SIST EN 17966:2024
(Main)Fire protection equipment - Carbon dioxide extinguishing systems for use on premises - Design and installation (ISO 6183:2022, modified)
Fire protection equipment - Carbon dioxide extinguishing systems for use on premises - Design and installation (ISO 6183:2022, modified)
This document specifies requirements and gives recommendations for the design, installation, testing, maintenance and safety of fixed carbon dioxide firefighting systems in buildings, plants or other structures. It is not applicable to extinguishing systems on ships, in aircraft, on vehicles or on mobile fire appliances, or to below ground systems in the mining industry; nor does it apply to carbon dioxide pre-inerting systems.
Design of systems where unclosable opening(s) of the protected volume exceed a specified area and where the opening(s) can be subject to the effect of wind is not specified, although general guidance on the procedure to be followed in such cases is given (see 7.4.3.2).
Brandschutzeinrichtungen - Kohlenstoffdioxid-Löschanlagen für den Einsatz in Gebäuden - Planung und Einbau (ISO 6183:2022, modifiziert)
Dieses Dokument legt Anforderungen fest und enthält Empfehlungen für die Auslegung, Installation, Prüfung, Instandhaltung und Sicherheit von ortsfesten Kohlenstoffdioxid-Brandbekämpfungsanlagen in Gebäuden, Produktionsanlagen oder anderen Bauwerken. Es ist nicht anwendbar für Löschanlagen auf Schiffen, in Flugzeugen, auf Fahrzeugen oder auf mobilen Feuerlöschgeräten oder für unterirdische Anlagen im Bergbau; ebenfalls ist es nicht anwendbar für Kohlenstoffdioxid-Vorinertisierungsanlagen.
Die Auslegung von Anlagen, mit (einer) nicht verschließbaren Öffnung(en) des geschützten Bereichs, deren Fläche einen festgelegten Wert überschreitet und welche der Auswirkung von Wind ausgesetzt sein kann/können, ist nicht festgelegt, obwohl allgemeine Hinweise auf das in solchen Fällen zu befolgende Verfahren gegeben werden (siehe 7.4.3.2).
Équipement de protection contre l'incendie - Installations d'extinction par dioxyde de carbone utilisées dans les bâtiments - Conception et installation (ISO 6183:2022, modifiée)
Le présent document spécifie les exigences et donne des recommandations pour la conception, l’installation, les essais, la maintenance et la sécurité des installations fixes de lutte contre l’incendie par dioxyde de carbone dans les bâtiments, les usines ou autres structures. Il ne s’applique pas aux installations d’extinction des navires, des aéronefs, des véhicules ou des appareils mobiles d’incendie, ni aux systèmes souterrains de l’industrie minière. Il ne s’applique pas non plus aux systèmes de pré inertage par dioxyde de carbone.
La conception de systèmes dans lesquels la ou les ouvertures non fermées du volume protégé dépassent une surface spécifiée et la ou les ouvertures peuvent être soumises à l’effet du vent n’est pas spécifiée, bien que des recommandations générales sur le mode opératoire à suivre dans de tels cas soient fournies (voir 7.4.3.2).
Oprema za požarno zaščito - Gasilni sistemi z ogljikovim dioksidom za uporabo v prostorih - Načrtovanje in vgradnja (ISO 6183:2022, spremenjen)
Ta dokument določa zahteve in podaja priporočila za načrtovanje, vgradnjo, preskušanje, vzdrževanje in varnost vgrajenih gasilnih sistemov z ogljikovim dioksidom v stavbah, obratih ali drugih zgradbah. Ne uporablja se za gasilne sisteme na ladjah, zrakoplovih, v vozilih ali za mobilne naprave za gašenje ali za podzemne sisteme za rudarsko industrijo; prav tako se ne uporablja za predhodno inertne sisteme z ogljikovim dioksidom.
Načrtovanje sistemov, v katerih odprtine, ki jih ni mogoče zapreti, presegajo določeno površino in v katerih so lahko odprtine izpostavljene učinku vetra, ni opredeljeno, čeprav so podane splošne smernice o postopku, ki ga je treba upoštevati v takšnih primerih (glej točko 7.4.3.2).
General Information
Overview
EN 17966:2024 - Fire protection equipment: Carbon dioxide extinguishing systems for use on premises - Design and installation (ISO 6183:2022, modified) - is a European standard published by CEN (approved 5 August 2024). It specifies requirements and guidance for the design, installation, testing, maintenance and safety of fixed carbon dioxide (CO2) firefighting systems in buildings, plants and other structures. The standard excludes systems on ships, aircraft, vehicles, mobile fire appliances, below-ground mining systems and CO2 pre-inerting systems. Special guidance is provided where protected volumes have unclosable openings or are subject to wind (see clause 7.4.3.2).
Key Topics and Requirements
EN 17966:2024 covers the full lifecycle of fixed CO2 systems with emphasis on safety and performance:
- Use and limitations - appropriate applications and temperature or occupancy constraints for CO2 systems.
