Fire resistance tests for service installations - Part 10: Smoke control dampers

This document specifies test methods for smoke control dampers to assess their performance under elevated temperature or fire conditions, as well as at ambient temperatures.
Smoke control damper tests are used to confirm that the furnace testing requirements of EN 12101-8 are met and EN 12101-8 is for consideration before carrying out these tests.
Smoke control dampers tested to this document are expected to be classified using EN 13501-4 and this document is expected to be considered before carrying out these tests.
NOTE   Some smoke control dampers to be tested might require testing following the information given in EN 1366-2 and this needs consideration before carrying out testing.
This document is expected to be read in conjunction with EN 12101-8, EN 13501-4, EN 1366-2 and EN 1363-1, the latter giving further details for fire resistance testing.
For installation details, the requirements for smoke extraction ducts are for consideration and these are defined in EN 1366-8 and EN 1366-9.

Feuerwiderstandsprüfungen für Installationen - Teil 10: Entrauchungsklappen

Dieses Dokument legt Prüfverfahren für Entrauchungsklappen zur Beurteilung ihrer Leistung bei erhöhten Temperaturen oder unter Brandbedingungen sowie unter Umgebungstemperaturen fest.
Prüfungen an Entrauchungsklappen werden durchgeführt, um zu beurteilen, ob die Brandschutzanforderungen nach EN 12101 8 erfüllt werden; EN 12101 8 ist vor der Durchführung dieser Prüfungen zu berücksichtigen.
Es wird davon ausgegangen, dass Entrauchungsklappen, die nach diesem Dokument geprüft wurden, nach EN 13501 4 klassifiziert werden. Dieses Dokument ist vor der Durchführung dieser Prüfungen zu berücksichtigen.
ANMERKUNG   Einige der zu prüfenden Entrauchungsklappen erfordern möglicherweise eine Prüfung nach den Angaben in EN 1366 2, was vor der Durchführung der Prüfung berücksichtigt werden muss.
Dieses Dokument muss im Zusammenhang mit EN 12101 8, EN 13501 4, EN 1366 2 und EN 1363 1 betrachtet werden, wobei die letztgenannte Norm weitere Einzelheiten zur Prüfung des Feuerwiderstands angibt.
Einzelheiten zum Einbau von Entrauchungsleitungen, die zu berücksichtigen sind, sind in EN 1366 8 und EN 1366 9 festgelegt.

Essais de résistance au feu des installations techniques - Partie 10 : Volets de désenfumage

Le présent document spécifie des méthodes d’essai pour évaluer la performance des volets de désenfumage dans des conditions de température élevée ou d’incendie, ainsi qu’à température ambiante.
Les essais relatifs aux volets de désenfumage sont utilisés pour confirmer que les exigences d’essai de résistance au feu de l’EN 12101-8 sont satisfaites ; dans ce cas, l’EN 12101-8 est à prendre en compte avant de réaliser ces essais.
Il est attendu que les volets de désenfumage soumis aux essais conformément au présent document soient classés conformément à l’EN 13501-4 et que ce document soit pris en compte avant de réaliser les essais.
NOTE   Certains volets de désenfumage à soumettre à essai peuvent exiger la réalisation des essais suivant les informations données dans l’EN 1366-2 et il est nécessaire de prendre cela en compte avant d’effectuer les essais.
Le présent document est destiné à être lu conjointement avec l’EN 12101-8, l’EN 13501-4, l’EN 1366-2 et l’EN 1363-1, cette dernière donnant des détails supplémentaires sur les essais de résistance au feu.
Pour les détails concernant l’installation, les exigences applicables aux conduits d’extraction de fumées sont à prendre en compte ; elles sont définies dans l’EN 1366-8 et l’EN 1366-9.

Preskusi požarne odpornosti servisnih inštalacij - 10. del: Dimne lopute

Ta dokument določa preskusne metode za dimne lopute za ocenjevanje njihovega delovanja pri povišanih temperaturah ali v požarnih razmerah.
Upoštevati je treba, da bo dimno loputo morda treba preskusiti v skladu s standardom EN 1366-2, kar je treba upoštevati pred izvedbo teh preskusov.
S preskusi dimnih loput se potrjuje, da so zahteve za preskušanje peči iz standarda EN 12101-8 izpolnjene, pred izvajanjem teh preskusov pa je treba upoštevati standard EN 12101-8.
Pričakuje se, da bodo dimne lopute, preskušene v skladu s tem dokumentom, razvrščene v skladu s standardom EN 13501-4 in da bo pred izvajanjem teh preskusov upoštevan ta dokument.
V ta namen se pričakuje, da se bo ta dokument bral skupaj s standardi EN 12101-8, EN 13501-4, EN 1366-2 in EN 1363-1, pri čemer zadnji podaja dodatne podrobnosti glede preskušanja požarne odpornosti.
Pri podrobnostih glede namestitve je treba upoštevati zahteve za kanale za odvod dima, ki so določene v standardih EN 1366-8 in EN 1366-9.

