Standard Specification for Coextruded Poly(Vinyl Chloride) (PVC) Plastic Pipe With a Cellular Core

ABSTRACT
This specification covers coextruded poly(vinyl chloride) plastic pipe with a cellular core and concentric inner and outer solid layers. The pipe is produced using a multilayer coextrusion die for nonpressure use in three series: an IPS Schedule 40 series; a PS series with an iron pipe size outside diameter with varying wall thickness as required for pipe stiffness of 25, 50, and 100; and a sewer and drain series. The pipe shall comply with the minimum wall thickness, outside diameter, length, stiffness, flattening, impact strength, bond strength, and extrusion quality requirements.
SCOPE
1.1 This specification covers coextruded poly(vinyl chloride) (PVC) plastic pipe with a cellular core and concentric inner and outer solid layers, and is produced using a multilayer coextrusion die for nonpressure use in three series: an IPS Schedule 40 series; a PS series with an iron pipe size outside diameter with varying wall thickness as required for pipe stiffness of 25, 50, and 100; and a sewer and drain series.  
1.2 The function of this specification is to provide standardization of product-technical data and serve as a purchasing guide.  
1.3 The text of this specification references notes, footnotes, and appendixes which provide explanatory material. The notes and footnotes (excluding those in tables and figures) shall not be considered as requirements of the specification.
Note 1—All the pipe series covered by this specification are permitted to be perforated or belled for joining by solvent cement or belled for joining by an elastomeric seal (gasket). Because this pipe is OD controlled, the inside diameter will vary, and therefore, the pipe ID is not suitable for use as a socket. (For more information see Specification D2672.)
Note 2—This standard specifies dimensional, performance and test requirements for plumbing and fluid handling applications, but does not address venting of combustion gases.
1.4 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory limitations prior to use.
1.5 The values stated in inch-pound units are to be regarded as standard. The values given in parentheses are mathematical conversions to SI units that are provided for information only and are not considered standard.
Note 3—Specifications related to this specification are as follows: D2665, D2729, D3034, F512, F758, and F789.

General Information

Status
Historical
Publication Date
30-Apr-2010
Technical Committee
Drafting Committee
Current Stage
Ref Project

Relations

Buy Standard

Technical specification
ASTM F891-10 - Standard Specification for Coextruded Poly(Vinyl Chloride) (PVC) Plastic Pipe With a Cellular Core
English language
9 pages
sale 15% off
Preview
sale 15% off
Preview
Technical specification
REDLINE ASTM F891-10 - Standard Specification for Coextruded Poly(Vinyl Chloride) (PVC) Plastic Pipe With a Cellular Core
English language
9 pages
sale 15% off
Preview
sale 15% off
Preview

Standards Content (Sample)

