EN 61803:1999/A2:2016
(Amendment)Determination of power losses in high-voltage direct current (HVDC) converter stations with line commutated converters
Determination of power losses in high-voltage direct current (HVDC) converter stations with line commutated converters
Applies to all line-commutated high-voltage direct current (HVDC) converter stations used for power exchange in utility systems. Presumes the use of 12-pulse thyristor converters but can also be used for 6-pulse thyristor converters. Presents procedures for determining the total losses of an HVDC converter station. Cover all parts, except synchronous compensators or static var compensators and address no-load operation and operating losses together with their methods of calculation which use, wherever possible, measured parameters.
Bestimmung der Leistungsverluste in Hochspannungsgleichstrom (HGÜ)-Stromrichterstationen mit netzgeführten Stromrichtern
Détermination des pertes en puissance dans les postes de conversion en courant continu à haute tension (CCHT) munis de convertisseurs commutés par le réseau
S'applique à tous les postes de conversion en courant continu à haute tnesion (CCHT), commutés par le réseau, et utilisés pour l'échange de puissance dans des systèmes de distribution d'énergie. Présuppose l'utilisation de convertisseurs à thyristors à 12 impulsions mais peut également s'appliquer à des convertisseurs à thyristors à 6 impulsions. Décrit un ensemble de procédures types permettant de déterminer l'ensemble des pertes d'un poste de conversion à CCHT. Les procédures recouvrent toutes les pièces, à l'exception des compensateurs synchrones ou des compensateurs var statiques et considèrent les pertes en fonctionnement à vide et les pertes en fonctionnement ainsi que leurs méthodes de calcul utilisant, dans la mesure du possible, des paramètres mesurés.
Ugotavljanje močnostnih izgub v visokonapetostnih enosmernih (HVDC) pretvorniških postajah s pretvorniki s komutiranjem (IEC 61803:1999/A2:2016) - Dopolnilo A2
General Information
Relations
Standards Content (Sample)
SLOVENSKI STANDARD
01-december-2016
8JRWDYOMDQMHPRþQRVWQLKL]JXEYYLVRNRQDSHWRVWQLKHQRVPHUQLK+9'&
SUHWYRUQLãNLKSRVWDMDKVSUHWYRUQLNLVNRPXWLUDQMHP,(&$
'RSROQLOR$
Determination of power losses in high-voltage direct current (HVDC) converter stations
with line-commutated converters (IEC 61803:1999/A2:2016)
Détermination des pertes en puissance dans les postes de conversion en courant
continu à haute tension (CCHT) munis de convertisseurs commutés par le réseau
Ta slovenski standard je istoveten z: EN 61803:1999/A2:2016
ICS:
29.200 8VPHUQLNL3UHWYRUQLNL Rectifiers. Convertors.
6WDELOL]LUDQRHOHNWULþQR Stabilized power supply
QDSDMDQMH
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.
EUROPEAN STANDARD EN 61803:1999/A2
NORME EUROPÉENNE
EUROPÄISCHE NORM
October 2016
ICS 29.200
English Version
Determination of power losses in high-voltage direct current
(HVDC) converter stations with line commutated converters
(IEC 61803:1999/A2:2016)
Détermination des pertes en puissance dans les postes de Bestimmung der Leistungsverluste in
conversion en courant continu à haute tension (CCHT) Hochspannungsgleichstrom (HGÜ)-Stromrichterstationen
munis de convertisseurs commutés par le réseau (IEC 61803:1999/A2:2016)
(IEC 61803:1999/A2:2016)
This amendment A2 modifies the European Standard EN 61803:1999; it was approved by CENELEC on 2016-06-29. CENELEC members
are bound to comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this amendment the status of a
national standard without any alteration.
Up-to-date lists and bibliographical references concerning such national standards may be obtained on application to the CEN-CENELEC
Management Centre or to any CENELEC member.
This amendment exists in three official versions (English, French, German). A version in any other language made by translation under the
responsibility of a CENELEC member into its own language and notified to the CEN-CENELEC Management Centre has the same status as
the official versions.
CENELEC members are the national electrotechnical committees of Austria, Belgium, Bulgaria, Croatia, Cyprus, the Czech Republic,
Denmark, Estonia, Finland, Former Yugoslav Republic of Macedonia, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia,
Lithuania, Luxembourg, Malta, the Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland,
Turkey and the United Kingdom.
European Committee for Electrotechnical Standardization
Comité Européen de Normalisation Electrotechnique
Europäisches Komitee für Elektrotechnische Normung
CEN-CENELEC Management Centre: Avenue Marnix 17, B-1000 Brussels
© 2016 CENELEC All rights of exploitation in any form and by any means reserved worldwide for CENELEC Members.
