ISO/TR 24188:2022
(Main)Large outdoor fires and the built environment — Global overview of different approaches to standardization
Large outdoor fires and the built environment — Global overview of different approaches to standardization
This document provides a review of global testing methodologies related to the vulnerabilities of buildings from large outdoor fire exposures. It also provides information on land use management practices. Some of the test methods outlined in this document have been developed in the context of building fires and extrapolated to external fire exposures.
Titre manque
General Information
Relations
Overview
ISO/TR 24188:2022 is a Technical Report from ISO/TC 92 that provides a global overview of approaches to standardization for large outdoor fires and the built environment. The report reviews testing methodologies related to building vulnerabilities from large outdoor fire exposures (including WUI fires, urban/post‑disaster fires, tsunami‑ or volcano‑generated fires and informal settlement fires) and summarizes land‑use management practices. It clarifies that some test methods were originally developed for internal building fires and have been extrapolated to external fire exposures. (Note: evacuation strategies are not addressed.)
Key Topics and Technical Coverage
- Ignition scenarios: clear explanation of the three primary ignition pathways - direct flame contact, thermal radiation, and firebrands/embers - and how combinations of these drive large outdoor fire behavior.
- Regulatory principles and strategies: comparative review of national and regional approaches (examples include Japan, California building code, NFPA 1144, IWUIC, France, Australia).
- Building element test approaches: summarized methods and considerations for high‑risk components such as:
- Roofing assemblies (performance tests and national approaches)
- Exterior walls and facades (indoor vs outdoor test extrapolations)
- Other elements - vents, decks, eaves, windows
- Reaction‑to‑fire provisions: discussions of how reaction‑to‑fire criteria are applied in different jurisdictions.
- Annex and references: informative Annex A gives a precise description of roof performance tests defined in CEN/TS 1187; comprehensive bibliography and terminology (e.g., WUI, firebrand, spot fire).
Practical Applications and Who Uses It
ISO/TR 24188:2022 is intended as a reference for practitioners and stakeholders working to reduce structure ignition and damage from large outdoor fires:
- Standards developers and regulators - to align or develop building codes and land‑use rules for WUI and other large fire exposures.
- Fire safety engineers and researchers - to compare test methodologies and identify knowledge gaps.
- Architects and building designers - to inform material and assembly selection for exterior assemblies (roofs, walls, windows).
- Manufacturers of cladding, roofing and facade systems - to understand test expectations and performance contexts.
- Urban planners and land‑use authorities - for integrating vegetation management and community‑scale mitigation measures.
- Emergency managers and policy makers - to support risk assessment and mitigation planning.
Related Standards (if applicable)
- NFPA 1144 - Standard for Reducing Structure Ignition Hazards from Wildland Fire (referenced in the report)
- International Wildland‑Urban Interface Code (IWUIC)
- California State Building Code provisions (discussed)
- CEN/TS 1187 - roof performance tests (described in Annex A)
- ISO/TC 92 publications and ISO/TS materials on wildland fire terminology
Keywords: ISO/TR 24188:2022, large outdoor fires, WUI, firebrands, thermal radiation, building vulnerabilities, testing methodologies, land use management, roofing assemblies, exterior facades.
Standards Content (Sample)
TECHNICAL ISO/TR
REPORT 24188
First edition
2022-06
Large outdoor fires and the built
environment — Global overview
of different approaches to
standardization
Reference number
© ISO 2022
All rights reserved. Unless otherwise specified, or required in the context of its implementation, no part of this publication may
be reproduced or utilized otherwise in any form or by any means, electronic or mechanical, including photocopying, or posting on
the internet or an intranet, without prior written permission. Permission can be requested from either ISO at the address below
or ISO’s member body in the country of the requester.