- Safety - hazards to personnel, warning notices, occupiable vs unoccupiable area rules, electrical and electrostatic safety, and earthing.
- System design - specifications, working documents, carbon dioxide supply (quality, quantity, storage), container arrangement and piping distribution.
- Enclosures (total flooding) - structural strength, loss through openings and interaction with ventilation systems.
- Detection, actuation and control - automatic detection, shutdown of plant/equipment, operating devices, alarms and visual indicators.
- Flow and concentration calculations - system hydraulics, friction and pressure drop, total flooding quantity, KB factor methodology, local application sizing (rate by area/volume).
- Commissioning and acceptance - pre- and post-installation testing, enclosure checks, functional and remote monitoring tests, documentation and completion certificates.
- Inspection, maintenance, testing and training - inspection routines, service schedules and required training for safe operation.
Applications and Who Uses It
EN 17966:2024 is intended for professionals involved in the specification, installation and upkeep of fixed CO2 fire suppression systems:
- Fire protection engineers and system designers using CO2 for total flooding or local applications.
- Installation contractors and commissioning authorities ensuring compliance.
- Facility owners, plant managers and safety officers in industrial plants, electrical rooms, process areas and other premises where CO2 is selected.
- Maintenance/service organizations and training providers responsible for periodic testing and personnel safety.
Related Standards
- Based on and modified from ISO 6183:2022; designers should also consider other applicable national or European standards for fire detection, electrical safety and building services when implementing EN 17966:2024.
Keywords: EN 17966:2024, carbon dioxide extinguishing systems, CO2 fire suppression, design and installation, fixed CO2 systems, total flooding, fire protection equipment.
Standards Content (Sample)
SLOVENSKI STANDARD
01-december-2024
Oprema za požarno zaščito - Gasilni sistemi z ogljikovim dioksidom za uporabo v
prostorih - Načrtovanje in vgradnja (ISO 6183:2022, spremenjen)
Fire protection equipment - Carbon dioxide extinguishing systems for use on premises -
Design and installation (ISO 6183:2022, modified)
Brandschutzeinrichtungen - Kohlenstoffdioxid-Löschanlagen für den Einsatz in
Gebäuden - Planung und Einbau (ISO 6183:2022, modifiziert)
Équipement de protection contre l'incendie - Installations d'extinction par dioxyde de
carbone utilisées dans les bâtiments - Conception et installation (ISO 6183:2022,
modifiée)
Ta slovenski standard je istoveten z: EN 17966:2024
ICS:
13.220.20 Požarna zaščita Fire protection
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.
EN 17966
EUROPEAN STANDARD
NORME EUROPÉENNE
October 2024
EUROPÄISCHE NORM
ICS 13.220.20
English Version
Fire protection equipment - Carbon dioxide extinguishing
systems for use on premises - Design and installation (ISO
6183:2022, modified)
Équipement de protection contre l'incendie - Brandschutzeinrichtungen - Kohlenstoffdioxid-
Installations d'extinction par dioxyde de carbone Löschanlagen für den Einsatz in Gebäuden - Planung
utilisées dans les bâtiments - Conception et installation und Einbau (ISO 6183:2022, modifiziert)
(ISO 6183:2022, modifiée)
This European Standard was approved by CEN on 5 August 2024.
CEN members are bound to comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this
European Standard the status of a national standard without any alteration. Up-to-date lists and bibliographical references
concerning such national standards may be obtained on application to the CEN-CENELEC Management Centre or to any CEN
member.
This European Standard exists in three official versions (English, French, German). A version in any other language made by
translation under the responsibility of a CEN member into its own language and notified to the CEN-CENELEC Management
Centre has the same status as the official versions.
CEN members are the national standards bodies of Austria, Belgium, Bulgaria, Croatia, Cyprus, Czech Republic, Denmark, Estonia,
Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway,
Poland, Portugal, Republic of North Macedonia, Romania, Serbia, Slovakia, Slovenia, Spain, Sweden, Switzerland, Türkiye and
United Kingdom.
EUROPEAN COMMITTEE FOR STANDARDIZATION
COMITÉ EUROPÉEN DE NORMALISATION
EUROPÄISCHES KOMITEE FÜR NORMUNG
CEN-CENELEC Management Centre: Rue de la Science 23, B-1040 Brussels
© 2024 CEN All rights of exploitation in any form and by any means reserved Ref. No. EN 17966:2024 E
worldwide for CEN national Members.
