Abstract

The present document defines classes of environmental conditions and their severities to which telecommunication equipment may be exposed. The severities specified are those which will have a low probability of being exceeded; generally less than 1 %. The present document applies to equipment mounted for stationary use including periods of erection work, down time, maintenance and repair at weatherprotected locations defined in clause 5.

Status
Published
Publication Date
31-Jan-2006
Current Stage
6060 - National Implementation/Publication (Adopted Project)
Start Date
01-Feb-2006
Due Date
01-Feb-2006
Completion Date
01-Feb-2006

Buy Documents

Standard

SIST EN 300 019-1-3 V2.2.2:2006

English language (20 pages)
Preview
Preview
e-Library read for
×1 day

SIST EN 300 019-1-3 V2.2.2:2006 is the Slovenian standard identical with EN 300 019-1-3 Version 2.2.2, published by SIST. It classifies environmental conditions and their severities for telecommunications equipment mounted for stationary use at weatherprotected locations, so designers, testers, quality managers, and buyers can match equipment to the site environment. The severities are intended to be levels with a low probability of being exceeded, generally less than 1%.

What does SIST EN 300 019-1-3 V2.2.2:2006 specify?

SIST EN 300 019-1-3 V2.2.2:2006 specifies the environmental classes for stationary telecommunications equipment at weatherprotected locations and the severity limits associated with those classes. It tells you what kind of temperature, humidity, contamination, vibration, and earthquake exposure to expect in different site types.

The document is organized into these main parts:

  • Clause 1 - Scope
  • Clause 2 - References
  • Clause 3 - Definitions and abbreviations
  • Clause 4 - Environmental classes
  • Clause 5 - Environmental conditions
  • Annex A - Bibliography

Clause 4 sets out six classes, from 3.1 to 3.6, and Clause 5 gives the environmental parameters that go with them. In practice, that means the standard is both a site classification document and a basis for deciding what environmental testing or design margin is appropriate.

What are the key requirements of SIST EN 300 019-1-3 V2.2.2:2006?

The document starts from the site class, not from a generic equipment rating

SIST EN 300 019-1-3 V2.2.2:2006 divides stationary use at weatherprotected locations into six environmental classes in Clause 4: temperature-controlled locations, partly temperature-controlled locations, not temperature-controlled locations, sites with heat-trap, sheltered locations, and telecommunication control room locations. Special classes in parentheses, such as (3C1), may be selected for special applications.

That matters because the standard is meant to be matched to the real installation site. A product for a controlled control room is not automatically suitable for an unattended shelter, even if both are indoors.

Each class describes a real type of location

Clauses 4.1 to 4.6 describe the intended site conditions for each class. The text links each class to typical places such as offices, workshops, garages, cellars, sheds, open telephone booths, telecommunication centres, and dedicated control rooms.

In practice, this helps a specifier decide whether the site is temperature controlled, partly controlled, exposed to solar loading, subject to heat-trap effects, or only sheltered from direct weather. The classification also makes the expected exposure easier to communicate in procurement and qualification documents.

Climate is handled through a parameter table and climatograms

Clause 5.1 and Table 1 define the climate parameters for classes 3.1 to 3.6, including air temperature, relative and absolute humidity, air pressure, solar radiation, heat radiation, movement of surrounding air, condensation, wind-driven rain or snow, water from sources other than rain, and icing. Figures 1 to 6 show the climatograms for the six classes.

For users, this means the standard is not just a label. It gives a structured checklist of environmental loads that can affect housing design, ventilation, sealing, condensation control, and material choice.

Biological, chemical, and dust exposure are separated into their own clauses

Clauses 5.2 to 5.4 deal with biological conditions, chemically active substances, and mechanically active substances. The chemical tables distinguish the ordinary classes from the special chemical classes 3C1 and 3C3, and they treat gases such as sulphur dioxide, hydrogen sulphide, chlorine, hydrochloric acid, hydrofluoric acid, ammonia, ozone, and nitrogen oxides.

That matters in practice because the environmental risk is not only temperature. A coastal site, a road-side site, or a plant building may need attention to salt mist, industrial gases, mould, rodents, sand, or dust even when the temperature is moderate.