General Information

Status
Withdrawn
Public Enquiry End Date
14-Oct-2020
Publication Date
09-Oct-2022
Withdrawal Date
18-Sep-2024
Technical Committee
POZ - Požarna varnost
Current Stage
9900 - Withdrawal (Adopted Project)
Start Date
19-Sep-2024
Due Date
12-Oct-2024
Completion Date
19-Sep-2024

Relations

Effective Date
01-Nov-2022
Effective Date
01-Nov-2024
Effective Date
03-Aug-2022
Standard

SIST EN 1366-10:2022

English language
100 pages
Preview
Preview
e-Library read for
1 day

Frequently Asked Questions

SIST EN 1366-10:2022 is a standard published by the Slovenian Institute for Standardization (SIST). Its full title is "Fire resistance tests for service installations - Part 10: Smoke control dampers". This standard covers: This document specifies test methods for smoke control dampers to assess their performance under elevated temperature or fire conditions, as well as at ambient temperatures. Smoke control damper tests are used to confirm that the furnace testing requirements of EN 12101-8 are met and EN 12101-8 is for consideration before carrying out these tests. Smoke control dampers tested to this document are expected to be classified using EN 13501-4 and this document is expected to be considered before carrying out these tests. NOTE Some smoke control dampers to be tested might require testing following the information given in EN 1366-2 and this needs consideration before carrying out testing. This document is expected to be read in conjunction with EN 12101-8, EN 13501-4, EN 1366-2 and EN 1363-1, the latter giving further details for fire resistance testing. For installation details, the requirements for smoke extraction ducts are for consideration and these are defined in EN 1366-8 and EN 1366-9.

This document specifies test methods for smoke control dampers to assess their performance under elevated temperature or fire conditions, as well as at ambient temperatures. Smoke control damper tests are used to confirm that the furnace testing requirements of EN 12101-8 are met and EN 12101-8 is for consideration before carrying out these tests. Smoke control dampers tested to this document are expected to be classified using EN 13501-4 and this document is expected to be considered before carrying out these tests. NOTE Some smoke control dampers to be tested might require testing following the information given in EN 1366-2 and this needs consideration before carrying out testing. This document is expected to be read in conjunction with EN 12101-8, EN 13501-4, EN 1366-2 and EN 1363-1, the latter giving further details for fire resistance testing. For installation details, the requirements for smoke extraction ducts are for consideration and these are defined in EN 1366-8 and EN 1366-9.

SIST EN 1366-10:2022 is classified under the following ICS (International Classification for Standards) categories: 13.220.50 - Fire-resistance of building materials and elements; 91.060.40 - Chimneys, shafts, ducts; 91.140.30 - Ventilation and air-conditioning systems. The ICS classification helps identify the subject area and facilitates finding related standards.

SIST EN 1366-10:2022 has the following relationships with other standards: It is inter standard links to SIST EN 1366-10:2011+A1:2017, SIST EN 1366-10:2022+A1:2024, SIST EN 1366-10:2022/kFprA1:2024. Understanding these relationships helps ensure you are using the most current and applicable version of the standard.

SIST EN 1366-10:2022 is associated with the following European legislation: EU Directives/Regulations: 305/2011; Standardization Mandates: M/117. When a standard is cited in the Official Journal of the European Union, products manufactured in conformity with it benefit from a presumption of conformity with the essential requirements of the corresponding EU directive or regulation.

You can purchase SIST EN 1366-10:2022 directly from iTeh Standards. The document is available in PDF format and is delivered instantly after payment. Add the standard to your cart and complete the secure checkout process. iTeh Standards is an authorized distributor of SIST standards.

Standards Content (Sample)


SLOVENSKI STANDARD
01-november-2022
Nadomešča:
SIST EN 1366-10:2011+A1:2017
Preskusi požarne odpornosti servisnih inštalacij - 10. del: Dimne lopute
Fire resistance tests for service installations - Part 10: Smoke control dampers
Feuerwiderstandsprüfungen für Installationen - Teil 10: Entrauchungsklappen
Essais de résistance au feu des installations techniques - Partie 10 : Volets de
désenfumage
Ta slovenski standard je istoveten z: EN 1366-10:2022
ICS:
13.220.50 Požarna odpornost Fire-resistance of building
gradbenih materialov in materials and elements
elementov
91.060.40 Dimniki, jaški, kanali Chimneys, shafts, ducts
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.

EN 1366-10
EUROPEAN STANDARD
NORME EUROPÉENNE
September 2022
EUROPÄISCHE NORM
ICS 13.220.50; 91.140.30 Supersedes EN 1366-10:2011+A1:2017
English Version
Fire resistance tests for service installations - Part 10:
Smoke control dampers
Essais de résistance au feu des installations techniques Feuerwiderstandsprüfungen für Installationen - Teil
- Partie 10 : Volets de désenfumage 10: Entrauchungsklappen
This European Standard was approved by CEN on 24 July 2022.

CEN members are bound to comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this
European Standard the status of a national standard without any alteration. Up-to-date lists and bibliographical references
concerning such national standards may be obtained on application to the CEN-CENELEC Management Centre or to any CEN
member.
This European Standard exists in three official versions (English, French, German). A version in any other language made by
translation under the responsibility of a CEN member into its own language and notified to the CEN-CENELEC Management
Centre has the same status as the official versions.

