EN 1634-3:2004
(Main)Fire resistance and smoke control tests for door and shutter assemblies, openable windows and elements of building hardware - Part 3: Smoke control test for door and shutter assemblies
Fire resistance and smoke control tests for door and shutter assemblies, openable windows and elements of building hardware - Part 3: Smoke control test for door and shutter assemblies
This Part of EN 1634 specifies a method for determining the leakage of cold and warm smoke from one side of a door assembly to the other under the specified test conditions. The test can be applied to door and shutter assemblies of different types intended for purposes of controlling the passage of smoke in case of fire. This test can also be applied to lift landing doors and conveyor system doors and shutters. The principle of the test is explained briefly in annex A.
Prüfungen zum Feuerwiderstand und zur Rauchdichte für Feuer- und Rauchschutzabschlüsse, Fenster und Beschläge – Teil 3: Prüfungen zur Rauchdichte für Rauchschutzabschlüsse
Essais de résistance au feu et d’étanchéité aux fumées des portes, fermetures, fenêtres et éléments de quincailleries – Partie 3: Essais d’étanchéité aux fumées des portes et fermetures
La présente partie de l'EN 1634 spécifie une méthode permettant d'établir l'étanchéité d'un côté d'un bloc porte à la fumée froide et chaude, dans les conditions d'essai spécifiées. L'essai peut être appliqué à différents types de blocs-portes et de blocs-fermetures destinés à contrôler le passage de la fumée en cas d'incendie. Cet essai peut également être appliqué aux portes palières des ascenseurs et aux portes et fermetures des systèmes de bandes transporteuses. Le principe de l'essai est expliqué brièvement dans l'Annexe A.
Preskusi požarne odpornosti vrat in drugih zapornih sestavov - 3. del: Dimna vrata in zapore
General Information
Relations
Standards Content (Sample)
SLOVENSKI STANDARD
01-maj-2005
Nadomešča:
SIST EN 1634-3:2002
Preskusi požarne odpornosti vrat in drugih zapornih sestavov - 3. del: Dimna vrata
in zapore
Fire resistance and smoke control tests for door and shutter assemblies, openable
windows and elements of building hardware - Part 3: Smoke control test for door and
shutter assemblies
Prüfungen zum Feuerwiderstand und zur Rauchdichte für Feuer- und
Rauchschutzabschlüsse, Fenster und Beschläge – Teil 3: Prüfungen zur Rauchdichte für
Rauchschutzabschlüsse
Essais de résistance au feu et d’étanchéité aux fumées des portes, fermetures, fenetres
et éléments de quincailleries – Partie 3: Essais d’étanchéité aux fumées des portes et
fermetures
Ta slovenski standard je istoveten z: EN 1634-3:2004
ICS:
13.220.50 Požarna odpornost Fire-resistance of building
gradbenih materialov in materials and elements
elementov
91.060.50 Vrata in okna Doors and windows
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.
EUROPEAN STANDARD
EN 1634-3
NORME EUROPÉENNE
EUROPÄISCHE NORM
October 2004
ICS 13.220.50 Supersedes EN 1634-3:2001
English version
Fire resistance tests for door and shutter assemblies - Part 3:
Smoke control doors and shutters
Essais de résistance au feu des portes et fermetures - Feuerwiderstandsprüfungen für Tür- und
Partie 3: Portes et volets pare-fumées Abschlusseinrichtungen - Teil 3: Rauchschutzabschlüsse
This European Standard was approved by CEN on 15 July 2004.
CEN members are bound to comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this European
Standard the status of a national standard without any alteration. Up-to-date lists and bibliographical references concerning such national
standards may be obtained on application to the Central Secretariat or to any CEN member.
This European Standard exists in three official versions (English, French, German). A version in any other language made by translation
under the responsibility of a CEN member into its own language and notified to the Central Secretariat has the same status as the official
versions.
CEN members are the national standards bodies of Austria, Belgium, Cyprus, Czech Republic, Denmark, Estonia, Finland, France,
Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Slovakia,
Slovenia, Spain, Sweden, Switzerland and United Kingdom.
EUROPEAN COMMITTEE FOR STANDARDIZATION
COMITÉ EUROPÉEN DE NORMALISATION
EUROPÄISCHES KOMITEE FÜR NORMUNG
Management Centre: rue de Stassart, 36 B-1050 Brussels
© 2004 CEN All rights of exploitation in any form and by any means reserved Ref. No. EN 1634-3:2004: E
worldwide for CEN national Members.
