Railway applications - Fixed installations - Traction transformers

Covers specific characteristics of traction transformers as defined in 1.3.1, used in traction substation or along the track for the supply of power to a.c. and d.c. traction systems or to provide power to auxiliary services. Traction transformers are either: single-phase traction transformers; - single-, three or poly-phase rectifier-transformers or converter/inverter-transformers for d.c. or a.c. contact line; single phase auto-transformers for traction power supply; single- or three phase auxiliary transformers at traction supply voltage.

Bahnanwendungen - Ortsfeste Anlagen - Bahn-Transformatoren

Applications ferroviaires - Installations fixes - Transformateurs de traction

Železniške naprave - Stabilne naprave električne vleke - Transformatorji vlečnih tokokrogov

Zajema določene značilnosti transformatorjev vlečnih tokokrogov, kot je določeno v točki 1.3.1, ki se uporabljajo v postajah vlečnih tokokrogov ali vzporedno s progo za dobavljanje elektrike za sisteme vlečnih tokokrogov enosmerne ali izmenične napetosti ali za zagotavljanje elektrike do pomožnih storitev. Transformatorji vlečnih tokokrogov so: enofazni transformatorji vlečnih tokokrogov; - eno-, tri ali polifazni usmerjevalni-transformatorji ali pretvorni/frekvenčno-menjalni transformatorji za vozni vod z enosmerno ali izmenično napetostjo; enofazni avto-transformatorji za dobavo elektrike vlečnim tokokrogom; eno- ali trifazni pomožni transformatorji pri dobavni napetosti vlečnih tokokrogov.

General Information

Status
Published
Public Enquiry End Date
30-Nov-2008
Publication Date
05-Oct-2010
Current Stage
6060 - National Implementation/Publication (Adopted Project)
Start Date
23-Sep-2010
Due Date
28-Nov-2010
Completion Date
06-Oct-2010

Relations

Buy Standard

Amendment
EN 50329:2003/prAA:2008
English language
10 pages
sale 10% off
Preview
sale 10% off
Preview
e-Library read for
1 day
Amendment
EN 50329:2003/A1:2010
English language
11 pages
sale 10% off
Preview
sale 10% off
Preview
e-Library read for
1 day

Standards Content (Sample)

SLOVENSKI STANDARD
oSIST EN 50329:2003/prAA:2008
01-september-2008
äHOH]QLãNHQDSUDYH6WDELOQHQDSUDYHHOHNWULþQHYOHNH7UDQVIRUPDWRUMLYOHþQLK
WRNRNURJRY
Railway applications - Fixed installations - Traction transformers
Bahnanwendungen - Ortsfeste Anlagen - Bahn-Transformatoren
Applications ferroviaires - Installations fixes - Transformateurs de traction
Ta slovenski standard je istoveten z: EN 50329:2003/prAA:2008
ICS:
29.180 Transformatorji. Dušilke Transformers. Reactors
29.280 (OHNWULþQDYOHþQDRSUHPD Electric traction equipment
oSIST EN 50329:2003/prAA:2008 en
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.

---------------------- Page: 1 ----------------------

oSIST EN 50329:2003/prAA:2008

---------------------- Page: 2 ----------------------

oSIST EN 50329:2003/prAA:2008
 DRAFT
EUROPEAN STANDARD
EN 50329
prAA
NORME EUROPÉENNE
June 2008
EUROPÄISCHE NORM

ICS 29.180; 29.280


English version


Railway applications -
Fixed installations -
Traction transformers



Applications ferroviaires -  Bahnanwendungen -
Installations fixes - Ortsfeste Anlagen -
Transformateurs de traction Bahn-Transformatoren



This draft amendment prAA, if approved, will modify the European Standard EN 50329:2003; it is submitted to
CENELEC members for CENELEC enquiry.
Deadline for CENELEC: 2008-11-21.

It has been drawn up by CLC/SC 9XC.

