SIST EN 1457-1:2012
(Main)Chimneys - Clay/ceramic flue liners - Part 1: Flue liners operation under dry conditions - Requirements and test methods
Chimneys - Clay/ceramic flue liners - Part 1: Flue liners operation under dry conditions - Requirements and test methods
This European Standard is a product standard for clay/ceramic flue liners operating under dry conditions with solid walls or walls with vertical perforations for use in the construction of multiwall chimneys and flue pipes which serve to convey products of combustion from fireplaces or heating appliances to the outside atmosphere by negative or positive pressure. It includes the flue liners used for domestic and industrial chimneys which are not structurally independent (free-standing). This European Standard specifies the performance requirements for factory made flue liners and chimney fittings. Testing including thermal testing with or without insulation, marking and inspection are covered by this standard. This part does not cover flue liners operating under wet conditions.
Abgasanlagen - Keramik-Innenrohre - Teil 1: Innenrohre im Trockenbetrieb - Anforderungen und Prüfungen
Diese Europäische Norm ist eine Produktnorm für Keramik-Innenrohre mit massiven oder vertikal gelochten Wandungen, die in mehrschaligen Abgasanlagen unter trockenen Bedingungen verwendet werden und die dazu dienen, Verbrennungsprodukte von Feuerstätten oder Wärmeerzeuger durch Über- oder Unterdruck an die Außenluft abzuleiten. Diese Norm behandelt Innenrohre für Haus- und Industrieabgasanlagen, die nicht freistehend sind. Diese Norm enthält Festlegungen der Leistungsanforderungen an werkmäßig hergestellte Innenrohre und Formstücke. Sie enthält ferner die Anforderungen an die thermische Prüfung mit oder ohne Wärmedämmung, an die Kennzeichnung und die Qualitätskontrolle. Dieser Teil gilt nicht für Innenrohre in feuchter Betriebsweise.
Conduits de fumée - Conduits intérieurs en terre cuite/céramique - Partie 1 : Exigences et méthodes d'essai pour utilisation en conditions sèches
La présente Norme Européenne est une norme de produit relative aux conduits intérieurs en terre cuite/céramique
fonctionnant dans des conditions sèches munis de parois pleines ou de parois à alvéoles verticales, utilisés dans la
construction des conduits de fumée à parois multiples et des conduits de raccordement destinés à évacuer dans
l’atmosphère, sous une pression négative ou positive, les produits de combustion produits par les foyers de
cheminées ou les générateurs de chaleur. La présente Norme européenne comprend les conduits intérieurs à
usage domestique et les conduits de fumée industriels qui ne sont pas structurellement indépendants (autostables).
La présente Norme Européenne spécifie les exigences de performance des conduits intérieurs et des
raccords fabriqués en usine. La présente norme couvre les essais, comprenant les essais de choc thermique avec
ou sans isolation, le marquage et le contrôle. La présente partie ne traite pas des conduits intérieurs pour utilisation
en conditions humides.
Dimniki - Keramične tuljave - 1. del: Tuljave za delovanje v suhih razmerah - Zahteve in preskusne metode
Ta evropski standard je standard za izdelek za keramične tuljave za delovanje v suhih razmerah s trdnimi stenami ali stenami z navpičnimi perforacijami, ki se uporabljajo pri gradnji večslojnih dimnikov in dimniških priključkov, ki so namenjeni odvajanju produktov gorenja iz kaminov ali grelnih naprav v ozračje po principu negativnega ali pozitivnega tlaka. Vključuje tuljave, ki se uporabljajo za dimnike v gospodinjstvih in industriji in niso strukturno neodvisni (samostoječi). Ta standard določa zahteve glede zmogljivosti za tovarniško izdelane tuljave in fitinge za dimnike. Zajema preskušanje, vključno s toplotnim preskušanjem z izolacijo ali brez nje, označevanje in nadzor.