CEN members are the national standards bodies of Austria, Belgium, Bulgaria, Croatia, Cyprus, Czech Republic, Denmark, Estonia,
Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway,
Poland, Portugal, Republic of North Macedonia, Romania, Serbia, Slovakia, Slovenia, Spain, Sweden, Switzerland, Türkiye and
United Kingdom.
EUROPEAN COMMITTEE FOR STANDARDIZATION
COMITÉ EUROPÉEN DE NORMALISATION

EUROPÄISCHES KOMITEE FÜR NORMUNG

CEN-CENELEC Management Centre: Rue de la Science 23, B-1040 Brussels
© 2022 CEN All rights of exploitation in any form and by any means reserved Ref. No. EN 1366-10:2022 E
worldwide for CEN national Members.

Contents Page
European foreword . 7
Introduction . 8
1 Scope . 9
2 Normative references . 9
3 Terms and definitions . 9
4 Test equipment . 12
4.1 General. 12
4.2 Test duct for surface mounted SCDs . 12
4.3 Connecting duct for compartment boundary mounted SCDs . 13
4.3.1 Compartmentation test . 13
4.3.2 Maintenance of opening test . 13
4.4 Cycling equipment . 13
4.5 Condensing unit . 13
4.6 Gas temperature measuring devices . 13
4.7 Exhaust fan system . 13
4.8 Perforated plate . 14
4.9 Volume and flow measurement for duct mounted SCDs . 14
4.10 Volume flow measurement for compartment boundary mounted SCDs . 14
4.10.1 Compartmentation test . 14
4.10.2 Maintenance of opening test . 14
4.11 Ambient leakage measurement equipment . 15
4.12 Pressure sensors for differential pressure control . 15
4.12.1 Duct mounted smoke control dampers . 15
4.12.2 Compartment boundary mounted smoke control dampers . 15
4.13 Welded connecting tube . 15
4.14 Extract fan connecting duct . 15
4.15 Extraction fan . 15
4.16 Thermocouples . 15
4.17 Oxygen measuring equipment . 15
4.18 Observation windows . 16
5 Test specimens . 16
5.1 Cross-section . 16
5.2 Design . 16
5.2.1 General. 16
5.2.2 Supporting constructions . 16
5.2.3 Inclusion of grilles . 17
6 Test methods . 17
6.1 General. 17
6.2 Test sequence . 17
6.3 Ambient leakage . 19
6.3.1 Units of the largest size . 19
6.3.2 Units of smallest size . 19
6.4 Cycling requirements . 19
6.4.1 General. 19
6.4.2 Smoke control damper to be used in dedicated smoke control systems, operated only
in the case of emergency . 19
6.4.3 Smoke control damper to be used as part of a general HVAC system as well as a smoke
control system, or as part of a smoke control systems that is cycled every day to check
operation . 19
6.4.4 Smoke control damper to be used as part of a general HVAC system as well as a smoke
control system, that uses a modulating actuator . 20
6.5 Selection of elevated temperature and fire resistance tests . 20
6.6 Fire resistance tests and elevated temperature tests . 21
6.6.1 Duct mounted smoke control dampers . 21
6.6.2 Compartment boundary mounted smoke control dampers . 22
6.6.3 Additional test information . 25
6.7 Initiation regime . 26
6.7.1 Smoke control dampers for systems with automatic activation (AA) . 26
6.7.2 Smoke control damper for systems with manual activation (MA) . 27
6.8 HOT400/30 extension test . 29
6.9 Special constructions . 29
7 Test procedure . 29
7.1 Fire resistance or elevated temperature and maintenance of opening test for duct
mounted smoke control dampers . 29
7.1.1 General . 29
7.1.2 Pre-test calibration . 29
7.1.3 Ignition of furnace . 31
7.1.4 Operate the damper . 31
7.1.5 Furnace conditions. 31
7.1.6 Thermocouples for insulation (I) . 31
7.1.7 Oxygen measurements . 32
7.1.8 General observations . 32
7.1.9 Reduction of cross-section/maintenance of opening . 32
7.1.10 Leakage calculations . 32
7.1.11 Termination of test . 32
7.2 Fire resistance tests for smoke control dampers mounted in a compartment boundary
................................................................................................................................................................... 33
7.2.1 General . 33
7.2.2 Pre-test calibration . 33
7.2.3 Ignition of furnace . 33
7.2.4 Operate the damper . 33
7.2.5 Furnace conditions. 33
7.2.6 Thermocouples for insulation (I) . 33
7.2.7 General observations . 34
7.2.8 Leakage calculations . 34
7.2.9 Termination of test . 34
7.3 Maintenance of opening test for compartment boundary mounted smoke control
dampers . 34
