Boxes and enclosures for electrical accessories for household and similar fixed electrical installations - Part 24: Particular requirements for enclosures for housing protective devices and similar power consuming devices

This part of IEC 60670 applies to empty enclosures and parts of them for electrical accessories intended to be used with a rated voltage not exceeding 400 V and a total incoming load current not exceeding 125 A for household and similar fixed electrical installations, where a maximum capability to dissipate power in normal use is declared by the manufacturer. These enclosures are intended for housing protective devices and devices with or without power dissipation. They are intended to be installed where the prospective short circuit current does not exceed 10 kA unless they are protected by current limiting protective devices with a cut-off current not exceeding 17 kA.

Boîtes et enveloppes pour appareillage électrique pour installations électriques fixes pour usages domestiques et analogues - Partie 24: Règles particulières pour enveloppes pour appareillages de protection et appareillages similaires ayant une puissance dissipée

La présente partie de la CEI 60670 s'applique aux enveloppes vides, et aux parties des enveloppes vides, qui sont prévues pour les appareillages électriques destinés à être utilisés avec une tension assignée n'excédant pas 400 V et un courant total à l'arrivée n'excédant pas 125 A pour les installations électriques fixes pour usages domestiques et analogues, et pour lesquelles le constructeur déclare une aptitude maximale à dissiper la puissance en usage normal. Ces enveloppes sont destinées à recevoir des appareillages de protection ou tout autre appareillage ayant ou non une puissance dissipée. Elles sont destinées à être installées là où le courant de court-circuit présumé n'excède pas 10 kA, sauf si elles sont protégées par des dispositifs de protection limiteurs de courant avec un courant coupé limité n'excédant pas 17 kA.

General Information

Status
Published
Publication Date
22-Feb-2005
Current Stage
DELPUB - Deleted Publication
Start Date
08-Mar-2011
Completion Date
26-Oct-2025
Ref Project

Relations

Standard
IEC 60670-24:2005 - Boxes and enclosures for electrical accessories for household and similar fixed electrical installations - Part 24: Particular requirements for enclosures for housing protective devices and similar power consuming devices Released:2/23/2005 Isbn:2831878675
English and French language
45 pages
sale 15% off
Preview
sale 15% off
Preview

Standards Content (Sample)


NORME CEI
INTERNATIONALE IEC
60670-24
INTERNATIONAL
Première édition
STANDARD
First edition
2005-02
Boîtes et enveloppes pour appareillage électrique
pour installations électriques fixes pour usages
domestiques et analogues –
Partie 24:
Règles particulières pour enveloppes pour
appareillages de protection et appareillages
similaires ayant une puissance dissipée

Boxes and enclosures for electrical accessories
for household and similar fixed electrical
installations –
Part 24:
Particular requirements for enclosures for housing
protective devices and similar power consuming
devices
Numéro de référence
Reference number
CEI/IEC 60670-24:2005
Numérotation des publications Publication numbering
Depuis le 1er janvier 1997, les publications de la CEI As from 1 January 1997 all IEC publications are
sont numérotées à partir de 60000. Ainsi, la CEI 34-1 issued with a designation in the 60000 series. For
devient la CEI 60034-1. example, IEC 34-1 is now referred to as IEC 60034-1.
Editions consolidées Consolidated editions
Les versions consolidées de certaines publications de la The IEC is now publishing consolidated versions of its
CEI incorporant les amendements sont disponibles. Par publications. For example, edition numbers 1.0, 1.1
exemple, les numéros d’édition 1.0, 1.1 et 1.2 indiquent and 1.2 refer, respectively, to the base publication,
respectivement la publication de base, la publication de the base publication incorporating amendment 1 and
base incorporant l’amendement 1, et la publication de the base publication incorporating amendments 1
base incorporant les amendements 1 et 2. and 2.
Informations supplémentaires Further information on IEC publications
sur les publications de la CEI
Le contenu technique des publications de la CEI est The technical content of IEC publications is kept
constamment revu par la CEI afin qu'il reflète l'état under constant review by the IEC, thus ensuring that
actuel de la technique. Des renseignements relatifs à the content reflects current technology. Information
cette publication, y compris sa validité, sont dispo- relating to this publication, including its validity, is
nibles dans le Catalogue des publications de la CEI available in the IEC Catalogue of publications
(voir ci-dessous) en plus des nouvelles éditions, (see below) in addition to new editions, amendments
amendements et corrigenda. Des informations sur les and corrigenda. Information on the subjects under
sujets à l’étude et l’avancement des travaux entrepris consideration and work in progress undertaken by the
par le comité d’études qui a élaboré cette publication, technical committee which has prepared this
ainsi que la liste des publications parues, sont publication, as well as the list of publications issued,
également disponibles par l’intermédiaire de: is also available from the following:
• Site web de la CEI (www.iec.ch) • IEC Web Site (www.iec.ch)
• Catalogue des publications de la CEI • Catalogue of IEC publications
Le catalogue en ligne sur le site web de la CEI The on-line catalogue on the IEC web site
(www.iec.ch/searchpub) vous permet de faire des (www.iec.ch/searchpub) enables you to search by a
recherches en utilisant de nombreux critères, variety of criteria including text searches,
comprenant des recherches textuelles, par comité technical committees and date of publication. On-
d’études ou date de publication. Des informations en line information is also available on recently
ligne sont également disponibles sur les nouvelles issued publications, withdrawn and replaced
publications, les publications remplacées ou retirées, publications, as well as corrigenda.
ainsi que sur les corrigenda.
• IEC Just Published • IEC Just Published
Ce résumé des dernières publications parues This summary of recently issued publications
(www.iec.ch/online_news/justpub) est aussi dispo- (www.iec.ch/online_news/justpub) is also available
nible par courrier électronique. Veuillez prendre by email. Please contact the Customer Service
contact avec le Service client (voir ci-dessous) Centre (see below) for further information.
pour plus d’informations.
• Service clients • Customer Service Centre
Si vous avez des questions au sujet de cette If you have any questions regarding this
publication ou avez besoin de renseignements publication or need further assistance, please
supplémentaires, prenez contact avec le Service contact the Customer Service Centre:
clients:
Email: custserv@iec.ch Email: custserv@iec.ch
Tél: +41 22 919 02 11 Tel: +41 22 919 02 11
Fax: +41 22 919 03 00 Fax: +41 22 919 03 00
.
NORME CEI
INTERNATIONALE IEC
60670-24
INTERNATIONAL
Première édition
STANDARD
First edition
2005-02
Boîtes et enveloppes pour appareillage électrique
pour installations électriques fixes pour usages
domestiques et analogues –
Partie 24:
Règles particulières pour enveloppes pour
appareillages de protection et appareillages
similaires ayant une puissance dissipée