General Information
Relations
Standards Content (Sample)
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.Abgasanlagen - Keramik-Innenrohre - Teil 1: Innenrohre im Trockenbetrieb - Anforderungen und PrüfungenConduits de fumée - Conduits intérieurs en terre cuite/céramique - Partie 1 : Exigences et méthodes d'essai pour utilisation en conditions sèchesChimneys - Clay/ceramic flue liners - Part 1: Flue liners operation under dry conditions - Requirements and test methods91.060.40Dimniki, jaški, kanaliChimneys, shafts, ductsICS:Ta slovenski standard je istoveten z:EN 1457-1:2012SIST EN 1457-1:2012en,fr,de01-maj-2012SIST EN 1457-1:2012SLOVENSKI
STANDARDSIST EN 1457:1999/A1:2003/AC:2007SIST EN 1457:1999/AC:1999SIST EN 1457:1999SIST EN 1457:1999/A1:20031DGRPHãþD
EUROPEAN STANDARD NORME EUROPÉENNE EUROPÄISCHE NORM
EN 1457-1
January 2012 ICS 91.060.40 Supersedes EN 1457:1999English Version
Chimneys - Clay/ceramic flue liners - Part 1: Flue liners operating under dry conditions - Requirements and test methods Conduits de fumée - Conduits intérieurs en terre cuite/céramique - Partie 1: Exigences et méthodes d'essai pour utilisation en conditions sèches
Abgasanlagen - Keramik-Innenrohre - Teil 1: Innenrohre für Trockenbetrieb - Anforderungen und Prüfungen This European Standard was approved by CEN on 16 December 2011.
CEN members are bound to comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this European Standard the status of a national standard without any alteration. Up-to-date lists and bibliographical references concerning such national standards may be obtained on application to the CEN-CENELEC Management Centre or to any CEN member.
This European Standard exists in three official versions (English, French, German). A version in any other language made by translation under the responsibility of a CEN member into its own language and notified to the CEN-CENELEC Management Centre has the same status as the official versions.
CEN members are the national standards bodies of Austria, Belgium, Bulgaria, Croatia, Cyprus, Czech Republic, Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland, Turkey and United Kingdom.
EUROPEAN COMMITTEE FOR STANDARDIZATION
COMITÉ EUROPÉEN DE NORMALISATION EUROPÄISCHES KOMITEE FÜR NORMUNG
Management Centre:
Avenue Marnix 17,
B-1000 Brussels © 2012 CEN All rights of exploitation in any form and by any means reserved worldwide for CEN national Members. Ref. No. EN 1457-1:2012: ESIST EN 1457-1:2012
Sampling procedures for an AQL of 10 % and inspection level S2 . 30A.1 Acceptability determination . 30A.1.1 Single sampling . 30A.1.2 Double sampling . 30A.2 Normal inspection . 30A.3 Normal to reduced inspection . 31A.4 Reduced to normal inspection . 32A.5 Tightened inspection . 32A.6 Tightened to normal inspection . 32A.7 Discontinuation of inspection . 32Annex B (normative)
Thermal resistance . 33B.1 Method 1: simplified calculation for flue liners without cavities . 33B.2 Method 2: thermal resistance of flue liners with or without cavities . 33B.2.1 General . 33B.2.2 Data . 34B.2.3 Specific conditions for the cavities . 35B.2.4 Calculations . 38B.3 Method Approximate thermal resistance values . 38Annex C (normative)
Measurement of the coefficient of friction of chimneys . 40SIST EN 1457-1:2012
Comparison with designation given in EN 1443:2003 . 42Annex ZA (informative)
Clauses of this European Standard addressing the provisions of the EU Construction Products Directive . 43ZA.1 Scope and relevant characteristics . 43ZA.2 Procedure of attestation of conformity of clay/ceramic flue liners and fittings . 44ZA.2.1 System of attestation of conformity . 44ZA.2.2 EC Certificate and Declaration of conformity . 45ZA.3 CE Marking and labelling . 46Bibliography . 49 SIST EN 1457-1:2012
EN 1457 has been split in 2 parts: EN 1457-1 is a product standard for clay/ceramic flue liners operating under dry conditions. According to the CEN/CENELEC Internal Regulations, the national standards organizations of the following countries are bound to implement this European Standard: Austria, Belgium, Bulgaria, Croatia, Cyprus, Czech Republic, Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland, Turkey and the United Kingdom.