ISO copyright office
CP 401 • Ch. de Blandonnet 8
CH-1214 Vernier, Geneva
Phone: +41 22 749 01 11
Email: copyright@iso.org
Website: www.iso.org
Published in Switzerland
ii
Contents Page
Foreword .iv
Introduction .v
1 Scope . 1
2 Normative references . 1
3 Terms and definitions . 1
4 Ignition scenarios .3
5 Regulation principle and strategies . 4
5.1 Japan . 4
5.2 California State Building Code (US) . 5
5.3 NFPA 1144, Standard for Reducing Structure Ignition Hazards from Wildland Fire
(US) . 5
5.4 International Wildland Urban Interface Code (IWUIC) . 5
5.5 France . 6
5.6 Australia . 6
6 Approach for roofing assemblies .6
6.1 Japan . 6
6.2 North America. 7
6.3 France . 7
6.4 Australia . 7
7 Approach for exterior walls and facades . 8
7.1 Japan . 8
7.2 North America. 8
7.2.1 Fire resistance for exterior walls based on traditional inside-building fire
test methods . 8
7.2.2 Exterior walls outdoor fire exposures. 8
7.3 France . 9
7.4 Australia . 9
8 Other building elements . 9
8.1 Vents . 9
8.2 Decks . 10
8.3 Eaves . 10
8.4 Windows. 10
8.4.1 North America . 10
8.4.2 Australia . 10
9 Additional provisions .10
9.1 Reaction-to-fire — California . 10
9.2 Reaction-to-fire — France. 11
10 Summary of scenarios and tests .11
Annex A (informative) Precise description of tests for roof performance defined in the
European Standard CEN/TS 1187 .14
Bibliography .17
iii
Foreword
ISO (the International Organization for Standardization) is a worldwide federation of national standards
bodies (ISO member bodies). The work of preparing International Standards is normally carried out
through ISO technical committees. Each member body interested in a subject for which a technical
committee has been established has the right to be represented on that committee. International
organizations, governmental and non-governmental, in liaison with ISO, also take part in the work.
ISO collaborates closely with the International Electrotechnical Commission (IEC) on all matters of
electrotechnical standardization.
The procedures used to develop this document and those intended for its further maintenance are
described in the ISO/IEC Directives, Part 1. In particular, the different approval criteria needed for the
different types of ISO documents should be noted. This document was drafted in accordance with the
editorial rules of the ISO/IEC Directives, Part 2 (see www.iso.org/directives).
Attention is drawn to the possibility that some of the elements of this document may be the subject of
patent rights. ISO shall not be held responsible for identifying any or all such patent rights. Details of
any patent rights identified during the development of the document will be in the Introduction and/or
on the ISO list of patent declarations received (see www.iso.org/patents).
Any trade name used in this document is information given for the convenience of users and does not
constitute an endorsement.
For an explanation of the voluntary nature of standards, the meaning of ISO specific terms and
expressions related to conformity assessment, as well as information about ISO's adherence to
the World Trade Organization (WTO) principles in the Technical Barriers to Trade (TBT), see
www.iso.org/iso/foreword.html.
This document was prepared by Technical Committee ISO/TC 92, Fire safety.
Any feedback or questions on this document should be directed to the user’s national standards body. A
complete listing of these bodies can be found at www.iso.org/members.html.
iv
Introduction
Large outdoor fires have the potential to negatively impact the built environment.
Examples of such fires are:
— wildland-urban interface (WUI) fires (wildland fires that spread into communities; this type of fire
has become a global problem);
NOTE Once a WUI reaches a community, a large urban fire can develop.
— post-earthquake fires (large urban fires that potentially occur after an earthquake);
— tsunami-generated fires (fires potentially generated from tsunamis);
— volcano-generated fires (fires potentially generated from volcanic activity); and
— fires that occur in informal settlements.
This document provides an overview of approaches to standardization for lessening the destruction on
the built environment caused by such fire exposure. Evacuation is not included as there are no known
approaches to standardization as the present time.
v
TECHNICAL REPORT ISO/TR 24188:2022(E)
Large outdoor fires and the built environment — Global
overview of different approaches to standardization
1 Scope
This document provides a review of global testing methodologies related to the vulnerabilities of
buildings from large outdoor fire exposures. It also provides information on land use management
practices. Some of the test methods outlined in this document have been developed in the context of
building fires and extrapolated to external fire exposures.
2 Normative references
There are no normative references in this document.
3 Terms and definitions
For the purposes of this document, the following terms and definitions apply.
ISO and IEC maintain terminology databases for use in standardization at the following addresses:
— ISO Online browsing platform: available at https:// www .iso .org/ obp
— IEC Electropedia: available at https:// www .electropedia .org/
3.1.1
bushfire
unplanned fire in a vegetated area, as opposed to an urban area
Note 1 to entry: Used primarily, but not exclusively, in Australia, New Zealand, and Africa.
Note 2 to entry: It is likely that the term was first used in South Africa and is possibly derived from the Dutch
th
word ‘bosch’ meaning uncultivated land. In Australia the term was first used in the first half of the 19 century.
th
The term passed into legislation in the first half of the 20 century, first in the Australian Capital Territory
(Bushfire Act, 1936), Western Australia (A Bush Fires Act, 1937) and New South Wales (Bush Fires Act, 1949).
Note 3 to entry: Definition adapted from Reference [42].
