Abstract

The present document applies to monitoring of power and cooling systems for telecommunication installations and equipment. This part 2 is the data description of DC power systems equipment. It provides the information tables, the DTD description and XML files. This description is based on generic recommendation of part 1 core document.

Status
Published
Publication Date
09-Jun-2009
Current Stage
6060 - National Implementation/Publication (Adopted Project)
Start Date
11-May-2009
Due Date
16-Jul-2009
Completion Date
10-Jun-2009

Buy Documents

Standard

ETSI ES 202 336-2 V1.1.1 (2009-01) - Environmental Engineering (EE); Monitoring and control interface for infrastructure equipment (Power, Cooling and environment systems used in telecommunication networks); Part 2: DC power system control and monitoring information model

English language (25 pages)
sale 15% off
Preview
sale 15% off
Preview
Standard

ETSI ES 202 336-2 V1.1.1 (2009-03) - Environmental Engineering (EE); Monitoring and control interface for infrastructure equipment (Power, Cooling and environment systems used in telecommunication networks); Part 2: DC power system control and monitoring information model

English language (26 pages)
sale 15% off
Preview
sale 15% off
Preview
Standardization document

SIST ES 202 336-2 V1.1.1:2009

English language (26 pages)
Preview
Preview
e-Library read for
×1 day

SIST ES 202 336-2 V1.1.1:2009 is the Slovenian adoption of ETSI ES 202 336-2 V1.1.1. It specifies the monitoring and control information model for DC power supply systems used in telecommunication equipment, including the data tables and XML structure used at the interface. It is meant for people who need a common way to supervise rectifiers, batteries, alarms, measurements, configuration, and control actions.

What does SIST ES 202 336-2 V1.1.1:2009 specify?

SIST ES 202 336-2 V1.1.1:2009 covers monitoring and control of DC power supply systems for telecommunication equipment. It defines the DC power system architectures that are covered, the minimum information exchanged at the interface, and the XML files that carry that information.

The document is organized around a short core and a set of annexes. Clause 1 gives the scope, clause 2 lists references, clause 3 defines terms and abbreviations, and clause 4 describes the DC power supply system model. The annexes separate mandatory content, optional content, and XML coding guidance.

AnnexWhat it covers
Annex AMandatory monitoring and supervision information and functions
Annex BNon-mandatory monitoring and supervision information and functions
Annex CMandatory XML structure and elements
Annex DExamples of XML elements for a DC power supply system
Annex EBibliography

What are the key requirements of SIST ES 202 336-2 V1.1.1:2009?

Clause 4 defines the DC system model and its place in the wider interface

SIST ES 202 336-2 V1.1.1:2009 treats the DC system as part of the Environmental Engineering interface family defined in Part 1. The DC system converts AC input to DC output for telecommunication sites, and it may include rectifiers, batteries, protection and distribution, and a system monitoring and control unit called the XCU. In practice, this tells implementers what equipment states, measurements, and commands must be exposed to remote supervision.

Clause 4 also notes that one XCU can monitor several power cabinets through a field bus, but the field bus itself is outside the scope of this part. That matters when designing the boundary between the local equipment and the management interface.

Annex A defines the mandatory information to be provided

Annex A is the mandatory set. For a DC power supply system without back-up, the required information includes a device description, at least one rectifier failure alarm, and a partial network failure indication, together with control functions such as program download with fallback to the previous release and reset to safe defaults.

For a DC power supply system with back-up, Annex A expands the mandatory set to cover protective devices, battery discharge, battery test failure, output low voltage, battery over-temperature, rectifier failures, mains failure, XCU reset, configuration changes, operating mode changes, measured DC voltage and currents, battery temperature, time-stamped data records, and control functions. In practice, this means the interface must support both fault reporting and the values needed to understand battery and load behavior.

Annex B adds optional information that improves supervision

Annex B lists non-mandatory data that may be provided in addition to the mandatory set. For systems without back-up, this includes dying gasp, DC bus voltage, load current, input energy consumption, power capacity management, and additive records for energy and power.

For systems with back-up, Annex B adds items such as unbalanced charge and discharge currents, unbalanced cell voltage, battery asymmetry, output overload, high output voltage, low voltage disconnect status, over-charge, mains outside input limits, battery replacement need, float voltage out of limits, earth leakage detection, battery age, estimated remaining autonomy, and battery capacity. In practice, these items support deeper diagnostics, battery health tracking, and energy reporting.

Annex B also separates data, data records, config, and control for the rectifier module. That helps vendors and operators decide which values are live measurements, which are historical records, and which are adjustable settings.

Annex C standardizes the XML structure

Annex C defines the XML organization for DC power supply data. A DC system appears as a child of a site energy system, and the XML structure groups information into tables for alarms, events, data, data records, config, control, and rectifiers. The annex also shows how a DC system can be delivered as a dc_system.xml document and then embedded in site.xml.

This matters because different products can still exchange data in a consistent way. The annex also introduces the specific element for detailed rectifier information.

Annex D gives examples of how the XML elements are used

Annex D shows example XML fragments for the main element types. It illustrates description elements for manufacturer and serial information, alarm and event elements with timestamps and severity, data elements for values such as bus voltage and load current, config elements for thresholds and operating settings, and control elements for actions such as starting battery test or switching modes.