Boxes and enclosures for electrical accessories
for household and similar fixed electrical
installations –
Part 24:
Particular requirements for enclosures for housing
protective devices and similar power consuming
devices
 IEC 2005 Droits de reproduction réservés  Copyright - all rights reserved
Aucune partie de cette publication ne peut être reproduite ni No part of this publication may be reproduced or utilized in any
utilisée sous quelque forme que ce soit et par aucun procédé, form or by any means, electronic or mechanical, including
électronique ou mécanique, y compris la photocopie et les photocopying and microfilm, without permission in writing from
microfilms, sans l'accord écrit de l'éditeur. the publisher.
International Electrotechnical Commission, 3, rue de Varembé, PO Box 131, CH-1211 Geneva 20, Switzerland
Telephone: +41 22 919 02 11 Telefax: +41 22 919 03 00 E-mail: inmail@iec.ch Web: www.iec.ch
CODE PRIX
Commission Electrotechnique Internationale PRICE CODE S
International Electrotechnical Commission
Международная Электротехническая Комиссия
Pour prix, voir catalogue en vigueur
For price, see current catalogue

– 2 – 60670-24 © CEI:2005
SOMMAIRE
AVANT-PROPOS.6

1 Domaine d’application .10
2 Références normatives .10
3 Définitions .10
4 Règles générales.12
5 Généralités sur les essais.12
6 Caractéristiques assignées .12
7 Classification.12
8 Marquage.12
9 Dimensions .14
10 Protection contre les chocs électriques .16
11 Disposition pour la mise à la terre .16
12 Construction.16
13 Résistance au vieillissement, protection contre la pénétration de corps solides et
contre la pénétration nuisible de l’eau .18
14 Résistance d'isolement et rigidité diélectrique .18
15 Résistance mécanique.18
16 Résistance à la chaleur .18
17 Lignes de fuite, distances d'isolement et distances à travers le matériau de
remplissage.18
18 Résistance du matériau isolant à la chaleur anormale et au feu .18
19 Résistance au cheminement .20
20 Résistance à la corrosion.20
21 Compatibilité électromagnétique (CEM) .20
101 Vérification de la puissance maximale dissipable (P ).20
de
Annexe AA (informative) Calcul de la puissance dissipée .34

Bibliographie .44

Figure 101 – Dispositions pour la vérification de la puissance maximale dissipable(P )
de
des enveloppes pour montage en saillie .24
Figure 102 – Résistance chauffante pour la vérification de la puissance maximale
dissipable(P ) .26
de
Figure 103 – Position de la résistance pour les enveloppes conçues ou prévues pour
être équipées d’accessoires et d’appareillages modulaires .28
Figure 104 - Position de la (les) résistance(s) pour les enveloppes autres que celles
conçues ou prévues pour être équipées d’accessoires et d’appareillages pour montage
sur rail.30
Figure 105 – Position de la (les) résistance(s) pour les enveloppes autres que celles
conçues ou prévues pour être équipées d’appareillages et d'équipements pour
montage sur rail permettant le montage de divers appareillages et équipements dans
différentes positions.32

