Abstract

This document specifies definitions, principles of construction, requirements and methods for testing the performance of UV devices (240 nm to 290 nm nominal) for potable water installations according to EN 806-2 which are permanently connected to the building’s supply.
Devices described by this document can be installed at the point of entry (POE), within the water distribution system inside the building or at the point of use (POU).
Additionally, the devices described in this document can be used in mobile or temporary potable water installations, where the system is not permanently connected to a water supply.
UV devices in the sense of this document are UV bactericidal treatment devices or UV disinfection devices for one of three specified water qualities, determined by the observed UV transmittance.
Devices can be standalone, integrated into a larger appliance or part of multi-staged treatment process. The document relates solely to the performance of the UV reactor.

Status
Not Published
Publication Date
28-Feb-2027
Technical Committee
CEN/TC 164 - Water supply
Current Stage
4060 - Closure of enquiry - Enquiry
Start Date
12-Nov-2026
Due Date
02-Feb-2026
Completion Date
02-Feb-2026

Buy Documents

prEN 18380 is a CEN draft European Standard for water conditioning equipment inside buildings that use ultraviolet light-emitting diode (UV LED) units. It specifies performance, safety and testing requirements for UV devices used in potable water installations, with a focus on the UV reactor and the evidence needed to validate its treatment performance.

The standard is intended for manufacturers, test laboratories, installers, and specifiers who need to select, build, document, test, or approve UV LED water treatment devices for building water systems.

What does prEN 18380 specify?

prEN 18380 specifies definitions, construction principles, performance requirements, and test methods for UV devices with nominal UV wavelengths from 240 nm to 290 nm. It applies to potable water installations according to EN 806-2, including devices at the point of entry (POE), within the building distribution system, and at the point of use (POU), and it also allows use in mobile or temporary potable water installations.

The document is organized into:

  • Clause 1 Scope
  • Clause 2 Normative references
  • Clause 3 Terms and definitions
  • Clause 4 Requirements
  • Clause 5 Device documentation
  • Clause 6 Requirements for testing
  • Clause 7 Test procedure
  • Clause 8 Structure and content of the test report
  • Annex A device documentation requirements
  • Annex B collimated beam irradiation apparatus
AnnexWhat it covers
Annex AThe documentation package for the device, including drawings, data sheets, type plate information, control system details, UV LED unit data, protective layer data, sensor data, and the manual
Annex BThe collimated beam irradiation apparatus and the method used to determine Petri factor and to expose biodosimeter samples

The standard relates solely to the performance of the UV reactor. That matters in practice because upstream or downstream treatment elements are not credited in the performance claim.

What are the key requirements of prEN 18380?

prEN 18380 sets out the main design, labeling, and type-test conditions needed to validate a UV LED device for potable water use. The most important points are the performance categories, the water-quality basis for validation, the physical and electrical safeguards, and the biodosimetric test method used to prove treatment effect.

Performance categories and validated fluence

Clause 4.1 divides devices into Category A and Category B. Category A is for disinfection and Category B is for microbial control, with different reduction equivalent fluence (REF) targets at 254 nm.

In practice, this means the manufacturer must declare the category and validate the device at the matching flow rate and UV transmittance (UVT) range. The test result is not just a pass/fail on hardware - it ties the device to a specific operating window.

Materials, hydraulics, and mechanical integrity

Clauses 4.2 to 4.4 require UV-exposed parts to be UV resistant and corrosion resistant where relevant, and all potable-water contact materials to be suitable for drinking water use. The device also needs a flow limiter or host-system control so the validated maximum flow rate is not exceeded.

Mechanically, the device must withstand pressure-related checks, including hydrostatic and cyclic pressure resistance, and it must prevent direct or indirect UV leakage below 400 nm. For a buyer or installer, this is the part that tells you whether the unit is built for the system pressure and can be installed safely.

UV LED unit performance and lifetime

Clause 4.5 requires the UV LED spectrum to have a unimodal peak in the range 240 nm to 290 nm. It also requires the maximum operating hours to be stated on the type plate and in the manual, and it allows validation at different operating points, including dimmed operation if the conditions are clearly defined.