These examples are practical guidance for software and integration work. They show how to encode the model, not just what the model contains.

What terms does SIST ES 202 336-2 V1.1.1:2009 define?

  • Control Unit (CU) - An integrated unit that monitors and controls equipment through sensors and actuators.
  • Data Gathering Unit (DGU) - A functional unit that collects serial, digital, and analog data and can forward information to management applications.
  • XCU - An XML-enabled Control Unit that communicates through the XML interface defined in this document.
  • Remote Management Application (RMA) - The supervisory application that receives the monitoring information and uses it for remote management.
  • alarm - Information that signals an abnormal state, such as a hardware, software, or environmental fault.
  • event - Information that signals a state change that is not an alarm, such as a battery test or charge-state change.
  • data record - A logged measurement entry, used for history, trends, and records such as voltage or temperature over time.
  • DTD - Document Type Definition, the XML description method used here for structuring the data model.

Who uses SIST ES 202 336-2 V1.1.1:2009?

This standard is used by telecommunication equipment manufacturers, DC power system suppliers, software developers for network management, and system integrators who need to exchange site data in a consistent XML form. It is also relevant to network operators, maintenance teams, and quality or procurement staff responsible for specifying how DC power systems are monitored and controlled.

The standard applies to telecommunication centres and access network locations that use power, cooling, and building environment systems. In practice, it supports remote supervision of rectifiers, batteries, protection devices, power measurements, alarms, and control commands.

Which standards are used with SIST ES 202 336-2 V1.1.1:2009?

  • ETSI ES 202 336-1 - Provides the generic interface framework, the shared element types, and the parameter model used by this part.
  • ETSI EN 300 132-2 - Defines the dc power supply interface at the input to telecommunications equipment.
  • ETSI EN 300 132-3 - Defines the power supply interface for rectified current source, alternating current source, or direct current source up to 400 V.
  • ETSI EN 302 099 - Covers powering of equipment in access networks.
  • ETSI ES 202 336-3 to ETSI ES 202 336-7 - Give the same interface approach for AC UPS, AC distribution, diesel back-up generator, air conditioning, and other utilities systems.

What does the SIST ES 202 336-2 V1.1.1:2009 document contain?

The document contains two system figures showing a simple DC power supply system without battery back-up and a modular DC power supply system with battery back-up. It then provides text tables for mandatory and optional information sets, organized by system type and by element type such as description, alarm, event, data, data record, config, and control.

It also contains XML structure guidance for the site, energy system, DC system, and rectifier elements. Annex D adds example XML fragments for system-level and rectifier-level monitoring, settings, alarms, events, and controls.

For implementers, this means the document is useful for defining the data model, mapping measurements and alarms into XML, and checking what a DC power supervision interface should expose to a remote management system.

Buy Documents

Standard

ETSI ES 202 336-2 V1.1.1 (2009-01) - Environmental Engineering (EE); Monitoring and control interface for infrastructure equipment (Power, Cooling and environment systems used in telecommunication networks); Part 2: DC power system control and monitoring information model

English language (25 pages)
sale 15% off
Preview
sale 15% off
Preview
Standard

ETSI ES 202 336-2 V1.1.1 (2009-03) - Environmental Engineering (EE); Monitoring and control interface for infrastructure equipment (Power, Cooling and environment systems used in telecommunication networks); Part 2: DC power system control and monitoring information model

English language (26 pages)
sale 15% off
Preview
sale 15% off
Preview
Standardization document

SIST ES 202 336-2 V1.1.1:2009

English language (26 pages)
Preview
Preview
e-Library read for
×1 day

Get Certified

Connect with accredited certification bodies for this standard

ANCE

Mexican certification and testing association.

EMA Mexico Verified

IMP NDT d.o.o.

Non-destructive testing services. Radiography, ultrasonic, magnetic particle, penetrant, visual inspection.

SA Slovenia Verified

Inštitut za kovinske materiale in tehnologije

Institute of Metals and Technology. Materials testing, metallurgical analysis, NDT.

SA Slovenia Verified

Sponsored listings

Frequently Asked Questions

SIST ES 202 336-2 V1.1.1:2009 is a standard published by the Slovenian Institute for Standardization (SIST). Its full title is "Environmental Engineering (EE) - Monitoring and control interface for infrastructure equipment (Power, Cooling and environment systems used in telecommunication networks) - Part 2: DC power system control and monitoring information model". This standard covers: The present document applies to monitoring of power and cooling systems for telecommunication installations and equipment. This part 2 is the data description of DC power systems equipment. It provides the information tables, the DTD description and XML files. This description is based on generic recommendation of part 1 core document.

The present document applies to monitoring of power and cooling systems for telecommunication installations and equipment. This part 2 is the data description of DC power systems equipment. It provides the information tables, the DTD description and XML files. This description is based on generic recommendation of part 1 core document.

SIST ES 202 336-2 V1.1.1:2009 is classified under the following ICS (International Classification for Standards) categories: 19.040 - Environmental testing; 33.050.01 - Telecommunication terminal equipment in general. The ICS classification helps identify the subject area and facilitates finding related standards.

