Fire detection and fire alarm systems - Part 21: Alarm transmission and fault warning routing equipment

This European Standard specifies requirements, test methods and performance criteria against which the effectiveness and reliability of routing equipment capable of transmitting fire alarm and/or fault warning signals for use with fire detection and fire alarm systems installed in buildings can be assessed (see EN 54-1). The routing equipment is designed to allow the system to function in accordance with the requirements of this European Standard. It also provides for the evaluation of conformity of the equipment to the requirements of this standard.

Brandmeldeanlagen - Teil 21: Übertragungseinrichtungen für Brand- und Störungsmeldungen

Diese Europäische Norm legt Anforderungen, Prüfverfahren und Leistungsmerkmale fest, hinsichtlich derer
die Wirksamkeit und Zuverlässigkeit von Übertragungseinrichtungen für Brandmelde- und/oder Störungs-signale
zur Verwendung in Verbindung mit Brandmeldeanlagen in Gebäuden bewertet werden können (siehe
EN 54-1). Übertragungseinrichtungen sind vorgesehen, um zu ermöglichen, dass die Anlage entsprechend
den Anforderungen dieser Europäischen Norm funktioniert. Die Norm dient ebenfalls der Bewertung der
Konformität der Einrichtungen mit den Anforderungen dieser Norm.

Systemes de détection et d'alarme incendie - Partie 21 : Dispositif de transmission de l'alarme feu et du signal de dérangement

La présente Norme européenne spécifie les exigences, les méthodes d’essai et les critères de performance
par rapport auxquels peuvent être évaluées l’efficacité et la fiabilité de l’équipement de transmission capable
de transmettre les signaux d’alarme incendie et/ou de dérangement à utiliser dans les systèmes de détection
et d’alarme incendie installés dans des bâtiments (voir l’EN 54-1). L’équipement de transmission est conçu
pour permettre au système de fonctionner conformément aux exigences de la présente Norme européenne. Il
prévoit également l’évaluation de la conformité de l’équipement aux exigences de la présente norme.

Sistemi za odkrivanje in javljanje požara ter alarmiranje - 21. del: Oprema za usmerjanje alarma in opozoril o napakah

General Information

Status
Published
Publication Date
30-Jun-2006
Technical Committee
POZ - Požarna varnost
Current Stage
6060 - National Implementation/Publication (Adopted Project)
Start Date
01-Jul-2006
Due Date
01-Jul-2006
Completion Date
01-Jul-2006

Relations

Effective Date
01-Jul-2006
Effective Date
08-Mar-2023
Effective Date
22-Dec-2008

Overview

EN 54-21:2006 is a CEN European standard for alarm transmission and fault warning routing equipment used with fire detection and fire alarm systems. It specifies the requirements, test methods and performance criteria to assess the effectiveness and reliability of routing equipment that transmits fire alarm and/or fault warning signals in buildings. EN 54-21 supports conformity assessment and the correct functioning of fire alarm systems in accordance with EN 54 series requirements.

Key Topics

  • Scope and purpose
    • Assessment of routing equipment that forwards alarm and fault signals from fire detection systems.
    • Evaluation of conformity to EN 54-21 requirements.
  • Functional requirements
    • Behavioural criteria for alarm transmission routing and fault warning routing equipment, including signal indication and reporting functions.
  • Design requirements
    • Manufacturer declarations, documentation, mechanical and electrical design, accessibility of controls and indicators, colour/light signalling requirements.
  • Software-controlled equipment
    • Additional documentation, software design, program monitoring, storage and memory integrity for devices that rely on embedded software.
  • Power supply and marking
    • Requirements for power sources and labelling for safe and reliable operation.
  • Testing and performance verification
    • Comprehensive test program covering functional tests, environmental tests (cold, damp heat, impact, vibration), EMC immunity, supply voltage variation and endurance tests.
  • Performance metrics
    • Transmission time, reporting time and availability criteria (see normative Annexes A and B).
  • Conformity and regulatory linkage
    • Clauses addressing conformity assessment and relationship to EU Construction Products Directive (informative Annex ZA).