This matters because the device may be approved only for the validated UVT and flow-rate combinations, and any lower-power mode has to be declared if it sits outside that validated window.

Electrical control, monitoring, and alarm functions

Clause 4.6 requires a controller that starts or maintains operation when water flows, records operating hours, monitors UV LED function, signals low-UV conditions, and provides a general malfunction signal. The device must also provide an optical sensor or be compatible with a host system that does the same job.

The practical meaning is that the device must be able to warn the user when output drops or water quality changes beyond the validated range, and it must allow the water flow to be stopped when treatment is no longer adequate.

Labeling, installation information, and manual

Clauses 4.7 to 4.9 require a durable type plate, installation instructions, and a manual. The label must include the manufacturer, type designation, year, serial number, category, water quality, maximum flow rate, pressure rating, maximum operating hours, and certification information.

The manual must describe installation, operation, cleaning, service, operating range, flow direction, electrical data, temperature limits, humidity limit, and the validated flow-rate limit for the stated water quality. In practice, these are the details a user or service technician needs to install the unit correctly and keep it within its tested envelope.

Testing, biodosimetry, and report content

Clauses 6 and 7 define the type test. The device is tested at end-of-life derated output, with flow rate and UVT set to the manufacturer’s claimed conditions, and the performance is measured by biodosimetric testing using MS2 bacteriophage as the surrogate microbe.

This means the claimed UV treatment is not based only on lamp power or sensor readings. It is backed by challenge testing, control measurements, and a calculated REF for each operating point. Clause 8 then requires a written report with device identification, test setup, calibration details, biodosimeter data, test water characterization, and the technical and biodosimetric results.

What terms does prEN 18380 define?

prEN 18380 defines the vocabulary used to describe UV treatment performance and testing.

  • Reduction equivalent fluence (REF) - the average germicidal fluence measured with the biodosimeter, used to back-calculate UV treatment performance.
  • UV transmittance (UVT) - the spectral transmission rate of water at 254 nm over a 10 mm path length, expressed as a percentage.
  • Irradiance - UV light flux divided by the area receiving it; the sensor reading influenced by lamp output, water UVT, fouling, and geometry.
  • Biodosimeter - the surrogate microbe used to determine REF; in this document, MS2 phage is used.
  • UV LED unit - a grouped set of UV LEDs that produces UV light.
  • Radiation chamber - the part of the device containing the radiation zone and connecting pipes through which the water flows.
  • Permissible operation range - the flow-rate and irradiance or UVT limits where adequate treatment is assured.

Who uses prEN 18380?

prEN 18380 is used by manufacturers of UV LED water treatment devices, especially those designing POE and POU products for potable water systems. It is also used by test laboratories that perform type testing, calibration, and biodosimetric validation.

Installers and system integrators use it to understand the installation conditions, flow direction, pressure limits, and control requirements. Quality managers, certifiers, and buyers use it to check whether a device has the right documentation, test evidence, and declared operating window for a given application.

Which standards are used with prEN 18380?

prEN 18380 cites EN 10253 (all parts) as a normative reference for butt-welding pipe fittings, which supports the test-rig installation details, including the 90° bend ahead of the device.

The body and bibliography also reference:

  • EN 806-2 - the building water installation context for potable water systems
  • EN 14743 - the cyclic pressure test reference
  • EN ISO 10705-1 - the method used for MS2 phage enumeration
  • EN ISO/IEC 17025 - the competence basis for testing and calibration laboratories, also referenced for certification on the type plate

These references tell the reader which related standards support the installation, pressure testing, microbiological method, and laboratory competence used with this document.

What does the prEN 18380 document contain?

prEN 18380 contains category definitions, material and mechanical requirements, electrical monitoring requirements, labeling rules, and the document set that must accompany the device. It also includes a detailed test rig arrangement, water-quality requirements for the test water, and calibration rules for the UV-Vis spectrophotometer, flow measurement, temperature measurement, and irradiance measurement.

The document goes further into biodosimeter preparation, collimated beam irradiation, and the calculation of fluence and log inactivation. Figures 1 to 3 and Annex B support the apparatus setup and Petri factor method, while Tables 2 to 7 define the validation ranges, test-result templates, and reporting format.

