Environmental damage limitation from fire-fighting water run-off

This Technical Report provides information for the development of specifications and procedures aimed at limiting adverse environmental impacts caused by fire-water run-off (see References [2] to [7]). The information is applicable to commercial facilities, such as warehouses, chemical storage facilities, refineries, process plants which handle and/or store products with a potential pollution potency, and vehicles for the transport of such substances. It is only applicable to land-based operations (i.e. not oil tankers or off-shore oil drilling platforms), and to wildland fires. As such, this Technical Report provides a summary of current potential approaches for controlling and eliminating adverse environmental impacts caused by fire-fighting water run-off. It offers relevant information for the design and sizing of water basins to limit the dispersion of contaminated water into the environment at large (see References [8] to [12]). This Technical Report is divided into three main parts: a description of the hazards of fire run-off, environmental damage limitation and details concerning the possible design of water basins.

Limitation des dommages environnementaux dus au ruissellement des eaux de lutte contre l'incendie

Le présent Rapport technique fournit des informations pour le développement de spécifications et de procédures destinées à limiter les impacts environnementaux négatifs causés par le ruissellement des eaux d'incendie (voir les Références [2] à [7]). Ces informations sont applicables aux installations commerciales, telles que les entrepôts, les installations de stockage de produits chimiques, les raffineries et les usines de traitement manipulant ou stockant des produits avec un potentiel de pollution, ainsi qu'aux véhicules utilisés pour transporter ces substances. Elles ne sont applicables qu'aux opérations terrestres (c'est-à-dire pas sur des pétroliers ou plateformes de forage off-shore) et aux feux de broussailles. En tant que tel, le présent Rapport technique présente un résumé des approches potentielles actuelles pour contrôler et éliminer les impacts environnementaux négatifs causés par le ruissellement des eaux de lutte contre l'incendie. Il fournit des informations pertinentes pour la conception et le dimensionnement des bassins de rétention en vue de limiter la dispersion de l'eau polluée dans l'environnement en général (voir les Références [8] à [12]). Il est divisé en trois grandes parties: une description des dangers dus au ruissellement des eaux de lutte contre l'incendie, la limitation des dommages environnementaux, et des détails concernant la conception possible des bassins de rétention.

General Information

Status
Published
Publication Date
10-May-2012
Current Stage
9092 - International Standard to be revised
Start Date
01-Nov-2023
Completion Date
13-Dec-2025

Overview

ISO/TR 26368:2012 - "Environmental damage limitation from fire‑fighting water run‑off" is an informative Technical Report from ISO that summarizes current approaches for limiting environmental harm caused by fire‑fighting water run‑off. It applies to land‑based commercial and industrial facilities (warehouses, chemical storage, refineries, process plants) and wildland fires, and provides guidance for developing specifications, procedures and design measures - notably for the design and sizing of water basins and other containment systems. The report is advisory (technical report) rather than a mandatory standard.

Key topics

  • Hazards of fire effluent and run‑off: definitions (fire effluent, contaminated fire water) and pathways by which combustion products and extinguishing agents reach surface water and groundwater.
  • Contamination and impact modes: acute and long‑term ecological effects, parameters of concern (toxicity, BOD, COD, pH, suspended solids, metals).
  • Environmental damage limitation: initial risk assessment, risk reduction strategies, and firefighting tactics that consider environmental consequences (including when controlled burning may be preferable).
  • Containment and control measures: permanent/portable tanks, lagoons, modified capture areas (e.g., car parks), shut‑off valves/penstocks to isolate drains and prevent dispersion of contaminated run‑off.
  • Water basin design: characteristics, common features and methods to determine required basin capacity; guidance to limit dispersion of contaminated water.
  • Monitoring and sampling: recommended analytes and sample types (PAHs, dioxins, metals, pH, BOD, COD, suspended solids, toxicity tests) to assess environmental impact.
  • Supporting material: informative annexes with case histories, water basin definition methods and a risk‑based Australian approach.

Practical applications

ISO/TR 26368 is used to:

  • Inform emergency planning and environmental protection measures for industrial sites and transport of hazardous substances.
  • Guide engineers and consultants in designing retention basins, portable tanks and drainage isolation systems to contain contaminated fire‑fighting water.
  • Support fire and rescue services, facility owners, environmental regulators and insurers in risk assessment and incident response planning.
  • Define monitoring strategies and post‑incident sampling to assess ecological impacts and support remediation decisions.

Who should use it

  • Fire‑fighters and incident commanders
  • Facility owners / safety managers and environmental officers
  • Process plant, warehouse and chemical storage operators
  • Environmental regulators, public health authorities, insurers and civil defence organizations
  • Consultants and engineers designing retention and containment systems

Related standards

Normative references include ISO 13943, ISO 14001, ISO 14050 and ISO 26367‑1, which cover fire safety vocabulary, environmental management systems and methods for assessing fire effluents.

Technical report

ISO/TR 26368:2012 - Environmental damage limitation from fire-fighting water run-off Released:5/11/2012

English language
24 pages
sale 15% off
Preview
sale 15% off
Preview
Technical report

ISO/TR 26368:2012 - Limitation des dommages environnementaux dus au ruissellement des eaux de lutte contre l'incendie Released:5/11/2012

French language
25 pages
sale 15% off
Preview
sale 15% off
Preview

Frequently Asked Questions

ISO/TR 26368:2012 is a technical report published by the International Organization for Standardization (ISO). Its full title is "Environmental damage limitation from fire-fighting water run-off". This standard covers: This Technical Report provides information for the development of specifications and procedures aimed at limiting adverse environmental impacts caused by fire-water run-off (see References [2] to [7]). The information is applicable to commercial facilities, such as warehouses, chemical storage facilities, refineries, process plants which handle and/or store products with a potential pollution potency, and vehicles for the transport of such substances. It is only applicable to land-based operations (i.e. not oil tankers or off-shore oil drilling platforms), and to wildland fires. As such, this Technical Report provides a summary of current potential approaches for controlling and eliminating adverse environmental impacts caused by fire-fighting water run-off. It offers relevant information for the design and sizing of water basins to limit the dispersion of contaminated water into the environment at large (see References [8] to [12]). This Technical Report is divided into three main parts: a description of the hazards of fire run-off, environmental damage limitation and details concerning the possible design of water basins.

This Technical Report provides information for the development of specifications and procedures aimed at limiting adverse environmental impacts caused by fire-water run-off (see References [2] to [7]). The information is applicable to commercial facilities, such as warehouses, chemical storage facilities, refineries, process plants which handle and/or store products with a potential pollution potency, and vehicles for the transport of such substances. It is only applicable to land-based operations (i.e. not oil tankers or off-shore oil drilling platforms), and to wildland fires. As such, this Technical Report provides a summary of current potential approaches for controlling and eliminating adverse environmental impacts caused by fire-fighting water run-off. It offers relevant information for the design and sizing of water basins to limit the dispersion of contaminated water into the environment at large (see References [8] to [12]). This Technical Report is divided into three main parts: a description of the hazards of fire run-off, environmental damage limitation and details concerning the possible design of water basins.

ISO/TR 26368:2012 is classified under the following ICS (International Classification for Standards) categories: 13.220.01 - Protection against fire in general. The ICS classification helps identify the subject area and facilitates finding related standards.

You can purchase ISO/TR 26368:2012 directly from iTeh Standards. The document is available in PDF format and is delivered instantly after payment. Add the standard to your cart and complete the secure checkout process. iTeh Standards is an authorized distributor of ISO standards.

Standards Content (Sample)


TECHNICAL ISO/TR
REPORT 26368
First edition
2012-05-15
Environmental damage limitation from
fire‑fighting water run‑off
Limitation des dommages environnementaux dus au ruissellement
des eaux de lutte contre l’incendie
Reference number
©
ISO 2012
All rights reserved. Unless otherwise specified, no part of this publication may be reproduced or utilized in any form or by any means,
electronic or mechanical, including photocopying and microfilm, without permission in writing from either ISO at the address below or ISO’s
member body in the country of the requester.
ISO copyright office
Case postale 56 • CH-1211 Geneva 20
Tel. + 41 22 749 01 11
Fax + 41 22 749 09 47
E-mail copyright@iso.org
Web www.iso.org
Published in Switzerland
ii © ISO 2012 – All rights reserved

Contents Page
Foreword .iv
Introduction . v
1 Scope . 1
2 Normative references . 1
3 Terms and definitions . 1
4 Emission to the aquatic environment . 2
4.1 Contamination pathways . 2
4.2 Control of fire‑fighting water run‑off to surface water and ground water. 3
4.3 Permanent or portable tanks are another option for fire‑water retention . 4
5 Environmental damage limitation . 4
5.1 Initial risk assessment . 4
5.2 Risk reduction strategies . 4
5.3 Fire‑fighting tactics . 5
5.4 Factors in assessing the volume of water run‑off . 6
6 Rules to design water basins . 7
6.1 Characteristics to design the water basins . 7
6.2 Common characteristics of water basins . 8
6.3 Methods to define water basin capacity . 9
Annex A (informative) Example case histories .14
Annex B (informative) Overview of water basin definition methods .17
Annex C (informative) Assessing water run‑off containment capacities in existing facilities and
facilities under development using risk‑based approach — Australian method .19
Bibliography .22
Foreword
ISO (the International Organization for Standardization) is a worldwide federation of national standards bodies
(ISO member bodies). The work of preparing International Standards is normally carried out through ISO
technical committees. Each member body interested in a subject for which a technical committee has been
established has the right to be represented on that committee. International organizations, governmental and
non-governmental, in liaison with ISO, also take part in the work. ISO collaborates closely with the International
Electrotechnical Commission (IEC) on all matters of electrotechnical standardization.
International Standards are drafted in accordance with the rules given in the ISO/IEC Directives, Part 2.
The main task of technical committees is to prepare International Standards. Draft International Standards
adopted by the technical committees are circulated to the member bodies for voting. Publication as an
International Standard requires approval by at least 75 % of the member bodies casting a vote.
In exceptional circumstances, when a technical committee has collected data of a different kind from that
which is normally published as an International Standard (“state of the art”, for example), it may decide by a
simple majority vote of its participating members to publish a Technical Report. A Technical Report is entirely
informative in nature and does not have to be reviewed until the data it provides are considered to be no longer
valid or useful.
Attention is drawn to the possibility that some of the elements of this document may be the subject of patent
rights. ISO shall not be held responsible for identifying any or all such patent rights.
ISO/TR 26368 was prepared by Technical Committee ISO/TC 92, Fire safety, Subcommittee SC 3, Fire threat
to people and environment.
iv © ISO 2012 – All rights reserved