SIST ES 202 336-2 V1.1.1:2009 is available in PDF format for immediate download after purchase. The document can be added to your cart and obtained through the secure checkout process. Digital delivery ensures instant access to the complete standard document.

Standards Content (Sample)

Contents

  • 1 Scope
  • 2 References
  • 2.1 Normative references
  • 6 Final draft ETSI ES 202 336-2 V1.1.1 (2009-01)
  • 2.2 Informative references
  • 3 Definitions and abbreviations
  • 3.1 Definitions
  • 12 V blocks)
  • 7 Final draft ETSI ES 202 336-2 V1.1.1 (2009-01)
  • 8 Final draft ETSI ES 202 336-2 V1.1.1 (2009-01)
  • 3.2 Abbreviations
  • 9 Final draft ETSI ES 202 336-2 V1.1.1 (2009-01)
  • 4 DC power supply system
  • 10 Final draft ETSI ES 202 336-2 V1.1.1 (2009-01)
  • 11 Final draft ETSI ES 202 336-2 V1.1.1 (2009-01)
  • 12 Final draft ETSI ES 202 336-2 V1.1.1 (2009-01)
  • 13 Final draft ETSI ES 202 336-2 V1.1.1 (2009-01)
  • 14 Final draft ETSI ES 202 336-2 V1.1.1 (2009-01)
  • 15 Final draft ETSI ES 202 336-2 V1.1.1 (2009-01)
  • 16 Final draft ETSI ES 202 336-2 V1.1.1 (2009-01)
  • 17 Final draft ETSI ES 202 336-2 V1.1.1 (2009-01)
  • 18 Final draft ETSI ES 202 336-2 V1.1.1 (2009-01)
  • 19 Final draft ETSI ES 202 336-2 V1.1.1 (2009-01)
  • 20 Final draft ETSI ES 202 336-2 V1.1.1 (2009-01)
  • 21 Final draft ETSI ES 202 336-2 V1.1.1 (2009-01)
  • 22 Final draft ETSI ES 202 336-2 V1.1.1 (2009-01)
  • 23 Final draft ETSI ES 202 336-2 V1.1.1 (2009-01)
  • 24 Final draft ETSI ES 202 336-2 V1.1.1 (2009-01)
  • Bibliography
  • 25 Final draft ETSI ES 202 336-2 V1.1.1 (2009-01)

1 Scope

The present document applies to monitoring and control of DC power supply systems for telecommunication equipment.

The present document defines:

  • The monitored and controlled DC power supply system architectures.
  • The minimum set of exchanged information required at the interface, described in "natural language" in text tables.
  • The XML files with tags and variables corresponding to the data in the tables.

2 References

References are either specific (identified by date of publication and/or edition number or version number) or non-specific.

  • For a specific reference, subsequent revisions do not apply.
  • Non-specific reference may be made only to a complete document or a part thereof and only in the following cases:
  • if it is accepted that it will be possible to use all future changes of the referenced document for the purposes of the referring document;
  • for informative references.

Referenced documents which are not found to be publicly available in the expected location might be found at http://docbox.etsi.org/Reference.

NOTE: While any hyperlinks included in this clause were valid at the time of publication ETSI cannot guarantee their long term validity.

2.1 Normative references

The following referenced documents are indispensable for the application of the present document. For dated references, only the edition cited applies. For non-specific references, the latest edition of the referenced document (including any amendments) applies.

[1] ETSI ES 202 336-1: "Environmental Engineering (EE); Monitoring and Control Interface for Infrastructure Equipment (Power, Cooling and Building Environment Systems used in Telecommunication Networks); Part 1: Generic Interface".

[2] ETSI EN 300 132-2: "Environmental Engineering (EE); Power supply interface at the input to telecommunications equipment; Part 2: Operated by direct current (dc)". [3] ETSI EN 300 132-3: "Environmental Engineering (EE); Power supply interface at the input to telecommunications equipment; Part 3: Operated by rectified current source, alternating current source or direct current source up to 400 V".

[4] ETSI EN 302 099: "Environmental Engineering (EE); Powering of equipment in access network". ETSI

6 Final draft ETSI ES 202 336-2 V1.1.1 (2009-01)

2.2 Informative references

The following referenced documents are not essential to the use of the present document but they assist the user with regard to a particular subject area. For non-specific references, the latest version of the referenced document (including any amendments) applies.

[i.1] IEEE 802.1 to 11: "IEEE Standard for Local and Metropolitan Area Networks: Overview and Architecture ".

[i.2] ISO/IEC 10164 (all parts): "Information technology - Open Systems Interconnection". [i.3] ISO/IEC 8879:"Information processing - Text and office systems - Standard Generalized Markup Language (SGML)".

[i.4] IEC 60896 (all parts): "Stationary lead-acid batteries".

3 Definitions and abbreviations

3.1 Definitions

For the purposes of the present document, the following terms and definitions apply:

NOTE: Terms referring to energy interface, equipment and distribution are described in power distribution standards EN 300 132-2 [2], EN 300 132-3 [3] for ac and dc interface and EN 302 099 [4] for access network equipment powering.

alarm: any information signalling abnormal state, i.e. different to specified normal state of hardware, software, environment condition (temperature, humidity, etc.).