60670-24  IEC:2005 – 3 –
CONTENTS
FOREWORD.7

1 Scope .11
2 Normative references .11
3 Definitions .11
4 General requirements .13
5 General notes on tests.13
6 Ratings .13
7 Classification.13
8 Marking .13
9 Dimensions .15
10 Protection against electric shock.17
11 Provisions for earthing.17
12 Construction.17
13 Resistance to ageing, protection against ingress of solid objects and against
harmful ingress of water .19
14 Insulation resistance and electric strength.19
15 Mechanical strength .19
16 Resistance to heat.19
17 Creepage distances, clearances and distances through sealing compound .19
18 Resistance of insulating material to abnormal heat and fire .19
19 Resistance to tracking .21
20 Resistance to corrosion .21
21 Electromagnetic compatibility.21
101 Verification of the maximum capability to dissipate power (P ) .21
de
Annex AA (informative) Calculation of the power loss .35

Bibliography .45

Figure 101 – Arrangement for the verification of the maximum capability to dissipate
power (P ) of surface type enclosures .25
de
Figure 102 – Heating resistor for the verification of the maximum capability to
dissipate power (P ).27
de
Figure 103 – Position of the resistor for enclosures designed or intended to be fitted
with modular accessories and equipment .29
Figure 104 – Position of the resistor(s) for enclosures other than those designed or
intended to be fitted with rail mounting accessories and equipment.31
Figure 105 – Position of the resistor(s) for enclosures other than those designed or
intended to be fitted with rail mounting accessories and equipment and allowing the
mounting of several accessories and equipment in different positions .33

– 4 – 60670-24 © CEI:2005
Tableau 101 — Facteur de diversité .36
Tableau 102 — Calcul de P .40
dp
Tableau 103 — Calcul de P .40
au
60670-24  IEC:2005 – 5 –
Table 101 – Diversity factor .37
Table 102 – Calculation of P .41
dp
Table 103 – Calculation of P .41
au
– 6 – 60670-24 © CEI:2005
COMMISSION ÉLECTROTECHNIQUE INTERNATIONALE
____________
BOÎTES ET ENVELOPPES POUR APPAREILLAGE ÉLECTRIQUE
POUR INSTALLATIONS ÉLECTRIQUES FIXES
POUR USAGES DOMESTIQUES ET ANALOGUES –

Partie 24: Règles particulières pour enveloppes pour appareillages de
protection et appareillages similaires ayant une puissance dissipée