Ref. No. EN 61803:1999/A2:2016 E
European foreword
The text of document 22F/374/CDV, future IEC 61803:1999/A2, prepared by SC 22F “Power
electronics for electrical transmission and distribution systems” of IEC/TC 22 “Power electronic
systems and equipment” was submitted to the IEC-CENELEC parallel vote and approved by
CENELEC as EN 61803:1999/A2:2016.
The following dates are fixed:
• latest date by which the document has to be (dop) 2017-04-14
implemented at national level by
publication of an identical national
standard or by endorsement
(dow) 2019-10-14
• latest date by which the national
standards conflicting with the
document have to be withdrawn
Endorsement notice
The text of the International Standard IEC 61803:1999/A2:2016 was approved by CENELEC as a
European Standard without any modification.
IEC 61803 ®
Edition 1.0 2016-05
INTERNATIONAL
STANDARD
NORME
INTERNATIONALE
AM ENDMENT 2
AM ENDEMENT 2
Determination of power losses in high-voltage direct current (HVDC) converter
stations with line commutated converters
Détermination des pertes en puissance dans les postes de conversion en
courant continu à haute tension (CCHT) munis de convertisseurs commutés par
le réseau
INTERNATIONAL
ELECTROTECHNICAL
COMMISSION
COMMISSION
ELECTROTECHNIQUE
INTERNATIONALE
ICS 29.200 ISBN 978-2-8322-3358-0
– 2 – IEC 61803:1999/AMD2:2016
© IEC 2016
FOREWORD
This amendment has been prepared by subcommittee 22F: Power electronics for electrical
transmission and distribution systems, of IEC technical committee 22: Power electronic
systems and equipment.
The text of this amendment is based on the following documents:
CDV Report on voting
22F/374/CDV 22F/393A/RVC
Full information on the voting for the approval of this amendment can be found in the report
on voting indicated in the above table.
The committee has decided that the contents of this amendment and the base publication will
remain unchanged until the stability date indicated on the IEC website under
"http://webstore.iec.ch" in the data related to the specific publication. At this date, the
publication will be
• reconfirmed,
• withdrawn,
• replaced by a revised edition, or
• amended.
_____________
CONTENTS
5.9 Series filter losse
Replace the entry as follows (to correct the misprint):
5.9 Series filter losses
3.1.1
auxiliary losses
Replace the existing definition by the following new definition and new note:
electric power required to feed the converter station auxiliary loads
NOTE 1 to entry: The auxiliary losses depend on the number of converter units used and whether the station is in
no-load operation or carrying load, in which case the auxiliary losses depend on the load level.
3.1.2
no-load operation losses
Replace the term and its definition as follows:
IEC 61803:1999/AMD2:2016 – 3 –
© IEC 2016
3.1.2
equipment no-load operation losses
losses produced in an item of equipment with the converter station energised but with the
converters blocked and all station service loads and auxiliary equipment connected as
required for immediate pick-up of load to specified minimum power
3.1.4
operating losses
Replace the existing term by the following new term:
3.1.4
equipment operating losses
3.1.5
rated load
Replace the existing definition by the following new definition and note:
load related to operation at nominal values of d.c. current, d.c. voltage, a.c. voltage and
converter firing angle
Note 1 to entry: The a.c. system shall be assumed to be at nominal frequency and its 3-phase voltages are
nominal and balanced. The position of the tap-changer of the converter transformer and the number of a.c. filters
and shunt reactive elements connected shall be consistent with operation at rated load, coincident with nominal
conditions.
3.1.6
total station losses
Replace the existing term and its definition by the following new term, definition and notes:
3.1.6
total station operating losses
sum of all equipment operating losses (3.1.4) and corresponding auxiliary losses (3.1.1) at a
particular load level
Note 1 to entry: It is recognised that some purchasers evaluate “total station no-load operation losses” (definition
3.1.8) and total station load losses individually instead of the evaluating “total station operating losses” (definition
3.1.6).
Note 2 to entry: "Operating losses” minus “no-load operation losses” may be considered as being quantitatively
equivalent to “load losses” as in conventional a.c. substation practice.
Note 3 to entry: An illustrative example to derive “load losses”, “equivalent load losses” and corresponding “loss
evaluation” is given in Annex D.
3.1.7
station essential auxiliary load
Delete, in the definition added by Amendment 1, the Note.
– 4 – IEC 61803:1999/AMD2:2016
© IEC 2016
Insert, between 3.1.5 and 3.1.6 the following new entry 3.1.8:
3.1.8
total station no-load operation losses
sum of all equipment no-load operation losses (3.1.2) and corresponding auxiliary losses
(3.1
...