NOTE: The alarm signal should be understood by itself by an operator and should always have at least one severity qualification or codification (colour, level, etc.). Example: rectifier failure, battery low voltage...) alarm loop: electrical loop which open or closed state correspond to alarm start (set) or end (clear) state alarm message: text parts of the alarm structure alarm structure: organized set of information fields in an alarm data frame (time stamp, set/clear, text, etc.) battery: complete arrangement of battery cells or blocks in one string or more in parallel battery block: battery cell (e.g. 2 V for lead-acid) connected and placed in the same container (forming 4 V, 6 V or

12 V blocks)

battery cell: basic electrochemical element (e.g. a 2 Vnominal cell for a high capacity lead acid battery) battery string: a number of serially interconnected battery blocks or cells client post: any device (laptop, PDA, console, etc.) connected to servers via the operation system networks to perform maintenance or supervision operations Control Unit (CU): integrated unit in an equipment to monitor and control this equipment through sensors and actuators Control form Style Sheet (CSS): simple mechanism for adding style (e.g. fonts, colours, spacing) to Web documents. Tutorials, books, mailing lists for users, etc.

ETSI

7 Final draft ETSI ES 202 336-2 V1.1.1 (2009-01)

Data Gathering Unit (DGU): functional unit used for several functions:

  • collect serial, digital, and analog data from several equipment;
  • option to send (output) serial or digital commands;
  • forward/receive information to/from the Local/Remote Management Application via agreed protocols;
  • mediation between interfaces and protocols.

NOTE: This function may be integrated as part of specific equipment. Dynamic Host Control Protocol (DHCP): protocol used for self configuration of TCP/IP parameters of a workstation assigning IP address and a subnetwork mask NOTE: DHCP may also configure DNS.

Dynamic Name Server (DNS): associates a single domain name to an IP address dynamic synoptic: dynamic display of geographical maps, networks, installations and equipment Ethernet: LAN protocol NOTE: Equivalent to IEEE 802.1 to 11 [i.1].

event: any information signalling a change of state which is not an alarm: e.g. battery test, change of state of battery charge NOTE: The event signal should be understood by itself by an operator and should always have at least one severity qualification or codification (colour, level, etc.). It should be transmitted in a formatted structure with text message and other fields like for alarm, e.g. an event can be coded as an alarm with severity "0". infrastructure equipment: power, cooling and building environment systems used in telecommunications centres and Access Networks locations EXAMPLE: Cabinets, shelters, underground locations, etc.

intranet: internal company network generally using Ethernet protocol and extended IP addresses logbook: chronological file that contains alarm and event messages may be paper or electronic Management Information Base (MIB): dynamic data base that gathers all objects and should evolve to include automatic and manual configuration tools with self coherence tests menu: list of possible input command choices that may be presented in different ways on a display NOTE: Selection is normally made by a keyboard, a pointing device, a mouse or directly by finger on a sensitive screen.

object: class description of items that accept a set of properties or functions NOTE: Generic objects can include more specific items and inherit from their properties. If correctly structured, object programming can allow the system to evolve, i.e. be more future-proof. The code should intrinsically be open and structured.

PHP: powerful tool for making dynamic and interactive Web pages pop-up: information or command screen that appears when a menu choice is selected NOTE: For example this may be a pop-up menu when the pointer is on a title button. REpresentational State Transfer (REST): way to build an application for distributed system as www ETSI

8 Final draft ETSI ES 202 336-2 V1.1.1 (2009-01)

Simple Object Access Protocol (SOAP): way to communicate between applications running on different operating systems, with different technologies and programming languages NOTE: SOAP communicates over HTTP, because HTTP is supported by all Internet browsers and servers, SOAP traffic is not blocked by firewalls and proxy servers (see W3C). Systems Management Function (SMF): object properties or classes with projection on CMIS application context communication NOTE: Set of ISO system management functions according to ISO/IEC 10164 [i.2]. warning: low severity alarm World Wide Web Consortium (W3C): consortium founded in October 1994 to develop common interoperable protocols and promote World Wide Web NOTE: See http://www.w3c.org.

Windows: virtual area on the display that corresponds to a specific application web: common name for the Internet or Intranet XCU: CU enabled to communicate using XML interface as defined in the present document XHTML: stricter and cleaner version of HTML. XHTML consists of all the elements in HTML 4.01 combined with the syntax of XML. It can be read by all XML browser (see W3C) eXtensible Mark-up Language (XML): application profile or restricted form of SGML NOTE: By construction, XML documents are conforming SGML the Standard Generalized Markup Language (ISO/IEC 8879 [i.3]). documents.XML is designed to describe data and focus on what data is. XML should be discerned from the well known Hypertext Transfer Mark-up Language (HTML) which was designed to display data and to focus on how data looks.

XML Schema Definition (XSD): new more detailed XML description compared to the previous one, the DTD Extensible Style sheet Language (XSL): language for expressing style sheets NOTE: It consists of two parts, a language for transforming XML documents, and an XML vocabulary for specifying formatting semantics. An XSL style sheet specifies the presentation of a class of XML documents by describing how an instance of the class is transformed into an XML document that uses the formatting vocabulary.