AVANT-PROPOS
1) La Commission Electrotechnique Internationale (CEI) est une organisation mondiale de normalisation
composée de l'ensemble des comités électrotechniques nationaux (Comités nationaux de la CEI). La CEI a
pour objet de favoriser la coopération internationale pour toutes les questions de normalisation dans les
domaines de l'électricité et de l'électronique. A cet effet, la CEI – entre autres activités – publie des Normes
internationales, des Spécifications techniques, des Rapports techniques, des Spécifications accessibles au
public (PAS) et des Guides (ci-après dénommés "Publication(s) de la CEI"). Leur élaboration est confiée à des
comités d'études, aux travaux desquels tout Comité national intéressé par le sujet traité peut participer. Les
organisations internationales, gouvernementales et non gouvernementales, en liaison avec la CEI, participent
également aux travaux. La CEI collabore étroitement avec l'Organisation Internationale de Normalisation (ISO),
selon des conditions fixées par accord entre les deux organisations.
2) Les décisions ou accords officiels de la CEI concernant les questions techniques représentent, dans la mesure
du possible, un accord international sur les sujets étudiés, étant donné que les Comités nationaux de la CEI
intéressés sont représentés dans chaque comité d’études.
3) Les Publications de la CEI se présentent sous la forme de recommandations internationales et sont agréées
comme telles par les Comités nationaux de la CEI. Tous les efforts raisonnables sont entrepris afin que la CEI
s'assure de l'exactitude du contenu technique de ses publications; la CEI ne peut pas être tenue responsable
de l'éventuelle mauvaise utilisation ou interprétation qui en est faite par un quelconque utilisateur final.
4) Dans le but d'encourager l'uniformité internationale, les Comités nationaux de la CEI s'engagent, dans toute la
mesure possible, à appliquer de façon transparente les Publications de la CEI dans leurs publications
nationales et régionales. Toutes divergences entre toutes Publications de la CEI et toutes publications
nationales ou régionales correspondantes doivent être indiquées en termes clairs dans ces dernières.
5) La CEI n’a prévu aucune procédure de marquage valant indication d’approbation et n'engage pas sa
responsabilité pour les équipements déclarés conformes à une de ses Publications.
6) Tous les utilisateurs doivent s'assurer qu'ils sont en possession de la dernière édition de cette publication.
7) Aucune responsabilité ne doit être imputée à la CEI, à ses administrateurs, employés, auxiliaires ou
mandataires, y compris ses experts particuliers et les membres de ses comités d'études et des Comités
nationaux de la CEI, pour tout préjudice causé en cas de dommages corporels et matériels, ou de tout autre
dommage de quelque nature que ce soit, directe ou indirecte, ou pour supporter les coûts (y compris les frais
de justice) et les dépenses découlant de la publication ou de l'utilisation de cette Publication de la CEI ou de
toute autre Publication de la CEI, ou au crédit qui lui est accordé.
8) L'attention est attirée sur les références normatives citées dans cette publication. L'utilisation de publications
référencées est obligatoire pour une application correcte de la présente publication.
9) L’attention est attirée sur le fait que certains des éléments de la présente Publication de la CEI peuvent faire
l’objet de droits de propriété intellectuelle ou de droits analogues. La CEI ne saurait être tenue pour
responsable de ne pas avoir identifié de tels droits de propriété et de ne pas avoir signalé leur existence.
La Norme internationale CEI 60670-24 a été établie par le sous-comité 23B: Prises de
courant et interrupteurs, du comité d'études 23 de la CEI: Petit appareillage.
Le texte de la présente norme est issu des documents suivants:
FDIS Rapport de vote
23B/773/FDIS 23B/780/RVD
Le rapport de vote indiqué dans le tableau ci-dessus donne toute information sur le vote ayant
abouti à l'approbation de cette norme.
Cette publication a été rédigée selon les Directives ISO/CEI, Partie 2.

60670-24  IEC:2005 – 7 –
INTERNATIONAL ELECTROTECHNICAL COMMISSION
____________
BOXES AND ENCLOSURES FOR ELECTRICAL ACCESSORIES FOR
HOUSEHOLD AND SIMILAR FIXED ELECTRICAL INSTALLATIONS –

Part 24: Particular requirements for enclosures for housing protective
devices and similar power consuming devices

FOREWORD
1) The International Electrotechnical Commission (IEC) is a worldwide organization for standardization comprising
all national electrotechnical committees (IEC National Committees). The object of IEC is to promote
international co-operation on all questions concerning standardization in the electrical and electronic fields. To
this end and in addition to other activities, IEC publishes International Standards, Technical Specifications,
Technical Reports, Publicly Available Specifications (PAS) and Guides (hereafter referred to as “IEC
Publication(s)”). Their preparation is entrusted to technical committees; any IEC National Committee interested
in the subject dealt with may participate in this preparatory work. International, governmental and non-
governmental organizations liaising with the IEC also participate in this preparation. IEC collaborates closely
with the International Organization for Standardization (ISO) in accordance with conditions determined by
agreement between the two organizations.
2) The formal decisions or agreements of IEC on technical matters express, as nearly as possible, an international
consensus of opinion on the relevant subjects since each technical committee has representation from all
interested IEC National Committees.
3) IEC Publications have the form of recommendations for international use and are accepted by IEC National
Committees in that sense. While all reasonable efforts are made to ensure that the technical content of IEC
Publications is accurate, IEC cannot be held responsible for the way in which they are used or for any
misinterpretation by any end user.
4) In order to promote international uniformity, IEC National Committees undertake to apply IEC Publications
transparently to the maximum extent possible in their national and regional publications. Any divergence
between any IEC Publication and the corresponding national or regional publication shall be clearly indicated in
the latter.
5) IEC provides no marking procedure to indicate its approval and cannot be rendered responsible for any
equipment declared to be in conformity with an IEC Publication.
6) All users should ensure that they have the latest edition of this publication.
7) No liability shall attach to IEC or its directors, employees, servants or agents including individual experts and
members of its technical committees and IEC National Committees for any personal injury, property damage or
other damage of any nature whatsoever, whether direct or indirect, or for costs (including legal fees) and
expenses arising out of the publication, use of, or reliance upon, this IEC Publication or any other IEC
Publications.
8) Attention is drawn to the Normative references cited in this publication. Use of the referenced publications is
indispensable for the correct application of this publication.
9) Attention is drawn to the possibility that some of the elements of this IEC Publication may be the subject of
patent rights. IEC shall not be held responsible for identifying any or all such patent rights.
International Standard IEC 60670-24 has been prepared by subcommittee 23B: Plugs, socket-
outlets and switches, of IEC technical committee 23: Electrical accessories.
The text of this standard is based on the following documents:
FDIS Report on voting
23B/773/FDIS 23B/780/RVD
Full information on the voting for the approval of this standard can be found in the report on
voting indicated in the above table.
This publication has been drafted in accordance with the ISO/IEC Directives, Part 2.

