IEC PAS 62424:2005
(Main)Representation of process control engineering requests in P&I diagrams and data exchange between P&ID tools and PCE-CAE tools
General Information
- Abstract
describes specifies how process control engineering requests are represented in a P&I diagram.also defines the exchange of process control engineering request relevant data between a process control engineering tool and a P&I tool by means of a data transfer language (called CAEX). These provisions apply to the export/import applications of such tools.
- Status
- Replaced
- Publication Date
- 26-Jun-2005
- Technical Committee
- TC 65 - Industrial-process measurement, control and automation
- Current Stage
- DELPUB - Deleted Publication
- Start Date
- 12-Aug-2008
- Completion Date
- 28-Aug-2026
Relations
- Effective Date
- 05-Sep-2023
Get Certified
Connect with accredited certification bodies for this standard

BSI Group
BSI (British Standards Institution) is the business standards company that helps organizations make excellence a habit.
DVS-ZERT GmbH
German welding certification society.
CARES (UK Certification Authority for Reinforcing Steels)
UK certification for reinforcing steels and construction.
Sponsored listings
Frequently Asked Questions
IEC PAS 62424:2005 is a technical specification published by the International Electrotechnical Commission (IEC). Its full title is "Representation of process control engineering requests in P&I diagrams and data exchange between P&ID tools and PCE-CAE tools". This standard covers: describes specifies how process control engineering requests are represented in a P&I diagram.also defines the exchange of process control engineering request relevant data between a process control engineering tool and a P&I tool by means of a data transfer language (called CAEX). These provisions apply to the export/import applications of such tools.
describes specifies how process control engineering requests are represented in a P&I diagram.also defines the exchange of process control engineering request relevant data between a process control engineering tool and a P&I tool by means of a data transfer language (called CAEX). These provisions apply to the export/import applications of such tools.
IEC PAS 62424:2005 is classified under the following ICS (International Classification for Standards) categories: 25.040.40 - Industrial process measurement and control; 35.240.50 - IT applications in industry. The ICS classification helps identify the subject area and facilitates finding related standards.
IEC PAS 62424:2005 has the following relationships with other standards: It is inter standard links to IEC 62424:2008. Understanding these relationships helps ensure you are using the most current and applicable version of the standard.
IEC PAS 62424:2005 is available in PDF format for immediate download after purchase. The document can be added to your cart and obtained through the secure checkout process. Digital delivery ensures instant access to the complete standard document.
Standards Content (Sample)
PUBLICLY
IEC
AVAILABLE
PAS 62424
SPECIFICATION
First edition
Pre-Standard
2005-06
Representation of process control
engineering requests in P&I diagrams
and data exchange between P&ID tools
and PCE-CAE tools
Reference number
IEC/PAS 62424:2005(E)
Publication numbering
As from 1 January 1997 all IEC publications are issued with a designation in the
60000 series. For example, IEC 34-1 is now referred to as IEC 60034-1.
Consolidated editions
The IEC is now publishing consolidated versions of its publications. For example,
edition numbers 1.0, 1.1 and 1.2 refer, respectively, to the base publication, the
base publication incorporating amendment 1 and the base publication incorporating
amendments 1 and 2.
Further information on IEC publications
The technical content of IEC publications is kept under constant review by the IEC,
thus ensuring that the content reflects current technology. Information relating to
this publication, including its validity, is available in the IEC Catalogue of
publications (see below) in addition to new editions, amendments and corrigenda.
Information on the subjects under consideration and work in progress undertaken
by the technical committee which has prepared this publication, as well as the list
of publications issued, is also available from the following:
• IEC Web Site (www.iec.ch)
• Catalogue of IEC publications
The on-line catalogue on the IEC web site (www.iec.ch/searchpub) enables you to
search by a variety of criteria including text searches, technical committees
and date of publication. On-line information is also available on recently issued
publications, withdrawn and replaced publications, as well as corrigenda.