Mechanical exposure includes vibration, shock, and a practical note on random vibration

Clause 5.5 and Table 5 define stationary vibration and non-stationary vibration, including shock, for the different class groups. The note under Table 5 says random vibration is often a more realistic description than sinusoidal vibration and points to ETSI EN 300 019-2-3 for random-vibration severities.

In practice, this tells engineers not to treat vibration as an afterthought. If the equipment sits on a structure, near traffic, or close to machines, the mechanical environment can drive enclosure design, mounting choice, and test selection.

Earthquake conditions are specified through response-spectrum logic

Clause 5.6 explains earthquake conditions using a Response Spectrum (RS) approach and the Zero Period Acceleration (ZPA) concept. It also gives the parameter severities used for classes 3.1 to 3.6 and shows the corresponding response spectrum in Figure 7 and Table 7.

This is important because seismic design is not reduced to one simple acceleration number. The standard helps users define the mounting motion expected during an earthquake and use that definition consistently in design and testing.

What terms does SIST EN 300 019-1-3 V2.2.2:2006 define?

  • Absolute humidity - the mass of water vapour in one cubic metre of dry air in an air and water vapour mixture.
  • Air conditioning system - a system that automatically controls temperature and humidity by heating, cooling, humidifying, and dehumidifying.
  • Climate-controlling system - a system that influences climate by acting on at least one climatic parameter in one direction.
  • Cooling system - a system that lowers air temperature only, which can also reduce absolute humidity.
  • Heating system - a system that raises air temperature only, which can also reduce relative humidity.
  • Relative humidity - the ratio of the water-vapour partial pressure in moist air to the saturation pressure at the same temperature.
  • Stationary use - equipment fixed to a structure or site, including short periods of handling during erection, downtime, maintenance, and repair.
  • Weatherprotected location - a location where direct weather influences are fully excluded or only partly excluded.
  • Response Spectrum (RS) - the graph used in seismic work to show the maximum response of oscillators as a function of frequency during transient base motion.
  • Zero Period Acceleration (ZPA) - the high-frequency asymptotic acceleration of the response spectrum, representing the largest peak value of the base motion.

Who uses SIST EN 300 019-1-3 V2.2.2:2006?

SIST EN 300 019-1-3 V2.2.2:2006 is used by telecommunications equipment designers, environmental test engineers, quality managers, site planners, installers, and purchasers. They use it to classify the intended installation, select environmental design margins, and decide which conditions need to be covered in qualification or acceptance planning.

It is especially relevant for:

  • telecommunications centres and control rooms
  • offices, workshops, garages, and storage rooms where telecom equipment is installed
  • shelters, sheds, shacks, and other partly protected locations
  • unattended equipment stations and similar stationary installations

Which standards are used with SIST EN 300 019-1-3 V2.2.2:2006?

Referenced documentWhat it contributes
IEC 60721-3-3The related environmental class structure and groupings of parameters and severities
IEC 60068-2-27Shock test guidance used for mechanical conditions
IEC 60721-2-6Earthquake vibration and shock classification used for seismic conditions
IEC 60068-3-3Guidance for seismic test methods and response-spectrum thinking
ETSI EN 300 019-2-3The corresponding environmental test severities and test methods for stationary use at weatherprotected locations

The foreword also places this part within the wider EN 300 019 series. Part 1-0 provides the general overview of part 1, and Part 2 specifies the recommended test severities and methods for the environmental classes.

What does the SIST EN 300 019-1-3 V2.2.2:2006 document contain?

The document contains class descriptions, definition clauses, and parameter tables that turn a site description into a standard environmental profile. Its figures are climatograms for the six classes, and its tables cover climatic, biological, chemical, mechanical, and earthquake conditions.

For practical use, it is a reference for environmental specification, product design, and environmental qualification of telecommunications equipment. Annex A gives the bibliography, and the foreword links this part to the rest of the ETSI environmental engineering series.

Buy Documents

Standard

SIST EN 300 019-1-3 V2.2.2:2006

English language (20 pages)
Preview
Preview
e-Library read for
×1 day

Get Certified

Connect with accredited certification bodies for this standard

ANCE

Mexican certification and testing association.