– 8 – 60670-24 © CEI:2005
La présente norme doit être utilisée conjointement avec la CEI 60670-1. Elle contient les
modifications à apporter à cette norme pour la transformer en norme particulière pour les
enveloppes pour appareillages de protection et appareillages similaires ayant une puissance
dissipée.
Lorsqu'un paragraphe particulier de la Partie 1 n'est pas mentionné dans cette partie,
ce paragraphe s'applique pour autant qu'il est raisonnable.
Dans la présente publication:
a) Les caractères d'imprimerie suivants sont utilisés:
– prescriptions proprement dites: caractères romains.
– modalités d'essais: caractères italiques.
– notes: petits caractères romains.
b) Les paragraphes, figures ou tableaux complémentaires à ceux de la Partie 1 sont
numérotés à partir de 101; les annexes complémentaires à celles de la Partie 1 sont
nommées AA, BB, etc.
La CEI 60670 comprend les parties suivantes, présentées sous le titre général Boîtes et
enveloppes pour appareillage électrique pour installations électriques fixes pour usages
domestiques et analogues :
Partie 1: Règles générales
Partie 21: Règles particulières concernant les boîtes et enveloppes avec dispositifs de
suspension
Partie 22: Règles particulières concernant les boîtes et enveloppes de connexion
Partie 23: Règles particulières concernant les boîtes et enveloppes au sol
Partie 24: Règles particulières pour enveloppes pour appareillages de protection et
appareillages similaires ayant une puissance dissipée

Le comité a décidé que le contenu de cette publication ne sera pas modifié avant la date de
maintenance indiquée sur le site web de la CEI sous «http://webstore.iec.ch» dans les
données relatives à la publication recherchée. A cette date, la publication sera
• reconduite;
• supprimée;
• remplacée par une édition révisée, ou
• amendée.
———————
1)
A publier.
60670-24  IEC:2005 – 9 –
This standard is to be used in conjunction with IEC 60670-1. It lists the changes necessary to
convert that standard into a specific standard for enclosures for housing protective devices
and similar power consuming devices.
When a particular subclause of Part 1 is not mentioned in this part, that subclause applies as
far as reasonable.
In this publication:
a) the following print types are used:
– requirements proper: in roman type;
– test specifications: in italic type;
– notes: in smaller roman type;
b) subclauses, figures or tables which are additional to those in Part 1 are numbered starting
from 101, annexes additional to those in Part 1 are lettered AA, BB etc.

IEC 60670 consists of the following parts, under the general title Boxes and enclosures for
electrical accessories for household and similar fixed electrical installations:
Part 1: General requirements
Part 21: Particular requirements for boxes and enclosures with provision for suspension
means
Part 22: Particular requirements for connecting boxes and enclosures
1)
Part 23: Particular requirements for floor boxes
Part 24 Particular requirements for enclosures for housing protective devices and similar
power consuming devices
The committee has decided that the contents of this publication will remain unchanged until
the maintenance result date indicated on the IEC web site under "http://webstore.iec.ch" in
the data related to the specific publication. At this date, the publication will be
• reconfirmed;
• withdrawn;
• replaced by a revised edition, or
• amended.
———————
1)
To be published.
– 10 – 60670-24 © CEI:2005
BOÎTES ET ENVELOPPES POUR APPAREILLAGE ÉLECTRIQUE
POUR INSTALLATIONS ÉLECTRIQUES FIXES
POUR USAGES DOMESTIQUES ET ANALOGUES –

Partie 24: Règles particulières pour enveloppes pour appareillages de
protection et appareillages similaires ayant une puissance dissipée