Applications

EN 54-21 is used to:

  • Evaluate and select alarm transmission equipment and fault routing devices for commercial, institutional and industrial buildings.
  • Guide manufacturers in product design, documentation and software management to meet European conformity.
  • Support installers, fire system designers and specifiers when integrating routing equipment with EN 54 fire alarm systems.
  • Provide test houses and certification bodies with test methods for performance verification and CE marking.

Who benefits:

  • Manufacturers, testing laboratories, certification bodies, fire safety consultants, system integrators and building owners concerned with reliable alarm transmission.

Related Standards

EN 54-21 complements other standards including:

  • EN 54-1, EN 54-2, EN 54-4 (fire alarm system parts)
  • EN 50136-1-1, EN 50136-2-1 (alarm transmission systems)
  • EN 50130-4, EN 60068 series (EMC and environmental testing)
  • EN 60529 (IP code)

Keywords: EN 54-21, alarm transmission, fault warning routing equipment, fire detection, fire alarm systems, CEN, testing, conformity.

Frequently Asked Questions

SIST EN 54-21:2006 is a standard published by the Slovenian Institute for Standardization (SIST). Its full title is "Fire detection and fire alarm systems - Part 21: Alarm transmission and fault warning routing equipment". This standard covers: This European Standard specifies requirements, test methods and performance criteria against which the effectiveness and reliability of routing equipment capable of transmitting fire alarm and/or fault warning signals for use with fire detection and fire alarm systems installed in buildings can be assessed (see EN 54-1). The routing equipment is designed to allow the system to function in accordance with the requirements of this European Standard. It also provides for the evaluation of conformity of the equipment to the requirements of this standard.

This European Standard specifies requirements, test methods and performance criteria against which the effectiveness and reliability of routing equipment capable of transmitting fire alarm and/or fault warning signals for use with fire detection and fire alarm systems installed in buildings can be assessed (see EN 54-1). The routing equipment is designed to allow the system to function in accordance with the requirements of this European Standard. It also provides for the evaluation of conformity of the equipment to the requirements of this standard.

SIST EN 54-21:2006 is classified under the following ICS (International Classification for Standards) categories: 13.220.20 - Fire protection; 13.320 - Alarm and warning systems. The ICS classification helps identify the subject area and facilitates finding related standards.

SIST EN 54-21:2006 has the following relationships with other standards: It is inter standard links to OSIST prEN 54-21:2004, OSIST prEN 54-21:2004; is excused to OSIST prEN 54-21:2004. Understanding these relationships helps ensure you are using the most current and applicable version of the standard.

SIST EN 54-21:2006 is associated with the following European legislation: EU Directives/Regulations: 2012-01-0929, 2020-01-0063, 305/2011, 89/106/EEC, EUR-PUB; Standardization Mandates: M/109. When a standard is cited in the Official Journal of the European Union, products manufactured in conformity with it benefit from a presumption of conformity with the essential requirements of the corresponding EU directive or regulation.

You can purchase SIST EN 54-21:2006 directly from iTeh Standards. The document is available in PDF format and is delivered instantly after payment. Add the standard to your cart and complete the secure checkout process. iTeh Standards is an authorized distributor of SIST standards.

Standards Content (Sample)


2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.Fire detection and fire alarm systems - Part 21: Alarm transmission and fault warning routing equipmentSistemi za odkrivanje in javljanje požara ter alarmiranje - 21. del: Oprema za usmerjanje alarma in opozoril o napakahSystemes de détection et d'alarme incendie - Partie 21 : Dispositif de transmission de l'alarme feu et du signal de dérangementBrandmeldeanlagen - Teil 21: Übertragungseinrichtungen für Brand- und StörungsmeldungenTa slovenski standard je istoveten z:EN 54-21:2006SIST EN 54-21:2006en13.32013.220.20ICS:OSIST prEN 54-21:20041DGRPHãþDSLOVENSKI
STANDARDSIST EN 54-21:200601-julij-2006