Buy Documents

Get Certified

Connect with accredited certification bodies for this standard

DIBt (Deutsches Institut für Bautechnik)

German Institute for Building Technology.

DAKKS Germany Verified

DIN CERTCO

DIN Group product certification.

DAKKS Germany Verified

Aboma Certification B.V.

Specialized in construction, metal, and transport sectors.

RVA Netherlands Verified

Sponsored listings

Frequently Asked Questions

prEN 18380 is a draft published by the European Committee for Standardization (CEN). Its full title is "Water conditioning equipment inside buildings - Devices using UV LED units - Requirements for performance, safety and testing". This standard covers: This document specifies definitions, principles of construction, requirements and methods for testing the performance of UV devices (240 nm to 290 nm nominal) for potable water installations according to EN 806-2 which are permanently connected to the building’s supply. Devices described by this document can be installed at the point of entry (POE), within the water distribution system inside the building or at the point of use (POU). Additionally, the devices described in this document can be used in mobile or temporary potable water installations, where the system is not permanently connected to a water supply. UV devices in the sense of this document are UV bactericidal treatment devices or UV disinfection devices for one of three specified water qualities, determined by the observed UV transmittance. Devices can be standalone, integrated into a larger appliance or part of multi-staged treatment process. The document relates solely to the performance of the UV reactor.

This document specifies definitions, principles of construction, requirements and methods for testing the performance of UV devices (240 nm to 290 nm nominal) for potable water installations according to EN 806-2 which are permanently connected to the building’s supply. Devices described by this document can be installed at the point of entry (POE), within the water distribution system inside the building or at the point of use (POU). Additionally, the devices described in this document can be used in mobile or temporary potable water installations, where the system is not permanently connected to a water supply. UV devices in the sense of this document are UV bactericidal treatment devices or UV disinfection devices for one of three specified water qualities, determined by the observed UV transmittance. Devices can be standalone, integrated into a larger appliance or part of multi-staged treatment process. The document relates solely to the performance of the UV reactor.

prEN 18380 is classified under the following ICS (International Classification for Standards) categories: 91.140.60 - Water supply systems. The ICS classification helps identify the subject area and facilitates finding related standards.

prEN 18380 is available in PDF format for immediate download after purchase. The document can be added to your cart and obtained through the secure checkout process. Digital delivery ensures instant access to the complete standard document.

Standards Content (Sample)

Contents

  • Introduction
  • 1 Scope
  • 2 Normative references
  • 3 Terms and definitions
  • 3.1 absorption
  • 3.2 irradiance
  • 3.3 disinfection
  • 3.4 fluence
  • 3.5 reduction equivalent fluence
  • 3.6 radiation chamber
  • 3.7 radiation zone
  • 3.8 exposure time
  • 3.10 minimum irradiance
  • 3.11 flow rate
  • 3.12 maximum flow rate
  • 3.13 permissible operation range
  • 3.14 sensor
  • 3.15 attenuation
  • 3.16 lamp service life
  • 3.17 UV LED unit
  • 3.18 UV LED device
  • 3.19 UV LED disinfection device
  • 3.20 UV LED bactericidal treatment device
  • 3.21 turbidity
  • 3.22 UV transmittance
  • 3.23 UV radiation
  • 3.24 modal peak wavelength
  • 3.25 spectral full-width half-maximum
  • 3.26 sampling event
  • 3.27 measurement point
  • 4 Requirements
  • 4.1 General
  • 4.2 Material requirements
  • 4.3 Hydraulic requirements
  • 4.4 Mechanical properties
  • 4.5 Requirements UV LED units
  • 4.6 Requirements on electrical equipment
  • 4.7 Labelling
  • 4.8 Assembly and installation description
  • 4.9 Manual
  • 5 Device documentation
  • 6 Requirements for testing
  • 6.1 General
  • 6.2 Test rig and installation
  • 3 UVT modifier dosing pump 11 upstream sampling port
  • 5 UVT modifier source 13 downstream static mixer
  • 8 UVT measurement device
  • 6.3 Requirements on testing agents
  • 6.4 Measurement technology for the test setup
  • 6.5 Biodosimeter calibration
  • 7 Test procedure
  • 7.1 General
  • 7.2 Technical testing
  • 7.3 Biodosimetric testing
  • 8 Structure and content of the test report
  • 8.1 General
  • 8.2 Specification of the UV device
  • 8.3 Test setup of the UV device
  • 8.4 Results of the testing
  • Annex A
  • Annex B
  • Bibliography