Contents Page
European foreword . 6
Introduction . 7
1 Scope . 8
2 Normative references . 8
3 Terms and definitions . 8
4 Use and limitations . 12
4.1 General. 12
4.2 Uses for carbon dioxide systems . 12
4.3 Limitations for carbon dioxide systems . 12
4.4 Temperature limitations . 12
5 Safety . 13
5.1 Hazard to personnel . 13
5.2 Safety precautions . 13
5.2.1 Normally occupied and normally unoccupied areas . 13
5.2.2 Warning notices for occupiable areas . 14
5.2.3 Warning notices for unoccupiable areas . 17
5.3 Electrical hazards . 18
5.4 Electrical earthing . 19
5.5 Electrostatic discharge. 19
6 System design . 19
6.1 General. 19
6.1.1 Introduction . 19
6.1.2 Specifications . 20
6.1.3 Working documents . 20
6.2 Carbon dioxide supply . 20
6.2.1 Quality . 20
6.2.2 Quantity . 20
6.2.3 Container arrangement . 21
6.2.4 Storage containers . 22
6.3 Distribution . 24
6.3.1 General. 24
6.3.2 Piping . 25
6.3.3 Fittings . 25
6.3.4 Pipe and valve support . 25
6.3.5 Valves . 26
6.3.6 Nozzles . 27
6.4 Enclosures (total flooding) . 28
6.4.1 Structural strength . 28
6.4.2 Loss through openings . 28
6.4.3 Ventilation systems . 28
6.5 Detection, actuation and control systems . 29
6.5.1 General. 29
6.5.2 Shut-down of plant and equipment . 29
6.5.3 Automatic detection . 29
6.5.4 Operating devices . 29
6.5.5 Control equipment . 30
6.5.6 Audible alarms and visual indicators . 31
7 Carbon dioxide flow and concentration calculations . 32
7.1 General . 32
7.2 System flow calculations . 32
7.2.1 General . 32
7.2.2 Friction losses . 33
7.2.3 Pressure drop . 33
7.2.4 Valves and fittings . 34
7.2.5 As-installed calculations . 34
7.2.6 Specific requirements . 34
7.3 Carbon dioxide concentration requirements . 34
7.3.1 Flame extinguishment . 34
7.3.2 Inerting . 34
7.4 Total flooding quantity . 35
7.4.1 General . 35
7.4.2 Design quantity . 35
7.4.3 KB factor . 36
7.5 Design of local application systems . 38
7.5.1 General . 38
7.5.2 Carbon dioxide requirements . 39
7.5.3 Rate by area method . 39
7.5.4 Rate by volume method . 41
7.6 Duration of protection — total flooding systems . 42
7.7 System performance . 43
7.7.1 Discharge time . 43
7.7.2 Extended discharge . 43
8 Commissioning and acceptance . 43
8.1 General . 43
8.2 Tests . 43
8.2.1 General . 43
8.2.2 Enclosure check . 44
8.2.3 Review of mechanical components . 44
8.2.4 Review of enclosure integrity . 45
8.2.5 Review of electrical components . 45
8.2.6 Preliminary functional tests . 46
8.2.7 System functional operational test . 46
8.2.8 Remote monitoring operations (if applicable) . 47
8.2.9 Control panel primary power source . 47
8.2.10 Completion of functional tests . 47
8.3 Completion certificate and documentation . 47
9 Inspection, maintenance, testing and training . 48
9.1 General . 48
9.2 Inspection . 48
9.2.1 General . 48
9.2.2 Container . 48
9.2.3 Hose . 48
9.2.4 Enclosures . 48
9.3 Maintenance . 49
9.3.1 General . 49
9.3.2 User's programme of inspection . 49
9.3.3 Service schedule . 49
9.4 Training . 49
Annex A (normative) Working documents . 50
A.1 General. 50
A.2 Working documents . 50
A.3 Specific details . 51
A.3.1 Pre-engineered systems . 51
A.3.2 Engineered systems . 51
A.4 Completion certificate and documentation . 51
Annex B (normative) Carbon dioxide system pipe and orifice size determination . 56
Annex C (informative) System performance verification . 66
Annex D (informative) General information on carbon dioxide . 67
D.1 General. 67
D.2 Free efflux . 68
D.3 Hazards to personnel . 70
Annex E (informative) Examples of calculations . 72
E.1 Rate by volume method — Example 1 . 72
E.1.1 Hazard . 72
E.1.2 Actual dimensions . 72
E.1.3 Assumed volume . 72
E.1.4 Percent perimeter enclosed . 73
E.1.5 Discharge rate for 71 % enclosure . 73
E.1.6 Discharge rate . 73
E.1.7 Carbon dioxide requirement . 73
E.2 Rate by volume method — Example 2 . 73
E.2.1 Hazard . 73
E.2.2 Actual dimensions . 73
E.2.3 Assumed volume . 73
E.2.4 Percent perimeter enclosed . 74
E.2.5 Discharge rate for 0 % enclosure . 74
E.2.6 Discharge rate . 74
E.2.7 Carbon dioxide requirement . 74
E.3 Rate by area method . 74
E.3.1 Hazard . 74
E.3.2 Surface dimensions . 74
E.3.3 Nozzle location . 74
E.3.4 Procedure . 74
E.3.5 Total flow rate . 74
E.3.6 Carbon dioxide requirement . 74
E.4 Total flooding system . 75
E.4.1 Storeroom . 75
E.4.2 Actual dimensions . 75
E.4.3 Assumed volume . 75
E.4.4 Additional volume for ventilation . 75
E.4.5 Deductible volume . 75
E.4.6 Total surface area of all sides . 75
E.4.7 Total surface area of all openings . 76
E.4.8 Area . 76
E.4.9 Carbon dioxide design quantity . 76
Bibliography . 77
European foreword
This document (EN 17966:2024) has been prepared by Technical Committee CEN/TC 191 “Fixed
firefighting systems”, the secretariat of which is held by BSI.