3.1.2
direct flame contact
flame impinging on building systems and materials
Note 1 to entry: Direct flame contact is one of the three structure ignition pathways, together with firebrands
and radiant heat.
Note 2 to entry: The flames can come either from the main wildfire flames, from burning elements and
ornamental vegetation surrounding structures, or from adjacent structures.
Note 3 to entry: Definition adapted from Reference [42].
3.1.3
evacuation
dispersal or removal of people from dangerous areas and their arrival at a place of relative safety
Note 1 to entry: Definition taken from Reference [42].
3.1.4
post-earthquake fire
fire which occurs after an earthquake
3.1.5
firebrand
airborne object capable of acting as an ignition source and carried for some distance in an airstream
Note 1 to entry: Firebrands are also sometimes referred to as flying brands or brands.
Note 2 to entry: Firebrands are similar to embers but with a slight distinction: ember refers to any small, hot,
carbonaceous particle and when embers have the capability of setting additional fires, they become firebrands.
Note 3 to entry: The aerodynamic properties of firebrands is an important characteristic requiring consideration.
Note 4 to entry: Firebrands or embers can be burning, flaming or smouldering.
Note 5 to entry: Definition adapted from Reference [42].
3.1.7
informal settlement
unplanned settlement or area where housing is not in compliance with current planning and building
regulations (unauthorized housing)
[SOURCE: Glossary of Environment Statistics, Studies in Methods, Series F, No. 67, United Nations, New
York, 1997]
3.1.8
large outdoor fire
urban fire, tsunami-generated fire, volcano-generated fire, WUI fire, wildland fire, or informal
settlement fire, where the total burnout area is significant
3.1.9
spot fire
fire caused by flying firebrands at a distance from the original fire
3.1.10
tsunami-generated fire
fire caused by tsunami, typically by burning elements contained in the flood waters
3.1.11
urban fire
fire which occurs in an urbanized area
3.1.13
volcano-generated fire
fire caused by volcanic eruption
3.1.14
wildland
land that either has never suffered human intervention or has been allowed to return to its natural
state, or that is managed for forestry or ecological purposes
[SOURCE: ISO/TS 19677:2019, 3.2]
3.1.15
wildland fire
fire occurring in peat, forests, scrublands, grasslands or rangelands, either of natural origin or caused
by human intervention
Note 1 to entry: Used primarily, but not exclusively, in North America.
[SOURCE: ISO/TS 19677:2019, 3.3, modified — reference to "peat" added and Note 1 to entry added.]
3.1.16
wildland firefighting
suppressive action involving a fire in forests, scrublands, grasslands or rangelands
3.1.17
wildland-urban interface
WUI
area where structures and other human development adjoin or overlap with wildland
[SOURCE: ISO/TS 19677:2019, 3.4]
3.1.18
wildland-urban interface community
WUI community
community where humans and their development meet or intermix with wildland fuel
Note 1 to entry: Definition adapted from Reference [45].
3.1.19
wildland-urban interface fire
WUI fire
wildland fire that has spread into the wildland-urban interface (WUI)
Note 1 to entry: It is also possible for fires to start in the wildland-urban interface (WUI) and spread into the
wildland.
3.1.20
wildland-urban interface firefighting
WUI firefighting
suppressive action involving a fire in the wildland-urban interface (WUI) where the action, tactics and
equipment used can differ from urban firefighting
4 Ignition scenarios
It is important to understand that large outdoor fires involve the interaction of topography, weather,
vegetation and structures. Large outdoor fires differ from enclosure fires in several ways; most notably
the fire spread processes are not limited to well-defined boundaries, as is the case of traditional building
or enclosure fires. Wildland firefighting and WUI firefighting techniques, as well as fire mitigation,
also differ in their nature, application and in terms of the distances involved in such situations. At the
interface, the interaction of buildings, construction products used, and urbanization rules are also key
parameters. Reference [32] gives a good overview of these phenomena. There are three ways in which
ignition can occur:
— Direct flame contact — This is the aspect usually managed by fire tests from building regulations.
— Thermal radiation — The probability of ignition depends on the distance and time of exposure. This
can occur at distances of tenths of meters.
— Firebrands — The probability of ignition depends on the accumulation. Spot fires can occur at long
distances (several hundred meters).
A combination of any of these three points is also possible. Direct flame contact and thermal radiation
act in combination as a flame exists and emits thermal radiation. Direct flame contact and firebrands
can also act in combination while direct flame contact is likely dominant. Thermal radiation and
firebrands can act in combination as shown in Figure 1.