If this draft becomes an amendment, CENELEC members are bound to comply with the CEN/CENELEC Internal
Regulations which stipulate the conditions for giving this amendment the status of a national standard without
any alteration.

This draft amendment was established by CENELEC in three official versions (English, French, German). A
version in any other language made by translation under the responsibility of a CENELEC member into its own
language and notified to the Central Secretariat has the same status as the official versions.

CENELEC members are the national electrotechnical committees of Austria, Belgium, Bulgaria, Cyprus, the
Czech Republic, Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia,
Lithuania, Luxembourg, Malta, the Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain,
Sweden, Switzerland and the United Kingdom.

Warning : This document is not a European Standard. It is distributed for review and comments. It is subject to
change without notice and shall not be referred to as a European Standard.


CENELEC
European Committee for Electrotechnical Standardization
Comité Européen de Normalisation Electrotechnique
Europäisches Komitee für Elektrotechnische Normung

Central Secretariat: rue de Stassart 35, B - 1050 Brussels


© 2008 CENELEC - All rights of exploitation in any form and by any means reserved worldwide for CENELEC members.
Project: 20527 Ref. No. EN 50329:2003/prAA:2008 E

Draft for Enquiry

---------------------- Page: 3 ----------------------

oSIST EN 50329:2003/prAA:2008
EN 50329:2003/prAA:2008 – 2 –
1 Foreword
2 This draft amendment to the European Standard EN 50329:2003 was prepared by SC 9XC, Electric
3 supply and earthing systems for public transport equipment and ancillary apparatus (Fixed
4 installations), of Technical Committee CENELEC TC 9X, Electrical and electronic applications for
5 railways. It is submitted to the CENELEC enquiry.
6 __________
Draft for Enquiry

---------------------- Page: 4 ----------------------

oSIST EN 50329:2003/prAA:2008
– 3 – EN 50329:2003/prAA:2008
7 Text of prAA to EN 50329:2003
8 1 General
9 1.2 Normative references
10 Delete the following normative references:
HD 464 S1 1988 Dry-type power transformers (IEC 60726:1982 + A1:1986, mod.)
+ A2 1991
1992
+ A3
+ A4 1995
IEC 60354 1991 Loading guide for oil-immersed power transformers
11 Add the following normative references:
EN 60076-11 2004 Power transformers – Part 11: Dry-type transformers (IEC 60076-11:2004)
IEC 60076-7 2005 Power transformers – Part 7: Loading guide for oil-immersed power
transformers
12 2 General requirements for a traction transformer
13 Replace Subclause 2.2 by the following:
14 2.2 Checking of the capability of the transformer to sustain the stipulated load cycle
15 2.2.1 General
16 The temperature rise test shall be carried out in accordance with either EN 60076-2 or EN 60076-11
17 as applicable.
18 The current basis for determining the temperature rises shall be the rated service current (the
19 approximate relationship between the rated current and the rated service current is given in
20 Table C.3).
21 The resulting temperature rises after long-time overloads shall be within the limits of the temperature
22 rises prescribed in EN 60076-2 and EN 60076-11 under the stipulated ambient conditions and altitude.
23 The winding temperature rise after short-time overload conditions may exceed by 15 K the applicable
24 temperature rise limits according to EN 60076-2 and EN 60076-11.
25 When determining the temperature rises the effect of the harmonics should be considered as follows.
26 2.2.2 Temperature rise measurement for liquid immersed transformers
27 The procedure of 5.2.2 of EN 60076-2 is applicable with the exceptions mentioned here below. The
28 specified duty class or load cycle shall be taken into account. For transformers designed according to
29 a duty class the test cycles given in Figure A.1 to Figure A.3 apply.
30 The transformer in short circuit conditions shall be injected with a current causing the total losses. In
31 case of a traction converter transformer, the total losses are intended as the sum of the no-load loss
32 and of the total load losses determined according to Annex C.
Draft for Enquiry