3.2 Abbreviations

For the purposes of the present document, the following abbreviations apply:

CSS Control form Style Sheet CU Control Unit of an equipment DGU Data Gathering Unit DHCP Dynamic Host Control Protocol DNS Dynamic Name Server DTD Document Type Definition HTML Hypertext Transfer Make-up Language HTTP Hypertext Transfer Protocol I Average output load current (DC) Av I Total battery current (DC) Batt I Total output load current (DC) Load IP Internet Protocol I Total rectifier output current (DC) Rect LAN Local Array Network MIB Management Information Base MN Management network ETSI

9 Final draft ETSI ES 202 336-2 V1.1.1 (2009-01)

PHP Hypertext Preprocessor REST REpresentational State Transfer RMA Remote Management Application SMF Systems Management Function SOAP Simple Object Access Protocol TCP Transmission Control Protocol for IP W3C World Wide Web Consortium XCU XML enabled CU XML eXtensible Markup Language (see W3C) XSD XML Schema Definition XSL Extensible Style sheet Language

4 DC power supply system

The DC system subset described in ES 202 336-1 [1] transforms AC interface from mains or AC back-up engine defined in EN 300 132-3 [3], in DC voltage on interface A defined in EN 300 132-2 [2] or EN 300 132-3 [3] for telecom centre or defined for local or remote power supply of access network equipment in EN 302 099 [4]. The DC power systems addressed by the present document are depicted in figures 1 and 2. One single control unit XCU can monitor and control several power cabinets through field bus. Field bus is outside the scope of the present document.

Mandatory monitoring/ supervision information and functions are given in annex A. Non-mandatory (optional) monitoring/ supervision information and functions are given in annex B.

Figure 1: Simple DC power supply system with no battery backup Rectifier Modules Output distribution IRect ILoad AC DC Bus (V dc) IBatt AC AC Battery strings

Figure 2: Modular DC power supply system with battery backup ETSI

10 Final draft ETSI ES 202 336-2 V1.1.1 (2009-01)

The main elements of DC power supply systems are:

...

Contents

  • 1 Scope
  • 2 References
  • 2.1 Normative references
  • 7 ETSI ES 202 336-2 V1.1.1 (2009-03)
  • 2.2 Informative references
  • 3 Definitions and abbreviations
  • 3.1 Definitions
  • 12 V blocks)
  • 8 ETSI ES 202 336-2 V1.1.1 (2009-03)
  • 9 ETSI ES 202 336-2 V1.1.1 (2009-03)
  • 3.2 Abbreviations
  • 10 ETSI ES 202 336-2 V1.1.1 (2009-03)
  • 4 DC power supply system
  • 11 ETSI ES 202 336-2 V1.1.1 (2009-03)
  • 12 ETSI ES 202 336-2 V1.1.1 (2009-03)
  • 13 ETSI ES 202 336-2 V1.1.1 (2009-03)
  • 14 ETSI ES 202 336-2 V1.1.1 (2009-03)
  • 15 ETSI ES 202 336-2 V1.1.1 (2009-03)
  • 16 ETSI ES 202 336-2 V1.1.1 (2009-03)
  • 17 ETSI ES 202 336-2 V1.1.1 (2009-03)
  • 18 ETSI ES 202 336-2 V1.1.1 (2009-03)
  • 19 ETSI ES 202 336-2 V1.1.1 (2009-03)
  • 20 ETSI ES 202 336-2 V1.1.1 (2009-03)
  • 21 ETSI ES 202 336-2 V1.1.1 (2009-03)
  • 22 ETSI ES 202 336-2 V1.1.1 (2009-03)
  • 23 ETSI ES 202 336-2 V1.1.1 (2009-03)
  • 24 ETSI ES 202 336-2 V1.1.1 (2009-03)
  • 25 ETSI ES 202 336-2 V1.1.1 (2009-03)
  • Bibliography
  • 26 ETSI ES 202 336-2 V1.1.1 (2009-03)

1 Scope

The present document applies to monitoring and control of DC power supply systems for telecommunication equipment.

The present document defines:

  • The monitored and controlled DC power supply system architectures.
  • The minimum set of exchanged information required at the interface, described in "natural language" in text tables.
  • The XML files with tags and variables corresponding to the data in the tables.

2 References

References are either specific (identified by date of publication and/or edition number or version number) or non-specific.

  • For a specific reference, subsequent revisions do not apply.
  • Non-specific reference may be made only to a complete document or a part thereof and only in the following cases:
  • if it is accepted that it will be possible to use all future changes of the referenced document for the purposes of the referring document;
  • for informative references.

Referenced documents which are not found to be publicly available in the expected location might be found at http://docbox.etsi.org/Reference.

NOTE: While any hyperlinks included in this clause were valid at the time of publication ETSI cannot guarantee their long term validity.

2.1 Normative references

The following referenced documents are indispensable for the application of the present document. For dated references, only the edition cited applies. For non-specific references, the latest edition of the referenced document (including any amendments) applies.