Key
1 direct flame contact
2 thermal radiation
3 firebrands
4 thermal radiation and firebrands
Figure 1 — Fire propagation modes in large outdoor fires (from Reference [32])
5 Regulation principle and strategies
5.1 Japan
[25]
The Building Standard Law (BSL) of Japan aims to cover the threat of large urban fires. According
to the BSL, there are two major fire tests conducted in Japan in the context of preventing urban fire
spread: a roof test and a fire resistance test for exterior walls.
The purpose of the BSL is to safeguard the life, health and property of people by providing minimum
standards concerning the site, construction, equipment and use of buildings, and thereby to contribute
to the furtherance of the public welfare. To prevent fires from spreading from one building to the next
and to minimize the occurrence of urban fires, buildings located in "fire protection zones (FPZs)",
"quasi-fire protection zones (QFPZs)", and "cities under Article 22” are required to conform to the BSL.
Figure 2 illustrates the basic philosophy of zoning. While no scientific research has yet been carried out
to determine the efficacy of these regulations, due at least in part to the regulations, large urban fires
are a relatively rare occurrence in Japan today, and are most likely to occur under extreme conditions
(in themselves rare), such as those following a major earthquake or in extremely high winds.
Key
1 fire protection zone
2 quasi-fire protection zone
3 city under Article 22
4 station
5 railway
Figure 2 — Zoning concept according to BSL of Japan (from Reference [25])
5.2 California State Building Code (US)
California refers to California Building Code, Title 24, Part 1, Chapter 7A Materials and Construction
Methods for Exterior Wildfire Exposure, as well as Chapter 49, Requirements for Wildland-Urban
Interface Areas. The following California State Fire Marshal (SFM) Test Standards are described: 12-7A-
[6] [20] [18] [14] [21]
1, 12-7A-2, 12-7A-3, 12-7A-4, 12-7A-5.
5.3 NFPA 1144, Standard for Reducing Structure Ignition Hazards from Wildland Fire
(US)
[50]
The National Fire Protection Association (NFPA) published the current edition of NFPA 1144 in
2018. This standard can serve as a model for adoption (in total or with amendment) by local building
codes. The scope of the document ranges from assessing fire hazard in the structure ignition zone to
building design, location and construction. Building components covered include: roof, exterior walls,
openings (including windows and doors), chimneys, and accessory structures. Sample qualitative and
quantitative hazard assessment methodologies are included in the Annex. In the 2022 revision process
[48] [49]
this document is to be combined with NFPA 1141 and NFPA 1143 to form a single document, NFPA
1140.
5.4 International Wildland Urban Interface Code (IWUIC)
[47]
The International Code Council (ICC) published the current edition of the IWUIC in 2018. This model
ranges in scope from water supply and vehicles access to building construction and fire protection
requirements. Appendix sections provide additional information on topics including: vegetation
management, fire hazard severity assessment forms and “self-defence mechanisms”. Notable is the
Ignition-Resistance Construction system described in Chapter 5. The system contains three class levels
(Class 1, Class 2 and Class 3) and specifies construction requirements for each. Class 3 requires the
nominally most ignition-resistant materials and construction. Several standards and test methods
from other organizations including ASTM, NFPA and UL are referenced.
5.5 France
The French standards and regulations are mainly dedicated to design (or certification by standard
tests) fire resistance or reaction to fire of construction products against compartment fire or
traditional building fires. Nevertheless, standards or performance requirements concern the design of
[51]
products against external fire. The Eurocode EN-1991-1-2 provides a dedicated external fire curve
(temperature-time) pertinent for exposure of structural construction elements against external flame
coming out from windows of other compartments, but this standard is not used for classification tests.
[37]
The European Standard EN-1363-2 indicates that this curve can be considered for outside fire, but in
practice it is also not employed for classification tests.
For wildland-urban interface (WUI) fires, no standards specify the fire exposure explicitly. Instead,
one finds two different categories of approaching standard tests are reviewed in detail in the following
subclauses:
— tests for some structural elements (roofs and facades essentially) which are ad hoc tests, allowing
to test reaction and resistance to fire with ad hoc fire curves and ad hoc acceptance criteria.
— tests for other structural elements which are tests with standard generic fire curves and acceptance
criteria.