EMA Mexico Verified

IMP NDT d.o.o.

Non-destructive testing services. Radiography, ultrasonic, magnetic particle, penetrant, visual inspection.

SA Slovenia Verified

Inštitut za kovinske materiale in tehnologije

Institute of Metals and Technology. Materials testing, metallurgical analysis, NDT.

SA Slovenia Verified

Sponsored listings

Frequently Asked Questions

SIST EN 300 019-1-3 V2.2.2:2006 is a standard published by the Slovenian Institute for Standardization (SIST). Its full title is "Environmental Engineering (EE); Environmental conditions and environmental tests for telecommunications equipment; Part 1-3: Classification of environmental conditions; Stationary use at weatherprotected locations". This standard covers: The present document defines classes of environmental conditions and their severities to which telecommunication equipment may be exposed. The severities specified are those which will have a low probability of being exceeded; generally less than 1 %. The present document applies to equipment mounted for stationary use including periods of erection work, down time, maintenance and repair at weatherprotected locations defined in clause 5.

The present document defines classes of environmental conditions and their severities to which telecommunication equipment may be exposed. The severities specified are those which will have a low probability of being exceeded; generally less than 1 %. The present document applies to equipment mounted for stationary use including periods of erection work, down time, maintenance and repair at weatherprotected locations defined in clause 5.

SIST EN 300 019-1-3 V2.2.2:2006 is classified under the following ICS (International Classification for Standards) categories: 19.040 - Environmental testing; 33.050.01 - Telecommunication terminal equipment in general. The ICS classification helps identify the subject area and facilitates finding related standards.

SIST EN 300 019-1-3 V2.2.2:2006 is available in PDF format for immediate download after purchase. The document can be added to your cart and obtained through the secure checkout process. Digital delivery ensures instant access to the complete standard document.

Standards Content (Sample)


SLOVENSKI STANDARD
01-februar-2006
2NROMVNLLQåHQLULQJ (( ±2NROMVNLSRJRMLLQSUHVNXVLYSOLYRYRNROMDQD
WHOHNRPXQLNDFLMVNRRSUHPR±GHO.ODVLILNDFLMDRNROMVNLKSRJRMHY±)LNVQD
XSRUDEDQDORNDFLMDK]DãþLWHQLKSUHGYUHPHQVNLPLYSOLYL
Environmental Engineering (EE); Environmental conditions and environmental tests for
telecommunications equipment; Part 1-3: Classification of environmental conditions;
Stationary use at weatherprotected locations
Ta slovenski standard je istoveten z: EN 300 019-1-3 Version 2.2.2
ICS:
19.040 Preskušanje v zvezi z Environmental testing
okoljem
33.050.01 Telekomunikacijska Telecommunication terminal
terminalska oprema na equipment in general
splošno
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.

European Standard (Telecommunications series)

Environmental Engineering (EE);
Environmental conditions and environmental tests
for telecommunications equipment;
Part 1-3: Classification of environmental conditions;
Stationary use at weatherprotected locations

2 ETSI EN 300 019-1-3 V2.2.2 (2004-07)

Reference
REN/EE-01027-1-3[3]
Keywords
environment, testing, equipment practice
ETSI
650 Route des Lucioles
F-06921 Sophia Antipolis Cedex - FRANCE

Tel.: +33 4 92 94 42 00  Fax: +33 4 93 65 47 16

Siret N° 348 623 562 00017 - NAF 742 C
Association à but non lucratif enregistrée à la
Sous-Préfecture de Grasse (06) N° 7803/88

Important notice
Individual copies of the present document can be downloaded from:
http://www.etsi.org
The present document may be made available in more than one electronic version or in print. In any case of existing or
perceived difference in contents between such versions, the reference version is the Portable Document Format (PDF).
In case of dispute, the reference shall be the printing on ETSI printers of the PDF version kept on a specific network drive
within ETSI Secretariat.
Users of the present document should be aware that the document may be subject to revision or change of status.
Information on the current status of this and other ETSI documents is available at
http://portal.etsi.org/tb/status/status.asp
If you find errors in the present document, send your comment to:
editor@etsi.org
Copyright Notification
No part may be reproduced except as authorized by written permission.
The copyright and the foregoing restriction extend to reproduction in all media.