NOTICE: This standard has either been superseded and replaced by a new version or withdrawn.
Contact ASTM International (www.astm.org) for the latest information
Designation:F891 −10
StandardSpecification for
Coextruded Poly(Vinyl Chloride) (PVC) Plastic Pipe With a
1
Cellular Core
ThisstandardisissuedunderthefixeddesignationF891;thenumberimmediatelyfollowingthedesignationindicatestheyearoforiginal
adoptionor,inthecaseofrevision,theyearoflastrevision.Anumberinparenthesesindicatestheyearoflastreapproval.Asuperscript
epsilon (´) indicates an editorial change since the last revision or reapproval.
NOTE 3—Specifications related to this specification are as follows:
1. Scope*
D2665, D2729, D3034, F512, F758, and F789.
1.1 This specification covers coextruded poly(vinyl chlo-
2. Referenced Documents
ride) (PVC) plastic pipe with a cellular core and concentric
2
innerandoutersolidlayers,andisproducedusingamultilayer
2.1 ASTM Standards:
coextrusion die for nonpressure use in three series: an IPS
D618Practice for Conditioning Plastics for Testing
Schedule 40 series; a PS series with an iron pipe size outside
D1600TerminologyforAbbreviatedTermsRelatingtoPlas-
diameter with varying wall thickness as required for pipe
tics
stiffness of 25, 50, and 100; and a sewer and drain series.
D2122Test Method for Determining Dimensions of Ther-
moplastic Pipe and Fittings
1.2 Thefunctionofthisspecificationistoprovidestandard-
D2152Test Method for Adequacy of Fusion of Extruded
ization of product-technical data and serve as a purchasing
Poly(Vinyl Chloride) (PVC) Pipe and Molded Fittings by
guide.
Acetone Immersion
1.3 Thetextofthisspecificationreferencesnotes,footnotes,
D2321PracticeforUndergroundInstallationofThermoplas-
and appendixes which provide explanatory material.The notes
tic Pipe for Sewers and Other Gravity-Flow Applications
and footnotes (excluding those in tables and figures) shall not
D2412Test Method for Determination of External Loading
be considered as requirements of the specification.
Characteristics of Plastic Pipe by Parallel-Plate Loading
NOTE 1—All the pipe series covered by this specification are permitted
D2444Test Method for Determination of the Impact Resis-
to be perforated or belled for joining by solvent cement or belled for
tance of Thermoplastic Pipe and Fittings by Means of a
joining by an elastomeric seal (gasket). Because this pipe is OD
Tup (Falling Weight)
controlled, the inside diameter will vary, and therefore, the pipe ID is not
D2564Specification for Solvent Cements for Poly(Vinyl
suitable for use as a socket. (For more information see Specification
D2672.) Chloride) (PVC) Plastic Piping Systems
NOTE 2—This standard specifies dimensional, performance and test
D2665Specification for Poly(Vinyl Chloride) (PVC) Plastic
requirements for plumbing and fluid handling applications, but does not
Drain, Waste, and Vent Pipe and Fittings
address venting of combustion gases.
D2672Specification for Joints for IPS PVC Pipe Using
1.4 This standard does not purport to address all of the
Solvent Cement
safety concerns, if any, associated with its use. It is the
D2729Specification for Poly(Vinyl Chloride) (PVC) Sewer
responsibility of the user of this standard to establish appro-
Pipe and Fittings
priate safety and health practices and determine the applica-
D2855Practice for Making Solvent-Cemented Joints with
bility of regulatory limitations prior to use.
Poly(Vinyl Chloride) (PVC) Pipe and Fittings
1.5 The values stated in inch-pound units are to be regarded
D3034Specification for Type PSM Poly(Vinyl Chloride)
as standard. The values given in parentheses are mathematical
(PVC) Sewer Pipe and Fittings
conversions to SI units that are provided for information only
D3212Specification for Joints for Drain and Sewer Plastic
and are not considered standard.
Pipes Using Flexible Elastomeric Seals
D3311Specification for Drain, Waste, and Vent (DWV)
Plastic Fittings Patterns
D4396Specification for Rigid Poly(Vinyl Chloride) (PVC)
and Chlorinated Poly(Vinyl Chloride) (CPVC) Com-
pounds for Plastic Pipe and Fittings Used in Nonpressure
1
This specification is under the jurisdiction ofASTM Committee F17 on Plastic
Piping Systems and is the direct responsibility of Subcommittee F17.25 on Vinyl
2
Based Pipe. For referenced ASTM standards, visit the ASTM website, www.astm.org, or
Current edition approved May 1, 2010. Published June 2010. Originally contact ASTM Customer Service at service@astm.org. For Annual Book of ASTM
approved in 1985. Last previous edition approved in 2009 as F891–09. DOI: Standards volume information, refer to the standard’s Document Summary page on
10.1520/F0891-10. the ASTM website.
*A Summary of Changes section appears at the end of this standard
Copyright © ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959. United States
1

---------------------- Page: 1 ----------------------
F891−10
3
Applications (Withdrawn 2015) 3.3.2 IPS Schedule 40 Series—pipeproducedtoanironpipe
F4
...