---------------------- Page: 5 ----------------------

oSIST EN 50329:2003/prAA:2008
EN 50329:2003/prAA:2008 – 4 –
33 Total losses calculated on the service current in basic load condition (I ) are injected as long to reach
BG
34 temperature steady-state conditions and then the long-term overload current is injected, for the
35 specified duration of said overload according to the duty class or load cycle. The final top oil
36 temperature rise shall be recorded.
37 For determining the temperature rises of windings, the transformer shall be subsequently loaded by
38 service currents representing the basic load (including the effect of harmonics), for the time necessary
39 to reach steady temperatures of the windings, and, for the respective durations, the service currents
40 corresponding to long-time overloads, and, when practicable and agreed between purchaser and
41 supplier, service currents corresponding to short-time overloads.
42 Measurements shall be taken at the end of the long-time overload duration and, when applicable, at
43 the end of the short-time overload duration. When actual measurements are found impossible, it is
44 allowed to agree to carry out calculations on temperature variations along the short-time load duration,
45 performed according to conventional methods.
46 IEC 60076-7 gives some guidance for such a calculation.
47 2.2.3 Temperature rise measurement for dry-type transformers
48 The requirements given in Clause 23 of EN 60076-11 apply taking into account that in the second part
49 of the test the losses attributable to the various stages of the current demand shall be calculated and
50 successively applied and the overloads for the respective duration. Annex C allows to determine total
51 load losses.
52 Measurements shall be taken at the end of the long-time overload duration and, when applicable, at
53 the end of the short-time overload duration. For transformers designed according to a duty class, the
54 test cycles given in Figure A.1 to Figure A.3 apply.
55 When actual measurements are not possible, it may be agreed to carry out calculations on
56 temperature variations along the short-time load duration, performed according to conventional
57 methods.
58 IEC 60905 gives some guidance for such a calculation.
59 2.2.4 Alternative criteria for determining temperature rise limits
60 On agreement between purchaser and manufacturer temperature limits and thermal ageing according
61 to IEC 60076-7 and IEC 60905 may be applied.
62 If the purchaser is able to define the load cycle in an extensive way as current demand, the capability
63 of the transformer to sustain this current demand shall be checked as follows:
64 – temperature rise and loss measurements shall be performed at sinusoidal load with rated service
65 current;
66 – based on these measurements, the top-oil temperature, the hot-spot temperatures of the
67 windings and the relative loss of life for the given current demand shall be calculated. The loss of
68 life calculation procedure of IEC 60076-7 can be used;
69 – the temperatures at the beginning of the load-cycle shall be set equal to those at the end of the
70 load cycle to consider a steady state condition; the maximum service temperature shall be taken
71 into account;
72 – the calculated relative loss of life for the load cycle shall be lower than 1;
73 – for oil immersed transformers, the maximum occasional hot-spot- temperature shall be lower than
74 140 °C and the maximum top oil temperature shall be lower than 115 °C during the load cycle;
75 – the influence of harmonics shall be considered as described in Annex C.
Draft for Enquiry