© European Telecommunications Standards Institute 2004.
All rights reserved.
TM TM TM
DECT , PLUGTESTS and UMTS are Trade Marks of ETSI registered for the benefit of its Members.
TM
TIPHON and the TIPHON logo are Trade Marks currently being registered by ETSI for the benefit of its Members.
TM
3GPP is a Trade Mark of ETSI registered for the benefit of its Members and of the 3GPP Organizational Partners.
ETSI
3 ETSI EN 300 019-1-3 V2.2.2 (2004-07)
Contents
Intellectual Property Rights.4
Foreword.4
1 Scope.5
2 References.5
3 Definitions and abbreviations.5
3.1 Definitions.5
3.2 Abbreviations.6
4 Environmental classes.6
4.1 Class 3.1: Temperature-controlled locations .6
4.2 Class 3.2: Partly temperature-controlled locations.7
4.3 Class 3.3: Not temperature-controlled locations .9
4.4 Class 3.4: Sites with heat-trap .10
4.5 Class 3.5: Sheltered locations.11
4.6 Class 3.6: Telecommunication control room locations .12
5 Environmental conditions.13
5.1 Climatic conditions.13
5.2 Biological conditions.14
5.3 Chemically active substances .14
5.4 Mechanically active substances.15
5.5 Mechanical conditions.16
5.6 Earthquake conditions.16
Annex A (informative): Bibliography.19
History .20

ETSI
4 ETSI EN 300 019-1-3 V2.2.2 (2004-07)
Intellectual Property Rights
IPRs essential or potentially essential to the present document may have been declared to ETSI. The information
pertaining to these essential IPRs, if any, is publicly available for ETSI members and non-members, and can be found
in ETSI SR 000 314: "Intellectual Property Rights (IPRs); Essential, or potentially Essential, IPRs notified to ETSI in
respect of ETSI standards", which is available from the ETSI Secretariat. Latest updates are available on the ETSI Web
server (http://webapp.etsi.org/IPR/home.asp).
Pursuant to the ETSI IPR Policy, no investigation, including IPR searches, has been carried out by ETSI. No guarantee
can be given as to the existence of other IPRs not referenced in ETSI SR 000 314 (or the updates on the ETSI Web
server) which are, or may be, or may become, essential to the present document.
Foreword
This European Standard (Telecommunications series) has been produced by ETSI Technical Committee Environmental
Engineering (EE).
The present document is part 1, sub-part 3 of a multi-part deliverable covering the classification of environmental
conditions for telecommunications equipment, as identified below:
Part 1: "Classification of environmental conditions"; (see note 1)
Sub-part 0: "Introduction";
Sub-part 1: "Storage";
Sub-part 2: "Transportation";
Sub-part 3: "Stationary use at weatherprotected locations";
Sub-part 4: "Stationary use at non-weatherprotected locations";
Sub-part 5: "Ground vehicle installations";
Sub-part 6: "Ship environments";
Sub-part 7: "Portable and non-stationary use";
Sub-part 8: "Stationary use at underground locations";
Part 2: "Specification of environmental tests" (see note 2).
NOTE 1: Specifies different standardized environmental classes covering climatic and biological conditions,
chemically and mechanically active substances and mechanical conditions during storage, transportation
and in use. Sub-part 1-0 forms a general overview of part 1.
NOTE 2: Specifies the recommended test severities and test methods for the different environmental classes.

National transposition dates
Date of adoption of this EN: 9 July 2004
Date of latest announcement of this EN (doa): 31 October 2004
Date of latest publication of new National Standard
or endorsement of this EN (dop/e): 30 April 2005
Date of withdrawal of any conflicting National Standard (dow): 30 April 2005