Contents Page
Foreword. 3
1 Scope. 4
2 Normative references . 4
3 Definitions, symbols and designations . 4
3.1 Terms and definitions. 4
3.2 Symbols and designation . 5
4 Test equipment. 6
4.1 Test apparatus. 6
4.2 Instrumentation . 6
5 Test conditions. 7
6 Test specimen . 7
6.1 Size . 7
6.2 Number. 7
6.3 Design and construction. 7
6.4 Verification. 8
7 Installation of test specimen. 8
8 Conditioning . 8
8.1 Moisture content . 8
8.2 Mechanical conditioning . 8
9 Application of instrumentation. 9
9.1 Thermocouples . 9
9.2 Pressure. 9
9.3 Air flow . 9
10 Test procedure . 9
10.1 Pre-test procedures . 9
10.2 Air leakage test. 10
10.3 Observations . 12
11 Expression of results. 12
11.1 Ambient temperature only test to satisfy S classification . 12
a
11.2 Ambient together with medium temperature tests to satisfy S . 13
m
12 Test report . 14
13 Field of direct application of test results. 14
13.1 General. 14
13.2 Construction of assembly. 15
13.3 Size and aspect ratio . 16
13.4 Glazing . 16
13.5 Hardware and fittings . 16
13.6 Seals. 16
Annex A (informative) Test principle . 17
Annex B (informative) Test apparatus . 18
Foreword
This document (EN 1634-3:2004) has been prepared by Technical Committee CEN/TC 127 “Fire
Safety in Buildings”, the secretariat of which is held by BSI.
This European Standard shall be given the status of a national standard, either by publication of an
identical text or by endorsement, at the latest by April 2005, and conflicting national standards shall
be withdrawn at the latest by April 2005.
This document has been prepared under mandate given to CEN by the European Commission and
the European Free Trade Association, and supports essential requirements of the Construction
Products Directive.
This document supersedes EN 1634-3:2001.
EN 1634 ‘Fire resistance tests for door and shutter assemblies’ consists of the following:
Part 1: Fire doors and shutters,
Part 2: Fire door hardware - Building hardware for fire resisting doorsets and openable windows (in
course of preparation),
Part 3: Smoke control doors and shutters.
According to the CEN/CENELEC Internal Regulations, the national standards organizations of the
following countries are bound to implement this European Standard: Austria, Belgium, Cyprus, Czech
Republic, Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy,
Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Slovakia, Slovenia,
Spain, Sweden, Switzerland and United Kingdom.
Caution
The attention of all persons concerned with managing and carrying out this test is drawn to the
following. Mechanical and operation hazards may arise during the construction of the test elements or
structures, their testing and disposal of test residues. An assessment of all potential hazards and risks
to health should be made and safety precautions should be identified and provided. Written safety
instructions should be issued. Appropriate training should be given to relevant personnel.
Laboratory personnel should ensure that they follow written safety instructions at all times.
1 Scope
This Part of EN 1634 specifies a method for determining the leakage of cold and warm smoke from
one side of a door assembly to the other under the specified test conditions. The test can be applied
to door and shutter assemblies of different types intended for purposes of controlling the passage of
smoke in case of fire. This test can also be applied to lift landing doors and conveyor system doors
and shutters. The principle of the test is explained briefly in annex A.
2 Normative references
The following referenced documents are indispensable for the application of this document. For dated
references, only the edition cited applies. For undated references, the latest edition of the referenced
document (including any amendments) applies.
EN 1363-1:1999, Fire resistance tests — Part 1: General requirements
EN 1634-1:2000, Fire resistance tests for door and shutter assemblies — Part 1: Fire doors and
shutters
EN 13501-2:2003, Fire classification of construction products and building elements — Part 2:
Classification using data from fire resistance tests, excluding ventilation services
prEN 14600, Fire resisting and/or smoke control doorsets and operable windows - Requirements and
classification
EN ISO 13943:2000, Fire safety — Vocabulary (ISO 13943:2000)
3 Definitions, symbols and designations
3.1 Terms and definitions
For the purposes of this document, the terms and definitions given in EN 1363-1:1999, EN 1634-
1:2000 and EN ISO 13943:2000, together with the following, apply:
3.1.1
smoke control door
door assembly which has the function of restricting the passage of smoke, when in a closed position,
to prescribed limits
3.1.2
ambient temperature
for the purpose of this standard ambient temperature is an air temperature of (20 ± 10) °C
3.1.3
medium temperature
for the purpose of this standard medium temperature is an air temperature of (200 ± 20) °C
3.1.4
smoke leakage Sa
ambient temperature smoke leakage classification as defined in 7.5.6.3.1 of EN 13501-2:2003
3.1.5
smoke leakage Sm
o
ambient plus medium temperature (200 C) smoke leakage classification as defined in 7.5.6.3.1 of
EN 13501-2:2003
3.1.6
test specimen
door or shutter assembly on which leakage measurements are to be made. It includes all the
components necessary for the use of the door when installed in a building e.g. side panels and over
panels
3.1.7
associated construction
specific form of construction in which the test specimen is mounted which is identical to that into which
the door or shutter assembly is designed to be installed in practice. The method of sealing the joint
between the test specimen and the associated construction is specific to that construction and forms
part of the construction being evaluated by the test
3.1.8
supporting construction
form of construction with adequate strength and stiffness which is used to support the test specimen
and to fill up the difference between the size of the test specimen and the opening in the test frame in
an impermeable manner. The seal between the test specimen and the supporting construction should
be impermeable and withstand the test temperature and is part of the test. The test frame may be
considered to be part of the supporting construction
3.1.9
test specimen leakage rate Q
spec
leakage through the test specimen (3.1.6) and seal between that and the test frame or any
supporting/associated construction used
...