Introduction
Fires involving commercial storage facilities and industrial plants are generally controlled by applying large
volumes of water. These facilities routinely store or use large quantities of materials and manufactured products,
often flammable and combustible. These substances, whether combusted or not, can be transported by
uncontrolled water run-off in the event of a fire and could give rise to severe environmental pollution problems.
The latest Organisation for Economic Co-operation and Development (OECD) report in the series Environmental
[1]
Outlook for the Chemicals Industry , notes that, in the European Union, chemical accidents that cause
ecological harm often involve water pollution; this pollution is frequently the result of fire-water run-off.
The seriousness of these threats depends on various factors, including the nature and quantity of the materials
involved, the emergency planning measures in place, and the location of the fire relative to susceptible
populations and environments. Contamination far beyond the locality of the fire can result from fire scenarios
that generate large quantities of harmful combustion products and fire suppression that involves large quantities
of water. The environmental hazard can be worsened by interactions between the product that is burning, the
combustion products produced and the extinguishing agent.
This Technical Report provides a summary of current approaches to controlling and reducing adverse
environmental impacts caused by fire-water run-off. The intended audience for this Technical Report includes,
but is not necessarily limited to:
— Fire-fighters and investigators.
— Building owners and managers.
— Storage facility operators.
— Materials and product manufacturers.
— Insurance providers.
— Environmental regulatory authorities.
— Civil defence organizations.
— Public health authorities.
— Industrial safety authorities.
TECHNICAL REPORT ISO/TR 26368:2012(E)
Environmental damage limitation from fire‑fighting water run‑off
1 Scope
This Technical Report provides information for the development of specifications and procedures aimed at
limiting adverse environmental impacts caused by fire-water run-off (see References [2] to [7]). The information
is applicable to commercial facilities, such as warehouses, chemical storage facilities, refineries, process plants
which handle and/or store products with a potential pollution potency, and vehicles for the transport of such
substances. It is only applicable to land-based operations (i.e. not oil tankers or off-shore oil drilling platforms),
and to wildland fires.
As such, this Technical Report provides a summary of current potential approaches for controlling and
eliminating adverse environmental impacts caused by fire-fighting water run-off. It offers relevant information for
the design and sizing of water basins to limit the dispersion of contaminated water into the environment at large
(see References [8] to [12]). This Technical Report is divided into three main parts: a description of the hazards
of fire run-off, environmental damage limitation and details concerning the possible design of water basins.
2 Normative references
The following referenced documents are indispensable for the application of this document. For dated
references, only the edition cited applies. For undated references, the latest edition of the referenced document
(including any amendments) applies.
ISO 13943, Fire safety — Vocabulary
ISO 14001, Environmental management systems — Requirements with guidance for use
ISO 14050, Environmental management — Vocabulary
ISO 26367-1, Guidelines for assessing the adverse environmental impact of fire effluents — Part 1: General
3 Terms and definitions
For the purposes of this document, the terms and definitions given in ISO 13943, ISO 14001, ISO 14050,
ISO 26367-1 and the following apply.
3.1
fire effluent
totality of gases and aerosols, including suspended particles, created by combustion or pyrolysis in a fire
NOTE For the purpose of this Technical Report, fire effluent also includes run-off water generated during fire-
fighting activities.
3.2
fire‑water run‑off
aqueous fire effluent containing dissolved and waterborne materials
NOTE Materials that may be present include substances affected by the fire, combustion products, and substances
used to fight the fire.
3.3
biochemical oxygen demand
BOD
indirect measure of the concentration of biologically degradable material present in water
NOTE This definition is based on OECD documents (References [13] and [14]).
3.4
chemical oxygen demand
COD
measure of the oxygen required to fully oxidize all compounds, both organic and inorganic, in water
NOTE This definition is based on OECD documents (References [13] and [14]).
3.5
contaminated fire water
water that has become contaminated with process materials used at a facility and the products resulting from
combustion or products used as part of the extinguishing process
4 Emission to the aquatic environment
4.1 Contamination pathways
4.1.1 General
The major threat to the aquatic environment posed by fires arises from the direct run-off of contaminated fire-
fighting water into rivers, streams, lakes, ground waters and sewage treatment works.
The polluting effects of fire-fighting water run-off, related to both surface water and ground water, are due to
one or more of the following:
— direct toxicity or ecotoxicity (i.e. LD determination on Daphnias);
— an increase or decrease in the biochemical oxygen demand (BOD);
— an increase or decrease in the chemical oxygen demand (COD);
— physical effects such as suspended solids polluting river beds or the gills of fish;
— sanitary quality of public bathing water;
— an increase or decrease in pH;
— metals released in the environment.
4.1.2 Impact modes
The impact that any discharge of fire run-off has on the aquatic environment is determined by a wide
variety of factors:
a) The volume of run-off produced, the time of travel from the site of the fire to the receptor, the dilution
afforded in the receiving water body, and the temperature and chemistry of the receiving water body.
b) The sensitivity and the distance (time of travel from the site) of the primary and secondary receptors, such
as public drinking-water abstraction points, fisheries and all potential aquatic and non-aquatic ecosystems.
c) The chemical composition of the run-off as determined by the source of the fire, e.g. in the case of fires at
sites storing chemicals, a complex mix will be involved including:
— the stored chemicals and their thermal decomposition products washed off the site by the run-off,
— the solid and condensed decomposition products of combustion of the building and of substances
stored on site, and
— additives to the water used in fire suppression, such as fire-fighting foam.
2 © ISO 2012 – All rights reserved

NOTE 1 Contamination could be a consequence of interactions between the pollutants and their targets. For
example, pollutants can be concentrated at different steps in a food chain and their impact can occur far from the
primary affected targets.
NOTE 2 References [15] to [20] give information on the toxicity of chemical fire suppressants.
Contamination can be in the form of pollutants floating on water, pollutants miscible in water, and pollutants
mixing with sediment.
4.1.3 Acute effects
The acute effects of a discharge of run-off to surface water usually appear immediately. The impacts, although
often short term, can be very serious and can include the contamination of public drinking water supplies
during or immediately following the fire. The effects are usually greatest within the immediate vicinity of the site,
where the levels of pollutants will be at their highest. Acute effects can be followed by long-term disruption in
the ecosystem that can occur up to several years after the contamination event (see A.4).
NOTE Acute effects can also peak at some distance from the fire. For example, an oxygen sag can form downstream
of the discharge point when more toxic breakdown products can be formed, such as ammonia forming from the breakdown
of protein-based foams. Furthermore, sensitive receptors can be located well downstream of the discharge point.
4.1.4 Long‑term effects
Long-term environmental impacts from exposures to large fires (i.e. the impacts occurring after the fire, over
a period of years) will be experienced largely within the local environment, within the fire deposition zone
and along impacted streams and watercourses and ground waters as defined in ISO 26367-1. Information
concerning such incidents can be found, for example, in the Major Accident Reporting System (MARS)
described in the Note below.
NOTE The Major Accident Reporting System (MARS) is a distributed information network consisting of 15 local
databases on an MS-Windows platform in each Member State of the European Union and a central UNIX-based analysis
system at the European Commission’s Joint Research Centre in Ispra (MAHB, Major Accident Hazards Bureau) that
allows complex text retrieval and pattern analysis. MARS is used by both EU and OECD member countries to report
industrial accidents in the MARS standard format and to exchange accident information (see Annex A).
Long-term impacts can also arise from direct ingestion by flora and fauna of toxic/carcinogenic/ecotoxic organic
compounds within watercourses contaminated by fire-water run-off. Pollution of ground water can also lead
to the long-term (decades) or permanent closure of public and commercial water supplies that are drawn from
ground water or taken from surface waters that are fed by contaminated ground waters.
The nature and place of any intervention that occurs has a major effect on the environmental impact of that
intervention. Some information is given below concerning what is appropriate to monitor in order to determine
the environmental impact of a particular intervention and whether a controlled burn (i.e. allowing a fire to burn
out under the control of the fire authorities) is not sometimes a viable alternative to traditional extinguishment.
If extinguishing media have been collected, samples should be taken for analysis. Further, samples should also
be taken from ground water and surrounding watercourses or lakes.
The exact species that should be monitored in samples taken on site should be determined based on the
products stored on site and their likely breakdown products as well as on the fire-fighting agent(s) used.
Examples of relevant analyses include: PAH, dioxins, metals, pH, BOD, COD and suspended solids (SS). In
some cases, toxicity tests and biological monitoring may also be useful.
In cases where action is required to prevent the fire from spreading, for example by applying cooling water to
the area around storage tanks, care should be taken to ensure this water does not become polluted.
4.2 Control of fire‑fighting water run‑off to surface water and ground water
Fire-fighting water containment should be considered for industrial sites over and above the requirements
for ordinary bundings and secondary containment systems. A containment system may be needed to protect
both surface and waste-water drainage systems. Lagoons may be constructed whose retention capacity is
adequate for the area concerned. Specific places, such as car parks, should be identified as potential capture
areas as these are easily modified to provide retention capacity for run-off water.
4.3 Permanent or portable tanks are another option for fire‑water retention
Permanent or portable tanks should be constructed of a material resistant to the substances intended to be
retained and tanks should be vented to avoid pressure build-up. Shut-off valves or penstocks that can isolate
parts of the site in an emergency are another alternative to prevent contaminated water from reaching a drain
or surface water. In this case, the contaminated water is held within the drainage system and removed as soon
as practicable (and with the approval of the environment gency and/or sewerage provider). Further information
on the types of system that can be used can be found in References [10], [21] and [33].
5 Environmental damage limitation
5.1 Initial risk assessment
Identification of pollution sources, assessment of the risk and development of protection strategies should be
defined and developed prior to a major incident. The protection strategies identified should take into account
possible atmospheric pollution, domino effects, water run-off displacement, which samples should be taken
and which analyses should be conducted.
5.2 Risk reduction strategies
If the risk screening assessment shows a high or medium risk of pollution from fire-fighting, site operators, in
liaison with fire and rescue services, environmental regulators and other stakeholders, should consider ways
to reduce this risk to an acceptable level or mitigate the impact of the risk.
There are four main ways to reduce risk, which can be implemented at any given site:
a) Prevention
This measure should be given the highest priority, i.e. the prevention of the fire in the first place, e.g. by
segregating or controlling sources of ignition.
b) Automatic detection and fire protection
This measure ensures that if a fire does start, it is detected and fire-fighting is instigated as quickly as
possible. The fitting of automatic detection and protection systems such as automatic sprinkler systems is
one traditional methodology although numerous others exist. Site operators should seek advice on such
systems from fire experts, such as the Fire and Rescue Service and their insurers.
c) Containment
This measure mitigates the impact of a fire through the installation of facilities for containing fire-water run-
off such as storage lagoons or chambers, shut-off valves and isolation tanks or areas.
d) Alternative strategies
This measure reduces the impact of a fire by planning suitable fire-fighting strategies with the Fire and
Rescue Service, such as:
— reducing the amount of fire water generated, such as by using sprays rather than jets;
— recycling fire water where this is not hazardous.
4 © ISO 2012 – All rights reserved