EN 1443:2003, Chimneys — General requirements EN 10088-1, Stainless steels — Part 1: List of stainless steels EN 14297:2004, Chimneys — Freeze-thaw resistance test method for chimney products EN ISO 6946, Building components and building elements Thermal resistance and thermal transmittance Calculation method (ISO 6946) EN ISO 7500-1, Metallic materials — Verification of static uniaxial testing machines — Part 1: Tension/compression testing machines — Verification and calibration of the force-measuring system (ISO 7500-1) ISO 2859-1, Sampling procedures for inspection by attributes — Part 1: Sampling schemes indexed by acceptance quality limit (AQL) for lot-by-lot inspection 3 Terms and definitions For the purposes of this document, the terms and definitions given in EN 1443:2003 and the following apply. 3.1 nominal size numerical designation of size which is a convenient round number equal to or approximately equal to either: a) the internal diameter in millimetres of circular flue liners; b) the internal width in millimetres of square flue liners; c) the internal width and breadth in millimetres of the cross section of rectangular flue liners 3.2 nominal height numerical designation of the internal height in millimetres of a straight flue liner which is a convenient round number approximately equal to the internal height of the flue liner
NOTE See Figure 1. SIST EN 1457-1:2012
Key 1 internal height Figure 1 — Internal height 3.3 nominal angle of curvature angle subtended in degrees by a curved flue liner at the centre of the curve
NOTE See Figure 2.
Key 1 angle of curvature 2 curved flue liner Figure 2 — Angle of curvature 3.4 wet operating condition condition when the chimney is designed to operate normally with the temperature of the inner surface of the flue liner above the water dew point 3.5 dry operating condition condition when the chimney is designed to operate normally with the temperature of the inner surface of the flue liner at and below the water dew point SIST EN 1457-1:2012
Square Rectangular Circular Wall with vertical perforations Figure 3 — Examples of cross-section configuration
Rebated Spigot & socket Sleeve Tapered Figure 4 — Joint configuration 4.2 Inspection openings and chimney junctions
Inspection openings are used for inspection and cleaning of the inner liners of chimneys and for soot removal and shall meet the requirements of flue liners as appropriate. Chimney junctions are used to connect flues from heat appliances to chimneys. Chimney junctions are purpose-made tee-pieces or inner liner sections with an opening to which branches are fitted. The branch SIST EN 1457-1:2012
For chimneys with area greater than 0,04 m2
the following equation shall be used: F = χ⋅H·G/100 (1) SIST EN 1457-1:2012
When flue liners are tested for soot fire resistance, thermal shock testing need not be carried out. 9.2.2 Final gas tightness after sootfire testing When tested in accordance with 16.8 flue liners A1 and B1 shall have a leakage rate after sootfire testing not greater than the values given in Table 3 for the appropriate type of flue liner, test temperature and differential pressure. Flue liners shall be tested with insulation as described in 16.8.3 or they shall be tested without insulation. If they are tested without insulation they shall be marked accordingly. The precision for the appropriate testing differential pressure is that given in 9.1. 9.2.3 Final gas tightness after thermal shock testing When tested in accordance with 16.8 flue liners not included in 9.2 shall have a leakage rate after thermal shock testing not greater than the values given in Table 3 for the appropriate type of flue liner, test temperature and differential pressure. Flue liners shall be tested with insulation as described in 16.8.3 or they shall be tested without insulation. If they are tested without insulation they shall be marked accordingly. SIST EN 1457-1:2012
10 Durability 10.1 Corrosion resistance When tested in accordance with 16.9, the mass loss from any test piece shall not exceed a mass loss of 5 %. NOTE This is an accelerated test to represent a corrosion resistance and practical installed life of at least 100 years. 10.2 Freeze/Thaw resistance Where national regulations require freeze/thaw resistance of flue liners, they shall be tested according to EN 14297. The product shall not present any damage of type 7, 8, 9 and 10 in accordance with EN 14297:2004, Table 1. 11 Water absorption and bulk density 11.1 General The flue liner body shall be tested for either water absorption or bulk density for production control. 11.2 Water absorption When tested in accordance with 16.10, the mean water absorption values expressed as a percentage of five samples shall not vary more than ± 2,5 % from the mean value obtained from the last type test. SIST EN 1457-1:2012
14 Thermal resistance The values of thermal resistance of flue liners shall be declared by the manufacturer for a flue temperature of 200 °C. The reference calculation method for flue liners without cavities shall be as given in B.1, and the reference calculation method for flue liners with cavities shall be as given in B.2. 15 Evaluation of conformity 15.1 General The compliance of the clay/ceramic flue liners under dry conditions with the requirements of this European Standard and with the declared values (including classes) shall be demonstrated by: initial type testing; factory production control by the manufacturer, including product assessment. 15.2 Initial type testing All characteristics are subject to Initial type testing. It is also recommended to make reference to the use of historical data. “Tests previously performed on the same products in accordance with the provisions of this standard (same characteristic(s), test method, sampling procedure, system of attestation of conformity, etc.) may be taken into account." Type tests relating to material composition shall be performed initially together with factory production control tests as given in Table 4. One test shall be carried out for each requirement. The thermal testing shall be carried out on one size of flue liner for each geometrical configuration e.g. circular, square, rectangular. For circular flue liners the size to be tested shall be 200 mm ± 50 mm internal diameter. For other geometrical configurations the flue liner shall have an equivalent cross-sectional area range. 15.3 Further type tests Type tests shall be performed when a change is made either in material composition, processing technique or the design or method of manufacture of the flue liner, but they may be performed more frequently by incorporation into a plan for monitoring the consistency of manufacture (see Table 4). SIST EN 1457-1:2012
Relevant requirement clauses Item Factory production control 15.4 a Initial type tests 15.2 and 15.3 Straight flue liners 7.1, 7.2, 7.4, 7.5, 7.6, 11 8.1, 9.2, 10, 12, and 13 Flue liner bends 7.1, 7.3, 11 8.2, 10 Opening section 7.1, 7.2, 11 8.3 a The tests carried out during FPC are intended to verify that the performance requirements assessed through the initial type testing are maintained.