• IEC Just Published
This summary of recently issued publications (www.iec.ch/online_news/ justpub)
is also available by email. Please contact the Customer Service Centre (see
below) for further information.
• Customer Service Centre
If you have any questions regarding this publication or need further assistance,
please contact the Customer Service Centre:
Email: custserv@iec.ch
Tel: +41 22 919 02 11
Fax: +41 22 919 03 00
PUBLICLY
IEC
AVAILABLE
PAS 62424
SPECIFICATION
First edition
Pre-Standard
2005-06
Representation of process control
engineering requests in P&I diagrams
and data exchange between P&ID tools
and PCE-CAE tools
IEC 2005 Copyright - all rights reserved
No part of this publication may be reproduced or utilized in any form or by any means, electronic or
mechanical, including photocopying and microfilm, without permission in writing from the publisher.
International Electrotechnical Commission, 3, rue de Varembé, PO Box 131, CH-1211 Geneva 20, Switzerland
Telephone: +41 22 919 02 11 Telefax: +41 22 919 03 00 E-mail: inmail@iec.ch Web: www.iec.ch
PRICE CODE
Commission Electrotechnique Internationale
XE
International Electrotechnical Commission
Международная Электротехническая Комиссия
For price, see current catalogue
– 2 – PAS 62424 © IEC:2005(E)
CONTENTS
FOREWORD. 6
INTRODUCTION. 7
1 Scope. 9
2 Normative references.9
3 Terms and definitions. 10
4 Abbreviations . 11
5 Conformity. 11
6 Representation of PCE requests in P&ID. 13
6.1 PCE request and PCE loop . 13
6.2 Objectives and principles . 13
6.3 Requirements for the identification and representation of PCE requests . 14
7 Neutral data exchange of PCE relevant P&ID information . 21
7.1 Objectives . 21
7.2 Meaning of P&I drawing elements. 22
7.3 PCE relevant information of P&ID tools. 22
7.4 Formal description of PCE relevant information of P&ID tools . 23
8 Recommended attributes . 29
Annex A (normative) CAEX – Data model for machine information exchange . 31
A.1 CAEX and its diagram conventions . 31
A.2 Definition of terms . 32
A.3 Definition of elements.34
A.3.1 General . 34
A.3.2 Element CAEXFile. 35
A.3.3 Element CAEXFile/SystemHierarchy. 36
A.3.4 Element CAEXFile/InterfaceClassLib . 37
A.3.5 Element CAEXFile/RoleClassLib. 38
A.3.6 Element CAEXFile/SystemUnitClassLib. 39
A.4 Definition of Types . 40
A.4.1 General . 40
A.4.2 ComplexType AttributeType . 40
A.4.3 Element AttributeType/DefaultValue . 41
A.4.4 Element AttributeType/refSemantic. 41
A.4.5 Element AttributeType/Constraint. 42
A.4.6 Element AttributeType/Quantity. 42
A.4.7 Element AttributeType/Attribute . 43
A.5 Group Header . 44
A.5.1 General . 44
PAS 62424 © IEC:2005(E) – 3 –
A.5.2 Element Header/Description. 45
A.5.3 Element Header/Version . 45
A.5.4 Element Header/Revision. 46
A.5.5 Element Header/Revision/RevisionDate. 46
A.5.6 Element Header/Revision/OldVersion . 46
A.5.7 Element Header/Revision/NewVersion. 47
A.5.8 Element Header/Revision/AuthorName. 47
A.5.9 Element Header/Revision/Comment . 47
A.5.10 Element Header/Copyright . 47
A.5.11 Element Header/AdditionalInformation. 48
A.5.12 complexType AttributeValueRequirementType . 48
A.5.13 Element AttributeValueRequirementType/OrdinalScaledType . 49
A.5.14 Element AttributeValueRequirementType/OrdinalScaledType/RequiredMaxValue . 49
A.5.15 Element AttributeValueRequirementType/OrdinalScaledType/RequiredValue . 49
A.5.16 Element AttributeValueRequirementType/OrdinalScaledType/RequiredMinValue . 50
A.5.17 Element AttributeValueRequirementType/NominalScaledType. 50
A.5.18 Element AttributeValueRequirementType/NominalScaledType/RequiredValues. 50
A.5.19 Element AttributeValueRequirementType/UnknownType . 51
A.5.20 Element AttributeValueRequirementType/UnknownType/Requirements . 51