1 Domaine d’application
L’article de la Partie 1 est remplacé par ce qui suit:
La présente partie de la CEI 60670 s’applique aux enveloppes vides, et aux parties des
enveloppes vides, qui sont prévues pour les appareillages électriques destinés à être utilisés avec
une tension assignée n’excédant pas 400 V et un courant total à l'arrivée n’excédant pas 125 A
pour les installations électriques fixes pour usages domestiques et analogues, et pour lesquelles
le constructeur déclare une aptitude maximale à dissiper la puissance en usage normal.
Ces enveloppes sont destinées à recevoir des appareillages de protection ou tout autre
appareillage ayant ou non une puissance dissipée. Elles sont destinées à être installées là où le
courant de court-circuit présumé n’excède pas 10 kA, sauf si elles sont protégées par des
dispositifs de protection limiteurs de courant avec un courant coupé limité n’excédant pas 17 kA.
Les enveloppes conformes à la présente norme sont appropriées pour un usage, après
installation, à une température ambiante ne dépassant pas normalement 25 °C, mais
atteignant occasionnellement 35 °C pendant 24 h, sans dépasser 40 °C ni descendre en
dessous de -5 °C. Une enveloppe qui fait partie intégrante d’un appareillage électrique et
fournit une protection contre les influences externes (par exemple choc mécanique,
pénétration de corps solides ou d’eau) est couverte par la norme appropriée pour cet
appareillage.
NOTE Au Royaume-Uni, les enveloppes conformes à la présente norme ne peuvent pas être utilisées en tant
qu'ensembles pour tableaux de répartition d'abonnés (tableaux d'abonnés). Il faut que de tels produits soient
conformes à la CEI 60439-3 (norme anglaise EN 60439-3).
2 Références normatives
L'article de la Partie 1 s'applique avec l'addition suivante:
CEI 60417-DB:2002 : Symboles graphiques utilisables sur le matériel
3 Définitions
L'article de la Partie 1 s'applique avec les additions suivantes.
3.101
puissance maximale dissipable (P )
de
aptitude maximale de l'enveloppe, déclarée par le constructeur, à dissiper en usage normal
les puissances dissipées par les appareillages installés
NOTE P s'exprime en watts (W).
de
———————
« DB » se réfère à la base de données « on-line » de la CEI.

60670-24  IEC:2005 – 11 –
BOXES AND ENCLOSURES FOR ELECTRICAL ACCESSORIES FOR
HOUSEHOLD AND SIMILAR FIXED ELECTRICAL INSTALLATIONS –

Part 24: Particular requirements for enclosures for housing protective
devices and similar power consuming devices

1 Scope
This clause of Part 1 is replaced by:
This part of IEC 60670 applies to empty enclosures and parts of them for electrical
accessories intended to be used with a rated voltage not exceeding 400 V and a total
incoming load current not exceeding 125 A for household and similar fixed electrical
installations, where a maximum capability to dissipate power in normal use is declared by the
manufacturer.
These enclosures are intended for housing protective devices and devices with or without
power dissipation. They are intended to be installed where the prospective short circuit
current does not exceed 10 kA unless they are protected by current limiting protective devices
with a cut-off current not exceeding 17 kA.
Enclosures complying with this standard are suitable for use, after installation, at ambient
temperature normally not exceeding 25 °C, but occasionally reaching 35 °C over 24 h, max.
40 °C and min. –5 °C. An enclosure which is an integral part of an electrical accessory and
provides protection against external influences (e.g. mechanical impacts, ingress of solid
objects or of water), is covered by the relevant standard for such an accessory.
NOTE In UK enclosures complying with this standard cannot be used for the assembly of customer distribution
boards (consumer units). Such products must comply with IEC 60439-3 [British standard EN 60439-3].
2 Normative references
This clause of Part 1 is applicable with the following addition:
2)
IEC 60417-DB:2002 , Graphical symbols for use on equipment
3 Definitions
This clause of Part 1 is applicable with the following modification:
3.101
maximum capability to dissipate power (P )
de
maximum capability of the enclosure to dissipate in normal use the power losses of the
installed devices, as declared by the manufacturer
NOTE P is expressed in watts (W).
de
———————
2)
“DB” refers to the IEC on-line database.

– 12 – 60670-24 © CEI:2005
3.102
courant assigné
courant fixé par le constructeur à l’appareillage ou aux appareillages d’arrivée. Dans le cas
où il y a plusieurs appareillages d’arrivée, le courant fixé par le constructeur est la somme
arithmétique des courants de tous les appareillages d'arrivée destinés à fonctionner
simultanément
3.103
tension assignée
tension fixée par le constructeur à une enveloppe
4 Règles générales
L'article de la Partie 1 s'applique.
5 Notes générales sur les essais
L'article de la Partie 1 s'applique.
6 Caractéristiques assignées
Vide.
7 Classification
L'article de la Partie 1 s'applique avec les modifications suivantes:
Tableau 1 – Classification des boîtes et enveloppes
Les critères de classification 7.7.2 et 7.7.3.1 ne s’appliquent pas.
Ajouter la nouvelle classification suivante:
7.101 Pour les boîtes et les 7.101.1 Selon la résistance du 7.101.1.1  650 C°
enveloppes vides matériau isolant au feu (Article 18):
7.101.1.2  850 C°
7.101.1.3  960 C°
8 Marquage
L'article de la Partie 1 s'applique avec les modifications suivantes:
Remplacer 8.1 par ce qui suit:
8.1 Les enveloppes pour appareillages de protection doivent être marquées avec:
a) le nom, la marque de fabrique ou la marque d'identification du constructeur ou du vendeur
responsable;
b) le degré IP de protection contre la pénétration nuisible de corps solides étrangers et
contre les accès aux parties dangereuses s'il est supérieur à IP2XC et/ou si le degré IP de
protection contre la pénétration nuisible de l’eau est supérieur à IPX0;