5.6 Australia
The Australian National Construction Code (NCC) has performance provisions that address buildings
that are located in a designated bushfire-prone area (WUI fire-prone area). The NCC has three volumes—
the Building Code of Australia is Volume One and Volume Two and the Plumbing Code of Australia is
[54]
Volume Three. Bushfire areas of the NCC 2019 Volume Two is satisfied if the building is constructed
[52]
in accordance with either 1) AS 3959 or 2) NASH Bushfire Standard — Non-combustible building
[44]
cavity construction in bushfire areas. AS 3959 contains normative reference to the two standards
[9] [8]
in the Australian Standard AS 1530.8.1 and AS 1530.8.2 test standards. The testing standards have
[41]
been applied to roof, wall and other assembly types. Baker et al. provide a comprehensive overview
of the regulatory framework of Australia for interested readers.
6 Approach for roofing assemblies
6.1 Japan
Roof tests in Japan are based on ISO 12468-1, with a minor modification of the size of the cribs placed
on the surface of roof specimens. Different cribs are used for the roofs located in different zones. For
the roof specimens which will be constructed in FPZs and QFPZs, total size of crib is (80 × 80 × 60) mm,
which is composed by lumbers, and each configuration is (19 × 19 × 80) mm. On the other hand, for the
[25]
roof specimens in “Cities under Article 22 of BSL (Building Standard Law)” or “Low-flame-spread
roof area”, lumber is used, where the size is (40 × 40 × 40) mm, which conforms to the specifications
of “Brand B” in ISO 12468-1. This difference on firebrands stems from the assumption that buildings
in FPZs and QFPZs are closely adjacent to each other and can therefore produce larger firebrands than
fires in “Cities under Article 22 of BSL”. Furthermore, the roofs of the buildings located in the FPZ and
QFPZ can be less vulnerable to the attacking of flying firebrands in case of urban fire than those in
“Cities under Article 22 of BSL”. The same criteria are applied when interpreting the results of tests for
all specimens, even when different crib configurations are used. There are three major elements in the
criteria, namely, 1) fire propagation (not reaching to the edge of specimen), 2) integrity (no flame on the
reverse side of the specimen), and 3) defect [no through-hole larger than (10 ×10) mm]. Furthermore,
non-combustible roof tiles do not even need to be tested. Recent joint USA/Japan research has shown
[27]
these methods do not simulate firebrand showers seen in large outdoor fires.
6.2 North America
There are a few existing test methods that measure the ability of a roof assembly to resist the passage of
[10]
fire into the attic and spread of fire on the roof surface. In Canada, CAN/ULC-S107 is used to measure
[17] [11]
the roof performance, which follows a similar procedure as ASTM E-108 , UL 790 and NFPA
[12]
276 . During the test the assembly is exposed to flames from a calibrated burner. For combustible
roof decks, a series of burning standard brands and an intermittent flame exposure are also required.
The roof assemblies are classified based on their effectiveness against fire exposure, flammability/
combustibility, and degree of fire protection provided to the roof deck, and propensity to produce
flying brands. They provide three classes, Class A, Class B, and Class C. Class A is the most resistant and
Class C the least resistant. Recent joint US/Japan research has shown these methods do not simulate
[27]
firebrand showers seen in large outdoor fires.
6.3 France
[34]
CEN/TS 1187 is a collection of 4 separate tests, and in France, test 3 is applied. Even if a roof is
validated according to test 3, it is not considered valid in the 3 other tests. Details are provided in
Annex A.
Test 3 has an ad hoc experimental setup, including firebrands positioned at defined positions on the
roof before being flamed, low atmospheric wind conditions (around 3 m/s) possibly propagating the
−2
fire to the roof components, and a radiative heating from a radiant panel at about 12,5 kWm . The
firebrands are composed of 4 pieces of wood assembled together to build a crib of (55 × 55 × 32) mm,
pre-conditioned in temperature and relative humidity. This setup has been initially designed not to
represent wildfire firebrands, but rather to represent burning pieces of timber or construction wooden
items, which have been projected from a neighbouring building fire. A 30 min fire exposure is performed.
[35]
Classification criteria (A, B, … roof) are given by the adjacent standard EN 13501-5 :2005+1 :2009.
Precise details on this test design, as well as comparison with the other tests, are found in Annex A.
6.4 Australia
[8]
AS 1530.8.2 is the Australian test standard for WUI exposure. AS 1530.8.2 is for severe fire exposure
or direct flame impingement (BAL FZ). During AS 1530.8.2, a representative element of construction
or combination of elements is exposed to the standard fire curve. The test duration is 90 min which
includes a 30-min exposure to the standard fire and a 60-min monitoring period.
[9]
For lower exposure levels, another standard, AS 1530.8.1, is used, which exposes the specimen to
a radiant heat, burning firebrands and burning debris. AS 1530.8.1 provides standard test methods
to determine the performance when a specimen is exposed to radiant heat, firebrands and burning
debris. Exposure to firebrands is simulated by application of a small gas flame and exposure to burning
debris is simulated by wood cribs. The radiant heat rapidly rises initially until it reaches a specified
maximum radiant heat of either 12.5, 19, 29, or 40 kW/m depending on the severity of exposure.