[1] ETSI ES 202 336-1: "Environmental Engineering (EE); Monitoring and Control Interface for Infrastructure Equipment (Power, Cooling and Building Environment Systems used in Telecommunication Networks); Part 1: Generic Interface".

[2] ETSI EN 300 132-2: "Environmental Engineering (EE); Power supply interface at the input to telecommunications equipment; Part 2: Operated by direct current (dc)". [3] ETSI EN 300 132-3: "Environmental Engineering (EE); Power supply interface at the input to telecommunications equipment; Part 3: Operated by rectified current source, alternating current source or direct current source up to 400 V".

[4] ETSI EN 302 099: "Environmental Engineering (EE); Powering of equipment in access network". ETSI

7 ETSI ES 202 336-2 V1.1.1 (2009-03)

2.2 Informative references

The following referenced documents are not essential to the use of the present document but they assist the user with regard to a particular subject area. For non-specific references, the latest version of the referenced document (including any amendments) applies.

[i.1] IEEE 802.1 to 11: "IEEE Standard for Local and Metropolitan Area Networks: Overview and Architecture".

[i.2] ISO/IEC 10164 (all parts): "Information technology - Open Systems Interconnection". [i.3] ISO/IEC 8879:"Information processing - Text and office systems - Standard Generalized Markup Language (SGML)".

[i.4] IEC 60896 (all parts): "Stationary lead-acid batteries".

3 Definitions and abbreviations

3.1 Definitions

For the purposes of the present document, the following terms and definitions apply:

NOTE: Terms referring to energy interface, equipment and distribution are described in power distribution standards EN 300 132-2 [2], EN 300 132-3 [3] for ac and dc interface and EN 302 099 [4] for access network equipment powering.

alarm: any information signalling abnormal state, i.e. different to specified normal state of hardware, software, environment condition (temperature, humidity, etc.) NOTE: The alarm signal should be understood by itself by an operator and should always have at least one severity qualification or codification (colour, level, etc.). Example: rectifier failure, battery low voltage, etc.).

alarm loop: electrical loop which open or closed state correspond to alarm start (set) or end (clear) state alarm message: text parts of the alarm structure alarm structure: organized set of information fields in an alarm data frame (time stamp, set/clear, text, etc.) battery: complete arrangement of battery cells or blocks in one string or more in parallel battery block: battery cell (e.g. 2 V for lead-acid) connected and placed in the same container (forming 4 V, 6 V or

12 V blocks)

battery cell: basic electrochemical element (e.g. a 2 Vnominal cell for a high capacity lead acid battery) battery string: number of serially interconnected battery blocks or cells client post: any device (laptop, PDA, console, etc.) connected to servers via the operation system networks to perform maintenance or supervision operations Control Unit (CU): integrated unit in an equipment to monitor and control this equipment through sensors and actuators Control form Style Sheet (CSS): simple mechanism for adding style (e.g. fonts, colours, spacing) to Web documents. Tutorials, books, mailing lists for users, etc.

ETSI

8 ETSI ES 202 336-2 V1.1.1 (2009-03)

Data Gathering Unit (DGU): functional unit used for several functions:

  • collect serial, digital, and analog data from several equipment;
  • option to send (output) serial or digital commands;
  • forward/receive information to/from the Local/Remote Management Application via agreed protocols;
  • mediation between interfaces and protocols.

NOTE: This function may be integrated as part of specific equipment. Dynamic Host Control Protocol (DHCP): protocol used for self configuration of TCP/IP parameters of a workstation assigning IP address and a subnetwork mask NOTE: DHCP may also configure DNS.

Dynamic Name Server (DNS): associates a single domain name to an IP address dynamic synoptic: dynamic display of geographical maps, networks, installations and equipment Ethernet: LAN protocol NOTE: Equivalent to IEEE 802.1 to 11 [i.1].

event: any information signalling a change of state which is not an alarm: e.g. battery test, change of state of battery charge NOTE: The event signal should be understood by itself by an operator and should always have at least one severity qualification or codification (colour, level, etc.). It should be transmitted in a formatted structure with text message and other fields like for alarm, e.g. an event can be coded as an alarm with severity "0". infrastructure equipment: power, cooling and building environment systems used in telecommunications centres and Access Networks locations EXAMPLE: Cabinets, shelters, underground locations, etc.

intranet: internal company network generally using Ethernet protocol and extended IP addresses logbook: chronological file that contains alarm and event messages may be paper or electronic Management Information Base (MIB): dynamic data base that gathers all objects and should evolve to include automatic and manual configuration tools with self coherence tests menu: list of possible input command choices that may be presented in different ways on a display NOTE: Selection is normally made by a keyboard, a pointing device, a mouse or directly by finger on a sensitive screen.

object: class description of items that accept a set of properties or functions NOTE: Generic objects can include more specific items and inherit from their properties. If correctly structured, object programming can allow the system to evolve, i.e. be more future-proof. The code should intrinsically be open and structured.