7.3.1 General . 34
7.3.2 Pre-test calibration . 34
7.3.3 Ignition of furnace . 35
7.3.4 Operate a damper . 35
7.3.5 Furnace conditions. 35
7.3.6 Thermocouples for insulation (I) . 35
7.3.7 General observations . 35
7.3.8 Reduction of cross-section/maintenance of opening . 36
7.3.9 Termination of test . 36
8 Performance criteria . 36
8.1 Integrity . 36
8.1.1 General. 36
8.1.2 Integrity at perimeter . 36
8.2 Insulation . 40
8.2.1 General. 40
8.2.2 Thermocouples at the compartment boundary outside of the furnace . 40
8.3 Reduced leakage . 40
8.4 Times and observations . 41
8.5 Other . 41
9 Test report . 41
9.1 General. 41
9.2 Duct mounted single and multi-compartment tests . 42
9.3 Compartment boundary compartmentation test . 43
9.4 Compartment boundary maintenance of opening test . 43
10 Direct field of application of test results (DIAP) . 44
10.1 Compartment boundary mounted smoke control dampers . 44
10.2 Smoke control damper sizes . 44
10.3 Duct mounted smoke control damper mounting positions . 44
10.4 Distance between mounting positions in compartment boundary applications . 44
10.5 Blade pivot axis . 44
10.6 Pressure difference . 45
10.7 Elevated temperatures . 45
10.8 Cycling tests . 45
10.8.1 Smoke control dampers meeting the cycling requirements for modulating
applications . 45
10.8.2 Smoke control dampers meeting the cycling requirements for use with combined
smoke control and general HVAC applications and for smoke control systems that are
cycle checked every day . 45
10.8.3 Smoke control dampers meeting the cycling requirements for smoke control dampers
that are operated only in the case of emergency. 45
10.8.4 Load application . 45
10.9 Initiation method . 45
10.10 Duct mounted smoke control dampers – application to ducts other than that tested
................................................................................................................................................................... 46
10.10.1 Single compartment smoke control dampers . 46
10.10.2 Multi compartment smoke control dampers . 46
10.11 Compartment mounted smoke control dampers – application to shafts, walls and
constructions other than that tested . 47
10.11.1 Single compartment smoke control dampers . 47
10.11.2 Multi compartment smoke control dampers . 47
10.12 Standard damper open or closed position. 47
Annex A (normative) Cycling test . 74
A.1 General. 74
A.2 Purpose of the test . 74
A.3 Method of Application for loading . 74
A.3.1 General. 74
A.3.2 Smoke control damper with single blade . 74
A.3.3 Smoke control damper with multi blades of smaller area. 75
A.3.4 Circular smoke control dampers load calculation . 75
A.3.5 Test arrangement for dampers with horizontal blade pivot axis . 76
A.3.6 Test arrangement for dampers with vertical blade pivot axis . 77
A.3.7 Report . 80
A.4 Background for the torque value (informative) . 80
A.4.1 Threshold rates of the working condition of the system . 80
A.4.2 Previous experience . 80
Annex B (informative) Leakage calculation from oxygen measurement . 82
B.1 General . 82
B.2 Supporting information on leakage flowrate calculations . 83
B.2.1 Components in mixed fluids (mass and volume ratios) . 83
B.2.2 Application to oxygen in air . 84
B.2.3 Volume ratios and conservation of the mass during the smoke exhaust test . 84
B.2.4 Assumptions and reworking . 86
Annex C (normative) Maintenance of opening calculation . 88
C.1 Calculation of the theoretical total mass M of hot gases during the fire test. 88
max
C.1.1 Basis. 88
C.1.2 Method . 88
C.1.3 Summary . 89
C.2 Calculation of the actual total mass M of hot gases during the fire test . 90
actual
C.2.1 Basis. 90
C.2.2 Method . 91
C.2.3 Summary . 92
C.2.4 Graphical representation of typical integral calculation from data . 92
Annex D (normative) Optional High Operating Test HOT 400/30 classification . 94
D.1 General . 94
D.2 Tests . 94
D.2.1 General . 94
D.2.2 Equipment . 94
D.2.3 Ambient leakage test . 95
D.2.4 Cycling test . 95
D.2.5 Ambient leakage test . 95
D.2.6 Standby temperature test . 95
D.2.7 HOT 400/30 Test . 95
D.2.8 Performance criteria . 96
Annex E (informative) Leakage and pressure classification clarification . 99
Bibliography . 100