EUROPEAN STANDARDNORME EUROPÉENNEEUROPÄISCHE NORMEN 54-21May 2006ICS 13.220.20 English VersionFire detection and fire alarm systems - Part 21: Alarmtransmission and fault warning routing equipmentSystèmes de détection et d'alarme incendie - Partie 21 :Dispositif de transmission de l'alarme feu et du signal dedérangementBrandmeldeanlagen - Teil 21: Übertragungseinrichtungenfür Brand- und StörungsmeldungenThis European Standard was approved by CEN on 27 April 2006.CEN members are bound to comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this EuropeanStandard the status of a national standard without any alteration. Up-to-date lists and bibliographical references concerning such nationalstandards may be obtained on application to the Central Secretariat or to any CEN member.This European Standard exists in three official versions (English, French, German). A version in any other language made by translationunder the responsibility of a CEN member into its own language and notified to the Central Secretariat has the same status as the officialversions.CEN members are the national standards bodies of Austria, Belgium, Cyprus, Czech Republic, Denmark, Estonia, Finland, France,Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Romania,Slovakia, Slovenia, Spain, Sweden, Switzerland and United Kingdom.EUROPEAN COMMITTEE FOR STANDARDIZATIONCOMITÉ EUROPÉEN DE NORMALISATIONEUROPÄISCHES KOMITEE FÜR NORMUNGManagement Centre: rue de Stassart, 36
B-1050 Brussels© 2006 CENAll rights of exploitation in any form and by any means reservedworldwide for CEN national Members.Ref. No. EN 54-21:2006: E

Performance requirements for alarm and fault warning transmission systems.24 Annex B (normative)
Verification of performance requirements for alarm and fault warning transmission systems.25 B.1 General.25 B.2 Transmission time.25 B.3 Reporting time.25 B.4 Availability.25 Annex C (informative)
Design requirements for software controlled routing equipments.26 Annex ZA (informative)
Clauses of this European Standard addressing the provisions of the EU Construction Products Directive (89/106/EEC).27 ZA.1 Scope and relevant clauses.27 ZA.2 Procedures for the attestation of conformity of alarm transmission and fault warning routing equipment covered by this standard.28 ZA.2.1 System of attestation of conformity.28 ZA.2.2 Evaluation of conformity.28 ZA.3 CE marking and labelling and accompanying documentation.32 ZA.4 EC certificate and declaration of conformity.34

1 Scope This European Standard specifies requirements, test methods and performance criteria against which the effectiveness and reliability of routing equipment capable of transmitting fire alarm and/or fault warning signals for use with fire detection and fire alarm systems installed in buildings can be assessed (see EN 54-1). The routing equipment is designed to allow the system to function in accordance with the requirements of this European Standard. It also provides for the evaluation of conformity of the equipment to the requirements of this standard. 2 Normative references The following referenced documents are indispensable for the application of this document. For dated references, only the edition cited applies. For undated references, the latest edition of the referenced document (including any amendments) applies. EN 54-1:1996, Fire detection and fire alarm systems — Part 1: Introduction EN 54-2:1997, Fire detection and fire alarm systems — Part 2: Control and indicating equipment EN 54-4:1997, Fire detection and fire alarm systems — Part 4: Power supply equipment EN 50130-4, Alarm systems — Part 4: Electromagnetic compatibility — Product family standard: Immunity requirements for components of fire, intruder and social alarm systems EN 50136-1-1:1998, Alarm systems — Alarm transmission systems and equipment — Part 1-1: General requirements for alarm transmission systems EN 50136-2-1:1998, Alarm systems — Alarm transmission systems and equipment — Part 2-1: General requirements for alarm transmission equipment EN 60068-1, Environmental testing - Part 1: General and guidance (IEC 60068-1:1988 + Corrigendum 1988 + A1:1992) EN 60068-2-1, Environmental testing; part 2: tests; tests A: cold (IEC 60068-2-1:1990) EN 60068-2-6, Environmental testing - Part 2: Tests - Tests Fc: Vibration (sinusoidal) (IEC 60068-2-6:1995 + Corrigendum 1995) EN 60068-2-47, Environmental testing - Part 2-47: Test Mounting of specimens for vibration, impact and similar dynamic tests (IEC 60068-2-47:2005) EN 60068-2-75, Environmental testing - Part 2: Tests - Test Eh: Hammer tests
(IEC 60068-2-75:1997) EN 60068-2-78, Environmental testing - Part 2-78: Tests; Test Cab: Damp heat, steady state (IEC 60068-2-78:2001) EN 60529:1991, Degrees of protection provided by enclosures (IP code) (IEC 60529:1989) EN 60721-3-3:1995, Classification of environmental conditions - Part 3: Classification of groups of environmental parameters and their severities - Section 3: Stationary use at weatherprotected locations (IEC 60721-3-3:1994) EN ISO 9001:2000, Quality management systems — Requirements (ISO 9001:2000).