5.3 Fire‑fighting tactics
5.3.1 Relation between fire‑fighting tactics and water usage
Fire-fighting tactics have a strong impact on the nature and volume of fire-water run-off. There are two main
strategies for fire-fighting tactics in industrial fires within the scope of this Technical Report. The choice between
the two different tactics depends mainly on the nature of the fuel involved. The main steps in both tactics are
listed below:
a) Limitation of the propagation of the fire. Fire-fighting is related to the limitation of the fire propagation
to a given limit determined generally by fire-fighters as part of the strategic planning for an industrial site.
The goal of this first step is to avoid propagation to surroundings, e.g. other buildings. At this step, the
extinguishment medium is typically water.
b) Fire control. In this case, propagation is limited and the progress of the fire towards extinguishment has
started. This part of the operation can begin within a few minutes to hours after starting the fire-fighting.
Depending on the nature of the fuel, tactics will differ in this step, e.g.:
1) Hydrocarbon fires (refineries and oil depots, gas stations, rail and road tanks), chemical industries and
some warehouses: In this case, foam is required in order to proceed to extinction. Tactics involving
foam need significant hydraulic systems and lead time before applying the extinguishing medium.
During this delay, fire is limited (“controlled”) by water.
2) All other fires: In this case, water is used in variable quantities to bring the fire to extinguishment,
depending on the specific fire to be controlled.
c) Fire extinguishment. This is the final step, which is also coupled with a survey of the damage and plan
for the next steps (i.e. fire survey).
In step 5.3.1 b), when foam is used, extinguishment will usually be quick (a few minutes) once the foam
application has begun. If not, there is a risk that the fire will reignite and the procedure must be restarted.
Tactics using foam are typically considered to require at least double the time of other tactics. This generates
a much greater volume of water, and the presence of foam and emulsifier agents leads to a more complex
composition of the water to be managed both in terms of quantity and toxicity.
5.3.2 Controlled burn
In some very specific cases, the fire-fighting tactics can specifically involve a decision to “not attack the fire
[22][23]
actively” in the fire-fighting operations once the risk of escalation has been minimized and there are no
further risks to humans. This is often called a “controlled burn” tactic. This is generally chosen for one of three
main reasons, i.e. when fire-fighters do not know how to extinguish the fire, when the risks associated with
active fire-fighting are too great for the fire-fighters, and upon directive from the relevant jurisdiction authority.
The choice to use this approach may minimize adverse environmental impacts caused by polluted fire-water
run-off by restricting the use of fire-fighting media such as water or foam. Under some circumstances, these
tactics may also reduce air pollution as a consequence of more efficient combustion and dispersion of gaseous
pollutants formed in the fire. This tactic may be used as the sole fire-fighting strategy or as part of a strategy
when water/foam are also used during different stages of the fire. The choice of this tactic, however, involves
complex decision making by the fire management team. In this contex, it is important to consider:
— What effect fighting the fire with water or foam may have in terms of potentially contaminating water
resources, fisheries, aquatic fauna and flora.
— Whether there is a realistic possibility of managing a controlled burn, without attempting extinguishment, taking
into account the accompanying risks of short-term air pollution and longer-term pollution of land and water in
the event that the smoke plume comes to ground level, and the risk of fire spread to adjacent structures.
— Whether it is possible to minimize adverse health effects on humans (as this takes priority over
environmental concerns).
5.4 Factors in assessing the volume of water run‑off
5.4.1 Process facilities
To assess the volume of contaminated fire water that may be generated in the process areas, the following
points should be considered:
a) The construction of the main sprinkler distribution pipes (150 mm or above) and level of explosion proofing
[61]
according to ISO 6182-1 . Rules to design sprinkler explosion resistance can be assessed by existing
[24][25]
engineering guidance .
b) The Assumed Maximum Area of Operation (AMAO) on which the sprinkler design is based compared to
the actual floor area.
c) The presence of compartmentalization and the level of fire resistance supporting such compartmentalization
(e.g. fire doors, etc.).
d) The presence of explosion-relieving areas and walls in the building design.
e) The volume of process water/product present in the process equipment that may combine with and
contaminate the fire water.
f) The volume needed for rain/standing water in the process.
5.4.2 Tank farm zones
To assess the volume of contaminated fire water that may be generated in the tank farms, the following points
should be considered:
a) The design and duration of the deluge system.
[26]
b) The number of tanks, their size, construction or separation distances .
c) The presence of radiation walls.
d) The size and make of bunds.
e) The type and quantity of product at risk.
f) The location of the tank farm and its proximity to other property.
g) The volume needed for rain/standing water in the process.
Potentially environmentally damaging materials should always be stored in adequately bunded areas. Bunds
are normally arranged to hold the total of the tank volume, plus 10 %, this being the volume of the initial fire-
fighting or fire protection water or foam. However, much more than this volume would be required to fight a fire.
Therefore, bunds cannot normally be relied on as fire-water retention. They should only realistically be used to
provide temporary containment to gain time.
5.4.3 Warehouse zones
[27][28][29]
To assess the volume of contaminated fire water that may be generated in warehouses , the following
points should be considered:
a) The sprinkler design density and duration at the roof level, and whether in-rack protection is included.
b) The nature of the materials stored.
c) The warehouse design.
NOTE The emergency plan may consider fire-fighting strategies and possible ways to reduce the amount of fire-
water run-off generated. For example, this could be by the use of sprays rather than jets, allowing controlled burning and
possibly recycling of fire-fighting water where it is safe to do so.
6 © ISO 2012 – All rights reserved

6 Rules to design water basins
6.1 Characteristics to design the water basins
Water basins are defined by three main characteristics: size, construction, and location. The level of risk one
is willing to assume applies to all three. Thus, one might assume a given level of risk by sizing the basin for an
above-average fire, rather than a maximum fire. Based on another risk assessment, one might choose not to
line the basin, allowing some rare solutes to leak into the soil. Further, again depending on the risk, one might
locate the basin so that not all the run-off water reaches it.
6.1.1 Risk classification
The risk classification and hazard category affect the containment design. These parameters are often
used as input data in water basin design methods. The risk quoted depends on fire causes (e.g. process
default affecting valves, pipelines and tanks, etc.). The initial risk analysis has to be evaluated regarding the
potential impact on the environment from water run-off as the safety objective. It is also important to note the
possible polluting effects of a mixture of materials (including physical or chemical modifications) that may arise
during a fire. Environmental risk assessment can be evaluated using a fire safety engineering approach (see
[62]
ISO 16732-1 ).
Another aspect to consider when determining the risk classification is the location of the water basin. The
distance between the possible fire area and the potential retention basin is an important parameter. It is
necessary to have a short distance between the water basin and the fire. The water run-off pathway should
be reduced or designed to limit leaks on the way to the retention basin. Further, the intensity of fire expected
will impact on the positioning of the basin. Damage to the water basin from the fire should be limited to avoid
compromising its retention capacity, i.e. the basin should be accessible during the fire if needed, but not so
close as to risk damage.
Risk classification in the design of water basins is an ambiguous parameter. Poor application of this parameter
can lead to a reduction in the capacity of the water basin because of the occurrence probability of fires.
Therefore, the risk classification should be considered carefully in establishing the seriousness of any given
event. In this context, the fire occurrence should be considered as deterministic.
6.1.2 Hazard category of substance
The quantity and nature of hazardous materials present is clearly an important factor. This should be taken
into account when determining the containment capacity. The quantity and nature of the materials present has
a direct impact on the fire growth, the difficulty to control or extinguish the fire, the compatibility with various
extinguishing agents, etc.
There are different hazard categories of substances in various methods used to design water basins. The
potential pollutants are classified according to a range of raw materials, products, fuels, wastes, etc. Their
intrinsic properties (chemical, physical), their potential environmental impact (biochemical, ecotoxicological,
etc.) and the quantity of these materials should also be taken into consideration. Hazard categories of a wide
range of substances may be found in different industrial methods or on the basis of European regulations (see
References [30] to [40]).
Depending on the prevention and protection measures considered, some methods suggest that the hazard
category proposed for a substance should be reduced in some way. Such measures include:
— Limitation of stored quantities.
— Prevention rules.
— Protection devices (detection, automatic extinction, fire-fighting proximity and equipment).
6.1.3 Possible fire area and fire duration
The design of a water basin is tied to fire intensity, in terms of size and duration. Some information concerning
material nature, quantity stored, storage configuration, meteorological conditions (e.g. wind, rain) is needed
to predict the fire area as a function of time and fire duration. Analytical or numerical models can be used to
determine the fire scenario in terms of fire size, heat released and temporal history. These models consider
several hypotheses and databases issued from literature, such as burning rates and heats of combustion.
The use of such models can be very sensitive to input data or model capabilities and should be applied with
care. In addition, data issued from statistics on similar fire size and duration can be useful for deterministic risk
classification.
6.2 Common characteristics of water basins
6.2.1 Common safety characteristics
To protect surface water and ground water, common safety characteristics include:
— Protection against loss of primary containment using high-integrity systems. These include distance
between fire and basin, leaks during water run-off pathway to the basin and containment leaks. To reduce
the loss of water run-off, some modifications such as impermeable liners are often used.
— Necessity to install retention basin with appropriated dimension, tightness and intermediate technology.
— Knowledge of position of chemical products, and selection of proper placement of basins installed.
6.2.2 Classification of water basins
Water basins can be classified in a few categories according to their base design and collection method:
— Those built directly inside or under the protected installation to retain contaminated fire water in the self-
working systems, such as in tank storages built in their own basin.
— Those built close to the protected installation. These systems should be triggered directly and automatically
by gravity or should be manually operated.
— Those placed in case of fire or defined by a variable capacity storage (mobile systems).