A.6 ComplexType AttributeValueType. 51
A.6.1 General . 51
A.6.2 Element AttributeValueType/Value. 52
A.6.3 Element AttributeValueType/Constraint. 52
A.7 ComplexType InterfaceClassLibType. 53
A.7.1 General . 53
A.7.2 Element InterfaceClassLibType/InterfaceClass. 54
A.8 ComplexType InterfaceClassType . 55
A.8.1 General . 55
A.8.2 Element InterfaceClassType/Attribute . 56
A.8.3 Element InterfaceClassType/AttributeValue . 56
A.9 ComplexType InterfaceFamilyType. 57
A.9.1 General . 57
A.9.2 Element InterfaceFamilyType/InterfaceClass . 58
A.10 ComplexType InterfaceRequirementType . 59
A.10.1 General . 59
A.10.2 Element InterfaceRequirementType/AdditionalAttribute . 60
A.10.3 Element InterfaceRequirementType/AttributeValue. 60
A.11 ComplexType MappingType. 61
A.11.1 General . 61
A.11.2 Element MappingType/AttributeNameMapping . 61
– 4 – PAS 62424 © IEC:2005(E)
A.11.3 Element MappingType/InterfaceNameMapping. 62
A.12 ComplexType RoleClassLibType . 62
A.12.1 General . 62
A.12.2 Element RoleClassLibType/RoleClass . 63
A.13 ComplexType RoleClassType . 64
A.13.1 General . 64
A.13.2 Element RoleClassType/Attribute. 65
A.13.3 Element RoleClassType/AttributeValue. 65
A.13.4 Element RoleClassType/ExternalInterface . 66
A.13.5 Element RoleClassType/PredefinedRealisation . 66
A.14 ComplexType RoleFamilyType . 68
A.14.1 General . 68
A.14.2 Element RoleFamilyType/RoleClass . 69
A.15 ComplexType SystemHierarchyElementType . 70
A.15.1 General . 70
A.15.2 Element SystemHierarchyElementType/SystemHierarchyElement . 71
A.16 ComplexType SystemHierarchyLibType. 72
A.16.1 General . 72
A.16.2 Element SystemHierarchyLibType/SystemHierarchyElement . 73
A.17 ComplexType SystemUnitClassLibType. 74
A.17.1 General . 74
A.17.2 Element SystemUnitClassLibType/SystemUnitClass . 74
A.18 ComplexType SystemUnitClassType . 76
A.18.1 General . 76
A.18.2 Element SystemUnitClassType/Attribute. 78
A.18.3 Element SystemUnitClassType/AttributeValue. 79
A.18.4 Element SystemUnitClassType/ExternalInterface . 79
A.18.5 Element SystemUnitClassType/InternalElement . 80
A.18.6 Element SystemUnitClassType/InternalElement/RoleRequirements . 82
A.18.7 Element SystemUnitClassType/InternalElement/RoleRequirements/
AdditionalAttribute.83
A.18.8 Element SystemUnitClassType/InternalElement/RoleRequirements/
AdditionalAttributeValue. 83
A.18.9 Element SystemUnitClassType/InternalElement/RoleRequirements/
AdditionalExternalInterface . 84
A.18.10 Element SystemUnitClassType/InternalElement/PredefinedRealisation. 84
A.18.11 Element SystemUnitClassType/InternalElement/MappingObject. 86
A.18.12 Element SystemUnitClassType/SupportedRoleClass . 86
A.18.13 Element SystemUnitClassType/SupportedRoleClass/MappingObject . 87
A.18.14 Element SystemUnitClassType/InternalLink . 87
A.19 ComplexType SystemUnitFamilyType. 87
PAS 62424 © IEC:2005(E) – 5 –
A.19.1 General . 87
A.19.2 Element SystemUnitFamilyType/SystemUnitClass. 89
A.20 ComplexType SystemUnitInstanceType. 90
A.20.1 General . 90
A.20.2 Element SystemUnitInstanceType/SingletonClassDescription . 91
A.21 SimpleType changeMode. 92
A.21.1 General . 92
A.22 SimpleType propertystring . 93
A.22.1 General . 93
A.23 SimpleType reference . 93
A.23.1 General . 93
Annex B (informative) Examples for PCE requests. 94
Annex C (normative) CAEX Model.104
C.1 Full XML schema of the CAEX model .104
Bibliography.110
– 6 – PAS 62424 © IEC:2005(E)
INTERNATIONAL ELECTROTECHNICAL COMMISSION
____________
REPRESENTATION OF PROCESS CONTROL ENGINEERING REQUESTS
IN P&I DIAGRAMS AND DATA EXCHANGE BETWEEN P&ID TOOLS
AND PCE-CAE TOOLS
FOREWORD
1) The International Electrotechnical Commission (IEC) is a worldwide organization for standardization comprising all
national electrotechnical committees (IEC National Committees). The object of IEC is to promote international co-