PHP: powerful tool for making dynamic and interactive Web pages pop-up: information or command screen that appears when a menu choice is selected NOTE: For example this may be a pop-up menu when the pointer is on a title button. REpresentational State Transfer (REST): way to build an application for distributed system as www ETSI

9 ETSI ES 202 336-2 V1.1.1 (2009-03)

Simple Object Access Protocol (SOAP): way to communicate between applications running on different operating systems, with different technologies and programming languages NOTE: SOAP communicates over HTTP, because HTTP is supported by all Internet browsers and servers, SOAP traffic is not blocked by firewalls and proxy servers (see W3C). Systems Management Function (SMF): object properties or classes with projection on CMIS application context communication NOTE: Set of ISO system management functions according to ISO/IEC 10164 [i.2]. warning: low severity alarm World Wide Web Consortium (W3C): consortium founded in October 1994 to develop common interoperable protocols and promote World Wide Web NOTE: See http://www.w3c.org.

Windows: virtual area on the display that corresponds to a specific application web: common name for the Internet or Intranet XCU: CU enabled to communicate using XML interface as defined in the present document XHTML: stricter and cleaner version of HTML. XHTML consists of all the elements in HTML 4.01 combined with the syntax of XML. It can be read by all XML browser (see W3C) eXtensible Mark-up Language (XML): application profile or restricted form of SGML NOTE: By construction, XML documents are conforming SGML the Standard Generalized Markup Language (ISO/IEC 8879 [i.3]). documents.XML is designed to describe data and focus on what data is. XML should be discerned from the well known Hypertext Transfer Mark-up Language (HTML) which was designed to display data and to focus on how data looks.

XML Schema Definition (XSD): new more detailed XML description compared to the previous one, the DTD Extensible Style sheet Language (XSL): language for expressing style sheets NOTE: It consists of two parts, a language for transforming XML documents, and an XML vocabulary for specifying formatting semantics. An XSL style sheet specifies the presentation of a class of XML documents by describing how an instance of the class is transformed into an XML document that uses the formatting vocabulary.

3.2 Abbreviations

For the purposes of the present document, the following abbreviations apply:

CSS Control form Style Sheet CU Control Unit of an equipment DGU Data Gathering Unit DHCP Dynamic Host Control Protocol DNS Dynamic Name Server DTD Document Type Definition HTML Hypertext Transfer Make-up Language HTTP Hypertext Transfer Protocol I Average output load current (DC) Av I Total battery current (DC) Batt I Total output load current (DC) Load IP Internet Protocol I Total rectifier output current (DC) Rect LAN Local Array Network MIB Management Information Base MN Management network ETSI

10 ETSI ES 202 336-2 V1.1.1 (2009-03)

PHP Hypertext Preprocessor REST REpresentational State Transfer RMA Remote Management Application SMF Systems Management Function SOAP Simple Object Access Protocol TCP Transmission Control Protocol for IP W3C World Wide Web Consortium XCU XML enabled CU XML eXtensible Markup Language (see W3C) XSD XML Schema Definition XSL eXtensible Style sheet Language

4 DC power supply system

The DC system subset described in ES 202 336-1 [1] transforms AC interface from mains or AC back-up engine defined in EN 300 132-3 [3], in DC voltage on interface A defined in EN 300 132-2 [2] or EN 300 132-3 [3] for telecom centre or defined for local or remote power supply of access network equipment in EN 302 099 [4]. The DC power systems addressed by the present document are depicted in figures 1 and 2. One single control unit XCU can monitor and control several power cabinets through field bus. Field bus is outside the scope of the present document.

Mandatory monitoring/ supervision information and functions are given in annex A. Non-mandatory (optional) monitoring/ supervision information and functions are given in annex B.

Figure 1: Simple DC power supply system with no battery backup Rectifier Modules Output distribution IRect ILoad AC DC Bus (V dc) IBatt AC AC Battery strings

Figure 2: Modular DC power supply system with battery backup ETSI

11 ETSI ES 202 336-2 V1.1.1 (2009-03)

The main elements of DC power supply systems are:

- Rectifier (one or more) that converts AC voltage to DC voltage (i.e. 230 VAC to DC voltage). NOTE: Other alternative energy sources may be used to provide DC power e.g. Photovoltaic, wind turbine, etc. - Battery (one or more strings of cells) that stores energy and can power the loads when AC interrupts or rectifiers fail. There can be test and permanent battery monitoring system to reduce the failure detection time and the MTTR.

  • Protection and distribution (DC bus, breaker, etc.) to power different user loads and discriminate faults
  • A system monitoring and control unit (XCU) to monitor voltage, current, power, temperature, etc., extend alarms and provide system control functionality.

Several measurements are possible: rectifier states, rectifier voltage and current, battery voltage, current and temperature, user load currents, etc.

...