General classification of systems
Self-working systems, purpose-built structures Active protection
Effective operation relying on technical
(passive protection)
or organizational measures
ex. : internal capacity inside warehouse
Fixed systems Mobile systems
ex. : remote water basin ex. : inflatable tank device
Automatically triggered Manually operated valve,
gravity flow pump device to activate
Figure 1 — General classification of water basin systems
8 © ISO 2012 – All rights reserved

6.3 Methods to define water basin capacity
6.3.1 Maximum required retention volume for fire‑water run‑off
The following quantities should be determined as a basis for calculation of the maximum required retention
volume for fire-water run-off:
a) The total volume of water likely to be used to fight the fire. Methods suitable to determine this volume are
presented in the following paragraphs.
b) The volume of contaminated water to be retained for each of the main site areas.
c) The expected total volume of contaminated fire water based on the largest volume calculated for each of
the main site areas.
d) The expected volume of rainfall, based on maximum level of water retention under normal usage conditions.
e) The total required retention volume for contaminated fire water.
The largest volume calculated for process areas, tank farms and warehouses is selected as the initial estimate
of the volume of contaminated fire water. This estimate is then compared with the fire water likely to be used for
the site. The larger volume is selected as the required retention volume for contaminated fire water.
Provision for the retention of rainwater that occurs prior to or during the fire must also be included in the
estimated retention volume required. The actual volume of rainwater to be retained should be determined on
a case-by-case basis fed by meteorological databases. In general, the area of coverage should comprise the
total plant area.
Different methods to define water basins and their main characteristics are presented in Annex B.
6.3.2 Size definition by “magic numbers”
The size definition by “magic numbers” is a deterministic approach based on feedback from specific accidents.
Many industries developed such methods after the Sandoz fire (see A.4 and References [46] to [51]). These
methods are mainly based on tabulated values. In general, the volume of the water basin is defined as ranging
3 3
from 3 m to 5 m per ton of material stored. The volume is defined based on the:
— Stored quantity of combustible materials, to define size of compartment.
— Hazard categories of stored products.
— Expected fire duration.
This kind of method is simple to apply, with little input data needed. Nevertheless, “magic numbers” are issued
based on only a few case studies and are difficult to extend to every potential fire scenario.
6.3.3 Size definition by model curves
[40]
Various authors (Thomas 1959, Baldwin 1972, Särdqvist 2000 ) statistically analysed water flow rates
needed by fire and rescue services to extinguish fires versus fire area, for small and large fires. They found
bi-logarithmic relationships between these parameters, with an important variability (see Figure 2). These data
complemented by fire duration can be useful to define common rules for water quantity needed to extinguish
fire, and therefore to define water basin capacity. Statistical data on the time needed to control fire were also
established (see Figure 3).
These analyses have advantages given the large number of fires considered. The total water quantity used,
and thus the size of water basin, is the product of the water flow rate by the control time. Nevertheless, detailed
analysis shows that there is an important variability in the water flow rate needed to extinguish any given fire.
Y
100 000
10 000
1 000
0,1
0,11 10 1001 000 10 000 100 000 X
Key
X fire area (m )
Y water flow rate (l/min)
Thomas - 59
Baldwin - 72
Särdqvist - 00
Figure 2 — Data and correlations from different investigations on the use of water by fire brigade
10 © ISO 2012 – All rights reserved

Y
10 000
1 000
0,1
0,11 10 1001 00010 000 100 000 X
Key
X fire area (m )
Y control time (min)
Thomas - 59
Baldwin - 72
Särdqvist - 00
Figure 3 — Data and correlations on time taken by fire brigade to control fire
All these statistics have been used to construct conventional curves defining the relationship between fire area
and water flow rate. The curves developed by various authors are presented in Figure 4. They all have an upper
and lower curve.
Y
100 000
10 000
1 000
0,11 10 1001 00010 000 100 000
X
Key
X fire area (m )
Y water flow rate (l/min)
Insurance Services Office
Buchanan
Sprinkler
Firepro
Royer
[40]
Figure 4 — Curves of water flow rate vs. area in fire
Regarding statistical data and the above curves, it appears that they often define the lowest rates rather than
what would realistically be expected to be produced by real fires. Moreover, models used to define these
curves are based on various hypotheses and approximations of the area of the fire and what is burning. There
is a lack of knowledge concerning the definition of these curves, which could limit their utility.
6.3.4 Size definition by risk‑based approach
A risk-based approach may be used to assess the pertinence of an existing capacity to retain contaminated fire
water for given premises or to determine the size of a new capacity for industrial facilities which do not have
existing means of retention. This methodology leads to the design of water systems based on hazard analysis
and quantified risk assessment. One possible flowchart to deploy such a method is given in Reference [41] and
Annex C. In general, such a method goes beyond the simple sizing of a water basin, as it is a global method of
risk management assuming a potential release of hazardous materials in receiving waters from an industrial site.
12 © ISO 2012 – All rights reserved

The main steps are as follows:
— Identification of hazardous materials that can contaminate waters.
— Identification of mechanisms of release (needs determination of typical accident scenarios).
— Evaluation of sensitivity of aqueous ecosystem (nearby rivers and lakes, ground water, etc.) according to
nature and quantity of pollutants received and characteristics of local fauna and flora.
— Estimation of potential volume of contaminated water as well as concentration and loading of pollutants,
including impacts of local rainfalls and volumes of fire-fighting waters from the range of pertinent fire
scenarios. In parallel, this step requires the estimation of material leakage and spillage volumes, according
to given accident scenarios.
— Consequence analysis of accidental discharge of water pollutants according to previously obtained data.
This is a complex step as it requires the consideration of many variables including:
— physical dispersion of pollutants,
— degradation of materials,
— concentrations reached in the receiving waters,
— duration of the pollution event (and concentrations of concern in receiving waters),
— short-, medium- and long-term impact of the contamination on the species of the ecosystem.
The water quality criteria that exist in many countries may be useful for this complex step. This part of the process
may lead to the conclusion that no water basin is required. If, however, the conclusion is that consequences are
not acceptable, a further process leads to the sizing of a retention capacity.
The effective sizing step, in addition to taking into account all previous data, will proceed to a frequency/
probability analysis obtained by a comprehensive fire safety study comprising: frequency and magnitude of rain
events, frequency of fires and quantity of water to be applied. From a probabilistic point of view, the final sizing
may be the result of an iterative process based on an acceptance criterion in terms of frequency of discharge
of contaminated waters off site. The probability that the contaminated water volume will exceed the capacity of
the water basin under consideration can be expressed as a function of the size of the retention capacity.
6.3.5 Moderation factors
Protective measures such as sprinklers or material limitations can be used in the design of the installation. For
some water basin design methods, the volume of the water basin may be reduced if protective measures have
been taken that can control the fire to a limited area. Nevertheless, if devices like sprinklers are used to control
fire, their water release has to be considered in the final design of the water basin.
Special attention has to be given to the maintenance of active protection devices and their efficiency when their
usage results in a reduction of water basin volume.
Annex A
(informative)
Example case histories
A.1 Buncefield Supply Depot
[42][43]
Buncefield, UK, December 2005 .
Following the Buncefield Depot fire, approximately 23 million litres of contaminated fire water were successfully
contained. However, the post-fire issue of how to deal with this contaminated run-off has caused as many
problems as extinguishing the fire itself. It should be recognized that this volume of contaminated fire-water
run-off did not reach sensitive water systems, in stark contrast to previous cases. Containment in this instance
was the first and most important priority, given that the degradation products from the foams used during this
1) 2)
fire were expected to contain both PFOS and H-PFOS . The problem in this case was not just the volume
of water but the level and types of contamination contained in the water. It is not credible to simply hope that
a water company can mix these waters with those that are normally treated, such as sewage. It is necessary
to define a plan for orderly treatment and destruction of such contaminated fire-water run-off, which was done
by the UK EPA.
The contaminants present in this fire-water run-off are likely to destroy vital biosystems used
...