European foreword
This document (EN 1366-10:2022) has been prepared by Technical Committee CEN/TC 127 “Fire safety
in buildings”, the secretariat of which is held by BSI.
This European Standard shall be given the status of a national standard, either by publication of an
identical text or by endorsement, at the latest by March 2023, and conflicting national standards shall be
withdrawn at the latest by March 2023.
Attention is drawn to the possibility that some of the elements of this document may be the subject of
patent rights. CEN shall not be held responsible for identifying any or all such patent rights.
This document supersedes EN 1366-10:2011+A1:2017.
This document has been prepared under a mandate given to CEN by the European Commission and the
European Free Trade Association.
EN 1366, Fire resistance tests for service installations consists of the following:
— Part 1: Ventilation ducts
— Part 2: Fire dampers
— Part 3: Penetration seals
— Part 4: Linear joint seals
— Part 5: Service ducts and shafts
— Part 6: Raised access and hollow core floors
— Part 7: Conveyor systems and their closures
— Part 8: Smoke extraction ducts
— Part 9: Single compartment smoke extraction ducts
— Part 10: Smoke control dampers
— Part 11: Fire protective systems for cable systems and associated components
— Part 12: Non-mechanical fire barrier for ventilation ductwork
— Part 13: Chimneys
Any feedback and questions on this document should be directed to the users’ national standards body.
A complete listing of these bodies can be found on the CEN website.
According to the CEN-CENELEC Internal Regulations, the national standards organisations of the
following countries are bound to implement this European Standard: Austria, Belgium, Bulgaria, Croatia,
Cyprus, Czech Republic, Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland,
Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Republic of North
Macedonia, Romania, Serbia, Slovakia, Slovenia, Spain, Sweden, Switzerland, Türkiye and the United
Kingdom.
Introduction
When smoke and heat exhaust ventilation is being considered, it becomes apparent that a clear path
between the area where heat and smoke is being generated (source of the fire) and the outside of the
building is needed.
To create this path ducts and an uninterrupted smoke extract path are needed. This means that smoke
control dampers at the fire and along the path are open and will remain open. Smoke control dampers at
branches, or on the surface of the duct, along the path are closed and will remain closed. In fact, if the duct
crosses a compartment boundary it becomes part of the fire compartment in which the fire started.
The purpose of this document is to define test methods to evaluate the abilities of smoke control dampers
to:
a) be applicable to single compartment and/or multi compartment fire resisting applications;
b) be applicable to automatic systems or systems with manual activation;
c) change state from closed to open at elevated temperatures, (and vice versa);
d) once opened maintain a defined cross-sectional area at elevated temperature or under fire conditions
following the standard time/temperature curve; and
e) maintain a satisfactory leakage performance when subjected to negative pressure at elevated
temperatures or under fire conditions following the standard time/temperature curve.
The units are mounted for the tests in a manner representative of practice.
Temperature and integrity measurements are carried out on various parts of the test construction during
the test. The required leakage measurements are measured by direct flow measurement at the prescribed
pressure differentials. Ambient leakage of the units is also recorded.
The satisfactory passing of some, or all, of these tests will allow products to be assessed in accordance
with EN 12101-8 and be classified to EN 13501-4. The required temperatures, pressure differentials etc.
are stated in EN 12101-8. EN 13501-4 requires a classification report.
CAUTION:
The attention of all persons concerned with managing and carrying out this furnace testing is drawn to
the fact that fire testing can be hazardous and that there is a possibility that toxic and/or harmful smoke
and gases can be evolved during the test. Mechanical and operational hazards can also arise during the
construction of the test elements or structures, their testing and disposal of test residues.
An assessment of all potential hazards and risks to health should be made and safety precautions should
be identified and provided. Written safety instructions should be issued. Appropriate training should be
given to relevant personnel. Laboratory personnel should ensure that they follow written safety
instructions at all times.
1 Scope
This document specifies test methods for smoke control dampers to assess their performance under
elevated temperature or fire conditions, as well as at ambient temperatures.
Smoke control damper tests are used to confirm that the furnace testing requirements of EN 12101-8 are
met and EN 12101-8 is for consideration before carrying out these tests.
Smoke control dampers tested to this document are expected to be classified using EN 13501-4 and this
document is expected to be considered before carrying out these tests.
NOTE Some smoke control dampers to be tested might require testing following the information given in EN
1366-2 and this needs consideration before carrying out testing.
This document is expected to be read in conjunction with EN 12101-8, EN 13501-4, EN 1366-2 and
EN 1363-1, the latter giving further details for fire resistance testing.
For installation details, the requirements for smoke extraction ducts are for consideration and these are
defined in EN 1366-8 and EN 1366-9.
2 Normative references
The following documents are referred to in the text in such a way that some or all of their content
constitutes requirements of this document. For dated references, only the edition cited applies. For
undated references, the latest edition of the referenced document (including any amendments) applies.
EN 1363-1, Fire resistance tests — Part 1: General requirements
EN 1366-2, Fire resistance tests for service installations — Part 2: Fire dampers
EN 1366-8, Fire resistance tests for service installations — Part 8: Smoke extraction ducts
EN 1366-9, Fire resistance tests for service installations — Part 9: Single compartment smoke extraction
ducts
EN 1751, Ventilation for buildings — Air terminal devices — Aerodynamic testing of damper and valves
EN 10095, Heat resisting steels and nickel alloys
EN 13501-4, Fire classification of construction products and building elements — Part 4: Classification
using data from fire resistance tests on components of smoke control systems
EN ISO 5167-1, Measurement of fluid flow by means of pressure differential devices inserted in circular
cross-section conduits running full — Part 1: General principles and requirements (ISO 5167-1)
3 Terms and definitions
For the purposes of this document, the following terms and definitions apply.
ISO and IEC maintain terminological databases for use in standardization at the following addresses:
— ISO Online browsing platform: available at https://www.iso.org/obp
— IEC Electropedia: available at https://www.electropedia.org/
3.1
elevated temperature
temperature in excess of normal ambient air, below those necessary for fire resistance testing (i.e. the