Introduction

A non-exhaustive list of potential applications of products described in this document:

  • upstream microbiological control ahead of water softeners, or treatment processes which remove a residual disinfectant (e.g. activated carbon);
  • within commercial drinks dispensers as a final polishing/assurance stage;
  • as a point of entry system where the municipal supply may be at risk of recontamination within distribution or interruption of sufficient disinfection at source;
  • Legionella control in hot water loops.

oSIST prEN 18380:2026 prEN 18380:2026 (E)

1 Scope

This document specifies definitions, principles of construction, requirements and methods for testing the performance of UV devices (240 nm to 290 nm nominal) for potable water installations according to EN 806-2 which are permanently connected to the building’s supply. Devices described by this document can be installed at the point of entry (POE), within the water distribution system inside the building or at the point of use (POU). Additionally, the devices described in this document can be used in mobile or temporary potable water installations, where the system is not permanently connected to a water supply. UV devices in the sense of this document are UV bactericidal treatment devices or UV disinfection devices for one of three specified water qualities, determined by the observed UV transmittance. Devices can be standalone, integrated into a larger appliance or part of multi-staged treatment process. The document relates solely to the performance of the UV reactor.

2 Normative references

The following documents are referred to in the text in such a way that some or all of their content constitutes requirements of this document. For dated references, only the edition cited applies. For undated references, the latest edition of the referenced document (including any amendments) applies. EN 10253 (all parts), Butt-welding pipe fittings

3 Terms and definitions

For the purposes of this document, the following terms and definitions apply. ISO and IEC maintain terminology databases for use in standardization at the following addresses:

  • ISO Online browsing platform: available at https://www.iso.org/obp/
  • IEC Electropedia: available at https://www.electropedia.org/

3.1 absorption

reduction in radiant energy or power, including transformation to other forms, e.g. heat, chemical, as a ray passes through or impinges upon a material Note 1 to entry: Expressed in J or W, as appropriate.

3.2 irradiance

measure of the UV light flux divided by the area that intercepts the radiation Note 1 to entry: The irradiance measured in UV disinfection devices by the UV device sensor is mainly influenced by the lamp output, the transmittance of the water, scaling/fouling of the protective window, and the position of the lamp(s) and sensor in the radiation chamber.

Note 2 to entry: Expressed in W/m .

oSIST prEN 18380:2026 prEN 18380:2026 (E)

3.3 disinfection

action of killing or inactivating relevant bacteria, viruses, and spores to a specified degree of at least 99,99 % using a UV disinfection device Note 1 to entry: Verification of reduction rates is done by biodosimetric testing on surrogate microbes.

3.4 fluence

dose, product of irradiance and exposure time Note 1 to entry: Fluence is the correct term from a strictly scientific point of view.

Note 2 to entry: Fluence is expressed in J/m .

3.5 reduction equivalent fluence

REF average germicidal fluence measured using the biodosimeter

Note 1 to entry: Expressed in J/m .

Note 2 to entry: Use of a low pressure mercury discharge lamp as reference gives a value for a relative exposure at 254 nm; REF (254 nm).

3.6 radiation chamber

part of the device that comprises the radiation zone and the connecting pipes, though which the water to be treated flows

3.7 radiation zone

part of the radiation chamber whose volume is used for the calculation of the fluence

3.8 exposure time

volumetric mean time interval during which a specific volume of water within the radiation zone is exposed to the radiation 3.9 microbial dosimeter; biodosimeter, surrogate test microbe used to determine the reduction equivalent fluence, whose UV inactivation behaviour has been determined in a standard collimated beam apparatus Note 1 to entry: In the case of this document, MS2 phage (ATCC 15597-B1).

3.10 minimum irradiance

UV sensor value determined in the type test that ensures the required reduction equivalent fluence at a defined water flow rate and at a defined UV transmittance value

Note 1 to entry: Expressed in W/m .

oSIST prEN 18380:2026 prEN 18380:2026 (E)

3.11 flow rate

Q volume of water per unit time flowing through the UV device

Note 1 to entry: Expressed in l/min or m /h.