RAPPORT ISO/TR
TECHNIQUE 26368
Première édition
2012-05-15
Limitation des dommages
environnementaux dus au ruissellement
des eaux de lutte contre l’incendie
Environmental damage limitation from fire‑fighting water run‑off
Numéro de référence
©
ISO 2012
DOCUMENT PROTÉGÉ PAR COPYRIGHT
Droits de reproduction réservés. Sauf prescription différente, aucune partie de cette publication ne peut être reproduite ni utilisée sous
quelque forme que ce soit et par aucun procédé, électronique ou mécanique, y compris la photocopie et les microfilms, sans l’accord écrit
de l’ISO à l’adresse ci-après ou du comité membre de l’ISO dans le pays du demandeur.
ISO copyright office
Case postale 56 • CH-1211 Geneva 20
Tel. + 41 22 749 01 11
Fax + 41 22 749 09 47
E-mail copyright@iso.org
Web www.iso.org
Publié en Suisse
ii © ISO 2012 – Tous droits réservés

Sommaire Page
Avant-propos .iv
Introduction . v
1 Domaine d’application . 1
2 Références normatives . 1
3 Termes et définitions . 1
4 Émissions dans l’environnement aquatique . 2
4.1 Voies de pollution . 2
4.2 Contrôle du ruissellement des eaux de lutte contre l’incendie, relativement aux eaux de surface
et aux eaux souterraines . 4
4.3 Réservoirs permanents ou mobiles: une autre possibilité de rétention des eaux d’incendie . 4
5 Limitation des dommages environnementaux . 4
5.1 Évaluation initiale des risques . 4
5.2 Stratégies de réduction des risques . 4
5.3 Tactiques de lutte contre l’incendie . 5
5.4 Facteurs pour l’évaluation du volume de ruissellement d’eau . 6
6 Règles pour la conception des bassins de rétention . 7
6.1 Caractéristiques pour la conception des bassins de rétention . 7
6.2 Caractéristiques communes des bassins de rétention . 9
6.3 Méthodes pour définir la capacité des bassins de rétention .10
Annexe A (informative) Exemples de cas .15
Annexe B (informative) Vue d’ensemble des méthodes de définition de bassins de rétention .18
Annexe C (informative) Évaluation des capacités de confinement du ruissellement d’eau dans
des installations existantes et en cours de développement au moyen de l’approche basée sur
les risques — Méthode australienne .20
Bibliographie .23
Avant-propos
L’ISO (Organisation internationale de normalisation) est une fédération mondiale d’organismes nationaux de
normalisation (comités membres de l’ISO). L’élaboration des Normes internationales est en général confiée aux
comités techniques de l’ISO. Chaque comité membre intéressé par une étude a le droit de faire partie du comité
technique créé à cet effet. Les organisations internationales, gouvernementales et non gouvernementales,
en liaison avec l’ISO participent également aux travaux. L’ISO collabore étroitement avec la Commission
électrotechnique internationale (CEI) en ce qui concerne la normalisation électrotechnique.
Les Normes internationales sont rédigées conformément aux règles données dans les Directives ISO/CEI, Partie 2.
La tâche principale des comités techniques est d’élaborer les Normes internationales. Les projets de Normes
internationales adoptés par les comités techniques sont soumis aux comités membres pour vote. Leur publication
comme Normes internationales requiert l’approbation de 75 % au moins des comités membres votants.
Exceptionnellement, lorsqu’un comité technique a réuni des données de nature différente de celles qui sont
normalement publiées comme Normes internationales (ceci pouvant comprendre des informations sur l’état
de la technique par exemple), il peut décider, à la majorité simple de ses membres, de publier un Rapport
technique. Les Rapports techniques sont de nature purement informative et ne doivent pas nécessairement
être révisés avant que les données fournies ne soient plus jugées valables ou utiles.
L’attention est appelée sur le fait que certains des éléments du présent document peuvent faire l’objet de droits
de propriété intellectuelle ou de droits analogues. L’ISO ne saurait être tenue pour responsable de ne pas avoir
identifié de tels droits de propriété et averti de leur existence.
L’ISO/TR 26368 a été élaboré par le comité technique ISO/TC 92, Sécurité au feu, sous-comité SC 3, Dangers
pour les personnes et l’environnement dus au feu.
iv © ISO 2012 – Tous droits réservés

Introduction
Les feux impliquant des installations de stockage commerciales et des usines industrielles sont généralement
contrôlés en appliquant des volumes d’eau importants. Ces installations stockent ou utilisent habituellement
de grandes quantités de matériaux et de produits manufacturés, souvent inflammables et combustibles. Ces
substances, qu’elles soient brûlées ou non, peuvent être transportées par un ruissellement d’eau incontrôlé en
cas d’incendie et pourraient entraîner de graves problèmes de pollution environnementale.
Le dernier rapport de l’Organisation de coopération et de développement économiques (OCDE) de la série
[1]
Les perspectives de l’environnement pour l’industrie chimique , relève que, dans l’Union européenne, les
accidents chimiques qui provoquent des dommages écologiques impliquent souvent une pollution de l’eau,
cette pollution résultant fréquemment du ruissellement des eaux d’incendie.
La gravité des dommages encourus dépend de différents facteurs, tels que la nature et la quantité des matières
impliquées, les mesures de planification d’urgence en place, et le lieu de l’incendie par rapport aux populations
et environnements sensibles. Les scénarios d’incendie qui génèrent de grandes quantités de produits de
combustion dangereux et l’extinction du feu qui implique des quantités d’eau importantes peuvent entraîner
une pollution dépassant largement le site de l’incendie. Les dangers pour l’environnement peuvent être majorés
par les interactions entre le produit en combustion, les produits de combustion générés et l’agent extincteur.
Le présent Rapport technique fournit un résumé des approches actuelles permettant de contrôler et de réduire
les impacts négatifs pour l’environnement provoqués par le ruissellement des eaux d’incendie. Le public visé
par ce Rapport technique comprend, sans nécessairement s’y limiter:
— pompiers et enquêteurs;
— propriétaires et gestionnaires de bâtiments;
— opérateurs d’installations de stockage;
— fabricants de matériaux et de produits;
— assureurs;
— autorités de réglementation environnementale;
— organismes de protection civile;
— autorités de la santé publique;
— autorités de la sécurité industrielle.
RAPPORT TECHNIQUE ISO/TR 26368:2012(F)
Limitation des dommages environnementaux dus
au ruissellement des eaux de lutte contre l’incendie
1 Domaine d’application
Le présent Rapport technique fournit des informations pour le développement de spécifications et de
procédures destinées à limiter les impacts environnementaux négatifs causés par le ruissellement des eaux
d’incendie (voir les Références [2] à [7]). Ces informations sont applicables aux installations commerciales,
telles que les entrepôts, les installations de stockage de produits chimiques, les raffineries et les usines de
traitement manipulant ou stockant des produits avec un potentiel de pollution, ainsi qu’aux véhicules utilisés
pour transporter ces substances. Elles ne sont applicables qu’aux opérations terrestres (c’est-à-dire pas sur
des pétroliers ou plateformes de forage off-shore) et aux feux de broussailles.
En tant que tel, le présent Rapport technique présente un résumé des approches potentielles actuelles
pour contrôler et éliminer les impacts environnementaux négatifs causés par le ruissellement des eaux de
lutte contre l’incendie. Il fournit des informations pertinentes pour la conception et le dimensionnement des
bassins de rétention en vue de limiter la dispersion de l’eau polluée dans l’environnement en général (voir les
Références [8] à [12]). Il est divisé en trois grandes parties: une description des dangers dus au ruissellement
des eaux de lutte contre l’incendie, la limitation des dommages environnementaux, et des détails concernant
la conception possible des bassins de rétention.
2 Références normatives
Les documents de référence suivants sont indispensables pour l’application du présent document. Pour les
références datées, seule l’édition citée s’applique. Pour les références non datées, la dernière édition du
document de référence (y compris les éventuels amendements) s’applique.
ISO 13943, Sécurité au feu — Vocabulaire
ISO 14001, Systèmes de management environnemental — Exigences et lignes directrices pour son utilisation
ISO 14050, Management environnemental — Vocabulaire
ISO 26367-1, Lignes directrices pour déterminer l’impact environnemental des effluents du feu — Partie 1: Généralités
3 Termes et définitions
Pour les besoins du présent document, les termes et définitions donnés dans l’ISO 13943, l’ISO 14001,
l’ISO 14050 et l’ISO 26367-1 ainsi que les suivants s’appliquent.
3.1
effluents du feu
ensemble des gaz et aérosols, y compris les particules en suspension, dégagés par combustion ou par
pyrolyse au cours d’un feu
NOTE Pour les besoins du présent Rapport technique, les effluents du feu incluent également l’eau de ruissellement
produite lors des activités de lutte contre l’incendie.
3.2
ruissellement des eaux d’incendie
effluents du feu aqueux contenant des matières dissoutes et en suspension dans l’eau
NOTE Les matériaux pouvant être présents incluent les substances affectées par l’incendie, les produits de
combustion et les substances utilisées pour lutter contre l’incendie.
3.3
demande biochimique en oxygène
DBO
mesure indirecte de la concentration de matière biodégradable présente dans l’eau
NOTE Cette définition est basée sur les documents de l’OCDE, Références [13] et [14].
3.4
demande chimique en oxygène
DCO
mesure de l’oxygène nécessaire pour oxyder complètement tous les composés, tant organiques
qu’inorganiques, dans l’eau
NOTE Cette définition est basée sur les documents de l’OCDE, Références [13] et [14].
3.5
eau d’incendie polluée
eau qui a été polluée par les matières de traitement utilisées dans une installation et les produits résultant de
la combustion ou les produits utilisés dans le cadre du processus d’extinction de l’incendie
4 Émissions dans l’environnement aquatique
4.1 Voies de pollution
4.1.1 Généralités
La menace principale des incendies envers l’environnement aquatique provient du ruissellement direct des
eaux polluées de lutte contre l’incendie dans les fleuves, cours d’eau, lacs, eaux côtières et stations d’épuration
des eaux usées.
Les effets polluants du ruissellement des eaux de lutte contre l’incendie, relativement aux eaux de surface et
aux eaux souterraines, sont dus à une ou plusieurs des raisons suivantes:
— toxicité directe ou écotoxicité (détermination de la DL sur daphnies);
— augmentation ou diminution de la demande biochimique en oxygène (DBO);
— augmentation ou diminution de la demande chimique en oxygène (DCO);
— effets physiques, tels que des solides en suspension, couvrant le lit des rivières ou affectant les branchies
des poissons;
— qualité sanitaire des eaux de baignade publiques affectée;
— augmentation ou diminution du pH;
— métaux libérés dans l’environnement.
4.1.2 Modes d’impact
L’impact de tout déversement de ruissellement issu d’un incendie sur l’environnement aquatique est déterminé
par une grande diversité de facteurs:
a) le volume de ruissellement produit, la durée du trajet depuis le site de l’incendie jusqu’au récepteur, la
dilution dans la masse d’eau réceptrice et la température et la chimie de la masse d’eau réceptrice;
b) la sensibilité et la distance (durée du trajet depuis le site) des récepteurs primaires et secondaires, tels
que les points de captage public d’eau potable, les pêcheries et tous les écosystèmes aquatiques et non
aquatiques potentiels;
2 © ISO 2012 – Tous droits réservés