Control and indicating equipment, PSE: Power supply equipment. 4 General requirements 4.1 General If functions other than those specified in this European Standard are provided, they shall not jeopardize the compliance with any requirements of this European Standard. 4.2 Compliance In order to comply with this standard the routing equipment shall meet the requirements of this clause, which shall be verified by visual inspection or engineering assessment, shall be tested as described in Clause 5 and shall meet the requirements of the tests. 5 Functional requirements 5.1 Alarm transmission routing equipment The alarm transmission routing equipment shall be capable of processing the following signals: a) receiving fire alarm signal from the CIE, b) transmitting fault warning signals to the CIE, c) receiving fault warning signals from the transmission network, d) transmitting fire alarm signal to the fire alarm receiving centre, e) receiving acknowledgement signal from the alarm receiving centre, f) transmitting acknowledgement to the CIE. 5.2 Fault warning routing equipment The fault warning routing equipment shall be capable of processing the following signals: a) receiving fault warning signal from the CIE, b) transmitting fault warning signals to the CIE,

7.10.5.1 All executable code and data necessary to comply with this European Standard shall be held in memory which is capable of continuous, non-maintained, reliable operation for a period of at least 10 years. 7.10.5.2 For the program, the following requirements shall apply: a) the program shall be held in non-volatile memory, which can only be written to at access level 4; b) it shall be possible to identify the version reference or references of the program at access level 3. The version reference or references shall be in accordance with the documentation of 7.10.2.1. 7.10.5.3 For site specific data, the following requirements shall apply: a) the alteration of site specific data shall only be possible at access level 3 or 4; b) the alteration of site specific data shall not affect the structure of the program; c) if stored in volatile memory, the site-specific data shall be protected against power loss by a back-up energy source which can only be separated from the memory at access level 4, and which is capable of maintaining the memory contents for at least 2 weeks; d) if stored in read-write memory, there shall be a mechanism which prevents the memory being written to during normal operation at access level 1 or 2, such that its contents are protected during a failure in program execution;

15 °C – 35 °C, Relative humidity:
25 % – 75 %, Air pressure:
86 kPa –106 kPa. The temperature and humidity shall be substantially constant for each environmental test where the standard atmospheric conditions are applied.

(-5 ± 3) °C, Duration:
16 h. 10.4.2.5 Measurements during conditioning Monitor the specimen during the conditioning period to detect any change in status. During the last hour of the conditioning period, subject the specimen to the functional test. 10.4.2.6 Final measurements After the recovery period, subject the specimen to the functional test and inspect it visually for mechanical damage both externally and internally. 10.5
Damp heat, steady state (operational) 10.5.1 Object of the test The object of the test is to demonstrate the ability of the specimen to function correctly at high relative humidity (without condensation), which may occur for short periods in the service environment. 10.5.2 Test procedure 10.5.2.1 General Use the test procedure described in EN 60068-2-78. 10.5.2.2 Initial examination Before conditioning, subject the specimen to the functional test. 10.5.2.3 State of the specimen during conditioning Mount the specimen as specified in 10.1.3 and connect it to suitable power supply, monitoring and loading equipment (see 10.1.4). The specimen shall be in the quiescent condition. 10.5.2.4 Conditioning Apply the following severity of conditioning: Temperature:
(40 ± 2) °C, Relative humidity:
(93 23+−) %, Duration:
4 days. Pre-condition the specimen at the conditioning temperature (40 ± 2) °C until temperature stability has been reached, to prevent the formation of water droplets on the specimen.
...

Questions, Comments and Discussion

Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.

Loading comments...