3.12 maximum flow rate

Q max highest flow at which, at a defined UV transmittance of the water and a defined irradiance, the required reduction equivalent fluence can be guaranteed

Note 1 to entry: Expressed in l/min or m /h.

3.13 permissible operation range

those limit values for the operation parameters (irradiance at the sensor or UV transmittance of the water) and flow rate where adequate bactericidal treatment or disinfection is assured

3.14 sensor

system for the measurement of the relative irradiance in UV disinfection devices Note 1 to entry: A relative signal may be used and calibration to an absolute irradiance [W m-2] is not required.

3.15 attenuation

total reduction in transmission (absorption and scattering) of radiation passing through an optical medium in a specific direction

3.16 lamp service life

service life of a UV LED unit after which the emission that is necessary to guarantee the minimum fluence can no longer be reached under the mode of operation given by the manufacturer

3.17 UV LED unit

grouped UV LEDs which produces UV light

3.18 UV LED device

general expression for products using UV light to irradiate water flow through, with the purpose of inactivating microbes present in the water

3.19 UV LED disinfection device

device designed to disinfect water Note 1 to entry: Category A device.

oSIST prEN 18380:2026 prEN 18380:2026 (E)

3.20 UV LED bactericidal treatment device

device designed for bactericidal water treatment Note 1 to entry: Category B device.

3.21 turbidity

reduction of transmittance of visible wavelengths through a liquid caused by the presence of suspended matter (via scattering or scattering and absorption) Note 1 to entry: Turbidity is not directly related to UV transmittance.

3.22 UV transmittance

% UVT

spectral transmission rate at a wavelength of 254 nm at an optical path length in the medium of 10 mm, in %.

Note 1 to entry: UVT100 is a similar metric, scaled for an optical path length of 100 mm. Note 2 to entry: In general, the UV transmittance includes the influence of scattering and absorption of the medium. The UV transmittance is measured in the unfiltered sample in quartz cuvettes of at least 40 mm at a wavelength of 254 nm in a spectrophotometer and is given in %.

3.23 UV radiation

UV electromagnetic radiation Note 1 to entry: Table 1 shows different wavelengths of UV radiation and their classification:

Table 1 — UV radiation Wavelength Type nm UV-C > 100 ≤ 280 UV-B > 280 ≤ 315 UV-A > 315 ≤ 400 NOTE For bactericidal and disinfection purposes, part of the UV range is used.

3.24 modal peak wavelength

wavelength at which the UV LED device emits its highest intensity radiation Note 1 to entry: I.e. at the peak of a spectral emission curve, expressed in nm.

3.25 spectral full-width half-maximum

FWHM measure of the breadth of an LED emission spectrum, taken as the width of the spectrum, at 50 % of the relative intensity

oSIST prEN 18380:2026 prEN 18380:2026 (E)

3.26 sampling event

action of drawing a sample of the test water from one of the sampling ports or a holding tank, within the biodosimetric testing phase

3.27 measurement point

set of operational conditions under which samples of the test water are drawn; multiple sampling events occur at a single measurement point, within the biodosimetric testing phase

4 Requirements

4.1 General

This document covers two different categories of UV LED devices. The categories differ in terms of their validated fluence delivery, at a specified flow rate and water quality, resulting in differences in the associated microbiological treatment of the water leaving the reactor. Both performance Categories A and B are intended to provide a pathogen barrier and maintain the user’s health, though the degree of treatment varies between the two based on the intent of the application. A distinction is drawn between the two treatment levels as follows:

  • Category A provides disinfection at a fluence known to be sufficient where no primary antimicrobial treatment has been applied upstream; waters of uncertain origin, influence, or where treatment is known not to exist upstream should be treated to this level.
  • Category B provides microbial control at a fluence intended as a secondary or higher treatment stage to water which has otherwise undergone disinfection; water which may be subject to incidental/retrograde contamination in distribution, stagnation, or microbial regrowth after otherwise sufficient disinfection should be treated to this level. This document primarily considers systems whose main function is the treatment of water by UV irradiation and though an integrated system may be considered, the following distinctions hold:
  • Water quality is defined as that which enters the UV disinfection portion of the system, which may not necessarily be the inlet port of a host system to the UV device, and the effect of upstream modifications to the water quality within the system may be considered when defining the UV LED device inlet water quality.
  • Assessment of disinfection/antimicrobial effect will only consider the action of the UV LED device, with no ‘credit’ ascribed to upstream processes.