---------------------- Page: 6 ----------------------

oSIST EN 50329:2003/prAA:2008
– 5 – EN 50329:2003/prAA:2008
76 For transformers designed according to a duty class, the text given in Figure A.1 to Figure A.3 applies.
77 Different temperature limits may be agreed between purchaser and supplier depending on the oil
78 characteristics.
79 2.8 Rating plate
80 Replace the reference to HD 464 by a reference to EN 60076-11.
81 4 Traction converter transformers
82 Replace Clause 4 by the following:
83 4 Traction converter transformers
84 4.1 General
85 The EN 61378 series specifies requirements for converter transformers for industrial use. This clause
86 specifies additional requirements for traction rectifier transformers of most common use in substations
87 with semiconductor diode rectifiers. Traction converter transformers for controlled converters need
88 additional considerations and are subject to special agreement between purchaser and supplier.
89 Transformers for 6-pulse three-phase bridge connections have one primary and one secondary
90 winding.
91 Transformers for 12-pulse rectifier connections have one or two primary windings and two secondary
92 windings with a 30° phase shift between the secondary windings. One secondary winding is commonly
93 star connected and the other is delta connected. Three types of rectifier transformers are preferably
94 used for 12-pulse traction rectifier groups:
95 a) three-windings transformer with one primary winding and two closely coupled secondary windings:
96 coupling factor K ≥ 0,9;
97 b) three-windings transformer with one primary winding and two loosely coupled secondary windings:
98 coupling factor 0,2 ≤ K < 0,9;
99 c) four-windings transformer with two primary windings and two uncoupled secondary windings:
100 coupling factor K < 0,2.
101 Three-windings transformers with closely coupled secondary windings are the preferred type for
102 12-pulse series connections and they are also used for 12-pulse parallel connections. The 12-pulse
103 parallel connection needs an interphase transformer between the two rectifier bridges.
104 NOTE 1 At low secondary voltages as for example for series connected rectifier groups for nominal voltage 750 V d.c. it is
105 practically impossible to reach a coupling factor K ≥ 0,9 due to the inductance of busbars.
106 Three-windings transformers with loosely coupled secondary windings are used for 12-pulse parallel
107 connections with interphase transformer where certain requirements regarding vo
...

SLOVENSKI STANDARD
SIST EN 50329:2003/A1:2010
01-november-2010
äHOH]QLãNHQDSUDYH6WDELOQHQDSUDYHHOHNWULþQHYOHNH7UDQVIRUPDWRUMLYOHþQLK
WRNRNURJRY
Railway applications - Fixed installations - Traction transformers
Bahnanwendungen - Ortsfeste Anlagen - Bahn-Transformatoren
Applications ferroviaires - Installations fixes - Transformateurs de traction
Ta slovenski standard je istoveten z: EN 50329:2003/A1:2010
ICS:
29.180 Transformatorji. Dušilke Transformers. Reactors
29.280 (OHNWULþQDYOHþQDRSUHPD Electric traction equipment
SIST EN 50329:2003/A1:2010 en,fr,de
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.

---------------------- Page: 1 ----------------------

SIST EN 50329:2003/A1:2010

---------------------- Page: 2 ----------------------

SIST EN 50329:2003/A1:2010

EUROPEAN STANDARD
EN 50329:2003/A1

NORME EUROPÉENNE
May 2010
EUROPÄISCHE NORM

ICS 29.180; 29.280


English version


Railway applications -
Fixed installations -
Traction transformers



Applications ferroviaires -  Bahnanwendungen -
Installations fixes - Ortsfeste Anlagen -
Transformateurs de traction Bahn-Transformatoren





This amendment A1 modifies the European Standard EN 50329:2003; it was approved by CENELEC on
2010-05-01. CENELEC members are bound to comply with the CEN/CENELEC Internal Regulations which
stipulate the conditions for giving this amendment the status of a national standard without any alteration.

Up-to-date lists and bibliographical references concerning such national standards may be obtained on
application to the Central Secretariat or to any CENELEC member.

This amendment exists in three official versions (English, French, German). A version in any other language
made by translation under the responsibility of a CENELEC member into its own language and notified to the
Central Secretariat has the same status as the official versions.

CENELEC members are the national electrotechnical committees of Austria, Belgium, Bulgaria, Croatia, Cyprus,
the Czech Republic, Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy,
Latvia, Lithuania, Luxembourg, Malta, the Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia,
Spain, Sweden, Switzerland and the United Kingdom.