c) la composition chimique du ruissellement déterminée par la source du feu, par exemple dans le cas des
incendies sur des sites de stockage de produits chimiques, un mélange complexe sera impliqué, avec:
— les produits chimiques stockés et leurs produits de décomposition thermique lessivés sur le site par
le ruissellement,
— les produits de décomposition solides et condensés de la combustion de l’ouvrage et des substances
stockées sur le site, et
— des additifs à l’eau utilisée pour la suppression de l’incendie, tels que de la mousse de lutte contre l’incendie.
NOTE 1 La pollution pourrait être une conséquence des interactions entre les polluants et leurs cibles. Par exemple,
les polluants peuvent être concentrés à différentes étapes dans une chaîne alimentaire, et leur impact peut être éloigné
des cibles initialement affectées.
NOTE 2 Les Références [15] à [20] fournissent des informations sur la toxicité des agents extincteurs chimiques.
La pollution peut prendre la forme de polluants flottant sur de l’eau, de polluants miscibles dans l’eau et de
polluants mélangés à des sédiments.
4.1.3 Effets aigus
Les effets aigus d’un déversement de ruissellement dans les eaux de surface apparaissent généralement
immédiatement. Les impacts, bien que généralement à court terme, peuvent être très graves et comprendre la
pollution des sources publiques d’alimentation en eau potable pendant l’incendie ou immédiatement après. Les
effets sont habituellement plus importants au voisinage immédiat du site, où les niveaux des polluants seront
les plus élevés. Les effets aigus peuvent être suivis de perturbations à long terme de l’écosystème, pouvant
apparaître jusqu’à plusieurs années après l’événement de pollution (voir A.4).
NOTE Les effets aigus peuvent atteindre leur niveau maximal à une certaine distance de l’incendie. Par exemple,
une poche d’oxygène se forme parfois quelque part en aval du point de déversement, tout comme cela peut se produire
pour des produits de décomposition plus toxiques, par exemple l’ammoniac créé par décomposition des mousses à base
de protéines. Par ailleurs, les récepteurs sensibles peuvent se trouver quelque part en aval du point de déversement.
4.1.4 Effets à long terme
Les impacts environnementaux à long terme découlant de l’exposition aux incendies majeurs (c’est-à-dire les
impacts se produisant après l’incendie, sur plusieurs années) seront en grande partie subis dans l’environnement
local, dans la zone de dépôt de panache de feu et le long des cours d’eaux et des eaux souterraines affectés, tel
que cela est défini dans l’ISO 26367-1. Des informations concernant ces incidents sont par exemple indiquées
dans le système de notification des accidents majeurs (MARS, Major Accident Reporting System; voir Note).
NOTE Le système de notification des accidents majeurs (MARS) consiste en un réseau d’information décentralisé,
qui comprend 15 bases de données locales sur une plate-forme MS-Windows pour chaque État membre de l’Union
européenne, ainsi qu’en un système d’analyse centralisé dans le cadre du Centre commun de recherche d’Ispra de la
Commission européenne (MAHB, Major Accident Hazards Bureau) qui permet d’effectuer des recherches complexes
de mots et des analyses structurelles. MARS est utilisé par les pays membres de l’UE et de l’OCDE afin de signaler les
accidents industriels dans le format standard MARS et d’échanger des informations sur les accidents (voir l’Annexe A).
Les impacts à long terme peuvent aussi provenir de l’ingestion directe, par la flore et la faune, de composés
organiques toxiques/cancérigènes/écotoxiques dans les cours d’eau pollués par le ruissellement des eaux
d’incendie. La pollution des eaux souterraines peut également conduire à la fermeture à long terme (pendant
des dizaines d’années) ou permanente de sources publiques et commerciales d’alimentation en eau, extraites
des eaux souterraines ou prélevées des eaux de surface alimentées par les eaux souterraines polluées.
La nature et le lieu de toute intervention ont un effet majeur sur l’impact environnemental de cette intervention.
Ci-dessous sont fournies des informations indiquant ce qu’il est approprié de surveiller lors de la détermination
de l’impact environnemental d’une intervention particulière, et si une combustion contrôlée (c’est-à-dire
permettant à un feu de brûler sous le contrôle des autorités de lutte contre l’incendie) n’est parfois une alternative
viable à une extinction traditionnelle. Si les moyens d’extinction ont été récupérés, il convient de réaliser un
échantillonnage pour analyse. Il convient par ailleurs que les échantillons soient également prélevés dans les
eaux souterraines et les cours d’eau ou les lacs environnants.
Il convient que les espèces exactes à surveiller dans les échantillons prélevés sur le site soient déterminées
sur la base des produits stockés sur le site et de leurs produits de décomposition probables, ainsi que de
l’agent de lutte contre l’incendie utilisé. Des exemples d’analyses pertinentes incluent: HAP, dioxines, métaux,
pH, DBO, DCO et solides en suspension (SS). Dans certains cas les essais de toxicité et la surveillance
biologique peuvent aussi être utiles.
Dans les cas où une action est nécessaire pour éviter la propagation du feu, par exemple l’application d’eau
de refroidissement dans la zone voisine des réservoirs de stockage, il convient de s’assurer que cette eau ne
devienne pas polluée.
4.2 Contrôle du ruissellement des eaux de lutte contre l’incendie, relativement aux eaux
de surface et aux eaux souterraines
Il convient d’envisager le confinement des eaux de lutte contre l’incendie pour les sites industriels au-dessus
et en dessous des exigences relatives aux systèmes de rétention ordinaires et aux systèmes de confinement
secondaire. Un système de confinement peut être nécessaire pour protéger les systèmes d’évacuation des
eaux de surface et des eaux usées. Il est possible de construire des étangs de capacité de rétention appropriée
pour la zone concernée. Il convient que des endroits spécifiques, tels que des parkings, soient identifiés
comme des zones de capture potentielles, car ils peuvent être facilement modifiés pour fournir une capacité
de rétention de l’eau de ruissellement.
4.3 Réservoirs permanents ou mobiles: une autre possibilité de rétention des eaux d’incendie
Il est recommandé de construire les réservoirs permanents ou mobiles dans un matériau résistant aux
substances destinées à être contenues et de les ventiler pour éviter toute accumulation de pression. Des
robinets d’arrêt ou des vannes de retenue pouvant isoler des parties du site en situation d’urgence constituent
une autre manière d’empêcher l’eau polluée d’atteindre un branchement d’assainissement ou les eaux de
surface. Dans ce cas, l’eau polluée est maintenue dans le système d’assainissement puis évacuée aussi
rapidement que possible (et avec l’approbation de l’agence pour l’environnement et/ou du fournisseur du
système d’assainissement). Des informations supplémentaires sur les types de système pouvant être utilisés
sont indiquées dans les Références [10], [21] et [33].
5 Limitation des dommages environnementaux
5.1 Évaluation initiale des risques
Il convient que l’identification des sources de pollution, l’évaluation du risque et le développement des stratégies
de protection soient définis et développés avant un incident majeur. Il est recommandé que les stratégies de
protection tiennent compte de la pollution atmosphérique, des effets domino, du déplacement du ruissellement
d’eau potentiels, des échantillons qu’il convient de prélever et des analyses qu’il convient de réaliser.
5.2 Stratégies de réduction des risques
Lorsque l’évaluation préliminaire des risques montre un risque élevé ou modéré de pollution due à la lutte
contre l’incendie, il convient que les opérateurs du site, conjointement aux services de lutte contre l’incendie
et de secours, à l’agence de réglementation environnementale et aux autres parties prenantes, étudient des
moyens de réduire le risque à un niveau acceptable ou d’atténuer son impact.
Il existe quatre méthodes principales pour réduire le risque, qui peuvent être mises en œuvre sur tout site:
a) Prévention
Il convient de donner la plus haute priorité à cette mesure, c’est-à-dire à la prévention contre l’incendie en
premier lieu, par exemple en séparant ou en contrôlant les sources d’allumage.
4 © ISO 2012 – Tous droits réservés