This European Standard shall be given the status of a national standard, either by publication of an
identical text or by endorsement, at the latest by April 2025, and conflicting national standards shall be
withdrawn at the latest by April 2025.
Attention is drawn to the possibility that some of the elements of this document may be the subject of
patent rights. CEN shall not be held responsible for identifying any or all such patent rights.
The text of ISO 6183:2022 has been prepared by Technical Committee ISO/TC 21 “Equipment for fire
protection and fire fighting” of the International Organization for Standardization (ISO) and has been
taken over as EN 17966:2024 by Technical Committee CEN/TC 191 “Fixed firefighting systems”, the
secretariat of which is held by BSI, with common modifications which are indicated by a straight line in
the margin of the text.
Any feedback and questions on this document should be directed to the users’ national standards body.
A complete listing of these bodies can be found on the CEN website.
According to the CEN-CENELEC Internal Regulations, the national standards organisations of the
following countries are bound to implement this European Standard: Austria, Belgium, Bulgaria, Croatia,
Cyprus, Czech Republic, Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland,
Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Republic of North
Macedonia, Romania, Serbia, Slovakia, Slovenia, Spain, Sweden, Switzerland, Türkiye and the United
Kingdom.
Introduction
This document is intended for use by those concerned with purchasing, designing, installing, testing,
inspecting, approving, operating and maintaining carbon dioxide (CO ) extinguishing systems.
This document applies only to carbon dioxide fixed fire-extinguishing systems in buildings and other
premises on land. Although the general principles can apply to other uses (e.g. maritime use), for these
other uses, it is likely that additional considerations will have to be taken into account and the application
of the requirements given in this document is therefore unlikely to be fully satisfactory. General
information about carbon dioxide as an extinguishing medium is given in Annex D. This can be useful
background information for those unfamiliar with the characteristics of this medium.
It has been assumed in the preparation of this document that the execution of its provisions will be
entrusted to those persons appropriately qualified and experienced in the specification, design,
installation, testing, approval, inspection, operation and maintenance of systems and equipment, for
whose guidance it has been prepared, and who can be expected to exercise a duty of care to avoid the
unnecessary release of carbon dioxide. New requirements to minimize the need to release carbon dioxide
during testing and commissioning procedures are included in this third edition. These are linked to the
inclusion of enclosure integrity testing.
Carbon dioxide has for many years been a recognized effective medium for the extinction of flammable
liquid fires as well as fires in the presence of electrical and ordinary Class A hazards. Nevertheless, in the
planning of comprehensive schemes, it should be remembered that there can be hazards for which this
media is not suitable, and that in certain circumstances or situations there can be dangers in its use
requiring special precautions.
The use of carbon dioxide is no longer recommended for total flooding of occupied areas if more
appropriate extinguishing agents are available. EN 15004 provides requirements for other extinguishing
agents that can be more appropriately used in these areas.
It is important that the fire protection of a building or plant be considered as a whole. Carbon dioxide
systems form only a part, albeit an important part, of the available facilities. It cannot be assumed that
their adoption necessarily removes the need to consider supplementary measures, such as the provision
of portable fire extinguishers or other mobile appliances for first aid or emergency use, or to deal with
special hazards.
Advice on these matters can be obtained from the appropriate manufacturer of the carbon dioxide or the
extinguishing system. Information can also be sought from the appropriate fire authority, the health and
safety authorities, and insurers. In addition, reference needs to be made, as appropriate, to the other
national standards and statutory regulations of a given country.
It is essential that firefighting equipment be carefully maintained to ensure instant readiness when
required. Routine maintenance is liable to be overlooked or given insufficient attention by the owner of
the system. It is, however, neglected at the peril of the lives of occupants of the premises and at the risk
of crippling financial loss. The importance of maintenance cannot be too highly emphasized. Inspection,
preferably by a third party, should include an evaluation concluding that the extinguishing system
continues to provide adequate protection for the risk (protected zones as well as state-of-the-art can
change over time).
1 Scope
This document specifies requirements and gives recommendations for the design, installation, testing,
maintenance and safety of fixed carbon dioxide firefighting systems in buildings, plants or other
structures. It is not applicable to extinguishing systems on ships, in aircraft, on vehicles or on mobile fire
appliances, or to below ground systems in the mining industry; nor does it apply to carbon dioxide pre-
inerting systems.
Design of systems where unclosable opening(s) of the protected volume exceed a specified area and
where the opening(s) can be subject to the effect of wind is not specified, although general guidance on
the procedure to be followed in such cases is given (see 7.4.3.2).
2 Normative references
The following documents are referred to in the text in such a way that some or all of their content
constitutes requirements of this document. For dated references, only the edition cited applies. For
undated references, the latest edition of the referenced document (including any amendments) applies.