CENELEC
European Committee for Electrotechnical Standardization
Comité Européen de Normalisation Electrotechnique
Europäisches Komitee für Elektrotechnische Normung

Management Centre: Avenue Marnix 17, B - 1000 Brussels


© 2010 CENELEC - All rights of exploitation in any form and by any means reserved worldwide for CENELEC members.
Ref. No. EN 50329:2003/A1:2010 E

---------------------- Page: 3 ----------------------

SIST EN 50329:2003/A1:2010
EN 50329:2003/A1:2010 – 2 –
Foreword
This amendment to the European Standard EN 50329:2003 was prepared by SC 9XC, Electric supply
and earthing systems for public transport equipment and ancillary apparatus (Fixed installations), of
Technical Committee CENELEC TC 9X, Electrical and electronic applications for railways. It was
submitted to the formal vote and was approved by CENELEC as A1 to EN 50329:2003 on 2010-05-01.
Attention is drawn to the possibility that some of the elements of this document may be the subject of
patent rights. CEN and CENELEC shall not be held responsible for identifying any or all such patent
rights.
The following dates were fixed:
– latest date by which the amendment has to be implemented

at national level by publication of an identical

national standard or by endorsement
(dop) 2011-05-01

– latest date by which the national standards conflicting

with the amendment have to be withdrawn
(dow) 2013-05-01
__________

---------------------- Page: 4 ----------------------

SIST EN 50329:2003/A1:2010
– 3 – EN 50329:2003/A1:2010
1 General
1.2 Normative references
Delete the following normative references:
HD 464 S1 1988 Dry-type power transformers (IEC 60726:1982 + A1:1986, mod.)
+ A2 1991
+ A3 1992
+ A4 1995
IEC 60354 1991 Loading guide for oil-immersed power transformers
Add the following normative references:
EN 60076-11 2004 Power transformers – Part 11: Dry-type transformers (IEC 60076-11:2004)
IEC 60076-7 2005 Power transformers – Part 7: Loading guide for oil-immersed power
transformers
2 General requirements for a traction transformer
Replace Subclause 2.2 by the following:
2.2 Checking of the capability of the transformer to sustain the stipulated load cycle
2.2.1 General
The temperature rise test shall be carried out in accordance with either EN 60076-2 or EN 60076-11 as
applicable.
Basis for determining the temperature rises shall be the rated service current (the approximate
relationship between the rated current and the rated service current is given in Table C.3).
The resulting temperature rises after long-time overloads shall be within the limits of the temperature rises
prescribed in EN 60076-2 and EN 60076-11 under the stipulated ambient conditions and altitude.
The winding temperature rise after short-time overload conditions may exceed by 15 K the applicable
temperature rise limits according to EN 60076-2 and EN 60076-11.
When determining the temperature rises the effect of the harmonics should be considered according to
2.2.2, 2.2.3 and 2.2.4.
2.2.2 Temperature rise measurement for liquid immersed transformers
The procedure of 5.2.2 of EN 60076-2 shall be applied with the exceptions mentioned here below. The
specified duty class or load cycle shall be taken into account. For transformers designed according to a
duty class the test cycles given in Figure A.1 to Figure A.3 shall apply.
The transformer in short circuit conditions shall be injected with a current causing the total losses. In case
of a traction converter transformer, the total losses are intended as the sum of the no-load loss and of the
total load losses determined according to Annex C.
Total losses calculated on the service current in basic load condition (I ) are injected until it reaches
BG
temperature steady-state conditions and then the long-term overload current is injected, for the specified
duration of said overload according to the duty class or load cycle. The final top oil temperature rise shall
be recorded.