standard fire curve in accordance with EN 1363-1), to which smoke and heat exhaust ducts for single
compartments are tested
3.2
HOT 400/30
additional test and classification for a smoke control damper that requires proof of opening and closing
operations for 30 minutes at 400 °C
3.3
HVAC
heating, ventilating and air conditioning
Note 1 to entry: Usually used with the addition of the word “system”.
3.4
interface control unit
device which controls the operation of the actuator located at the smoke control damper or within the
same fire zone as the smoke control damper and usually associated with a smoke control/fire alarm
system
3.5
largest size
greatest size of smoke control damper individual unit including the maximum width and height (as
opposed to an assembly/battery of units) proposed for sale/manufacture
3.6
modulating actuator
smoke control damper control mechanism which can control the smoke control damper to be in a
position or number of positions between fully open and fully closed in normal day to day operation (not
fire conditions)
3.7
penetration seal
fire stopping method
product(s) used between the smoke control system duct/damper and the fire compartment structure to
maintain the fire resistance, and tested in accordance with EN 1366-8 (ducts) or EN 1366-10 (dampers)
3.8
safety position
position (open or closed) into which specific projects could require certain dampers to move to, or remain
in, depending upon the fire location within the building
Note 1 to entry: Specific projects can require certain smoke control dampers to move to an open or closed position,
depending upon the fire location within the building.
3.9
smallest size
least size of smoke control damper individual unit including the minimum width and height proposed for
sale/manufacture
3.10
multi-compartment smoke control damper
multi-compartment SCD
device which can be open or closed to control the flow of smoke and hot gases into, from or within a duct
for use in multi-compartment applications which is required to maintain compartmentation when closed
3.11
single compartment smoke control damper
single compartment SCD
device which can be open or closed to control the flow of smoke and hot gases into, from or within a duct
for use in single compartment applications at elevated temperatures (600 °C)
3.12
builders work
any construction formed from concrete, blockwork, light wall or other materials as part of general
construction, such as used to construct shafts, walls and floors
3.13
duct mounted smoke control damper
duct mounted SCD
smoke control damper mounted on the surface of, or in line with a smoke control duct and not associated
with a compartment boundary formed from builders’ work – e.g. a shaft, wall, floor
3.14
compartment mounted smoke control damper
compartment mounted SCD
smoke control damper mounted at a compartment boundary formed from builders’ work – e.g. a shaft,
wall, floor
3.15
smoke control damper for systems with automatic activation
smoke control damper that is applicable to the smoke control systems that operate automatically on
receipt of a smoke or fire alarm without any manual action/intervention and allow no firefighter
overrides
Note 1 to entry: A smoke control system with an attended control room can also be accepted as an automatic
system, provided that once initiated, the system does not cause the smoke control damper position to be changed.
3.16
smoke control damper for systems with manual activation
smoke control damper that is applicable to the smoke control systems (smoke and heat exhaust
ventilation type or pressurization type), that will be put into operation, on detection smoke or fire, by
human intervention (e.g. by pressing a button or pulling a handle) leading to a sequence of automatic
actions in the operation of the smoke control system or a system that allows firefighter overrides
3.17
thermal operating device
temperature sensitive device such as a fusible element which responds to temperature to initiate a
subsequent action such as causes the damper to change position
Note 1 to entry: Further information is given in Figure 1.
Key
1 fire compartments
2 smoke reservoirs
4 air inlets
5 smoke barriers
6 powered smoke and heat exhaust ventilator (fan)
7 smoke control dampers for single compartments (EN 12101-8 and EN 1366-10)
8 smoke control ducts for single compartments (EN 12101-7 and EN 1366-9)
9 smoke control ducts for multi compartments (EN 12101-7 and EN 1366-8)
10 smoke control dampers for multi compartments (EN 12101-8 and EN 1366-10) mounted inside or
outside of wall or floor (compartmentation tests)
11 smoke control dampers for multi compartments (EN 12101-8 and EN 1366-10) mounted on the surface
of the duct (surface of duct tests)
12 electrical equipment
Figure 1 — Example of powered smoke and heat exhaust ventilation system in cross-section
4 Test equipment
4.1 General
In addition to the test equipment specified in EN 1363-1, the equipment in the following clauses is
required (examples of test arrangements are given in Figure 4, Figure 5, Figure 8 and Figure 9).
4.2 Test duct for surface mounted SCDs
See 5.2.2.2 and 5.2.2.3.
4.3 Connecting duct for compartment boundary mounted SCDs
4.3.1 Compartmentation test
See EN 1366-2.
4.3.2 Maintenance of opening test
The duct connector (Figure 9, item 9) shall be classified in accordance with EN 13501-4 and match the
damper cross section.
A normal steel fabricated duct may be used for the mounting of the perforated plate (Figure 9, item 5).
The perforated plate mounting duct shall have a cross section 1 000 mm × 250 mm and have a minimum
length of 2 m. The perforated plate mounting duct may be provided with a gas tight observation window.
4.4 Cycling equipment
Full information on the equipment needed to perform the cycling tests is shown in Annex A. In addition,
the following shall be considered:
Equipment shall be required to control a supply to allow the smoke control damper actuator to be cycled.
This equipment shall be able to provide the nominal operating motive force less 10 %, plus 15 %, and be
variable between these values to confirm that the smoke control damper shall operate at the extremes. If
the unit to be tested requires a control signal of any type this shall be provided in addition and shall be
able to give the device a signal at each extreme and any in between these.
Methods of adding a load to the smoke control damper are required (see Annex A).
NOTE A device that allows the smoke control damper to be cycled automatically, together with a method of
recording completed cycles, would be useful. A test could thereby be set to run without attendance, noting that each
cycle could potentially take 120 s.
4.5 Condensing unit
When performing the compartmentation test, there could be a requirement for a condensing unit,
because the smoke control damper could generate some steam; refer to EN 1366-2.
4.6 Gas temperature measuring devices
These shall be positioned adjacent to the flow measuring device. A suitable device is a 1,5 mm diameter
sheathed thermocouple (Type K) orientated vertically with its measuring junction located at the centre
line of the measuring duct and at a distance equal to twice the diameter of the measuring duct
downstream from the flow measuring device. A similar thermocouple shall be located at the exit from the
connecting duct plenum (see Figure 8, Figure 19, Figure 20).
4.7 Exhaust fan system
This shall be capable of controlling the flow rates and maintaining the speci
...