EN ISO 7731, Ergonomics — Danger signals for public and work areas — Auditory danger signals
(ISO 7731)
EN 15004-1, Fixed firefighting systems — Gas extinguishing systems — Part 1: Design, installation and
maintenance (ISO 14520-1 modified)
EN 12094 (all parts), Fixed firefighting systems — Components for gas extinguishing systems
EN 54 (all parts), Fire detection and fire alarm systems
3 Terms and definitions
For the purposes of this document, the following terms and definitions apply.
ISO and IEC maintain terminology databases for use in standardization at the following addresses:
— ISO Online browsing platform: available at https://www.iso.org/obp
— IEC Electropedia: available at https://www.electropedia.org/
3.1
approved
acceptable to a relevant authority (3.2)
Note 1 to entry: In determining the acceptability of installations or procedures, equipment or materials, the
authority can base acceptance on compliance with the appropriate standards.
3.2
authority
organization, office or individual responsible for approving equipment, installations or procedures
3.3
automatic/manual switch
means of converting the system from automatic to manual actuation
Note 1 to entry: This can be in the form of a manual switch on the control panel or other units, or a personnel door
interlock. In all cases, this changes the actuation mode of the system from automatic and manual to manual only or
vice versa.
3.4
clearance
air gap between equipment, including piping and nozzles and unenclosed or uninsulated live electrical
components at other than ground potential
3.5
deep-seated fire
fire involving solids subject to smouldering
Note 1 to entry: Examples of a deep-seated fire include baled, stacked or piled materials such as paper, wool and
grain.
3.6
design concentration
concentration of carbon dioxide, including a safety factor (3.25), required for system design purposes
3.7
engineered system
system in which the supply of carbon dioxide is discharged through a system of pipes and nozzles in
which the size of each section of pipe and nozzle orifice has been calculated in accordance with the
requirements of this document
3.8
extinguishing concentration
minimum concentration of carbon dioxide required to extinguish a fire involving a particular fuel under
defined experimental conditions excluding any safety factor (3.25)
3.9
fill density
mass of carbon dioxide per unit volume (3.12) of container
3.10
design quantity
mass of carbon dioxide required to achieve the design concentration (3.6) within the protected volume
(3.11)
3.11
volume
protected space enclosed by the building elements
3.12
high pressure storage
storage of carbon dioxide in pressurized containers at ambient temperatures
3.13
hold time
period of time during which a concentration of carbon dioxide not less than 85 % of the design
concentration is maintained
Note 1 to entry: See 7.6.2.
3.14
inspection
examination for conformity by measuring, observing, or testing the relevant characteristics of an item
[Source: EN 13306:2017, 8.1 [3] ]
3.15
liquid discharge time
time during which predominantly liquid carbon dioxide is present at the nozzle
3.16
lock-off device
manually operated shut-off valve installed in the discharge piping downstream of the carbon dioxide
containers, or other type of device that mechanically prevents agent container actuation
Note 1 to entry: The actuation of this device provides an indication of system isolation.
Note 2 to entry: The intent is to prevent the discharge of carbon dioxide into the hazard area when the lock-off
device is activated.
3.17
local application system
automatic or manual fire-extinguishing system in which a fixed supply of carbon dioxide is permanently
connected to fixed piping with nozzles arranged to discharge the carbon dioxide directly to a fire
occurring in a defined area that has no enclosure surrounding it, or is only partially enclosed, and that
does not produce an extinguishing concentration (3.8) throughout the entire volume (3.11) containing
the protected hazard
3.18
low pressure storage
storage of carbon dioxide in pressurized containers at a controlled low temperature, normally −18 °C to
−20 °C
Note 1 to entry: The pressure in this type of storage is approximately 21 bar .
3.19
maintenance
combination of all technical, administrative and managerial actions during the life cycle of an item
intended to retain it in, or restore it to, a state in which it can perform the required function
Note 1 to entry: Technical maintenance actions include observation and analyses of the items state (e.g. inspection,
monitoring, testing, diagnosis, prognosis, etc.) and active maintenance actions (e.g. repair, refurbishment).
[Source: EN 13306:2017, 2.1 – modified: Note 2 and 3 to entry are deleted. [3] ]
3.20
maximum working pressure
maximum equilibrium pressure developed in the component or system at the highest temperature (50 °C,
or higher, if specified by the manufacturer)
Note 1 to entry: For high pressure storage (3.12), at the maximum fill density (3.9). For a container in transit, the
equilibrium pressure can differ from that in storage within a building.
Note 2 to entry: For low pressure storage (3.18), the pressure corresponding to the maximum controlled
temperature of −18 °C.
1 5 2
1 bar = 0,1 MPa = 10 Pa; 1 MPa = 1 N/mm .