---------------------- Page: 5 ----------------------

SIST EN 50329:2003/A1:2010
EN 50329:2003/A1:2010 – 4 –
For determining the temperature rises of windings, the transformer shall be subsequently loaded by
service currents representing the basic load (including the effect of harmonics), for the time necessary to
reach steady temperatures of the windings, and, for the respective durations, the service currents
corresponding to long-time overloads, and, when practicable and agreed between purchaser and
supplier, service currents corresponding to short-time overloads.
Measurements shall be taken at the end of the long-time overload duration and, when applicable, at the
end of the short-time overload duration. When actual measurements are not possible, it may be agreed to
carry out calculations on temperature variations along the short-time load duration, performed according
to conventional methods.
IEC 60076-7 gives some guidance for such a calculation.
2.2.3 Temperature rise measurement for dry-type transformers
The requirements given in Clause 23 of EN 60076-11 apply taking into account that in the second part of
the test the losses attributable to the various stages of the current demand shall be calculated and
successively applied and the overloads for the respective duration. Annex C allows determining total load
losses.
Measurements shall be taken at the end of the long-time overload duration and, when applicable, at the
end of the short-time overload duration. For transformers designed according to a duty class, the test
cycles given in Figure A.1 to Figure A.3 apply.
When actual measurements are not possible, it may be agreed to carry out calculations on temperature
variations along the short-time load duration, performed according to conventional methods.
IEC 60905 gives some guidance for such a calculation.
2.2.4 Alternative criteria for determining temperature rise limits
On agreement between purchaser and manufacturer temperature limits and thermal ageing according to
IEC 60076-7 and IEC 60905 may be applied.
If the purchaser is able to define the load cycle in an extensive way as current demand, the capability of
the transformer to sustain this current demand shall be checked as follows:
– temperature rise and loss measurements shall be performed at sinusoidal load with rated service
current;
– based on these measurements, the top-oil temperature, the hot-spot temperatures of the windings
and the relative loss of life for the given current demand shall be calculated. The loss of life
calculation procedure of IEC 60076-7 may be used;
– the temperatures at the beginning of the load-cycle shall be set equal to those at the end of the load
cycle to consider a steady state condition; the maximum service temperature shall be taken into
account;
– the calculated relative loss of life for the load cycle shall be lower than 1;
– for oil immersed transformers, the maximum occasional hot-spot- temperature shall be lower than
140 °C and the maximum top oil temperature shall be lower than 115 °C during the load cycle;
– the influence of harmonics shall be considered as described in Annex C.
For transformers designed according to a duty class, the text given in Figure A.1 to Figure A.3 applies.
Different temperature limits may be agreed between purchaser and supplier depending on the oil
characteristics.

---------------------- Page: 6 ----------------------

SIST EN 50329:2003/A1:2010
– 5 – EN 50329:2003/A1:2010
2.8 Rating plate
Replace the reference to HD 464 by a reference to EN 60076-11.
4 Traction converter transformers
Replace Clause 4 by the following:
4 Traction converter transformers
4.1 General
The EN 61378 series specifies requirements for converter transformers for industrial use. This clause
specifies additional requirements for traction rectifier transformers of most common use in substations
with semiconductor diode rectifiers. Traction converter transformers for controlled converters need
additional considerations and shall be subject to special agreement between purchaser and supplier.
Transformers for 6-pulse three-phase bridge connections have one primary and one secondary winding.
Transformers for 12-pulse rectifier connections have one or two primary windings and two secondary
windings with a 30° phase shift between the secondary windings. One secondary winding is commonly
star connected and the other is delta connected. Three types of rectifier transformers are preferably used
for 12-pulse traction rectifier groups:
a) three-windings transformer with one primary winding and two closely coupled secondary windings:
coupling factor K ≥ 0,9;
b) three-windings transformer with one primary winding and two loosely coupled secondary windings:
coupling factor 0,2 ≤ K < 0,9;
c) four-windings transformer with two primary windings and two uncoupled secondary windings:
coupling factor K < 0,2.
Three-windings transformers with closely coupled secondary windings are the preferred type for 12-pulse
series connections and they are also used for 12-pulse parallel connections. The 12-pulse parallel
connection needs an interphase transformer between the two rectifier bridges.
NOTE 1 At low secondary voltages as for example for series connected rectifier groups for nominal voltage 750 V d.c. it is
practically impossible to reach a coupling factor K ≥ 0,9 due to the inductance of busbars.
Three-windings transformers with loosely coupled secondary windings are used for 12-pulse parallel
connections with interphase transformer whe
...