operation on all questions concerning standardization in the electrical and electronic fields. To this end and in
addition to other activities, IEC publishes International Standards, Technical Specifications, Technical Reports,
Publicly Available Specifications (PAS) and Guides (hereafter referred to as “IEC Publication(s)”). Their preparation is
entrusted to technical committees; any IEC National Committee interested in the subject dealt with may participate in
this preparatory work. International, governmental and non-governmental organizations liaising with the IEC also
participate in this preparation. IEC collaborates closely with the International Organization for Standardization (ISO)
in accordance with conditions determined by agreement between the two organizations.
2) The formal decisions or agreements of IEC on technical matters express, as nearly as possible, an international
consensus of opinion on the relevant subjects since each technical committee has representation from all interested
IEC National Committees.
3) IEC Publications have the form of recommendations for international use and are accepted by IEC National
Committees in that sense. While all reasonable efforts are made to ensure that the technical content of IEC
Publications is accurate, IEC cannot be held responsible for the way in which they are used or for any
misinterpretation by any end user.
4) In order to promote international uniformity, IEC National Committees undertake to apply IEC Publications
transparently to the maximum extent possible in their national and regional publications. Any divergence between any
IEC Publication and the corresponding national or regional publication shall be clearly indicated in the latter.
5) IEC provides no marking procedure to indicate its approval and cannot be rendered responsible for any equipment
declared to be in conformity with an IEC Publication.
6) All users should ensure that they have the latest edition of this publication.
7) No liability shall attach to IEC or its directors, employees, servants or agents including individual experts and
members of its technical committees and IEC National Committees for any personal injury, property damage or other
damage of any nature whatsoever, whether direct or indirect, or for costs (including legal fees) and expenses arising
out of the publication, use of, or reliance upon, this IEC Publication or any other IEC Publications.
8) Attention is drawn to the Normative references cited in this publication. Use of the referenced publications is
indispensable for the correct application of this publication.
9) Attention is drawn to the possibility that some of the elements of this IEC Publication may be the subject of patent
rights. IEC shall not be held responsible for identifying any or all such patent rights.
A PAS is a technical specification not fulfilling the requirements for a standard, but made available
to the public.
IEC-PAS 62424 has been processed by IEC technical committee 65: Industrial-process
measurement and control.
The text of this PAS is based on the This PAS was approved for publication
following document: by the P-members of the committee
concerned as indicated in the
following document
Draft PAS Report on voting
65/356/NP 65/361/RVN
Following publication of this PAS, which is a pre-standard publication, the technical committee or
subcommittee concerned will transform it into an International Standard.
This PAS shall remain valid for an initial maximum period of three years starting from
2005-06. The validity may be extended for a single three-year period, following which it shall be
revised to become another type of normative document or shall be withdrawn.