The maximum radiation is maintained for two minutes followed by a gradual decay period. The total
radiant heat exposure period is 10 minutes. Overall, the Australian approach is more representative of
the WUI exposure with some shortcomings; the main one is the lack of wind during the tests. Radiation
exposure is more representative of the approaching wildfire.
A successful testing outcome from either of these testing methods is deemed to be sufficient evidence of
conformance to the standard up to and including the particular exposure level to which it was tested. In
addition to this testing conformance, the roof exterior is required to be non-combustible, and the NASH
standard also requires the roof internals to be non-combustible.
7 Approach for exterior walls and facades
7.1 Japan
Ordinary wall furnaces (3 m × 3 m) are used in Japan for the fire resistance tests following ISO 834-1
standard fire. Regarding the traditional classification system of fire resistance in Japan, there are four
different classes: 1) fire-resistive construction, 2) quasi-fire-resistive construction, 3) fire preventive
construction, and 4) quasi-fire preventive construction. Among these, especially 3) fire preventive
construction, and 4) quasi-fire preventive construction are the performance required for an exterior
wall to restrict the spread of a normal fire that starts in the area surrounding a building, for thirty
minutes in case of 3), and for twenty minutes in case of 4). Regarding these two classes, only stability
and insulation, (not integrity), are counted for evaluating the fire resistance of exterior walls.
For reference, regarding the other two classes, 1) fire-resistive construction, is the performance
required for the building parts to prevent a normal fire from causing both the collapse of the building
and the spread of fire even after the end of a normal fire, and 2) quasi-fire-resistive construction, is the
performance required for the building parts to prevent a normal fire from causing both the collapse of
the building and the spread of fire until the end of a normal fire.
Additionally, regarding building façade fire safety in Japan, there is JIS A 1310 “Test method for fire
[26]
propagation over building façades” , which is a screening method for determining the fire propagation
of products and constructions of a building façade when exposed to flames ejected from the building
opening. The primary aim of JIS A 1310 is to assess the vertical fire propagation over facades, but it
can be partially applied for evaluating the potential horizontal fire spreading from the building where
façade is burning to its adjacent building, because it is prescribed by JIS A 1310 to install the heat flux
meter at two meters horizontally separated from the façade specimen. Additionally, its measured heat
flux data can be helpful for fire engineers to technically extrapolate whether the adjacent building could
be ignited or not. According to the current Building Standard Law of Japan, JIS A 1310 is not mandatory
but voluntary, and used for research and development purposes.
7.2 North America
7.2.1 Fire resistance for exterior walls based on traditional inside-building fire test methods
[1] [2] [3] [4]
Standards CAN/ULC S101, ASTM E119, UL 263, and NFPA 251 describe the standard method
of determining the fire resistance of building components. During fire resistance tests, the assembly
is exposed to heat from a furnace whose temperature follows a specific time-temperature curve. The
assembly fails if the fire passes through the assembly, or the temperature of the unexposed side rises
by a certain amount or if the assembly collapses. Since these tests were developed to represent the fire
severity of a compartment fire, they impose a very high temperature (which follows a standard time-
temperature curve reaching approximately ~1 100 °C at 2 h) which is not representative of an external
transient fire source. In Canada, the National Building Code of Canada (NBCC) imposes a certain fire
resistance rating for walls. When fire resistance ratings are required for an exterior wall assembly,
the exposure to CAN/ULC-S101 is only required to be assessed from the interior of the building to the
outside. The NBCC does not require fire resistance ratings to be determined from the exterior to the
interior. Other measures are used to limit the fire hazard posed by materials used on the exterior of
buildings.
7.2.2 Exterior walls outdoor fire exposures
[6] [7]
Standards SFM 12-7A-1 and ASTM E2707 utilize a diffusion burner to expose the wall to a short
10-min exposure to a 150 kW fire. The test attempts to simulate a scenario where an indirect exposure
of flame impingement happens as a result of ignition of plants, trash, a deck or other combustible
materials beside the wall. Unless fire resistance of a longer period is also prescribed in addition to this
test, the test does not apply to a scenario where the building is exposed to a large radiation source for a
long duration of time, such as the burning of an adjacent building.
