Standard Practice for On-Site Inspection of Installed Fire Stops

SIGNIFICANCE AND USE
This practice is intended to provide a standard set of guidelines that are to be followed when conducting and reporting on inspections of installed fire stops.
This practice is intended to provide a means to verify compliance of the installed fire stops to the inspection documents.
This practice is not intended to provide a basis for selecting installers or products or both.
This practice is not intended to establish any performance criteria of the inspected fire stops.
SCOPE
1.1 This practice covers the establishing of procedures to inspect fire stops, including methods for field verification and inspection.
1.2 This practice addresses all types of fire stops installed through or into fire resistive assemblies.
Note 1—Fire stop is defined in Test Method E814.
1.3 This practice provides methods by which qualified inspectors verify that required fire stops on a project have been installed and that their installations are in accordance with the inspection documents.
1.4 The values stated in inch-pound units are to be regarded as standard. The values given in parentheses are mathematical conversions to SI units that are provided for information only and are not considered standard.
1.5 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory limitations prior to use.
1.6 The text of this standard references notes and footnotes that provide explanatory material. These notes and footnotes (excluding those in tables and figures) shall not be considered as requirements of the standard.

General Information

Status
Historical
Publication Date
14-Feb-2010
Technical Committee
Drafting Committee
Current Stage
Ref Project

Relations

Buy Standard

Standard
ASTM E2174-10 - Standard Practice for On-Site Inspection of Installed Fire Stops
English language
6 pages
sale 15% off
Preview
sale 15% off
Preview
Standard
REDLINE ASTM E2174-10 - Standard Practice for On-Site Inspection of Installed Fire Stops
English language
6 pages
sale 15% off
Preview
sale 15% off
Preview

Standards Content (Sample)

NOTICE: This standard has either been superseded and replaced by a new version or withdrawn.
Contact ASTM International (www.astm.org) for the latest information
Designation:E2174–10
Standard Practice for
1
On-Site Inspection of Installed Fire Stops
This standard is issued under the fixed designation E2174; the number immediately following the designation indicates the year of
original adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. A
superscript epsilon (´) indicates an editorial change since the last revision or reapproval.
3
1. Scope 2.2 Other Standards:
UL 1479-94 Fire Tests of Through-Penetration Fire Stops
1.1 This practice covers the establishing of procedures to
4
2.3 Other Documents:
inspect fire stops, including methods for field verification and
International Building Code
inspection.
1.2 This practice addresses all types of fire stops installed
3. Terminology
through or into fire resistive assemblies.
3.1 Definitions—Terms defined in Terminology E631, Ter-
NOTE 1—Fire stop is defined in Test Method E814.
minology E176, and Practice E699 will prevail for terms not
defined in this document.
1.3 This practice provides methods by which qualified
inspectors verify that required fire stops on a project have been 3.2 Definitions of Terms Specific to This Standard:
3.2.1 authorizing authority (AA)—the designated person, or
installed and that their installations are in accordance with the
inspection documents. organization, or their duly authorized representative, charged
with the administration and enforcement of the provisions of
1.4 The values stated in inch-pound units are to be regarded
as standard. The values given in parentheses are mathematical this inspection document.
conversions to SI units that are provided for information only
NOTE 2—Examples of the AA include the responsible architect, engi-
and are not considered standard.
neer, building owner, or their representative.
1.5 This standard does not purport to address all of the
3.2.2 authority having jurisdiction (AHJ)—the designated
safety concerns, if any, associated with its use. It is the
authority, or their duly authorized representative, charged with
responsibility of the user of this standard to establish appro-
the administration and enforcement of the local fire code or
priate safety and health practices and determine the applica-
building code, or both.
bility of regulatory limitations prior to use.
3.2.3 accredited testing laboratory—a company engaged in
1.6 The text of this standard references notes and footnotes
conducting testing and possesses a valid evaluation report for
that provide explanatory material. These notes and footnotes
testing services and is recognized by the AHJ.
(excluding those in tables and figures) shall not be considered
3.2.4 evaluation report—an approved document issued by
as requirements of the standard.
the Model Code Body Evaluation Service or by the AHJ.
3.2.5 inspection document—any information provided to
2. Referenced Documents
the inspector by the AA that is to be used as the basis for the
2
2.1 ASTM Standards:
inspection process. This information shall include, but is not
E176 Terminology of Fire Standards
limited to, project specifications, contract drawings, Listed
E631 Terminology of Building Constructions
Designs, judgments, manufacturer’s instructions and designs,
E699 Practice for Evaluation of Agencies Involved in Test-
building codes, and other documentation.
ing, Quality Assurance, and Evaluating of Building Com-
ponents NOTE 3—Theapprovedfirestopsubmittalshouldhavesufficientdetails
including the fire stop manufacturer’s product data, a design listing of the
E814 Test Method for Fire Tests of Penetration Firestop
tested fire stop or the engineering judgment design with illustrated
Systems
drawings or descriptive text or both for the purpose of verifying each
installation and conducting the field-inspection procedures.
1
3.2.6 inspection form—the document contained in this stan-
This practice is under the jurisdiction of ASTM Committee E06 on Perfor-
mance of Buildings and is the direct responsibility of Subcommittee E06.21 on
dard practice that is used to record information obtained during
Serviceability.
the inspection(s).
Current edition approved Feb. 15, 2010. Published March 2010. Originally
approved in 2001. Last previous edition approved in 2009 as E2174 – 09. DOI:
10.1520/E2174-10.
2 3
For referenced ASTM standards, visit the ASTM website, www.astm.org, or Available from Underwriters Laboratories (UL), Corporate Progress, 333
contact ASTM Customer Service at service@astm.org. For Annual Book of ASTM Pfingsten Rd., Northbrook, IL 60062, http://www.ul.com.
4
Standards volume information, refer to the standard’s Document Summary page on Available from International Code Council (ICC), 500 New Jersey Ave., NW,
the ASTM website. 6th Floor, Washington, DC 20001-2070, http://www.iccsafe.org.
Copyright © ASTM International, 100 Bar
...