3.21
minimum working pressure
minimum equilibrium pressure at the lowest temperature (-20 °C or lower, if specified by manufacturer)
3.22 Terms related to occupied and unoccupiable areas
3.22.1
normally occupied area
area intended for occupancy
3.22.2
normally unoccupied area
area not normally occupied by people, but which may be entered occasionally for brief periods
3.22.3
unoccupiable area
area which cannot be occupied by people due to dimensional or other physical constraints
EXAMPLE Shallow voids and cabinets.
3.23
pre-engineered system
system consisting of a supply of extinguishant of specified capacity coupled to pre-calculated pipework
and nozzle arrangement up to maximum permitted limits
Note 1 to entry: No deviation is permitted from the limits specified by the manufacturer or authority (3.2).
3.24
pre-liquid vapour flow time
time from the opening of the container or selector valve (3.26) to the start of predominantly liquid flow
at the most unfavourable nozzle
3.25
safety factor
multiplier of the carbon dioxide extinguishing concentration (3.8), used to determine minimum design
concentration (3.6)
3.26
selector valve
valve installed in the discharge piping downstream of the storage containers, used to direct the carbon
dioxide to the appropriate hazard
Note 1 to entry: It is used where one or more storage containers are arranged to selectively discharge carbon
dioxide to any of several separate hazards.
3.27
surface fire
fire involving combustible or flammable liquids, gases and solids not subject to smouldering
3.28
total flooding system
system arranged to discharge carbon dioxide into an enclosed space to achieve the appropriate design
concentration (3.6)
3.29
working pressure
equilibrium pressure of the system or component at 20 °C
4 Use and limitations
4.1 General
The design, installation, service and maintenance of carbon dioxide fire-extinguishing systems shall be
performed by those competent in fire-extinguishing system technology. Maintenance and installation
shall only be performed by qualified personnel and companies.
4.2 Uses for carbon dioxide systems
Carbon dioxide, local application and total flooding systems are useful within the limits of this document
in extinguishing fires involving specific hazards or equipment.
The following are typical of such hazards, but the list is not exhaustive:
a) combustible or flammable liquid and gases;
b) electrical hazards such as transformers, switches, circuit breakers, rotating equipment and electronic
equipment;
c) engines utilizing gasoline and other flammable liquid fuels;
d) ordinary combustibles such as paper, wood, and textiles.
4.3 Limitations for carbon dioxide systems
Carbon dioxide cannot extinguish fires involving certain types of materials such as:
a) chemicals containing their own supply of oxygen, such as cellulose nitrate; or
b) metals and chemicals which react with carbon dioxide, e.g. alkali metals and metal hydrides.
While carbon dioxide does not extinguish certain fuels containing their own oxygen of combustion, it
does not react dangerously with these materials or increase their burning rate. Carbon dioxide, if used in
this situation in a total flooding system, provides protection for adjacent combustibles or can be
successfully used if the reactive metals or hydride are first covered by another material. Examples of the
latter condition are sodium stored or used under kerosene, cellulose nitrate in a solution of lacquer
thinner, and magnesium chips covered with heavy oil.
4.4 Temperature limitations
All devices shall be designed for the service they will encounter and shall not be readily rendered
inoperative or susceptible to accidental operation. Devices shall normally be designed to function
properly from −20 °C to +50 °C, or marked to indicate temperature limitations, or in accordance with the
manufacturer's specifications, which shall be marked on the name-plate, or (where there is no name-
plate) in the manufacturer's instruction manual.
5 Safety
5.1 Hazard to personnel
The discharge of carbon dioxide at a fire-extinguishing concentration creates serious hazards to
personnel, such as suffocation and reduced visibility during and after the discharge period. Hazards to
personnel created by the discharge of carbon dioxide shall be considered in the design of the system.
Carbon dioxide gas is heavier than air and will collect in pits, wells, shaft bottoms or other low-lying areas,
and can migrate into adjacent places outside the protected space. Consideration shall also be given to
places to which the carbon dioxide can migrate or collect in the event of a discharge from a safety relief
device of a storage container.
In addition to the release by response of a safety relief device, the following aspects shall also be
considered:
a) release when the system is triggered by flowing out of overpressure vents or other openings in the
protected area;
b) release during opening of accesses to the flooded protected zone (e.g. in the context of
reconnaissance or exting
...
Frequently Asked Questions
SIST EN 17966:2024 is a standard published by the Slovenian Institute for Standardization (SIST). Its full title is "Fire protection equipment - Carbon dioxide extinguishing systems for use on premises - Design and installation (ISO 6183:2022, modified)". This standard covers: This document specifies requirements and gives recommendations for the design, installation, testing, maintenance and safety of fixed carbon dioxide firefighting systems in buildings, plants or other structures. It is not applicable to extinguishing systems on ships, in aircraft, on vehicles or on mobile fire appliances, or to below ground systems in the mining industry; nor does it apply to carbon dioxide pre-inerting systems. Design of systems where unclosable opening(s) of the protected volume exceed a specified area and where the opening(s) can be subject to the effect of wind is not specified, although general guidance on the procedure to be followed in such cases is given (see 7.4.3.2).