PAS 62424 © IEC:2005(E) – 7 –
INTRODUCTION
Efficient process engineering requires highly sophisticated tools for the different needs of the
departments involved. These engineering tools are normally specialised in process design (PD),
in process control engineering (PCE), etc. Therefore, working interoperability is essential to
optimise the engineering process in total. Thus, the definition of a harmonised interface and data
management is a core task to ensure a smooth workflow throughout the whole project and to
guarantee data consistency in the different tools.
This document defines procedures and specifications for the exchange of PCE relevant data
provided by the P&ID module. The requirements for a change management procedure are
described. A generally accepted technology for machine information exchange, the Extensible
Markup Language (XML) is employed. Hereby, a common basis is given for information
integration.
However, a definition is still necessary for uniform semantics. CAEX (Computer Aided
Engineering eXchange) as defined in this document is an appropriate data format for this
purpose. This concept of data exchange is open for different applications.
The main task of a data exchange is transporting/synchronizing information from the P&ID
database to the PCE databases and vice versa. The owner's naming system is the key for a
unique identification. For detailed information about representation of PCE loops in P&I diagrams,
see Clause 6.
The data exchange system may be a stand-alone, vendor-independent application or a module in
an engineering environment. The data between a P&ID tool and a PCE tool and vice versa is
exchanged via CAEX.
After the data exchange, there are three places where information about the plant is stored. Both
the proprietary databases of the tools considered include private and common information. Both
are stored at different places and different divisions that are working on them. Hereby, the
intermediate database CAEX only stores common information. In a wider approach, the
intermediate database can store both common and private information. This becomes important if
a third application is connected to the neutral database. If the intermediate database is used as a
temporary data stream only (without storing the information in a file), the information will be lost
after processing the data conciliation.
Figure 1 illustrates the information flow for the P&ID and the PCE database reconciliation. The
data exchange is carried out via a neutral intermediate CAEX database, not direct from database
to database. The intermediate CAEX database can be a file (for file-based data exchange) or a
stream (for network-based data exchange). The term "CAEX database“ within this specification
has to be understood in this way, it does not denominate a database product such as SQL.
– 8 – PAS 62424 © IEC:2005(E)
P&ID
3D-Model
User
proprietary P&ID - Database
PCE relevant Intersection
modifications
addition
P&ID export/import application
error list
loops
Process designer
Further Further
CAEX
applications applications
(XML file with neutral data format)
XML-Files
XML-Files
PCE relevant Intersection
Process control engineer
error list
PCE import/export application
addition
loops
modifications
PCE - System
(loops, tags, process data)
PCE relevant
User
Intersection
Figure 1 – Information flow of P&ID and PCE tools
PAS 62424 © IEC:2005(E) – 9 –
REPRESENTATION OF PROCESS CONTROL ENGINEERING REQUESTS
IN P&I DIAGRAMS AND DATA EXCHANGE BETWEEN P&ID TOOLS
AND PCE-CAE TOOLS
1 Scope
This specification describes how process control engineering requests are represented in a P&I
diagram.
It also defines the exchange of process control engineering request relevant data between a
process control engineering tool and a P&I tool by means of a data transfer language (called
CAEX). These provisions apply to the export/import applications of such tools.
The representation of the PCE functionality in P&I diagrams is defined by a minimum number of
rules to clearly indicate their category and processing function, independent from the technique of
realization (see Clause 6). The definition of graphical symbols for process equipment (for example
vessels, valves, columns, etc.), their implementation and rules for the numbering system are not
the scope of this standard. These rules are independent from this standard and can be found, for
example, within DIN EN ISO 10628 or ISO 14617.
Clause 7 specifies the data flow between the different tools and the data model CAEX.
2 Normative references
The following referenced documents are indispensable for the application of this document. For
dated references, only the edition cited applies. For undated references, the latest edition of the
referenced document (including any amendments) applies.