60670-24  IEC:2005 – 13 –
3.102
rated current
current assigned by the manufacturer of the incoming device(s). If there is more than one
incoming device, the current assigned by the manufacturer is the arithmetic sum of the
currents of all incoming devices intended to operate simultaneously
3.103
rated voltage
voltage assigned to the enclosure by the manufacturer
4 General requirements
This clause of Part 1 is applicable.
5 General notes on tests
This clause of Part 1 is applicable.
6 Ratings
Void.
7 Classification
This clause of Part 1 is applicable with the following modifications:
Table 1 – Classification of boxes and enclosures
Classification criteria 7.7.2 and 7.7.3.1 do not apply.
Add the following new classification:
7.101 For empty boxes and 7.101.1 According to resistance of 7.101.1.1  650 C°
enclosures insulating material to fire (Clause
18):
7.101.1.2  850 C°
7.101.1.3  960 C°
8 Marking
This clause of Part 1 is applicable with the following modifications:
Replace 8.1 by the following:
8.1 Enclosures for housing protective devices shall be marked with:
a) the name, trade mark or identification mark of the manufacturer or the responsible vendor;
b) IP code against ingress of solid foreign objects and against access to hazardous parts if
higher than IP2XC and/or if IP code against harmful ingress of water is higher than IPX0;

– 14 – 60670-24 © CEI:2005
Le degré IP de protection, s’il y a lieu, doit être marqué à l’extérieur de l’enveloppe afin
d'être vu facilement lorsque l’enveloppe est montée et posée comme en usage normal. La
visibilité du marquage est aussi autorisée après ouverture de la porte ou du couvercle si le
degré IP de protection est maintenu après ouverture. Le degré IP de protection peut être
marqué derrière la porte dans la mesure où ce degré IP est maintenu la porte étant
ouverte.
NOTE 1 Lorsque le marquage est à l'extérieur de l'enveloppe, (par exemple sur la porte), cela signifie que le
degré IP de protection est assuré lorsque la porte est fermée. Lorsque le marquage est visible après
l'ouverture de la porte (par exemple derrière la porte), cela signifie que le degré IP de protection est assuré
lorsque la porte est ouverte.
c) la tension assignée;
d) le courant assigné /le courant à l'arrivée établi maximal déclaré par le constructeur;
e) le symbole de la classe II, si applicable (CEI 60417-5172 (DB :2003-02))
f) la référence de la présente norme, c'est-à-dire CEI 60670-24;
g) la désignation du type, le numéro de série ou le numéro de catalogue;
h) la température maximale pendant le processus de construction, si 90 °C;
i) pour les boîtes et enveloppes classifiées selon 7.3.7 (sans ouvertures), les
renseignements nécessaires concernant les ouvertures qui peuvent être réalisées pendant
l’installation;
j) la puissance maximale dissipable (P );
de
NOTE 2 Dans le cas d'une enveloppe conçue avec des ouvertures d'aération, il est recommandé que le
constructeur déclare la puissance maximale dissipable (P ) de cette enveloppe, pour les positions ouverte et
de
fermée de ces ouvertures.
k) pour les boîtes et enveloppes classifiées selon 7.7, l’information sur leur utilisation dans
une installation à mur creux;
l) la feuille dimensionnelle correspondante.
Les informations c), d), f), h), i), j) et k) doivent être marquées sur les boîtes ou les
enveloppes, ou fournies par le constructeur sur le plus petit emballage ou dans les
instructions du constructeur.
Addition du paragraphe suivant:
8.101 Informations requises dans les notices et/ou la documentation
Le constructeur doit inclure dans la documentation accompagnant l’enveloppe les instructions
nécessaires pour l’installation.
Le constructeur doit également fournir les informations nécessaires concernant les moyens à
utiliser pour obtenir le degré de protection prévu (par exemple presse-étoupe, joints,
barrières…).
Le constructeur doit déclarer la puissance maximale dissipable (P ) de l'enveloppe en
de
fonction de l'environnement de montage approprié, mesurée selon l’Article 101, et fournir la
documentation appropriée.
NOTE Un exemple d’utilisation de la puissance maximale dissipable (P ) est donné dans l’Annexe A.
de
9 Dimensions
L'article de la Partie 1 s'applique.
———————
« DB » se réfère à la base de données « on-line » de la CEI.