ETSI
5 ETSI EN 300 019-1-3 V2.2.2 (2004-07)
1 Scope
The present document defines classes of environmental conditions and their severities to which telecommunication
equipment may be exposed. The severities specified are those which will have a low probability of being exceeded;
generally less than 1 %.
The present document applies to equipment mounted for stationary use including periods of erection work, down time,
maintenance and repair at weatherprotected locations defined in clause 5.
2 References
The following documents contain provisions which, through reference in this text, constitute provisions of the present
document.
• References are either specific (identified by date of publication and/or edition number or version number) or
non-specific.
• For a specific reference, subsequent revisions do not apply.
• For a non-specific reference, the latest version applies.
Referenced documents which are not found to be publicly available in the expected location might be found at
http://docbox.etsi.org/Reference.
[1] IEC 60721-3-3: "Classification of environmental conditions - Part 3-3: Classification of groups of
environmental parameters and their severities - Stationary use at weatherprotected locations".
[2] IEC 60068-2-27: "Environmental testing. Part 2: Tests. Test Ea and guidance: Shock".
[3] IEC 60721-2-6: "Classification of environmental conditions. Part 2: Environmental conditions
appearing in nature. Earthquake vibration and shock".
[4] IEC 60068-3-3: "Environmental testing - Part 3: Guidance. Seismic test methods for equipment".
[5] ETSI EN 300 019-2-3: "Environmental Engineering (EE); Environmental conditions and
environmental tests for telecommunications equipment; Part 2-3: Specification of environmental
tests; Stationary use at weatherprotected locations".
3 Definitions and abbreviations
3.1 Definitions
For the purposes of the present document, the following terms and definitions apply:
absolute humidity: mass of water vapour in grams which is associated with one cubic metre of dry air in an air/water
vapour mixture
air conditioning system: system that fully and automatically controls the climatic parameters air temperature and
humidity by heating, cooling, humidifying and dehumidifying
climate-controlling system: system that controls or influences climate, acting at least on one climatic parameter in one
direction
cooling system: system that controls or influences climate by decreasing the air temperature only
NOTE: This can decrease the absolute humidity.
ETSI
6 ETSI EN 300 019-1-3 V2.2.2 (2004-07)
forced ventilation system: system that controls or influences climate by introducing outdoor air into the room or
expelling air out of the room
heating system: system that controls or influences climate by increasing the air temperature only
NOTE: This can decrease the relative humidity.
relative humidity: ratio of the partial pressure of the water vapour in moist air at a given temperature, to the partial
pressure of the water vapour in saturated air at the same temperature
stationary use: The equipment is mounted firmly on the structure, or on mounting devices, or it is permanently placed
at a certain site. It is not intended for portable use - but short periods of handling during erection works, down time,
maintenance and repair at the location are included.
weatherprotected location: location at which the equipment is protected from direct weather influences:
• totally weatherprotected location (enclosed location):
- direct weather influences are totally excluded,
• partly weatherprotected location (sheltered location):
- direct weather influences are not completely excluded.
3.2 Abbreviations
For the purposes of the present document, the following abbreviations apply:
RS Response Spectrum
ZPA Zero Period Acceleration
4 Environmental classes
The classes shown in parentheses, e.g. (3C1), may be selected for special applications.
4.1 Class 3.1: Temperature-controlled locations
Class 3.1 is a combination of classes 3K3/3Z2/3Z4/3B1/3C2(3C1)/3S2/3M1 in IEC 60721-3-3 [1].
The climatogram is shown in figure 1 in clause 4.1.
Seismic environment: zone 4 as defined in IEC 60721-2-6 [3]. Option zone 4 (modified Mercalli scale ≥ 9): if earthquake
conditions are specified by the customer, the conditions stated in clause 5.6 apply.
This class applies to a permanently temperature controlled enclosed location. Humidity is usually not controlled. The
climatogram is shown in figure 1.
Heating, cooling, forced ventilation and humidification are used as necessary to maintain the required
conditions - especially where there is a significant difference between the room environment and the external ambient.
The climate-controlling systems could be periodically switched on or off but extremely high or low temperatures are
prevented.
This class applies to locations:
- where installed equipment may be exposed to solar radiation and to heat radiation. It may also be exposed to
movements of the surrounding air due to draughts in buildings. They are not subjected to condensed water,
precipitation, water from sources other than rain or icing;
- without particular risks of biological attacks. This includes protective measures, e.g. special product design, or
installations at locations of such construction that mould growth and attacks by animals, etc. are not probable;
ETSI
7 ETSI EN 300 019-1-3 V2.2.2 (2004-07)
- with normal levels of contaminants experienced in urban areas with industrial activities scattered over the
whole area and/or with heavy traffic;
- without special precautions to minimize the presence of sand or dust, but which are not situated in proximity to
sources of sand or dust;
- with insignificant vibration and shock.
The conditions of this class may be found in:
- normal living or working areas, e.g. living rooms, rooms for general use (theatres, restaurants);
- offices;
- shops;
- workshops for electronic assemblies and other electrotechnical products;
- telecommunication centres;
- storage rooms for valuable and sensitive products.