SIST EN 54-21:2006 표준은 화재 탐지 및 화재 경보 시스템에 관한 중요한 요구사항을 구체적으로 명시하고 있습니다. 이 표준은 화재 신호 및 결함 경고 신호를 전송할 수 있는 라우팅 장비의 효과성과 신뢰성을 평가하기 위한 요구사항, 시험 방법 및 성능 기준을 제공합니다. 이 표준의 강점은 화재 탐지 및 경보 시스템이 설치된 건물에서 사용되는 장비의 검증을 가능하게 한다는 점입니다. SIST EN 54-21:2006는 라우팅 장비가 이 유럽 표준의 요구사항에 따라 기능할 수 있도록 설계되어 있어, 실질적인 감지와 경고 기능을 수행하는 데 필요한 신뢰성을 보장합니다. 또한, 이 표준은 장비가 요구사항에 부합하는지를 평가할 수 있는 기준을 제공하여, 사용자가 시스템의 신뢰성을 높일 수 있는 방안을 제시합니다. 이러한 점에서 SIST EN 54-21:2006은 화재 안전 시스템의 효율성을 극대화하는 데 필수적인 문서입니다. 결론적으로, SIST EN 54-21:2006 표준은 화재 경보 및 경고 전송 장비의 성능과 신뢰성을 확보하기 위한 중요한 기준을 제시하며, 이를 통해 화재 안전 분야에서의 응용 가능성을 높입니다.

The SIST EN 54-21:2006 standard provides a comprehensive framework for evaluating alarm transmission and fault warning routing equipment in fire detection and fire alarm systems. Its scope is clearly defined, focusing on the requirements, test methods, and performance criteria essential for ensuring effective and reliable operation within these systems. One of the key strengths of this standard is its emphasis on testing methodologies that ensure robustness in performance. By outlining clear criteria for assessing routing equipment, it facilitates the identification of reliable devices that can transmit critical fire alarm and fault warning signals, thus enhancing overall safety in building environments. This is particularly important given the life-critical nature of fire alarm systems, where timely communication can prevent catastrophic outcomes. Furthermore, the standard incorporates guidelines for assessing conformity, which is crucial for manufacturers and installers of fire detection systems. The ability to verify that routing equipment aligns with the specified performance criteria not only helps in maintaining high safety standards but also supports regulatory compliance across different jurisdictions. This aspect of the standard underscores its relevance in promoting not only safety but also quality assurance within the industry. Additionally, the connection to EN 54-1 emphasizes the integration and compatibility of the routing equipment with wider fire detection systems. This ensures that all components function cohesively, contributing to the system's overall efficacy. Such interoperability is a significant advantage for system designers and engineers who strive for seamless integration in safety solutions. Overall, the SIST EN 54-21:2006 stands out as an essential document for stakeholders in the fire safety industry, providing a solid foundation for the implementation and assessment of alarm transmission and fault warning systems. Its focus on requirements, testing, and conformity not only enhances the reliability of fire detection mechanisms but also fosters a culture of safety and accountability in building management practices.

SIST EN 54-21:2006は、火災探知および火災警報システムにおける警報伝送および故障警告ルーティング装置に関するヨーロッパの標準です。この標準は、建物に設置された火災探知および火災警報システムと共に使用されるルーティング装置に対する要件、試験方法、および性能基準を規定しています。つまり、火災警報や故障警告信号を伝送する能力を持つ装置の効果と信頼性を評価するための指針を提供します。 この標準の強みは、まずその包括的な範囲にあります。火災探知および警報システムに関連する技術的要求を明確にし、性能基準を設定することで、智慧的なシステム設計を促進しています。さらに、この標準は、ルーティング装置が適切に機能するための基準を提供することにより、ユーザーの安全性を高める役割も果たします。 加えて、SIST EN 54-21:2006は、ルーティング装置の適合性評価を可能にするための枠組みを整えており、この評価プロセスは、製品の品質と信頼性を保証する重要な要素です。これにより、利用者は信頼性のある火災警報システムを確保することが可能になります。 この標準は、特に消防関連の業界において非常に重要であり、火災探知および火災警報システムの設計・実装に関わるすべての専門家にとっての必須文書となっています。したがって、SIST EN 54-21:2006は、その適用範囲の広さや評価の基準としての信頼性によって、多くの建物における火災安全確保に貢献し続けています。