltages over which the equipment will not be expected to maintain normal service but will survive undamaged customer premises: any location which is the sole responsibility of the customer datacom equipment: information technology equipment interface A3: interface, physical point, at which power supply is connected to the telecommunications and datacom equipment load unit: power consuming equipment, that is part of a system block nominal load conditions: set of values dedicated to a test performance nominal voltage value: nominal value of the voltage that designates the type of supply normal service: service mode where telecommunications equipment operates within its specification normal service voltage range: range of the steady-state voltage over which the equipment will maintain normal service power supply: power supply to which telecommunications equipment is intended to be connected system block: functional group of equipment depending for its operation and performance on its connection to the same power supply telecommunication centre: any location where telecommunications equipment is installed and is the sole responsibility of the operator

3.2 Abbreviations

For the purposes of the present document, the following abbreviations apply:

ac alternating current (also when used as a suffix to units of measurement) AMN Artificial Mains Network dc direct current (also when used as a suffix to units of measurement) EUT Equipment Under Test EMC Electric Magnetic Compatibility Im maximum current It Instantaneous surge current LISN Line Impedance Stabilization Network PE Protective Earth R Resistance of resistive element of LISN rms root mean square (also when used as a suffix to units of measurement) UPS Uninterrupted Power Supply ETSI

SIST EN 300 132-3 V1.2.1:2006

7 ETSI EN 300 132-3 V1.2.1 (2003-08)

4 Interface A3 The power supply interface, interface A3 of figure 1, is a physical point to which all the requirements are related. This point is situated between the power supply system(s) and the power consuming telecommunications equipment. NOTE 1: Interface A3 is located at the power terminals of the telecommunications equipment. Subject to the installation preconditions, this point may be located at any other point between the power supply system and the telecommunications equipment by mutual agreement of the relevant parties. NOTE 2: In the case where the same type of equipment is used for mains 230 V ac and dc for the following document, normal fuses (e.g. 5x20) may be unsuitable for dc (> 200 V). If the appropriate fusing is located outside of the equipment the internal fuse should be bridged. It is intended to use a different plug or appliance inlet to the equipment for power supply to the following document that is safe for disconnecting under load conditions. In addition the equipment shall be labelled.

L(-)

telecommunication s N(+) and datacom Power supply equipment PE system block

L (-) = phase or negative pole.

N (+) = ac neutral or dc return conductor (see clause 6).

PE = Protective earth.

Figure 1: General identification of the interface A3

5 Requirements

The requirement of the alternating voltage for the public mains is defined in HD 472 S1 [3].

5.1 Nominal voltage

The telecommunication equipment connected to interface A3 shall be designed to operate with the following nominal voltage:

  • 230 Vrms.

See clause A.1 for discussion on possible power supply.

ETSI

SIST EN 300 132-3 V1.2.1:2006

8 ETSI EN 300 132-3 V1.2.1 (2003-08)

5.2 Normal service voltages at interface A3 The normal service voltage range is as follows:

  • maximum peak voltage: 375 V;
  • minimum rms voltage: 188 V.

...