Questions, Comments and Discussion

Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.

Loading comments...

The SIST EN 1366-10:2022 standard provides a comprehensive framework for fire resistance tests specifically designed for smoke control dampers. Its scope is well-defined, focusing on the test methods necessary to evaluate the performance of these dampers under both elevated temperature conditions typical of a fire scenario and standard ambient conditions. This inclusivity ensures that manufacturers and safety professionals can assess the full range of operational capabilities of smoke control dampers. A notable strength of this standard is its alignment with existing European standards, such as EN 12101-8, which outlines the general requirements for smoke and heat control systems. By specifying that smoke control damper tests must meet the furnace testing requirements of EN 12101-8, the document underscores its commitment to interoperability and coherence within the broader regulatory framework. This synergy enhances the reliability of test results, giving stakeholders confidence in the performance claims of smoke control dampers. Furthermore, the document emphasizes the importance of classification according to EN 13501-4, which categorizes the fire performance of construction products and building elements. This classification process is crucial for ensuring that smoke control dampers meet stringent fire safety standards and are suitable for their intended uses in various building designs. Another strength lies in the standard’s attention to additional relevant documents. It encourages users to consult associated standards, such as EN 1366-2, EN 1366-8, and EN 1366-9, which provide further guidance on installation details and the testing of smoke extraction ducts. This interconnectedness not only enhances the robustness of the testing regime but also ensures that users adopt a holistic approach to fire safety compliance. In conclusion, SIST EN 1366-10:2022 plays a vital role in promoting safety and performance testing for smoke control dampers. Its well-structured guidelines, combined with the integration of broader European standards, underscore its relevance in the ongoing pursuit of effective fire safety measures in buildings. The emphasis on compliance and systematic assessment establishes it as an essential reference point for manufacturers, engineers, and safety professionals involved in the design and installation of smoke control systems.

Die Norm SIST EN 1366-10:2022 behandelt die praxisrelevanten Prüfmethoden für Rauchkontrollklappen, um deren Leistung unter erhöhten Temperaturen oder Brandbedingungen sowie bei Umgebungsbedingungen zu bewerten. Diese Norm ist von zentraler Bedeutung für die Gewährleistung der Brandsicherheit in Gebäuden, da sie sicherstellt, dass die Prüfanforderungen der EN 12101-8 für Rauchkontrollklappen erfüllt werden. Ein herausragendes Merkmal dieser Norm ist die Aktualität und Relevanz der Prüfmethoden, die den neuesten Standards entsprechen. Die Norm stellt sicher, dass die getesteten Rauchkontrollklappen gemäß der Klassifizierung in EN 13501-4 einsortiert werden, was die Transparenz und Nachvollziehbarkeit der Ergebnisse erhöht. Dies ist für Ingenieure und Fachleute in der Brandschutzbranche von entscheidender Bedeutung, um die Brandschutzsysteme entsprechend zu planen und zu implementieren. Ein weiterer Stärke dieser Norm liegt in ihrer Verknüpfung zu anderen wichtigen Dokumenten, einschließlich EN 12101-8, EN 13501-4, EN 1366-2 und EN 1363-1. Diese Verknüpfung sorgt dafür, dass die Anwender ein umfassendes Verständnis für die Anforderungen an Rauchkontrollklappen entwickeln und somit die erforderlichen Schritte zur Gewährleistung der Brandsicherheit ergreifen können. Es ist jedoch wichtig zu beachten, dass einige Rauchkontrollklappen möglicherweise auch gemäß EN 1366-2 getestet werden müssen, was die Komplexität der Anwendung dieser Norm unterstreicht. Zusätzlich sind die Installationsdetails und die Anforderungen für die Rauchabzugskanäle, die in EN 1366-8 und EN 1366-9 definiert sind, von entscheidender Bedeutung. Die Berücksichtigung dieser Aspekte erleichtert die korrekte Umsetzung der Norm und trägt zu einer effektiven Brandkontrolle und -sicherheit bei. Insgesamt bietet die Norm SIST EN 1366-10:2022 ein strukturiertes und umfassendes Framework für die Prüfung von Rauchkontrollklappen, das sowohl technische Präzision als auch Relevanz für die aktuelle Brandschutzpraxis fördert.