This document specifies requirements and gives recommendations for the design, installation, testing, maintenance and safety of fixed carbon dioxide firefighting systems in buildings, plants or other structures. It is not applicable to extinguishing systems on ships, in aircraft, on vehicles or on mobile fire appliances, or to below ground systems in the mining industry; nor does it apply to carbon dioxide pre-inerting systems. Design of systems where unclosable opening(s) of the protected volume exceed a specified area and where the opening(s) can be subject to the effect of wind is not specified, although general guidance on the procedure to be followed in such cases is given (see 7.4.3.2).
SIST EN 17966:2024 is classified under the following ICS (International Classification for Standards) categories: 13.220.20 - Fire protection. The ICS classification helps identify the subject area and facilitates finding related standards.
You can purchase SIST EN 17966:2024 directly from iTeh Standards. The document is available in PDF format and is delivered instantly after payment. Add the standard to your cart and complete the secure checkout process. iTeh Standards is an authorized distributor of SIST standards.
La norme SIST EN 17966:2024 traite des systèmes d'extinction à dioxyde de carbone, spécifiquement destinés à être utilisés sur des locaux tels que des bâtiments ou des installations industrielles. Son domaine d'application est clairement délimité, excluant notamment les systèmes destinés aux navires, avions, véhicules ou appareils d'incendie mobiles, ainsi que les systèmes situés sous terre dans l'industrie minière. De plus, elle ne s'applique pas aux systèmes de pré-inertage au dioxyde de carbone, ce qui permet de concentrer son applicabilité sur des installations fixes dans des environnements contrôlés. Les points forts de cette norme résident dans la clarté de ses exigences et recommandations concernant la conception, l'installation, le test et la maintenance des systèmes d'extinction fixes. En fournissant des directives précises, elle contribue de manière significative à la sécurité incendie au sein des structures, garantissant que les installations répondent aux normes modernes de sécurité. La norme inclut également des considérations sur la sécurité, ce qui en fait un outil précieux pour les concepteurs et les installateurs de systèmes de lutte contre les incendies. Un aspect notable est qu'elle propose des orientations générales concernant les systèmes dans lesquels des ouvertures non fermables du volume protégé dépassent une certaine superficie. Bien que cette situation ne soit pas spécifiquement traitée, la norme fournit des indications précieuses sur la manière de procéder dans de telles circonstances, enrichissant ainsi son contenu pratique. En résumé, la SIST EN 17966:2024 est une norme pertinente et importante pour le secteur de la protection incendie, offrant un cadre clair pour l'installation et l'entretien des systèmes à dioxyde de carbone, tout en abordant les défis rencontrés dans la conception de systèmes de sécurité incendie.
SIST EN 17966:2024は、固定式二酸化炭素消火システムに関する設計、設置、試験、保守、そして安全性に関する要求事項と推奨事項を提供する重要な標準です。この文書は、建物、プラント、またはその他の構造物における火災防止のための基準を確立しており、特に二酸化炭素消火システムの安全性と効果を高めることに寄与しています。 この標準の強みは、固定式二酸化炭素消火システムを対象としているため、火災に対する高い防護性能を求める施設において実用的かつ確実なガイドラインを提示している点です。また、設計や設置において求められる基準が明確に定められているため、関係者は必要な基準を遵守しやすくなっています。 SIST EN 17966:2024は、他の移動型消火システムや特定の用途(たとえば、船舶や航空機など)には適用されないことを明記しているため、特定の環境における消火システムの適用に関する明確な方向性を提供しています。これは、一貫した安全基準を維持するために重要です。 さらに、文書内では、風の影響を受ける可能性のある保護対象の未閉塞開口部が指定された面積を超える場合には、設計に関する具体的な仕様はないものの、そのようなケースにおける手続きの一般指針が提供されている点も評価できます。この柔軟性は、設計者が特定の状況に応じた最適な設計を行う助けとなります。 全体として、SIST EN 17966:2024は、二酸化炭素消火システムの設計と設置に関わる専門家にとって、非常に価値のあるリソースであり、国際的な基準ISO 6183:2022の修正版としてその有用性をさらに高めています。この標準は、火災防止策の一環として、適切な実施が求められる現代の施設において特に重要な役割を果たします。
SIST EN 17966:2024 표준은 고정된 이산화탄소 소화 시스템의 설계, 설치, 테스트, 유지보수 및 안전에 관한 요구 사항과 권장 사항을 명확히 제시합니다. 이 표준은 건물이나 플랜트와 같은 고정 구조물에 적용되며, 소방 장비 및 시스템의 안전성을 높이는 데 기여합니다. 특히, 이산화탄소 소화 시스템은 화재 상황에서 효과적인 대처를 위한 중요한 장비로, 이 문서는 설계 및 설치 단계에서 안전성을 보장하는 데 중점을 두고 있습니다. SIST EN 17966:2024의 강점 중 하나는 이산화탄소 소화 시스템의 유지보수와 테스트에 대한 상세한 지침을 제공한다는 것입니다. 이러한 지침은 시스템이 항상 최상의 상태를 유지하도록 보장하며, 화재 발생 시 신뢰성을 높이는 데 필수적입니다. 또한, 이 표준은 시스템 설계 시 고려해야 할 안전 규정을 명확히 하여, 사용자와 관리자 모두가 이산화탄소 소화 시스템의 적절한 사용 및 관리에 대해 잘 이해할 수 있도록 돕습니다. 범위 측면에서도 이 표준은 특정 환경에서의 적용 가능성을 명확히 하고 있으며, 선박, 항공기, 차량 및 이동식 소화 장치와 같은 특정 시스템에 대해서는 적용되지 않음을 분명히 하고 있습니다. 이는 사용자들이 각각의 상황에 맞는 소화 시스템을 선택할 수 있도록 돕는 중요한 정보입니다. SIST EN 17966:2024는 이산화탄소 소화 시스템의 설계 및 설치 시 안전성을 확보할 수 있는 필수 가이드라인을 제공하여, 화재 안전 관리의 중요한 기준으로 자리 잡고 있습니다. 이 표준은 효율적인 화재 예방 및 대응 시스템을 구축하는 데 필요한 모든 요소를 체계적으로 다루고 있으며, 각종 건축물 및 시설의 안전성을 높이는 데 필수적인 역할을 수행합니다.