Normal Conditions
-10
1,5
Exceptional Conditions
-20
0  10 20  30  40  50  60 70 80 90 100
Relative Air Humidity [%]
Values outside this field have a probability of occurrence of
less than 10 % (see IEC 60721-3-0).
Exceptional climatic limits.
Normal climatic limits: Values outside these limits have a probability of
occurrence of less than 1 % .
NOTE: Exceptional conditions may occur following the failure of the temperature controlling system. This is
described as 3.1E in the tables but it should be noted that there is no separate class 3.1E.

Figure 1: Climatogram for Class 3.1: Temperature-controlled locations
4.2 Class 3.2: Partly temperature-controlled locations
This class is a combination of classes 3K5/3Z2/3Z4/3B2/3C2(3C1)/3S3/3M2 in IEC 60721-3-3 [1] .
Seismic environment: zone 4 as defined in IEC 60721-2-6 [3]. Option zone 4 (modified Mercalli scale ≥ 9): if earthquake
conditions are specified by the customer, the conditions stated in clause 5.6 apply.
ETSI
Air Temperature [°C]
Absolute Air Humidity [g/m³]
8 ETSI EN 300 019-1-3 V2.2.2 (2004-07)
This class applies to an enclosed location having neither temperature nor humidity control. The climatogram is shown
in figure 2.
Heating may be used to raise low temperatures especially where there is a significant difference between the conditions
of this class and the open-air climate. Building construction is designed to avoid extremely high temperatures.
This class applies to locations:
- where installed equipment may be exposed to solar radiation and heat radiation. They may also be exposed to
movements of the surrounding air due to draughts in buildings, e.g. through open windows. They may be
subjected to condensed water. They are not subjected to precipitation;
- where mould growth or attacks by animals, except termites, may occur;
- with normal levels of contaminants experienced in urban areas with industrial activities scattered over the
whole area and/or with heavy traffic;
- in close proximity to sources of sand or dust;
- with vibration of low significance, e.g. for products fastened to light supporting structures subjected to
negligible vibrations.
The conditions of this class may be found in:
- entrances and staircases of buildings;
- garages;
- cellars;
- certain workshops;
- buildings in factories and industrial process plants;
- unattended equipment stations;
- certain telecommunication buildings;
- ordinary storage rooms for frost resistant products and farm buildings, etc.

-10
-20
0 10 2030 4050 60 708090 100
Relative Air Humidity [%]
Figure 2: Climatogram for class 3.2: Partly temperature-controlled locations
ETSI
Air Temperature [°C]
Absolute Air Humidity [g/m ]
9 ETSI EN 300 019-1-3 V2.2.2 (2004-07)
4.3 Class 3.3: Not temperature-controlled locations
This class is a combination of classes 3K6/3Z2/3Z4/3Z7/3B2/3C2(3C1)/3S3/3M2 in IEC 60721-3-3 [1].
Seismic environment: zone 4 as defined in IEC 60721-2-6 [3], Option zone 4 (modified Mercalli scale ≥ 9): if earthquake
conditions are specified by the customer, the conditions stated in clause 5.6 apply.
This class applies to a weatherprotected location having neither temperature nor humidity control. The location may
have openings directly to the open air, i.e. may be only partially-weather protected. The climatogram is shown in
figure 3.
The climatic conditions of this class may be affected to a varying extent by the conditions of the open-air climate and
the construction of the building.
This class applies to locations:
- where installed equipment may be exposed to solar radiation and temporarily to heat radiation. It may also be
exposed to movements of the surrounding air due to draughts e.g. through doors, windows or other openings.
It
...