b) Détection automatique et protection contre l’incendie
Cette mesure garantit que, si un incendie se déclenche, il est détecté, et que la lutte contre l’incendie
démarre aussi rapidement que possible. L’installation de systèmes automatiques de détection et de
protection, tels que des systèmes de sprinklers automatiques, est une méthodologie traditionnellement
utilisée dans ce but, bien qu’il en existe de nombreuses autres. Il convient que les opérateurs du site
demandent toujours le conseil des experts en incendie, tels que les services de lutte contre l’incendie et
de secours et leurs assureurs.
c) Confinement
Cette mesure atténue l’impact d’un incendie par la mise en place d’installations pour la rétention des eaux
d’incendie, telles que des étangs ou des chambres de stockage, des robinets d’arrêt et des réservoirs ou
des zones de confinement.
d) Autres stratégies possibles
Cette mesure réduit l’impact d’un incendie en planifiant avec les services de lutte contre l’incendie et de
secours des stratégies appropriées de lutte contre l’incendie, telles que:
— la réduction de la quantité d’eau d’incendie générée, notamment en utilisant la pulvérisation plutôt
que les jets;
— le recyclage de l’eau d’incendie, lorsque cela n’est pas trop dangereux.
5.3 Tactiques de lutte contre l’incendie
5.3.1 Relation entre les tactiques de lutte contre l’incendie et l’utilisation d’eau
Les tactiques de lutte contre l’incendie ont un impact important sur la nature et le volume de ruissellement des
eaux d’incendie. Deux principales stratégies pour les tactiques de lutte contre l’incendie dans les incendies
industriels font partie du domaine d’application du présent Rapport technique. Le choix de l’une de ces deux
tactiques différentes dépend principalement de la nature du combustible concerné. Les principales étapes des
deux tactiques sont indiquées ci-dessous.
a) Limitation de la propagation du feu. La lutte contre l’incendie est liée à la limitation de la propagation du
feu jusqu’à une limite donnée, généralement déterminée par les pompiers dans le cadre de la planification
stratégique d’un site industriel. Cette première étape a pour objectif d’éviter la propagation du feu aux
éléments environnants, par exemple d’autres bâtiments. À cette étape, le moyen d’extinction utilisé est
généralement de l’eau.
b) Contrôle du feu. La propagation est limitée et le processus d’extinction du feu a commencé. Le démarrage de
cette partie de l’opération peut s’effectuer entre quelques minutes et quelques heures après le début de la lutte
contre l’incendie. En fonction de la nature du combustible, les tactiques différeront à cette étape, par exemple:
1) Feux d’hydrocarbures (raffineries et dépôts pétroliers, stations‑services, citernes), industries chimiques
et certains entrepôts: dans ce cas, de la mousse est nécessaire pour procéder à l’extinction. Les
tactiques à base de mousse nécessitent des systèmes hydrauliques importants et impliquent un délai
d’attente avant de pouvoir commencer l’application du moyen d’extinction. Pendant ce temps, le feu
est limité («contrôlé») avec de l’eau.
2) Tous les autres feux: de l’eau est alors utilisée en quantités variables pour éteindre le feu, en fonction
du feu spécifique à contrôler.
c) Extinction du feu. Il s’agit de la dernière étape, qui est également associée à une enquête concernant
les dommages et à un plan pour les étapes suivantes (c’est-à-dire enquête incendie).
Lors de l’étape 5.3.1 b), lorsque de la mousse est utilisée, l’extinction sera généralement rapide (en quelques
minutes) après le début de l’application de la mousse. Dans le cas contraire, le feu risque de reprendre et
il faudra alors recommencer la procédure. Il est généralement considéré que les techniques utilisant de la
mousse nécessitent au moins deux fois plus de temps que les autres tactiques. Le volume d’eau généré est
alors beaucoup plus important, et la présence de mousse et d’agents émulsifiants génère une composition
plus complexe de l’eau qu’il faut gérer à la fois en termes de quantité et de toxicité.
5.3.2 Combustion contrôlée
Dans certains cas très spécifiques, les tactiques de lutte contre l’incendie peuvent spécifiquement impliquer une
[22][23]
décision de «ne pas combattre l’incendie de manière active» dans les opérations de lutte contre l’incendie
lorsque le risque d’escalade a été minimisé et qu’il n’existe pas de risque pour les personnes. Cette tactique est
souvent appelée «combustion contrôlée». Elle est généralement choisie pour l’une des trois principales raisons
suivantes: lorsque les pompiers ne savent pas comment éteindre le feu, lorsque les risques associés à la lutte
active contre l’incendie sont trop élevés pour les pompiers, et en se basant sur des lignes directrices de l’autorité
compétente concernée. Le choix d’utiliser cette approche peut minimiser les impacts environnementaux
négatifs causés par le ruissellement des eaux d’incendie polluées en limitant l’utilisation de moyens de lutte
contre l’incendie, tels que l’eau ou la mousse. Dans certains cas, ces tactiques peuvent également réduire la
pollution de l’air du fait d’une combustion et d’une dispersion plus efficaces des polluants gazeux formés dans
l’incendie. Cette tactique peut être utilisée comme la seule stratégie de lutte contre l’incendie ou dans le cadre
d’une stratégie lorsque de l’eau ou la mousse sont également utilisées à différentes phases de l’incendie. Le
choix de cette tactique implique néanmoins une prise de décision complexe par l’équipe chargée de la gestion
de l’incendie. Dans ce contexte, il est important de tenir compte des éléments suivants:
— l’effet que la lutte contre l’incendie avec de l’eau ou de la mousse peut avoir en termes de pollution
potentielle des ressources d’eau, pêcheries, faune et flore aquatique;
— s’il existe une possibilité réaliste de gérer une combustion contrôlée, sans essayer d’éteindre le feu, en
tenant compte des risques associés de la pollution de l’air à court terme et de la pollution du sol et de
l’eau à plus long terme si le panache de fumée venait à atteindre le niveau du sol, ainsi que du risque de
propagation du feu aux structures adjacentes;
— s’il est possible de minimiser les effets indésirables pour la santé des personnes (car cela prime sur les
préoccupations environnementales).
5.4 Facteurs pour l’évaluation du volume de ruissellement d’eau
5.4.1 Industries de procédés chimiques
Pour évaluer le volume d’eau d’incendie polluée pouvant être généré dans les zones d’industries de procédés
chimiques, il convient de considérer les points suivants.
a) La construction des conduites principales de distribution des sprinklers (150 mm ou plus) et le degré de
[61]
protection anti-déflagration, conformément à l’ISO 6182-1 . Les règles de conception de la résistance à
[24][25]
l’explosion des sprinklers peuvent être évaluées à l’aide de lignes directrices d’ingénierie existantes .
b) La zone maximale de fonctionnement présumée (AMAO, Assumed Maximum Area of Operation) sur
laquelle la conception des sprinklers est basée par rapport à la surface au sol réelle.
c) La présence d’un compartimentage et le niveau de résistance au feu étayant ce compartimentage (par
exemple portes coupe-feu, etc.).
d) La présence, dans la conception de l’ouvrage, de murs ou de zones permettant d’atténuer les explosions.
e) Le volume d’eau/produit de traitement présent dans l’équipement de traitement pouvant être combiné aux
eaux d’incendie et les contaminer.
f) Le volume nécessaire pour les eaux pluviales/stagnantes dans le processus.
6 © ISO 2012 – Tous droits réservés