oSIST prEN 18380:2026 prEN 18380:2026 (E) Table 2 — Categories for different performance claims Category A B Performance Disinfection Microbial Control claim 2 2 Reduction 400 J/m 250 J/m Equivalent Fluence (254 nm) Optical yes yes Sensor Water Quality 70 % to 85 % 85 % to >95 % 70 % to 85 % 85 % to >95 % UV 95 % 95 % transmittance (UVT ) range

Descriptive Raw water with Raw water Very high Treated water with Typical Very high water quality unknown of high quality, an otherwise high municipal quality, microbiological quality or requiring concentration of potable typically quality but having additional dissolved/suspended water municipal without an undergone disinfection material potable obvious source some pre- for water with of treatment exceptional additional contamination conditions treatment at the installation (e.g. Active Carbon, Reverse Osmosis) The water quality descriptions provided here are intended to be descriptive of common use cases, but not at all limiting to the final application.

Determination of the appropriate Category and Water Quality of the UV systems validated to this document for a given applications should be considered based on the provenance of the water and an observed UVT. Selection of the appropriate water quality should be made such that the observed UVT falls within that range, with the test condition representing the worst-case for that range. Since this document considers water of "drinking water quality” (according to [1]), then other parameters not described (e.g. chemical composition, turbidity, etc.) are considered to be sufficiently within range to render the source water potable, except for the potential for microbiological contamination which this document aims to address.

4.2 Material requirements

All components in contact with UV radiation shall be made of corrosion resistant (if applicable) and UV resistant materials. All materials in contact with potable water shall be suitable for that use. NOTE European and national regulation(s) can apply.

oSIST prEN 18380:2026 prEN 18380:2026 (E)

4.3 Hydraulic requirements

All devices shall be equipped with a flow limiter to ensure that the maximum flow rate, as defined by the manufacturer, is not exceeded. The flow limiter shall operate in a pressure range, as described by the manufacturer. Alternately, flow limitation or control may be deferred to a host system to maintain the validated maximum flow rate.

The flow limiter is not subject to the testing-schemes described in this document.

4.4 Mechanical properties

4.4.1 General

The mechanical design and the construction shall comply with the relevant requirements for the pressure range, as specified by the manufacturer.

Direct or indirect leaking of radiation from the radiation chamber to the environment with a wavelength <400 nm shall be avoided.

4.4.2 Resistance to pressure
4.4.2.1 Resistance to hydrostatic pressure

The UV device may be exposed to a hydrostatic pressure of 1,5 times the maximum design pressure or 10 bar, whichever is the higher pressure, for a period of 10 (+2/-0) min without visible damage or leaks.

4.4.2.2 Resistance to cyclic pressure

The UV device shall not fail a cyclic pressure test after less than 5 000 cycles with a pressure cycle frequency of 15 (+2/-1) cycles per minute between 1,5 bar and 1,3 times the maximum design pressure, as specified by the manufacture, show neither visible damage nor leaks (see EN 14743).

4.5 Requirements UV LED units

4.5.1 Radiation

UV spectrum of the device for the purposes of water irradiation shall match that of a typical LED array, with a unimodal peak in the range 240 nm to 290 nm, thus preventing photochemical effects that may result from shorter wavelengths and potential algae growth stimulated by longer wavelengths.

4.5.2 Lifetime

Performance of the UV device is majority governed by the duration for which the UV LED unit is active, and not the installed duration.

Manufacturers may make individual operating lifetime claims based on the performance characteristics and design of the system. Maximum operating hours for the UV LED lamp unit shall be indicated on the type plate and in the manual.

Performance testing shall be conducted on UV-LED devices artificially ‘aged’ according to manufacturers’ specification of end-of-life relative output, see 7.2.6.