16 Test methods 16.1 Size The maximum and minimum diameters of a clay/ceramic flue liner shall be those calculated from the tolerances given in 7.1. If direct measurement is to be carried out, two measurements should be taken at the observed maximum and minimum diameters. The test also may be carried out by using two gauges whose diameters are set at the minimum and maximum diameters. The minimum gauges should be able to be turned through 360° within the ends of the flue liner. The maximum gauge should not be able to enter the flue liner when tested through a rotation of 360°. For square and rectangular flue liners, the internal cross-section dimensions shall be measured between the mid-points of opposite sides of the flue liners. 16.2 Height The maximum and minimum internal height of a clay/ceramic flue liner shall be those calculated from the tolerances given in 7.2. If direct measurement is to be carried out, two measurements should be taken at the observed maximum and minimum heights. The test can also be carried out by using two gauges whose heights are set at the minimum and maximum internal heights. The minimum gauges should be not able to fit over the internal height of the flue liner SIST EN 1457-1:2012
Key H is the nominal height of the flue liner, in millimetres L is the test length, in millimetres D is the deviation from straightness, in millimetres H - L = 150 mm Figure 6 — Deviation from straightness 16.5 Squareness of ends The test gauge as shown in Figure 7 with one arm set at a slope of 30 mm/m to the other shall be provided with two pairs of supports at (50 ± 5) mm centres. The end support shall be positioned so that there is a recess of (30 ± 5) mm from the inside of the angled arm. The slope of the supports shall be such as to provide a clearance of at least 5 mm under the test gauge. The angled arm shall be of such a length as to span the outside diameter/width of the flue liner. The gauge shall be placed on the end of the flue liner, at the line of the longest external measurement of the flue liner. The slope of the end shall be checked against that of the gauge. SIST EN 1457-1:2012
Key 1 30 mm/m slope
a) Longitudinal section of gauge
b): Cross section of gauge
c) Liner passing test d): Liner failing test Figure 7 — Squareness test for ends 16.6 Deviation from shape of cross-section The test gauge shall be constituted of two arms, as shown in Figure 8, with one arm set at an angle of (90 ± 0,5)° to the other and both arms of the test gauge of such a length as to span the outside width of the flue liner under test. SIST EN 1457-1:2012
Key x1 deviation from shape x2 deviation from square Figure 8 — Squareness test for angles and flatness of walls The gauge shall be placed against two adjoining walls of square or rectangular straight flue liners and the distances x1 and x2 measured between the inner edge of the test gauge and the outside of the flue liner, excluding the rounded external corners, to an accuracy of ± 0,5 mm. The percentage deviation from flatness shall be calculated as: 11100Lxx× (2) The percentage deviation from squareness shall be calculated as: 22100Lxx× (3) where x1 is the deviation from flatness of the wall, in millimetres; x2 is the deviation from squareness of the wall, in millimetres; Lxl is the manufacturer's stated nominal internal length of the wall; against which x1 is measured, in millimetres; Lx2 is the manufacturer’s stated nominal internal length of the wall; against which x2 is measured, in millimetres. SIST EN 1457-1:2012
...