5.4.2 Zones de réservoirs de stockage
Pour évaluer le volume d’eau d’incendie polluée pouvant être généré dans les zones de réservoirs de stockage,
il convient de considérer les points suivants.
a) La conception et la durée de l’installation de type déluge.
[26]
b) Le nombre de réservoirs, leurs dimensions, construction ou distances de séparation .
c) La présence de murs anti-rayonnements.
d) Les dimensions et la construction de murets de rétention.
e) Le type et la quantité de produit à risque.
f) L’emplacement de la zone de réservoirs de stockage et sa proximité avec une autre propriété.
g) Le volume nécessaire pour les eaux pluviales/stagnantes dans le processus.
Il convient que les matières susceptibles de provoquer des dommages pour l’environnement soient toujours
stockées dans des zones équipées de murets de rétention adéquats. Les murets de rétention sont généralement
disposés de façon à contenir le volume total du réservoir, plus 10 % (soit le volume de l’eau ou de la mousse de
lutte ou de protection contre l’incendie initiale). Toutefois, un volume beaucoup plus important serait nécessaire
pour lutter contre un incendie. C’est pourquoi les murets de rétention ne sont normalement pas considérés
comme un moyen fiable de rétention des eaux d’incendie. Il convient de ne les utiliser de façon réaliste que
pour fournir un confinement temporaire afin de gagner du temps.
5.4.3 Zones d’entrepôts
[27][28][29]
Pour évaluer le volume d’eau d’incendie pouvant être généré dans les entrepôts , il convient de
considérer les points suivants.
a) La densité de conception des sprinklers et la durée au niveau de la toiture, et si une protection en racks
est intégrée.
b) La nature des matières stockées.
c) La conception de l’entrepôt.
NOTE Le plan d’urgence peut prendre en compte les stratégies de lutte contre l’incendie et les différentes manières
de réduire la quantité de ruissellement des eaux d’incendie généré. Pour cela, il pourrait par exemple être possible
d’utiliser la pulvérisation plutôt que les jets, de permettre la combustion contrôlée et éventuellement de recycler l’eau de
lutte contre l’incendie lorsque cela ne présente pas de danger.
6 Règles pour la conception des bassins de rétention
6.1 Caractéristiques pour la conception des bassins de rétention
Les bassins de rétention sont définis par trois caractéristiques principales: les dimensions, la construction et
l’emplacement. Le niveau de risque que l’on souhaite supposer s’applique à ces trois caractéristiques. Par
conséquent, un niveau de risque donné peut être supposé en dimensionnant le bassin pour un incendie au-
dessus de la moyenne plutôt qu’un incendie maximal. À partir d’une autre évaluation des risques, on pourrait
décider de ne pas installer de revêtement sur le bassin, permettant ainsi à certains solutés rares de fuir dans
le sol. Une fois encore, en fonction du risque, on pourrait installer le bassin de façon qu’une partie seulement
de l’eau de ruissellement l’atteigne.
6.1.1 Classification des risques
La classification des risques et la catégorie de danger ont une incidence sur la conception de confinement.
Ces paramètres sont souvent utilisés comme données d’entrée dans les méthodes de conception des bassins
de rétention. Le risque coté dépend des causes de l’incendie (par exemple défaut du processus touchant les
vannes, conduites et réservoirs, etc.). Il faut évaluer l’analyse initiale des risques par rapport à l’impact potentiel
sur l’environnement du ruissellement d’eau comme étant l’objectif de sécurité. Il est également important de
noter les effets polluants potentiels d’un mélange de matières (y compris les modifications physiques ou
chimiques) susceptibles de survenir pendant un incendie. L’évaluation du risque environnemental peut être
[62]
considérée dans le cadre d’une approche d’ingénierie de la sécurité incendie (voir l’ISO 16732-1 ).
Un autre aspect à prendre en compte dans la détermination de la classification des risques est l’emplacement
du bassin de rétention. La distance entre la zone potentielle de l’incendie et le bassin de rétention potentiel
constitue un paramètre important. La distance entre le bassin de rétention et l’incendie doit être courte. Il
convient que le trajet de ruissellement de l’eau soit réduit ou conçu pour limiter les fuites sur le trajet jusqu’au
bassin de rétention. De plus, l’intensité de l’incendie prévu aura des incidences sur le positionnement du
bassin. Il est recommandé de limiter les dommages au bassin de rétention dus à l’incendie afin d’éviter de
compromettre sa capacité de rétention, c’est-à-dire qu’il convient que le bassin soit accessible pendant
l’incendie si nécessaire, mais qu’il ne soit pas trop proche pour ne pas risquer de provoquer des dommages.
La classification des risques dans la conception des bassins de rétention est un paramètre ambigu. Une
mauvaise application de ce paramètre peut entraîner une réduction de la capacité du bassin de rétention
en raison de la probabilité de survenue d’incendies. Il convient par conséquent d’examiner attentivement la
classification des risques lors de l’établissement de la gravité d’un événement donné. Dans ce contexte, il est
recommandé de considérer la survenue d’un incendie comme étant déterministe.
6.1.2 Catégorie de danger d’une substance
La quantité et la nature des matières dangereuses présentes constituent incontestablement un facteur
important. Il convient d’en tenir compte lors de la détermination de la capacité de confinement. La quantité et
la nature des matières présentes ont un impact direct sur la croissance du feu, la difficulté à contrôler ou à
éteindre le feu, la compatibilité avec différents agents extincteurs, etc.
Il existe différentes catégories de danger des substances dans diverses méthodes utilisées pour la conception
des bassins de rétention. Les polluants potentiels sont classés en fonction d’une plage de matières premières,
produits, combustibles, déchets, etc. Il convient également de tenir compte de leurs propriétés intrinsèques
(chimiques, physiques), de leur impact environnemental potentiel (biochimique, écotoxicologique, etc.) et de
leur quantité. Les catégories de danger d’une vaste plage de substances sont indiquées dans différentes
méthodes industrielles ou dans le cadre des réglementations européennes (voir les Références [30] à [40]).
Selon les mesures de prévention et de protection prises en compte, certaines méthodes suggèrent qu’il
convient de réduire la catégorie de danger proposée pour une substance. Ces mesures comportent:
— la limitation des quantités stockées;
— des règles de prévention;
— des dispositifs de protection (détection, extinction automatique, proximité et équipement de lutte
contre l’incendie).
6.1.3 Zone potentielle d’incendie et durée de l’incendie
La conception d’un bassin de rétention est liée à l’intensité de l’incendie, en termes de dimensions et de durée.
Certaines informations concernant la nature de la matière, la quantité stockée, la configuration de stockage,
les conditions météorologiques (par exemple vent, pluie) sont nécessaires pour prédire la zone d’incendie en
fonction du temps et de la durée de l’incendie. Il est possible d’utiliser des modèles analytiques ou numériques
pour déterminer le scénario d’incendie en termes de dimensions de l’incendie, de chaleur libérée et d’histoire
temporelle. Ces modèles tiennent compte de plusieurs hypothèses et bases de données issues de la littérature,
telles que les vitesses de combustion et les pouvoirs calorifiques.
L’utilisation de ces modèles peut être très sensible aux données d’entrée et aux capacités du modèle et il
convient donc de les appliquer avec précaution. Par ailleurs, les données issues de statistiques concernant des
dimensions et une durée d’incendie similaires peuvent être utiles pour la classification déterministe des risques.
8 © ISO 2012 – Tous droits réservés

6.2 Caractéristiques communes des bassins de rétention
6.2.1 Caractéristiques de sécurité communes
Pour protéger les eaux de surface et les eaux souterraines, les caractéristiques de sécurité communes incluent
les suivantes.
— Protection contre la perte du confinement primaire à l’aide de systèmes à haute intégrité, prenant en
compte la distance entre l’incendie et le bassin, les fuites sur le trajet de ruissellement d’eau jusqu’au
bassin et les fuites du confinement. Pour réduire la perte de ruissellement d’eau, des modifications telles
que des revêtements imperméables sont souvent utilisées.
— Nécessité d’installer un bassin de rétention, de dimensions, étanchéité et technologie intermédiaire appropriées.
— Connaissance de l’emplacement des produits chimiques et sélection de l’emplacement adéquat des
bassins installés.
6.2.2 Classification des bassins de rétention
Les bassins de rétention pourraient être classés en plusieurs catégories en fonction de leur conception de
base et de la méthode de collecte:
— les bassins construits directement dans ou sous l’installation protégée pour confiner les eaux d’incendie
polluées dans les systèmes autonomes, notamment dans des réservoirs construits dans leur propre bassin;
— les bassins construits à proximité de l’installation protégée; il convient que ces systèmes soient alimentés
directement et automatiquement par gravité ou qu’ils soient commandés manuellement;
— les bassins installés en cas d’incendie ou définis par un stockage à capacité variable (systèmes mobiles).
Classification générale des systèmes
Systèmes autonomes, structures spécialisées
Protection active
(protection passive)
Fonctionnement efficace reposant sur des
Par exemple : capacité interne
mesures techniques ou organisationnelles
à l’intérieur de l’entrepôt
Systèmes fixes Systèmes mobiles
Par exemple : bassins Par exemple : réservoirs
de rétention distants gonflables
Vanne à commande
Automatiquement
manuelle,
alimentés par gravité
dispositif à pompe à activer
Figure 1 — Classification générale des systèmes de bassins de rétention
6.3 Méthodes pour définir la capacité des bassins de rétention
6.3.1 Volume de rétention maximal requis pour le ruissellement des eaux d’incendie
Il convient de déterminer les quantités suivantes, qui serviront de base au calcul du volume de rétention
maximal requis pour le ruissellement des eaux d’incendie:
a) le volume total d’eau susceptible d’être utilisé pour lutter contre l’incendie; des méthodes appropriées pour
déterminer ce volume sont présentées dans les paragraphes suivants;
b) le volume d’eau polluée à confiner pour chacune des principales zones du site;
c) le volume total prévu d’eau d’incendie polluée basé sur le volume le plus important calculé pour chacune
des principales zones du site;
d) le volume de pluie prévu, basé sur le niveau maximal de rétention d’eau en conditions normales d’utilisation;
e) le volume de rétention total requis pour les eaux d’incendie polluées.
Le volume le plus important calculé pour les zones de traitement, les zones de réservoirs de stockage et les
entrepôts est sélectionné comme l’estimation initiale du volume d’eau d’incendie polluée. Cette estimation est
ensuite comparée à l’eau d’incendie susceptible d’être utilisée pour le site. Le volume le plus important est
sélectionné comme le volume de rétention requis pour l’eau d’incendie polluée.
Le volume de rétention estimé requis doit également prévoir la rétention des eaux pluviales produites avant ou
après l’incendie. Il convient de déterminer le volume réel d’eaux pluviales à confiner au cas par cas à l’aide de
bases de données météorologiques. Il est en général recommandé que la zone de couverture comprenne la
surface totale de l’usine.
Différentes méthodes de définition de bassins de rétention et leurs principales caractéristiques sont présentées
à l’Annexe B.
6.3.2 Définition des dimensions à l’aide de «nombres magiques»
La définition des dimensions à l’aide de «nombres magiques» est une approche déterministe basée sur le retour
d’informations issues d’accidents spécifiques. De nombreuses industries ont développé ce type de méthode
après l’incendie de l’usine Sandoz (voir A.4 et les Références [46] à [51]). Ces méthodes sont principalement
basées sur des valeurs tabulées. Le volume du bassin de rétention est généralement défini comme étant
3 3
compris entre 3 m et 5 m par tonne de matière stockée. Le volume est défini à partir des éléments suivants:
— quantité stockée de matières combustibles, pour définir les dimensions du compartiment;
— catégories de danger des produits stockés;
— durée prévue de l’incendie.
Ce type de méthode est simple à appliquer et ne nécessite que peu de données d’entrée. Néanmoins, les
«nombres magiques» sont tirés de quelques études de cas seulement et sont difficiles à extrapoler à chaque
scénario d’incendie potentiel.
6.3.3 Définition des dimensions à l’aide de courbes modèles
[40]
Divers auteurs (Thomas, 1959; Baldwin, 1972; Särdqvist, 2000 ) ont procédé à une analyse statistique des
débits d’eau dont les services de lutte contre l’incendie et de secours ont besoin pour éteindre les feux par
rapport à la surface de l’incendie, pour les petits et grands incendies. Ils ont établi des relations bi-logarithmiques
entre ces paramètres, avec une variabilité importante (voir Figure 2). Complét
...