This document is not anASTM standard and is intended only to provide the user of anASTM standard an indication of what changes have been made to the previous version. Because
it may not be technically possible to adequately depict all changes accurately, ASTM recommends that users consult prior editions as appropriate. In all cases only the current version
of the standard as published by ASTM is to be considered the official document.
An American National Standard
Designation:F891–09 Designation: F891 – 10
Standard Specification for
Coextruded Poly(Vinyl Chloride) (PVC) Plastic Pipe With a
1
Cellular Core
ThisstandardisissuedunderthefixeddesignationF891;thenumberimmediatelyfollowingthedesignationindicatestheyearoforiginal
adoptionor,inthecaseofrevision,theyearoflastrevision.Anumberinparenthesesindicatestheyearoflastreapproval.Asuperscript
epsilon (´) indicates an editorial change since the last revision or reapproval.
1. Scope*
1.1 This specification covers coextruded poly(vinyl chloride) (PVC) plastic pipe with a cellular core and concentric inner and
outersolidlayers,andisproducedusingamultilayercoextrusiondiefornonpressureuseinthreeseries:anIPSSchedule40series;
a PS series with an iron pipe size outside diameter with varying wall thickness as required for pipe stiffness of 25, 50, and 100;
and a sewer and drain series.
1.2 The function of this specification is to provide standardization of product-technical data and serve as a purchasing guide.
1.3 Thetextofthisspecificationreferencesnotes,footnotes,andappendixeswhichprovideexplanatorymaterial.Thenotesand
footnotes (excluding those in tables and figures) shall not be considered as requirements of the specification.
NOTE 1—All the pipe series covered by this specification are permitted to be perforated or belled for joining by solvent cement or belled for joining
by an elastomeric seal (gasket). Because this pipe is OD controlled, the inside diameter will vary, and therefore, the pipe ID is not suitable for use as
a socket. (For more information see Specification D2672.)
NOTE 2—This standard specifies dimensional, performance and test requirements for plumbing and fluid handling applications, but does not address
venting of combustion gases.
1.4 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility
of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory
limitations prior to use.
1.5 The values stated in inch-pound units are to be regarded as standard. The values given in parentheses are mathematical
conversions to SI units that are provided for information only and are not considered standard.
1
This specification is under the jurisdiction ofASTM Committee F17 on Plastic Piping Systems and is the direct responsibility of Subcommittee F17.25 on Vinyl Based
Pipe.
Current edition approved Aug. 15, 2009. Published August 2009. Originally approved in 1985. Last previous edition approved in 2007 as F891–07. DOI:
10.1520/F0891-09.
Current edition approved May 1, 2010. Published June 2010. Originally approved in 1985. Last previous edition approved in 2009 as F891–09. DOI: 10.1520/F0891-10.
*A Summary of Changes section appears at the end of this standard.
Copyright © ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959, United States.
1

---------------------- Page: 1 ----------------------
F891 – 10
NOTE 3—Specifications related to this specification are as follows: D2665, D2729, D3034, F512, F758, and F789.
2. Referenced Documents
2
2.1 ASTM Standards:
D618 Practice for Conditioning Plastics for Testing
D1600 Terminology for Abbreviated Terms Relating to Plastics
D2122 Test Method for Determining Dimensions of Thermoplastic Pipe and Fittings
D2152 Test Method for Adequacy of Fusion of Extruded Poly(Vinyl Chloride) (PVC) Pipe and Molded Fittings by Acetone
Immersion
D2321 Practice for Underground Installation of Thermoplastic Pipe for Sewers and Other Gravity-Flow Applications
D2412 Test Method for Determination of External Loading Characteristics of Plastic Pipe by Parallel-Plate Loading
D2444 TestMethodforDeterminationoftheImpactResistanceofThermoplasticPipeandFittingsbyMeansofaTup(Falling
Weight)
D2564 Specification for Solvent Cements for Poly(Vinyl Chloride) (PVC) Plastic Piping Systems
D2665 Specification for Poly(Vinyl Chloride) (PVC) Plastic Drain, Waste, and Vent Pipe and Fittings
D2672
D2672 Specification for Joints for IPS PVC Pipe Using Solvent Cement
D2729 Specification for Poly(Vinyl Chloride) (PVC) Sewer Pipe and Fittings
D2855 Practice for Making Solvent-Cemented Joints with Poly(Vinyl Chloride) (PVC) Pipe and Fittings
D3034 Specification for Type PSM Poly(Vinyl Chloride) (PVC) Sewer Pipe and Fittings
D3212 Specification for Joints for Drain and Sewer Plastic Pipes Using Flexible Elastomeric Seals
D3311 Specification for Drain, Waste, and Vent (DWV) Plastic Fittings Patterns
D4396 Sp
...