7.3 France
[36]
Façades are covered by LEPIR2 test (National decree of 10-09-1970). This French specification is
currently part of an ongoing work of EU harmonization. The current façade test is a large-scale test
performed on façade mock-ups. Its field of application is to all façade systems (including testing of
windows). Its setup includes a two-level façade, with fire starting in the lower compartment (600 kg
of wood cribs), and openings at the two levels (no glass in the generic setup). A 30 min, fire exposure
is performed. Then, requirements regarding fire spread through façades (external surface but also
through cavity, facade floor-junction.) need to fulfil rules based on available combustible mass
calculations and technical arrangements about installation (C+D rules).
[37]
Exterior walls: Even if the norm EN-1363-2 was initially designed for the characterization of external
flame temperatures of compartment fire, it could be used to design fire curve of “natural” external
fire, although link to the thread observed in real wildland fires is questionable. Internal fire curve
38]
(EN-1363-1 ) is used by default to test structural elements in fire resistance (REI criteria). It is based
on ISO 834-1, which reflects the fire in compartment context. Some local prescriptions ask for such
curve to be applied to a building envelope close to wildland, even if the relation between this standard
exposure and the real fire is questionable in terms of intensity and time.
7.4 Australia
[8]
AS 1530.8.2 is the Australian test standard for WUI exposure. AS 1530.8.2 is for severe fire exposure
or direct flame impingement (BAL FZ). In AS 1530.8.2, a representative element of construction
or combination of elements is exposed to the standard fire curve. The test duration is 90 min which
includes a 30-min exposure to the standard fire and a 60-min monitoring period.
[9]
For lower exposure levels, another standard AS 1530.8.1 is used, which exposes the specimen to a
radiant heat, firebrands and burning debris. AS 1530.8.1 provides standard test methods to determine
the performance when a specimen is exposed to radiant heat, firebrands and burning debris. Exposure
to firebrands is simulated by application of a small gas flame and exposure to burning debris is
simulated by wood cribs. The radiant heat rapidly rises initially until it reaches a specified maximum
radiant heat of either 12,5, 19, 29, or 40 kW/m depending on the severity of exposure. The maximum
radiation is maintained for two min followed by a gradual decay period. The total radiant heat exposure
period is 10 minutes. Overall, the Australian approach is more representative of the WUI exposure
with some shortcomings: the main one is the lack of wind during the tests. Radiation exposure is more
representative of the approaching wildfire.
A successful testing outcome from either of these testing methods is deemed to be sufficient evidence of
conformance to the standard up to and including the particular exposure level to which it was tested. In
addition, the NASH standard also requires the whole wall assembly to be non-combustible.
8 Other building elements
8.1 Vents
[13]
The US refers to ASTM E2886. While protecting roofs by ignition-resistant materials can protect
the combustible materials in the attic, the entry of firebrands through vents or other openings can
[13]
compromise the effectiveness of the fire protection system. ASTM E2886 attempts to measure the
performance of vents to resist the entry of firebrands and direct flames. During the firebrand test, a
flow of generated firebrands are pulled using a fan to pass through a vent. The firebrand generator
consists of a rotating steel mesh tumbler. Burning Class C firebrands are placed inside the rotating
tumbler and generated by the agitation of the brands and steel nuts that pass the perimeter steel mesh
is transported by the flow of air through the vent. If the vent prevents the ignition of cotton pads which
are located at the end, it passes the test. USA/Japan experiments form the scientific basis for this test
[28]
method, and a detailed comparison was undertaken with ASTM to develop this test method. Flame
intrusion is evaluated separately using different test procedures.
8.2 Decks
[14] [15] [16]
The standards concerned in North America are SFM 12-7A-4; ASTM E2632; and ASTM E2726.
Combustible decking material during a WUI fire event is a vulnerable section of a building. Since decks
are attached to the building, ignition of decks could result in the spread of fire to the building itself.
Firebrands from the wildfire could accumulate under or within the crevices of the deck and result in
the ignition of the deck. There are several standard test methods for decks. The California building
code has adopted SFM 12-7A-4 for this purpose. The test exposes a 60 cm × 60 cm (24 inch × 24 inch)
sample of the deck to a either a flame (SFM 12-7A-4A) or a burning brand (SFM 12-7A-4B). Two scenarios
are considered: in the first one it is assumed that the accumulation of firebrands has resulted in a fire
under the deck, and the second scenario assumes the firebrands are accumulated over the deck. During
the deck flame test the deck is exposed to a flame of 80 kW for 3 min, equivalent to 1 kg of paper. The
sample fails if there is runaway combustion, structural collapse, or flaming dripping materials. The test
procedure requires the sample to be observed for 40 min after the flame exposure.