60670-24  IEC:2005 – 15 –
The IP code, if applicable, shall be marked on the outside of the enclosure so as to be
easily discernible when the enclosure is mounted and wired as for normal use. The
visibility of the marking is also allowed after opening the door or the lid if the IP degree is
maintained after opening. The IP code can be marked behind the door provided the IP
degree is maintained with the door opened.
NOTE 1 When the marking is on the outside of the enclosure (e.g. on the door) it means that the IP code is
assured with the door closed. When the marking is visible after the opening of the door (i.e. marked behind
the door) it means that the IP code is maintained with the door open.
c) rated voltage;
d) rated current/highest permanent incoming current as declared by the manufacturer;
3)
e) the symbol for class II, if applicable (IEC 60417-5172 (DB :2003-02))
f) reference number of this standard i.e. IEC 60670-24;
g) type designation, reference number or catalogue number;
h) maximum temperature during the building process if 90 °C;
i) for boxes and enclosures classified according to 7.3.7 (without inlets), the necessary
information concerning the openings that can be made during installation;
j) maximum capability to dissipate power (P );
de
NOTE 2 In case of an enclosure designed with ventilation openings, the maximum capability to dissipate
power (P ) should be declared by the manufacturer, with the ventilation openings both covered and
de
uncovered.
k) for boxes and enclosures classified according to 7.7 the usability for hollow wall
installation;
l) the corresponding dimension sheet.
The items c), d), f), h), i), j) and k) shall be marked on the boxes or enclosures or provided by
the manufacturer on the smallest package unit or in the instructions of the manufacturer.
Add the following subclause:
8.101 Required data for instruction sheet and/or documentation
The manufacturer shall include in the documentation accompanying the enclosure the
necessary instructions for installation.
The manufacturer shall also provide appropriate information regarding the means (for
instance glands, grommets, barriers…) to be used to obtain the intended degree of protection.
The manufacturer shall declare the maximum capability to dissipate power (P ) of the
de
enclosure, according to the appropriate mounting environment, measured according to Clause
101 and provide appropriate documentation.
NOTE An example of the use of the maximum capability to dissipate power (P ) is given in Annex A.
de
9 Dimensions
This clause of Part 1 is applicable.
———————
“DB” refers to the IEC on-line database.

– 16 – 60670-24 © CEI:2005
10 Protection contre les chocs électriques
L'article de la Partie 1 s'applique avec la modification suivante:
Remplacement du second alinéa par ce qui suit:
Les enveloppes doivent avoir un degré de protection d’au moins IPXXC quand elles sont
montées et installées comme en usage normal.
Lorsqu'elles sont montées et installées comme en usage normal, les enveloppes de classe II
doivent
a)  envelopper complètement les dispositifs dans un matériau isolant;
b) en aucun point n'être traversées par les parties conductrices d'une façon qui pourrait
conduire à l'apparition d'une tension de défaut à l’extérieur de l’enveloppe;
c) ne pas avoir de parties conductrices, telles que plaques, plaques de recouvrement ou
châssis, connectées au circuit de protection.
11 Dispositions pour la mise à la terre
L'article de la Partie 1 s'applique.
12 Construction
L'article de la Partie 1 s'applique avec les modifications suivantes:
12.1 Couvercles, capots ou plaques de recouvrement ou parties de ceux-ci
Remplacement:
Les couvercles, capots ou plaques de recouvrement, ou parties de ceux-ci, qui sont destinés
à assurer la protection contre les chocs électriques, doivent être maintenus en place
efficacement. Ils ne doivent pouvoir être enlevés qu'au moyen d’un outil et/ou d’une clé.
12.11 Boîtes et enveloppes classifiées selon 7.7.1
Remplacement:
Les boîtes et enveloppes pour murs creux classifiées selon 7.7.1 doivent être pourvues des
moyens appropriés de fixation de la boîte ou de l'enveloppe dans des murs creux.
La conformité est vérifiée par examen.
Ajouter le nouveau paragraphe suivant:
12.101 Les enveloppes pour murs creux doivent être conçues pour pouvoir être équipées de
dispositifs de retenue de câbles ou de dispositifs pour l'utilisation d'une retenue séparée.
La conformité est vérifiée par examen.

60670-24  IEC:2005 – 17 –
10 Protection against electric shock
This clause of Part 1 is applicable with the following modification:
Replacement of the second paragraph by:
Enclosures shall have a degree of protection of at least IPXXC, when mounted and installed
as for normal use.
When mounted and installed as for normal use, class II enclosures shall:
a) completely enclose the built-in devices in insulating material;
b) at no point be pierced by conducting parts in such a manner that there is a possibility of a
fault voltage being brought out of the enclosure;
c) not have conductive
...