Ventilation for buildings - Performance testing of components/products for residential ventilation - Part 2: Exhaust and supply air terminal devices

This European Standard specifies laboratory methods for testing exhaust and supply air terminal devices operating under pressure differences.
It applies to devices used in mechanical and natural residential ventilation systems, of the following types:
-   device with a manually adjustable opening; or
-   device with a fixed opening; or
-   pressure difference controlled device.
It describes tests intended to characterize:
-   flow rate/pressure;
-   air diffusion characteristics (for supply air terminal devices);
-   noise production for components of systems;
-   insertion loss of component of systems;
-   sound insulation.

Lüftung von Gebäuden - Leistungprüfungen von Bauteilen/Produkten für die Lüftung von Wohnungen - Teil 2: Abluft- und Zuluftdurchlässe

Diese Europäische Norm legt Laborverfahren für die Prüfung von Abluft  und Zuluftdurchlässen fest, die unter Druckdifferenzen betrieben werden.
Sie gilt für Luftdurchlässe der folgenden Typen, die in Anlagen für die maschinelle und natürliche Lüftung von Wohnungen angewendet werden:
-   Luftdurchlässe mit manuell einstellbarer Öffnung; oder
-   Luftdurchlässe mit nicht verstellbarer Öffnung; oder
-   druckdifferenzgeregelte Luftdurchlässe.
Sie beschreibt Prüfungen, die für die Bestimmung folgender Größen vorgesehen sind:
-   Volumenstrom/Druck;
-   Luftverteilungskenngrößen (für Zuluftdurchlässe);
-   Geräuscherzeugung durch Anlagenbauteile;
-   Einfügungsdämpfung von Anlagenbauteilen;
-   Schalldämmung.

Ventilation des bâtiments - Essais des performances des composants/produits pour la ventilation des logements - Partie 2: Bouches d'air d'évacuation et d'alimentation

La présente Norme européenne spécifie les méthodes de laboratoire pour l'essai des bouches d'air d'évacuation et d'alimentation fonctionnant sous des différences de pression.
Elle s’applique aux dispositifs utilisés dans les systèmes de ventilation naturelle ou mécanique du secteur résidentiel, des types suivants :
-   dispositif équipé d'une ouverture réglable manuellement ou ;
-   dispositif équipé d'une ouverture fixe ou ;
-   dispositif contrôlé par différence de pression.
Elle décrit les essais destinés à caractériser :
-   le rapport débit/pression ;
-   les caractéristiques de diffusion de l’air (pour les bouches d’alimentation) ;
-   le bruit produit par les composants des systèmes ;
-   les pertes d'insertion des composants des systèmes ;
-   l'isolement acoustique.

Prezračevanje stavb - Preskušanje lastnosti stanovanjskih prezračevalnih komponent/izdelkov - 2. del: Odvodne in dovodne zračne naprave

Ta evropski standard določa laboratorijske metode za preskušanje odvodnih in dovodnih zračnih naprav, ki delujejo pri tlačnih razlikah. Velja za pripomočke naslednjih vrst, ki se uporabljajo pri mehanskih in naravnih stanovanjskih prezračevalnih sistemih: - pripomočki z ročno nastavljivo odprtino; ali – pripomočki s stalno odprtino; ali – pripomočki, krmiljene s tlačno razliko. Opisuje preskuse, namenjene ugotavljanju: - hitrosti pretoka/tlaka; - značilnosti difuzije zraka (za oskrbovanje zračnih naprav); - proizvodnje hrupa sestavnih delov sistemov; - notranje izgube sestavnih delov sistemov; - zvočne izolacije.

General Information

Status
Published
Publication Date
27-Jul-2010
Withdrawal Date
30-Jan-2011
Current Stage
9093 - Decision to confirm - Review Enquiry
Start Date
07-Jan-2025
Completion Date
14-Apr-2025

Relations

Standard
EN 13141-2:2010
English language
23 pages
sale 10% off
Preview
sale 10% off
Preview
e-Library read for
1 day

Standards Content (Sample)


2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.HYDOQLKLüftung von Gebäuden - Leistungprüfungen von Bauteilen/Produkten für die Lüftung von Wohnungen - Teil 2: Abluft- und ZuluftdurchlässeVentilation dans les bâtiments - Essais des performances des composants/produits pour la ventilation des logements - Partie 2: Bouches d'air d'évacuation et d'alimentationVentilation for buildings - Performance testing of components/products for residential ventilation - Part 2: Exhaust and supply air terminal devices91.140.30VLVWHPLVentilation and air-conditioningICS:Ta slovenski standard je istoveten z:EN 13141-2:2010SIST EN 13141-2:2010en,fr,de01-oktober-2010SIST EN 13141-2:2010SLOVENSKI
STANDARDSIST EN 13141-2:20041DGRPHãþD

EUROPEAN STANDARD NORME EUROPÉENNE EUROPÄISCHE NORM
EN 13141-2
July 2010 ICS 91.140.30 Supersedes EN 13141-2:2004English Version
Ventilation for buildings - Performance testing of components/products for residential ventilation - Part 2: Exhaust and supply air terminal devices
Ventilation des bâtiments - Essais des performances des composants/produits pour la ventilation des logements - Partie 2: Bouches d'air d'évacuation et d'alimentation
Lüftung von Gebäuden - Leistungprüfungen von Bauteilen/Produkten für die Lüftung von Wohnungen - Teil 2: Abluft- und Zuluftdurchlässe This European Standard was approved by CEN on 22 April 2010.
CEN members are bound to comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this European Standard the status of a national standard without any alteration. Up-to-date lists and bibliographical references concerning such national standards may be obtained on application to the CEN Management Centre or to any CEN member.
This European Standard exists in three official versions (English, French, German). A version in any other language made by translation under the responsibility of a CEN member into its own language and notified to the CEN Management Centre has the same status as the official versions.
CEN members are the national standards bodies of Austria, Belgium, Bulgaria, Croatia, Cyprus, Czech Republic, Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland and United Kingdom.
EUROPEAN COMMITTEE FOR STANDARDIZATION
COMITÉ EUROPÉEN DE NORMALISATION EUROPÄISCHES KOMITEE FÜR NORMUNG
Management Centre:
Avenue Marnix 17,
B-1000 Brussels © 2010 CEN All rights of exploitation in any form and by any means reserved worldwide for CEN national Members. Ref. No. EN 13141-2:2010: ESIST EN 13141-2:2010