This document is not an ASTM standard and is intended only to provide the user of an ASTM standard an indication of what changes have been made to the previous version. Because
it may not be technically possible to adequately depict all changes accurately, ASTM recommends that users consult prior editions as appropriate. In all cases only the current version
of the standard as published by ASTM is to be considered the official document.
Designation:E2174–09 Designation: E2174 – 10
Standard Practice for
1
On-Site Inspection of Installed Fire Stops
This standard is issued under the fixed designation E2174; the number immediately following the designation indicates the year of
original adoption or, in the case of revision, the year of last revision. A number in parentheses indicates the year of last reapproval. A
superscript epsilon (´) indicates an editorial change since the last revision or reapproval.
1. Scope
1.1 This practice covers the establishing of procedures to inspect fire stops, including methods for field verification and
inspection.
1.2 This practice addresses all types of fire stops installed through or into fire resistive assemblies.
NOTE 1—Fire stop is defined in Test Method E814.
1.3 This practice provides methods by which qualified inspectors verify that required fire stops on a project have been installed
and that their installations are in accordance with the inspection documents.
1.4 The values stated in inch-pound units are to be regarded as standard. The values given in parentheses are mathematical
conversions to SI units that are provided for information only and are not considered standard.
1.5 This standard does not purport to address all of the safety concerns, if any, associated with its use. It is the responsibility
of the user of this standard to establish appropriate safety and health practices and determine the applicability of regulatory
limitations prior to use.
1.6 The text of this standard references notes and footnotes that provide explanatory material. These notes and footnotes
(excluding those in tables and figures) shall not be considered as requirements of the standard.
2. Referenced Documents
2
2.1 ASTM Standards:
E176 Terminology of Fire Standards
E631 Terminology of Building Constructions
E699 Practice for Evaluation of Agencies Involved in Testing, Quality Assurance, and Evaluating of Building Components
E814 Test Method for Fire Tests of Penetration Firestop Systems
3
2.2 Other Standards:
UL 1479-94 Fire Tests of Through-Penetration Fire Stops
4
2.3 Other Documents:
International Building Code
3. Terminology
3.1 Definitions—Terms defined in Terminology E631, Terminology E176, and Practice E699 will prevail for terms not defined
in this document.
3.2 Definitions of Terms Specific to This Standard:
3.2.1 authorizing authority (AA)—the designated person, or organization, or their duly authorized representative, charged with
the administration and enforcement of the provisions of this inspection document.
NOTE 2—Examples of the AA include the responsible architect, engineer, building owner, or their representative.
3.2.2 authority having jurisdiction (AHJ)—the designated authority, or their duly authorized representative, charged with the
administration and enforcement of the local fire code or building code, or both.
3.2.3 accredited testing laboratory—a company engaged in conducting testing and possesses a valid evaluation report for
testing services and is recognized by the AHJ.
1
This practice is under the jurisdiction ofASTM Committee E06 on Performance of Buildings and is the direct responsibility of Subcommittee E06.21 on Serviceability.
Current edition approved May 1, 2009. Published July 2009. Originally approved in 2001. Last previous edition approved in 2004 as E2174–04. DOI: 10.1520/E2174-09.
Current edition approved Feb. 15, 2010. Published March 2010. Originally approved in 2001. Last previous edition approved in 2009 as E2174 – 09. DOI:
10.1520/E2174-10.
2
For referencedASTM standards, visit theASTM website, www.astm.org, or contactASTM Customer Service at service@astm.org. For Annual Book of ASTM Standards
volume information, refer to the standard’s Document Summary page on the ASTM website.
3
Available from Underwriters Laboratories (UL), Corporate Progress, 333 Pfingsten Rd., Northbrook, IL 60062, http://www.ul.com.
4
Available from International Code Council (ICC), 500 New Jersey Ave., NW, 6th Floor, Washington, DC 20001-2070, http://www.iccsafe.org.
Copyright © ASTM International, 100 Barr Harbor Drive, PO Box C700, West Conshohocken, PA 19428-2959, United States.
1

---------------------- Page: 1 ----------------------
E2174 – 10
3.2.4 evaluation report—an approved document issued by the Model Code Body Evaluation Service or by the AHJ.
3.2.5 inspection document—anyinformationprovidedtotheinspectorbytheAAthatistobeusedasthebasisfortheinspection
process. This information shall include, but is not limited to, project specifications, contract drawings, Listed Desi
...