Die Norm SIST EN 17966:2024 behandelt zentrale Aspekte von Kohlenstoffdioxid-Feuerlöscheinrichtungen und legt Anforderungen sowie Empfehlungen für die Planung, Installation, Prüfung, Wartung und Sicherheit von fixen Kohlenstoffdioxid-Feuerbekämpfungssystemen in Gebäuden, Anlagen oder anderen Strukturen fest. Die Relevanz dieser Norm ist insbesondere hoch, da sie einen klaren Rahmen für die Gewährleistung der Brandschutzsicherheit in vielen Einsatzbereichen bietet, die nicht nur auf hochriskante Industrieumgebungen beschränkt sind, sondern auch auf alltägliche Gebäude. Ein starker Punkt dieser Norm ist ihre umfassende Betrachtung der sicherheitsrelevanten Aspekte in der Konstruktion und Installation. Durch detaillierte Empfehlungen zur Wartung und Prüfung wird sichergestellt, dass die Systeme stets funktionsfähig bleiben und im Brandfall effektiv arbeiten. Dies trägt wesentlich zur Minimierung von Gefahren und zur Erhöhung der Systemeinhaltung bei. Des Weiteren ist die Norm so strukturiert, dass sie auch für Systeme mit weniger spezifischen Anforderungen einen wertvollen Leitfaden bietet. Die allgemeine Anleitung für den Umgang mit unabschließbaren Öffnungen in geschützten Volumen, die den Einfluss von Wind ausgesetzt sind, ist ein Beispiel für die Flexibilität und Anwendbarkeit dieser Norm in verschiedenen Szenarien. Die SIST EN 17966:2024 ist nicht für Löschsysteme auf Schiffen, in Flugzeugen, an Fahrzeugen oder mobilen Feuerlöscheinrichtungen anwendbar, was ihrer Spezifizierung und Fokussierung auf stationäre Systeme Rechnung trägt. Dies unterstreicht den klaren Anwendungsbereich der Norm und macht sie für die relevanten Akteure in der Bau- und Sicherheitsbranche besonders wertvoll. Insgesamt ist die SIST EN 17966:2024 eine bedeutende Norm, die durch ihre detaillierte Herangehensweise an die Planung und den Betrieb von Kohlenstoffdioxid-Feuerlöscheinrichtungen einen bedeutsamen Beitrag zur Verbesserung der Brandschutzmaßnahmen in stationären Einrichtungen leistet.
The SIST EN 17966:2024 standard provides comprehensive criteria for the design and installation of fixed carbon dioxide extinguishing systems in various premises, ensuring safety and efficiency in fire protection equipment. Its scope is precisely defined, focusing exclusively on buildings, plants, and other structures, which reinforces its relevance in a broad range of industrial and commercial applications. One of the strengths of this standard is its detailed recommendations for the installation and maintenance of carbon dioxide firefighting systems, which are essential for ensuring compliance with safety regulations. It emphasizes the importance of thorough testing protocols and maintenance practices, ensuring that systems operate effectively when required. Additionally, the standard highlights safety considerations, which is critical in minimizing risks associated with the use of carbon dioxide in firefighting scenarios. Moreover, the inclusion of guidance for scenarios involving unclosable openings subject to wind effects demonstrates a forward-thinking approach to real-world conditions, even though it does not provide exhaustive specifications in such instances. This aspect allows practitioners in the field to apply professional judgment and adapt standard practices based on situational variables. Overall, SIST EN 17966:2024 serves as a pivotal resource for practitioners involved in the fire protection equipment industry, especially concerning carbon dioxide extinguishing systems. It ensures that professionals have clear guidelines to follow, promoting effective fire safety measures in various premises while aligning with international standards.








Questions, Comments and Discussion
Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.
Loading comments...