Mechanical Building Services
Control systems
Ventilation and air conditioning systems
Heating systems
Ductwork
Air terminal devices
Air handling units
Mechanical and natural residential ventilation
Design criteria for the indoor environment
System performance
Installation
Components/products for residential ventilation Required and optional performance characteristics
Performance testing of components/products for residential ventilation
Simplified calculation methods for residential ventilation systems
Design and dimensioning for residential ventilation systems
Performance testing and installation checks for residential ventilation systems
Part 1: Externally and internally mounted air transfer devices
Part 2: Exhaust and supply air terminal devices
Part 3: Range hoods for residential use
Part 4: Fans used in residential ventilation systems
Part 5: Cowls and roof outlet terminal devices
Part 6: Exhaust ventilation system packages used in a single dwelling
Part 7: Performance testing of a mechanical supply and exhaust ventilation units (including heat recovery) for mechanical ventilation
systems intended for single family dwellings
Part 8: Performance testing of un-ducted mechanical supply and exhaust ventilation units (including heat recovery) for mechanical
ventilation systems intended for a single room
Part 9: Externally mounted humidity controlled air transfer device
Part 10: Humidity controlled extract air terminal device
Figure 1 — Position of EN 13141-2 in the field of the mechanical building services
a) For exhaust air terminal device b) For supply air terminal device Key 1 airflow 7 flow straightener 2 airflow meter 8 connection to fan, flowrate control and airflow meter 3 plane of temperature measurement 9 transition to test duct size 4 plane of pressure measurement 10 plane of pressure measurement 5 air terminal device 11 signal to display or computer 6 test duct, diameter De 12 with flow straightener
13 without flow straightener Figure 2 — Test installation for exhaust air terminal device (Figure 2a)) and supply air terminal device (Figure 2b)) 4.1.2.2 Uncertainty of measurement In the case of air terminal devices with pressure difference controlled openings:  the pressure shall be measured with an uncertainty lower than: (Pa)
value)(measured 0,03
0,2×+ (1)  the volume flow rate shall be measured with an uncertainty lower than: SIST EN 13141-2:2010

value)(measured 0,03
0,31−⋅×+s (2) For other air terminal devices:  the pressure shall be measured with an uncertainty lower than: (Pa)
value)(measured 0,03
0,5×+ (3)  the volume flow rate shall be measured with an uncertainty lower than:
)(l
value)(measured 0,03
0,31−⋅×+s (4) NOTE The combined uncertainties of measurement will result in a total accuracy of the test method in the range of 3 % to 5 %. 4.1.3 Test procedure The measurements shall be taken for six points, each taken within one of the pressure difference ranges (bands) given in Table 1 so as to match with / cover the operational range of the device as stated by the manufacturer. Table 1 — Pressure difference ranges Pressure difference ∆p Pa 3 to 4 4 to 6 6 to 8 8 to 10 13 to 18 18 to 24 24 to 32 32 to 42 42 to 55 55 to75 75 to 100 100 to 130 130 to 170 170 to 225 225 to 300
The environmental conditions existing during the tests such as temperature, barometric pressure shall be recorded. Air temperature θa shall be (20 ± 5) °C. During the test, temperature θa shall not vary more than ± 2 °C. The test shall be carried out by continuously increasing the pressure difference across the device. SIST EN 13141-2:2010

Key 1 reverberation room
2 silencer (or silent air inlet) 3 air terminal device under test 4 test duct 5 to the exhaust fan and the flow rate measuring instrument
6 anechoic termination (300 mm of fibrous sound absorbent plug with a density close to 40 kg/m³ before the closed side of the duct) 7 pressure probes Figure 3 — Test facility and test installation of the air terminal device on its test duct 5.1.2.2 Position of the air terminal device in reverberation room The duct centreline should be placed at 300 mm from an edge of the test room and at least at 1 500 mm from any wall other than those forming the edge. If the edge is not at 300 mm from the duct centreline, it shall be simulated by using a baffle of particle board, thickness 22 mm, minimum density 500 kg/m³ and minimum area 1 500 mm × 1 500 mm. 5.1.2.3 Air handling circuit The air circuit shall be designed as shown in Figure 3. An extraction fan shall be mounted in the air circuit and fitted with regulation devices and a silencer. The measured background noise of the test room when the air terminal device is removed should remain at least 6 dB lower than the noise measured with the device. SIST EN 13141-2:2010

The pressure drop through the air terminal device shall be measured as:
1atm
- ppp=∆ (5) where
patm is the atmospheric pressure in the room;
p1 is the static pressure measured in the duct at the position indicated in Figure 3. The static pressure shall be measured according to 4.1.
The air terminal device shall be mounted such that no air leakage can occur between the device and the air duct, to avoid the generation of narrow-band noise which can affect the results. The setting of any positioning parameter indicated on the adjustable terminal devices shal
...