IEC 60050-826, International Electrotechnical Vocabulary – Part 826: Electrical installations of
buildings
IEC 61346-1 (all parts), Industrial systems, installations and equipment and industrial products –
Structuring principles and reference designation
IEC 61511-1 (all parts) , Functional safety – Safety Instrumented Systems for the process industry
sector
ISO 10628, Flow diagrams for process plants – General rules
ISO 14617 (all parts), Graphical symbols for diagrams
EN 13480-1, Metallic industrial piping – Part 1: General
EN 1594, Gas supply systems – Pipelines for maximum operating pressure over 16 bar –
Functional requirements
EN 982, Safety of machinery – Safety requirements for fluid power systems and their components
– Hydraulics
Extensible Markup Language (XML) 1.0 (Third Edition), W3C Recommendation 04 February 2004
(available at )
– 10 – PAS 62424 © IEC:2005(E)
3 Terms and definitions
For the purpose of this document, the following terms and definitions, as well as those given in
60050-826, apply
3.1
process control equipment
equipment, having a process control function
3.2
process control function
function to work on process variables, which is composed of basic functions of process control,
specific to units of the plant
NOTE In addition to process control functions associated with single sensors and actuators, there can also be process
control functions that link input and output variables across several sensors and actuators. For instance, a process
control function in the feedback path with the controlled variable as input variable and the manipulated variable as output
variable, describes the action path from the sensor via the controller to the final controlling element.
3.3
PCE request
a PCE request describes requirements for process control equipment. Each PCE request is
graphically represented by a bubble which collects all information on the functional requirements
3.4
sensor
functional unit that senses the effect of a measured variable at its input and places a
corresponding measurement signal at its output
NOTE Examples of sensors are:
a) Thermocouple; b) Foil strain gauge; c) pH electrode.
3.5
Actuator
functional unit that generates from the controller output variable the manipulated variable required
to drive the final controlling element
NOTE If the final controlling element is mechanically actuated, it is controlled via an actuating drive. The actuator drives
the actuating drive in this case.
EXAMPLE A practical example of an actuator acting directly on the final controlling element is a d.c. drive. The control
unit takes the function of an actuator. The final controlling element is formed by the thyristor assembly that delivers a
variable d.c. voltage as an output variable. The control unit and the thyristor assembly together form the final controlling
equipment.
3.6
CE loop
collection of PCE requests and PCE control functions depicting their functional coherence
3.7
Bubble
symbol used to denote and identify a process function. It contains an identification
3.8
process function
function in a process
[IEC 61512-1]
PAS 62424 © IEC:2005(E) – 11 –
3.9
PCE control function
function in a PCE control
[IEC 61512-1]
3.10
process category
letter that designates the kind of process control request
4 Abbreviations
Table 1 shows the abbreviations used in this specification.
Table 1 – Abbreviations
CAD Computer Aided Design
CAE Computer Aided Engineering
CAEX Computer Aided Engineering eXchange
CCR Central Control Room
E&I Electrical and Instrumentation
ERP Enterprise Resource Planning
GMP Good Manufacturing Practice
N.A. Not applicable
PCE Process Control Engineering
PCS Process Control System
P&ID Piping and Instrumentation Diagram
PD Process design
PU Package Unit
SIL Safety Integrety Level
XML Extensible Markup Language
5 Conformity
To claim conformity to this specification with respect to the graphical representation of PCE
requests in P&ID, the requirements of Clause 6 shall be fulfilled.
To claim conformity to this specification with respect to the PCE relevant data exchange, the
requirements of Clause 7 and the following requirements shall be fulfilled.
The data exchange shall be performed by a separate or integrated import/export application
that provides for the data exchange between the related tool and CAEX.
NOTE The goal of the import/export application is to provide for a data reconciliation for the intersection of the
source and target databases. It is able to read the proprietary database of the considered tool and to reconcile the data
with the neutral CAEX database.
The export/import application shall check, report and provide the intersection data of both
databases. The neutral database shall be open for additional applications.