SLOVENSKI STANDARD
01-maj-2005
1DGRPHãþD
SIST EN 1634-3:2002
Preskusi požarne odpornosti vrat in drugih zapornih sestavov - 3. del: Dimna vrata
in zapore
Fire resistance and smoke control tests for door and shutter assemblies, openable
windows and elements of building hardware - Part 3: Smoke control test for door and
shutter assemblies
Prüfungen zum Feuerwiderstand und zur Rauchdichte für Feuer- und
Rauchschutzabschlüsse, Fenster und Beschläge – Teil 3: Prüfungen zur Rauchdichte für
Rauchschutzabschlüsse
Essais de résistance au feu et d’étanchéité aux fumées des portes, fermetures, fenetres
et éléments de quincailleries – Partie 3: Essais d’étanchéité aux fumées des portes et
fermetures
Ta slovenski standard je istoveten z: EN 1634-3:2004
ICS:
13.220.50 Požarna odpornost Fire-resistance of building
gradbenih materialov in materials and elements
elementov
91.060.50 Vrata in okna Doors and windows
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.
EUROPEAN STANDARD
EN 1634-3
NORME EUROPÉENNE
EUROPÄISCHE NORM
October 2004
ICS 13.220.50 Supersedes EN 1634-3:2001
English version
Fire resistance tests for door and shutter assemblies - Part 3:
Smoke control doors and shutters
Essais de résistance au feu des portes et fermetures - Feuerwiderstandsprüfungen für Tür- und
Partie 3: Portes et volets pare-fumées Abschlusseinrichtungen - Teil 3: Rauchschutzabschlüsse
This European Standard was approved by CEN on 15 July 2004.
CEN members are bound to comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for giving this European
Standard the status of a national standard without any alteration. Up-to-date lists and bibliographical references concerning such national
standards may be obtained on application to the Central Secretariat or to any CEN member.
This European Standard exists in three official versions (English, French, German). A version in any other language made by translation
under the responsibility of a CEN member into its own language and notified to the Central Secretariat has the same status as the official
versions.
CEN members are the national standards bodies of Austria, Belgium, Cyprus, Czech Republic, Denmark, Estonia, Finland, France,
Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Slovakia,
Slovenia, Spain, Sweden, Switzerland and United Kingdom.
EUROPEAN COMMITTEE FOR STANDARDIZATION
COMITÉ EUROPÉEN DE NORMALISATION
EUROPÄISCHES KOMITEE FÜR NORMUNG
Management Centre: rue de Stassart, 36 B-1050 Brussels
© 2004 CEN All rights of exploitation in any form and by any means reserved Ref. No. EN 1634-3:2004: E
worldwide for CEN national Members.
Contents Page
Foreword. 3
1 Scope. 4
2 Normative references . 4
3 Definitions, symbols and designations . 4
3.1 Terms and definitions. 4
3.2 Symbols and designation . 5
4 Test equipment. 6
4.1 Test apparatus. 6
4.2 Instrumentation . 6
5 Test conditions. 7
6 Test specimen . 7
6.1 Size . 7
6.2 Number. 7
6.3 Design and construction. 7
6.4 Verification. 8
7 Installation of test specimen. 8
8 Conditioning . 8
8.1 Moisture content . 8
8.2 Mechanical conditioning . 8
9 Application of instrumentation. 9
9.1 Thermocouples . 9
9.2 Pressure. 9
9.3 Air flow . 9
10 Test procedure . 9
10.1 Pre-test procedures . 9
10.2 Air leakage test. 10
10.3 Observations . 12
11 Expression of results. 12
11.1 Ambient temperature only test to satisfy S classification . 12
a
11.2 Ambient together with medium temperature tests to satisfy S . 13
m
12 Test report . 14
13 Field of direct application of test results. 14
13.1 General. 14
13.2 Construction of assembly. 15
13.3 Size and aspect ratio . 16
13.4 Glazing . 16
13.5 Hardware and fittings . 16
13.6 Seals. 16
Annex A (informative) Test principle . 17
Annex B (informative) Test apparatus . 18
Foreword
This document (EN 1634-3:2004) has been prepared by Technical Committee CEN/TC 127 “Fire
Safety in Buildings”, the secretariat of which is held by BSI.