The ASTM E2632 test method is almost identical to SFM 12-7A-4A. In SFM 12-7A-4B /ASTM 2726, a
[17]
standard burning brand (standard brand of ASTM E108 ) is placed over the deck while a fan blows an
air flow of approximately 5,4 m/s (12 mph) over the specimen and the sample is observed for 40 min for
signs of sustained flaming or falling brands. In all tests, the samples need to be exposed to conditions of
accelerated aging or weathering to create a more realistic representation of the actual deck in the test.
Recent firebrand shower research has shown these tests are not adequate for wind-driven firebrand
[29-31]
exposure.
8.3 Eaves
Eaves or similar projections are vulnerable to ignition, namely because heat partially accumulates
under the eave and the material used for the construction of eaves cannot be as fire resistant at the
roofing and exterior walls. Open eaves are a particularly weak point for entry of flames or firebrands.
[18] [19]
SFM 12-7A-3 or ASTM E2957 both expose a 609 mm projection to a flame of 300 kW for 10 min.
The sample is then observed for another 30 min to monitor the existence of glowing or flaming on the
unexposed side of the specimen.
8.4 Windows
8.4.1 North America
[20]
California refers to SFM 12-7A-2. In order to assess the performance of windows exposed to direct
flames, SFM 12-7A-2 uses a 150 kW, 100 mm by 1 000 mm diffusion burner under the target window.
The specimen is exposed to the flame for 8 min. This test simulates a scenario where a flame is burning
a combustible material around the building and under a window.
8.4.2 Australia
[8] [9]
For radiation exposure of windows, AS 1530.8.2 or AS 1530.8.1 can be considered.
9 Additional provisions
9.1 Reaction-to-fire — California
[21]
Ignition-resistant material is defined in SFM 12-7A-5. . Any material designated as ignition resistant
[46]
is required to pass a 30 min ASTM E84 test. ASTM E84 was not developed by the SFM of California
but is a legacy standard test method, also known as the Steiner Tunnel test method.
9.2 Reaction-to-fire — France
[39]
Reaction-to-fire of construction products according to EN 13501-1 is requested for all products
[53]
listed in the EU Construction Product Directive. For the other elements, such as sun blinds, curtains,
[40]
etc, M- classification, formerly the French reaction-to-fire provisions, are still applicable; some
requirements are prescribed locally in areas subject to possible wildland fire attack.
10 Summary of scenarios and tests
Table 1 summarizes which scenario of fire is modelled by each standard test reviewed in the previous
clause, detailed according to three different exposures on buildings: radiative effect, firebrands and
direct flame contact.
Table 1 — Summary of test methods
Tested Country Method Radiative effect Firebrands Wind effect Others
structural scenario scenario scenario
element
Roofs Japan ISO 12468-1 No Cribs placed on No —
roof surface, of
different types
according to a
building pro-
tection zone
criteria (FPZ,
QFPZ, “Low-
flame-spread”)
USA / CAN/ULC- Flames from a cali- Burning stand- Yes. The spread
[10]
Canada S107 brated burner ard brands, of flame test
is conducted
[17]
ASTM E108 Intermittent /
at a 5,4 m/s
cyclic flame
[11]
(12 mph) wi
...
Frequently Asked Questions
ISO/TR 24188:2022 is a technical report published by the International Organization for Standardization (ISO). Its full title is "Large outdoor fires and the built environment — Global overview of different approaches to standardization". This standard covers: This document provides a review of global testing methodologies related to the vulnerabilities of buildings from large outdoor fire exposures. It also provides information on land use management practices. Some of the test methods outlined in this document have been developed in the context of building fires and extrapolated to external fire exposures.
This document provides a review of global testing methodologies related to the vulnerabilities of buildings from large outdoor fire exposures. It also provides information on land use management practices. Some of the test methods outlined in this document have been developed in the context of building fires and extrapolated to external fire exposures.
ISO/TR 24188:2022 is classified under the following ICS (International Classification for Standards) categories: 13.220.01 - Protection against fire in general. The ICS classification helps identify the subject area and facilitates finding related standards.
ISO/TR 24188:2022 has the following relationships with other standards: It is inter standard links to ISO/TR 24188:2025. Understanding these relationships helps ensure you are using the most current and applicable version of the standard.
You can purchase ISO/TR 24188:2022 directly from iTeh Standards. The document is available in PDF format and is delivered instantly after payment. Add the standard to your cart and complete the secure checkout process. iTeh Standards is an authorized distributor of ISO standards.








Questions, Comments and Discussion
Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.
Loading comments...