The data import function shall enforce a configurable checking step (for example,. rule-based)
during the import process; it shall not allow unguided automatic changes. The configurable
– 12 – PAS 62424 © IEC:2005(E)
checking step shall include functionality for automatic or manual acceptance of data changes,
allowing single decisions up to bulk data management.
All changes in the proprietary database and all data inconsistencies discovered shall be reported
by the import application. The generation of the report shall be configurable. The import/export
application shall assure that the intersection of the different databases holds the same information
and that additional division specific data is handled in a consistent way. Data manipulation by a
project division is an ongoing process during the whole project and beyond it. Thus, the creation,
changing and deletion of data shall be possible during the life-cycle of the plant.
CAEX databases shall be consistent. This requires a consistency check before exporting the data.
This procedure shall be followed after a successful data manipulation in a P&ID-tool or PCE-tool
in order to bring the new information into the neutral database or vice versa. Before any data
changing action is carried out, the user shall be informed and asked for confirmation. The
consistency check shall encompass at least the following steps and fulfil the following
requirements.
a) Data export from source database to neutral database
1) Check P&ID and PCE database for at least
i) duplicate PCE requests or loop designations;
ii) mandatory fields being filled in;
iii) correct use of numbering system of the PCE requests;
Inconsistent data shall not be exported
2) Generate PCE relevant information.
3) Check for changed information in comparison with previously stored data in the neutral
database.
4) Renaming of PCE request shall be supported by the export functionality.
5) Perform data export from proprietary into neutral database
i) e. g. if the PCE request has been changed, the old PCE request within the neutral
database shall be deleted and the new one can be exported from the proprietary
database into the neutral database. The old PCE request information may be stored
in a backup.
ii) Other changes shall be performed with the existing object.
6) Generate reports after each data exchange
i) new PCE requests list, missing PCE requests list, changed PCE requests list,
deleted PCE requests list, problems and error list.
b) Data import from neutral database into the target database
1) Generate PCE relevant information from neutral database.
2) Check for changed information by comparing the neutral database with the target
database.
3 Perform data import from the neutral into the proprietary database.
4 Renaming of PCE request shall be supported by the import functionality.
5 Generate reports after each data exchange.
i) error lists:
ii) inconsistencies due to imported data can be detected by the target application during
the import process and are not considered within this specification.
PAS 62424 © IEC:2005(E) – 13 –
6 Representation of PCE requests in P&ID
6.1 PCE request and PCE loop
In a P&ID the functional design of a plant is determined. Details of technical equipment are given
only if functions are correlated with the design of specific equipment. Consequently the P&ID
describes requirements for the design of the process control equipment. Each PCE request shall
be illustrated in the P&ID with an individual identification. In order to meet the requirements of
data handling, the same identification shall not be used for different PCE requests. Functional
coherence may be depicted by collecting the individual PCE requests in a PCE loop. A PCE loop
does not have a graphical representation but is embedded into a numbering system. Depending
on the engineering strategy, a PCE loop thereby consists of at least one, but can also combine
several, PCE requests. If PCE loops are used, these shall be represented in the identification of
all PCE requests concerned. An example of this concept is given in Figure 2.
PCE loop xxxx
PCE request
(optional)
SHH
AH
TI
xxxx.1
a
PCE request PCE control function PCE request
SHH
OH
AH
FI
US YS
xxxx.2 AL
xxxx.3 xxxx.2
a
The PCE control function used in Figure 2 is defined in 6.3.10.
Figure 2 – Organisation of PCE requests
6.2 Objectives and principles
This subclause defines how to represent the process control engineering functionality in P&ID.
Technical details of the equipment used shall not be depicted in general. This is due to the goal to
ensure a smooth engineering workflow by separating process and instrumentation design.
Therefore, it is necessary to clarify
a) the PCE category and function;
b) the numbering system for PCE requests in P&ID;
c) the graphical representation of PCE requests in P&ID;
d) the type of functional connection between the PCE requests: the control functions;
e) the graphical representation of signals in P&ID.