SIST EN 1366-10:2022は、煙制御ダンパーの試験方法を規定した重要な標準であり、火災や高温条件下での性能を評価するための試験を詳細に示しています。この標準は、煙制御ダンパーがEN 12101-8の炉試験要件を満たしていることを確認するために使用されるものであり、その関連性は非常に高いといえます。 本標準の強みは、煙制御ダンパーの試験を実施する際の明確な指針を提供することにあります。特に、煙制御ダンパーはEN 13501-4に基づいて分類されることが期待されており、試験実施前にこの文書を考慮することが推奨されています。これにより、適切な評価を受けることができ、関連する規制に準拠した製品の信頼性が向上します。 また、試験においては、EN 1366-2に基づく追加的な試験が必要な煙制御ダンパーについても考慮されるべきであり、この点は標準の組織的な妥当性を示しています。さらには、同文書はEN 12101-8、EN 13501-4、EN 1366-2、EN 1363-1と併用されることが想定されており、これらの関連する文書との整合性が確保されています。 最後に、煙抽出ダクトに関する設置要件はEN 1366-8およびEN 1366-9で定義されており、これを考慮することで、煙制御ダンパーの設置がより安全で効果的になることが期待されます。総じて、SIST EN 1366-10:2022は、煙制御ダンパーの試験において非常に重要な標準であり、実務における適用性と有用性が高いことが特徴です。

La norme SIST EN 1366-10:2022 est un document essentiel qui spécifie les méthodes d'essai pour les dispositifs de contrôle de fumée, permettant d'évaluer leur performance dans des conditions de température élevée ou en cas d'incendie, ainsi qu'à des températures ambiantes. Cette norme est d'une grande pertinence car elle garantit que les tests réalisés sur les dispositifs de contrôle de fumée répondent aux exigences de test de four conforme à la norme EN 12101-8. En intégrant les méthodes de test adaptées, la norme assure que les dispositifs sont non seulement conformes, mais également performants lors d’événements critiques. De plus, les dispositifs de contrôle de fumée testés selon cette norme sont classifiés à l'aide de la norme EN 13501-4, ce qui renforce leur fiabilité et leur intégration dans une approche globale de gestion des risques d'incendie. Les professionnels doivent également tenir compte de la norme EN 1366-2 pour certains dispositifs et de EN 1363-1, qui offre un guide supplémentaire sur les tests de résistance au feu. La nécessité de lire cette norme en conjonction avec EN 12101-8, EN 13501-4, EN 1366-2, et d'autres normes pertinentes, souligne son rôle central dans le cadre réglementaire sur la sécurité incendie. Les détails d'installation et les exigences relatives aux conduits d'extraction de fumée, définis dans les normes EN 1366-8 et EN 1366-9, renforcent également l'importance de cette norme dans le processus d'installation et de mise en conformité des équipements. En somme, la norme SIST EN 1366-10:2022 constitue un outil fondamental pour assurer la sécurité incendie en fournissant des directives claires et rigoureuses pour le test des dispositifs de contrôle de fumée, crucial dans le contexte de la construction moderne et des exigences croissantes en matière de sécurité.

SIST EN 1366-10:2022 표준은 연기가 제어되는 댐퍼의 성능을 평가하기 위한 시험 방법을 명확히 규정하고 있어, 이 문서의 강력한 점 중 하나입니다. 이 표준은 고온 또는 화재 조건뿐만 아니라 일반 온도에서도 댐퍼의 작동을 검증하는 데 필요한 검사 절차를 제공합니다. 특히, 연기 제어 댐퍼의 시험은 EN 12101-8의 화로 시험 요구사항에 부합하는지 확인하기 위해 필수적입니다. SIST EN 1366-10:2022의 적용 범위는 연기에 대한 효과적인 통제를 보장하는 데 큰 의의를 가지며, 최종적으로 EN 13501-4에 따라 분류될 댐퍼를 테스트하는 데 중요한 기초 자료가 됩니다. 또한, 테스트 전에는 EN 1366-2에서 제시된 정보를 기반으로 한 추가 고려가 필요할 수 있음을 명확히 하고 있어, 사용자가 실질적인 요구사항을 충분히 이해할 수 있도록 돕습니다. 이 문서는 내부의 관계성을 고려하여 EN 12101-8, EN 13501-4, EN 1366-2 및 EN 1363-1과 함께 읽혀야 하며, 이로 인해 화재 저항 시험 진행 시 더욱 심층적인 정보를 반영할 수 있습니다. 이는 연기 추출 덕트의 설치 요건을 정의하는 EN 1366-8과 EN 1366-9에 대한 사항도 고려해야 함을 강조합니다. 결론적으로, SIST EN 1366-10:2022 표준은 연기 제어 댐퍼의 테스트 방법 및 관련 규정을 포괄적으로 다루며, 해당 분야에서의 안전성과 효율성을 높이는 데 중요한 기준을 제시합니다.