4.5.3 Operation

Devices can be validated with different operating points (UVT vs. Q), these shall be verified by the type test accordingly.

oSIST prEN 18380:2026 prEN 18380:2026 (E) Devices that allow operation at dimmed radiant power (e.g. at lower flow rates for the purpose of energy efficiency or life extension), can be used. Such devices shall either have additional operational points within the type test or shall clearly state within the manual and type plate the conditions of this mode which are outside of the validated operating window of the device. Devices intended to be operated in systems with elevated water temperatures (>25 °C) shall specify the maximum acceptable water temperature in the manual and on the type plate. The materials used shall ensure hygiene suitability and mechanical stability of the device for the intended operational temperature range.

4.6 Requirements on electrical equipment

4.6.1 General

Requirements for the electrotechnical design of UV devices are regulated by the relevant EC Directives. The IP rating shall be indicated.

4.6.2 Controller

The UV disinfection device shall be equipped with a controller, which provides the following functions:

  • when water starts to flow, the device shall be switched on immediately upon flow exceeding the stated initialization flow rate; alternately, the device could be in continual operation;
  • operation of the electrical function of UV LED units shall be monitored;
  • total UV LED unit operating hours shall be recorded;
  • operation beyond the permissible limits of operation (UV-intensity too low) shall be indicated and a signal shall be provided which allows the waterflow to be stopped;
  • general malfunction signal shall be provided.

The following functions shall be displayed:

  • device operational: on/off;
  • general malfunction.

Alternatively, the UV disinfection device shall be compatible with the above functionality as supported by a host system, and these functions need not be provided exclusively by the UV disinfection device.

4.6.3 Sensor

For the measurement of irradiation within the device, an optical sensor shall be provided to ensure sufficient fluence delivery under consideration of possible changes in water UV transmittance and UV LED unit performance.

The approach here is to define a minimum UV alarm set point; this shall be set as the UV sensor signal at the challenge UVT of the test and for a UV source artificially aged according to 7.2.6. The alarm shall trigger if the UV sensor reads a value below this threshold, signifying a drop in UV power (below end of life output) or reduction in UVT below the validated range. Therefore, in the majority of conditions (as new LED source, higher UVT) the system shall provide a fluence in excess of the validated minimum. The control system shall be calibrated on the relative irradiance recorded by the sensor. The sensor shall be located in a way that the UV LEDs can be monitored appropriately and is not unduly disturbed by gas bubbles or sediment deposits. The sensor shall be located with the UV source, adjacent, opposite, or otherwise, but shall have sufficient sensitivity to the emissions of the source and be able to sense a change in UVT of the water.

oSIST prEN 18380:2026 prEN 18380:2026 (E) Additional considerations for the UV sensor:

  • the sensitivity range of the sensor should be appropriate to the device as new and under an end of life condition;
  • absolute irradiance calibration of the sensor is not required;
  • absolute sensor signals can therefore differ between devices, with interpretation by a control system accounting for relative response;
  • if a sensor with absolute irradiance calibration is used, then sufficient evidence shall be provided to support the validity and calibration of an absolute irradiance determination;
  • control system should read “100 %” as new, and have sufficient range to show lowest UVT and or UV output in derated modes and or end of life;
  • sensors are typically coupled to the LED array in such a way that if one is required to be replaced that the other is also be replaced, if either or both are replaced the system shall undergo recalibration as initially conducted in device production;
  • the sensor should exhibit a stable response over the lifetime of the product as described by the system manufacturer; not exceeding a +5% increase over that lifetime for an equivalent irradiance.

4.7 Labelling

A type plate with the following minimum information shall be attached to the irradiation chamber:

  • manufacturer;
  • address of the manufacturer;
  • type designation of the UV device;
  • year of manufacture;
  • serial number;
  • category and water quality (according to Table 2);
  • maximum flow rate;
  • pressure rating/operating pressure;
  • maximum operating hours;
  • certification (based on tests by competent laboratories, e.g. according to EN ISO/IEC 17025). The material of the type plate, including the lettering and the fastening, shall be durable and waterproof.

4.8 Assembly and installation description

Installation instructions with all the necessary information for the correct energy connection and for the required control and safety circuits (if applicable).

...