Detailed information on complex control functions shall not be part of the P&ID. Therefore,
additional documentation shall be prepared to define the required functionality. A control function
shall also be individually identified and may be represented on the P&ID.
– 14 – PAS 62424 © IEC:2005(E)
6.3 Requirements for the identification and representation of PCE requests
6.3.1 General
Each PCE request shall be graphically represented by a bubble, which collects all information
about the functional requirements. Three data fields inside and 10 data fields outside the bubble
are defined to hold all the information about a PCE request (see Figure 3). For detailed
information, see 6.3.3-6.3.9.
ZHHH
SHH
AH
PU Vendor
(SIL3)
Safety relevant
PCE category and function
Typical ident. GMP
PCE Identification
Quality relevant
Device information
AL
ALL
SLLL
Figure 3 – General representation of a PCE-request in P&ID
As stated before, only the PCE functionality shall be depicted on P&ID, not the PCE
implementation. In exceptional cases however, there might be constellations where the
presentation of detailed realization information is inevitable. For example, in the case of a multi
sensor element which means an instrument that produces measurements for different categories,
every category shall be represented by its own bubble. The bubbles are stacked up, as shown in
Figure 4.
AI
xxxx
Dens.
FI
xxxx
PI
xxxx
Figure 4 – Multi sensor element
In all cases where the PCE request is connected to the equipment or pipe this shall be shown by
a full line, connecting the bubble with the equipment or pipe.
6.3.2 Types of lines
Signal lines are used to illustrate the functional relationship between PCE requests. A signal line
shall be depicted as a dashed line with an arrow to indicate the information flow. The source of
the information flow shall be a bubble of a PCE control function or request or a switching action
consisting of the six fields right outside the bubble. The sink of the information flow shall be a
bubble of a PCE request or a control function.
Process connections shall be depicted by a solid line without a direction. Multisensor instruments
with only one process connection shall have an extra bubble for each category and only one
process connection.
PAS 62424 © IEC:2005(E) – 15 –
6.3.3 Displaying the location of the operator interface
Each PCE request is graphically represented by a bubble. This standard distinguishes the
location of the operator interface between local, the local control panel and a central control room.
The location does not reflect any realization in systems.
A local interface shall be represented by a plain bubble as shown in Figure 5. It could be a
pressure gauge, for example.
PI
xxxx
Figure 5 – Local interface
Operator action/information on a local control panel shall be represented as shown in
Figure 6.
HS
xxxx
Figure 6 – Manually operated switch in local control panel
Remote requests operated in a central control room shall be represented as shown in
Figure 7.
PI
xxxx
Figure 7 – Pressure indication in a central control room
6.3.4 PCE categories and processing functions
6.3.4.1 Indication of PCE categories and processing functions
The upper part of the bubble shall show the information of the PCE category and its PCE
processing function. Each bubble shall have at least one PCE category and one PCE processing
function. As an exception for the processing function, see 6.3.4.3.
6.3.4.2 PCE categories
The first character shall be selected according to the measured or manipulated variable. Table 2
shows the list of the PCE categories used.
– 16 – PAS 62424 © IEC:2005(E)
Table 2 – PCE categories
Letter PCE category
A Analysis
1)
B
1)
C
1)
D
E Electrical value (detail definition by user)
F Flow
G Distance, length, position
H Manual and manually initiated operation
1)
I
1)
J
K Time-based function
L Level
1)
M
N Actuation setting (motor)
1)
O
P Pressure
Q Quantity or counter
R Radiation
S Speed or frequency
T Temperature
U N.A. (see 6.3.10)
V Vibration
W Weight, mass, force
2)
X
Y Actuation setting (valve)
Z 1)
1)
These letters can be defined by users.
2)
The unclassified letter X is intended to cover unlisted meanings that will
be used only once or used to a limited extent. If used, the letter may have
any number of meanings as a PCE category and any number of meanings
as a PCE function.
6.3.4.3 PCE processing functions
Starting with the second character, the successive letters in the upper part of the bubb
...