This European Standard shall be given the status of a national standard, either by publication of an
identical text or by endorsement, at the latest by April 2005, and conflicting national standards shall
be withdrawn at the latest by April 2005.
This document has been prepared under mandate given to CEN by the European Commission and
the European Free Trade Association, and supports essential requirements of the Construction
Products Directive.
This document supersedes EN 1634-3:2001.
EN 1634 ‘Fire resistance tests for door and shutter assemblies’ consists of the following:
Part 1: Fire doors and shutters,
Part 2: Fire door hardware - Building hardware for fire resisting doorsets and openable windows (in
course of preparation),
Part 3: Smoke control doors and shutters.
According to the CEN/CENELEC Internal Regulations, the national standards organizations of the
following countries are bound to implement this European Standard: Austria, Belgium, Cyprus, Czech
Republic, Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy,
Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Slovakia, Slovenia,
Spain, Sweden, Switzerland and United Kingdom.
Caution
The attention of all persons concerned with managing and carrying out this test is drawn to the
following. Mechanical and operation hazards may arise during the construction of the test elements or
structures, their testing and disposal of test residues. An assessment of all potential hazards and risks
to health should be made and safety precautions should be identified and provided. Written safety
instructions should be issued. Appropriate training should be given to relevant personnel.
Laboratory personnel should ensure that they follow written safety instructions at all times.
1 Scope
This Part of EN 1634 specifies a method for determining the leakage of cold and warm smoke from
one side of a door assembly to the other under the specified test conditions. The test can be applied
to door and shutter assemblies of different types intended for purposes of controlling the passage of
smoke in case of fire. This test can also be applied to lift landing doors and conveyor system doors
and shutters. The principle of the test is explained briefly in annex A.
2 Normative references
The following referenced documents are indispensable for the application of this document. For dated
references, only the edition cited applies. For undated references, the latest edition of the referenced
document (including any amendments) applies.
EN 1363-1:1999, Fire resistance tests — Part 1: General requirements
EN 1634-1:2000, Fire resistance tests for door and shutter assemblies — Part 1: Fire doors and
shutters
EN 13501-2:2003, Fire classification of construction products and building elements — Part 2:
Classification using data from fire resistance tests, excluding ventilation services
prEN 14600, Fire resisting and/or smoke control doorsets and operable windows - Requirements and
classification
EN ISO 13943:2000, Fire safety — Vocabulary (ISO 13943:2000)
3 Definitions, symbols and designations
3.1 Terms and definitions
For the purposes of this document, the terms and definitions given in EN 1363-1:1999, EN 1634-
1:2000 and EN ISO 13943:2000, together with the following, apply:
3.1.1
smoke control door
door assembly which has the function of restricting the passage of smoke, when in a closed position,
to prescribed limits
3.1.2
ambient temperature
for the purpose of this standard ambient temperature is an air temperature of (20 ± 10) °C
3.1.3
medium temperature
for the purpose of this standard medium temperature is an air temperature of (200 ± 20) °C
3.1.4
smoke leakage Sa
ambient temperature smoke leakage classification as defined in 7.5.6.3.1 of EN 13501-2:2003
3.1.5
smoke leakage Sm
o
ambient plus medium temperature (200 C) smoke leakage classification as defined in 7.5.6.3.1 of
EN 13501-2:2003
3.1.6
test specimen
door or shutter assembly on which leakage measurements are to be made. It includes all the
components necessary for the use of the door when installed in a building e.g. side panels and over
panels
3.1.7
associated construction
specific form of construction in which the test specimen is mounted which is identical to that into which
the door or shutter assembly is designed to be installed in practice. The method of sealing the joint
between the test specimen and the associated construction is specific to that construction and forms
part of the construction being evaluated by the test
3.1.8
supporting construction
form of construction with adequate strength and stiffness which is used to support the test specimen
and to fill up the difference between the size of the test specimen and the opening in the test frame in
an impermeable manner. The seal between the test specimen and the supporting construction should
be impermeable and withstand the test temperature and is part of the test. The test frame may be
considered to be part of the supporting construction
3.1.9
test specimen leakage rate Q
spec
leakage through the test specimen (3.1.6) and seal between that and the test frame or any
supporting/associated construct
...
Questions, Comments and Discussion
Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.