Contents

  • 1 Scope
  • 2 References
  • 2.1 Normative references
  • 7 ETSI ES 202 336-2 V1.1.1 (2009-03)
  • 2.2 Informative references
  • 3 Definitions and abbreviations
  • 3.1 Definitions
  • 12 V blocks)
  • 8 ETSI ES 202 336-2 V1.1.1 (2009-03)
  • 9 ETSI ES 202 336-2 V1.1.1 (2009-03)
  • 3.2 Abbreviations
  • 10 ETSI ES 202 336-2 V1.1.1 (2009-03)
  • 4 DC power supply system
  • 11 ETSI ES 202 336-2 V1.1.1 (2009-03)
  • 12 ETSI ES 202 336-2 V1.1.1 (2009-03)
  • 13 ETSI ES 202 336-2 V1.1.1 (2009-03)
  • 14 ETSI ES 202 336-2 V1.1.1 (2009-03)
  • 15 ETSI ES 202 336-2 V1.1.1 (2009-03)
  • 16 ETSI ES 202 336-2 V1.1.1 (2009-03)
  • 17 ETSI ES 202 336-2 V1.1.1 (2009-03)
  • 18 ETSI ES 202 336-2 V1.1.1 (2009-03)
  • 19 ETSI ES 202 336-2 V1.1.1 (2009-03)
  • 20 ETSI ES 202 336-2 V1.1.1 (2009-03)
  • 21 ETSI ES 202 336-2 V1.1.1 (2009-03)
  • 22 ETSI ES 202 336-2 V1.1.1 (2009-03)
  • 23 ETSI ES 202 336-2 V1.1.1 (2009-03)
  • 24 ETSI ES 202 336-2 V1.1.1 (2009-03)
  • 25 ETSI ES 202 336-2 V1.1.1 (2009-03)
  • Bibliography
  • 26 ETSI ES 202 336-2 V1.1.1 (2009-03)

1 Scope

The present document applies to monitoring and control of DC power supply systems for telecommunication equipment.

The present document defines:

  • The monitored and controlled DC power supply system architectures.
  • The minimum set of exchanged information required at the interface, described in "natural language" in text tables.
  • The XML files with tags and variables corresponding to the data in the tables.

2 References

References are either specific (identified by date of publication and/or edition number or version number) or non-specific.

  • For a specific reference, subsequent revisions do not apply.
  • Non-specific reference may be made only to a complete document or a part thereof and only in the following cases:
  • if it is accepted that it will be possible to use all future changes of the referenced document for the purposes of the referring document;
  • for informative references.

Referenced documents which are not found to be publicly available in the expected location might be found at http://docbox.etsi.org/Reference.

NOTE: While any hyperlinks included in this clause were valid at the time of publication ETSI cannot guarantee their long term validity.

2.1 Normative references

The following referenced documents are indispensable for the application of the present document. For dated references, only the edition cited applies. For non-specific references, the latest edition of the referenced document (including any amendments) applies.

[1] ETSI ES 202 336-1: "Environmental Engineering (EE); Monitoring and Control Interface for Infrastructure Equipment (Power, Cooling and Building Environment Systems used in Telecommunication Networks); Part 1: Generic Interface".

[2] ETSI EN 300 132-2: "Environmental Engineering (EE); Power supply interface at the input to telecommunications equipment; Part 2: Operated by direct current (dc)". [3] ETSI EN 300 132-3: "Environmental Engineering (EE); Power supply interface at the input to telecommunications equipment; Part 3: Operated by rectified current source, alternating current source or direct current source up to 400 V".

[4] ETSI EN 302 099: "Environmental Engineering (EE); Powering of equipment in access network". ETSI

SIST ES 202 336-2 V1.1.1:2009

7 ETSI ES 202 336-2 V1.1.1 (2009-03)

2.2 Informative references

The following referenced documents are not essential to the use of the present document but they assist the user with regard to a particular subject area. For non-specific references, the latest version of the referenced document (including any amendments) applies.

[i.1] IEEE 802.1 to 11: "IEEE Standard for Local and Metropolitan Area Networks: Overview and Architecture".

[i.2] ISO/IEC 10164 (all parts): "Information technology - Open Systems Interconnection". [i.3] ISO/IEC 8879:"Information processing - Text and office systems - Standard Generalized Markup Language (SGML)".

[i.4] IEC 60896 (all parts): "Stationary lead-acid batteries".

3 Definitions and abbreviations

3.1 Definitions

For the purposes of the present document, the following terms and definitions apply:

NOTE: Terms referring to energy interface, equipment and distribution are described in power distribution standards EN 300 132-2 [2], EN 300 132-3 [3] for ac and dc interface and EN 302 099 [4] for access network equipment powering.

alarm: any information signalling abnormal state, i.e. different to specified normal state of hardware, software, environment condition (temperature, humidity, etc.) NOTE: The alarm signal should be understood by itself by an operator and should always have at least one severity qualification or codification (colour, level, etc.). Example: rectifier failure, battery low voltage, etc.).

alarm loop: electrical loop which open or closed state correspond to alarm start (set) or end (clear) state alarm message: text parts of the alarm structure alarm structure: organized set of information fields in an alarm data frame (time stamp, set/clear, text, etc.) battery: complete arrangement of battery cells or blocks in one string or more in parallel battery block: battery cell (e.g. 2 V for lead-acid) connected and placed in the same container (forming 4 V, 6 V or

12 V blocks)

battery cell: basic electrochemical element (e.g. a 2 Vnominal cell for a high capacity lead acid battery) battery string: number of serially interconnected battery blocks or cells client post: any device (laptop, PDA, console, etc.) connected to servers via the operation system networks to perform maintenance or supervision operations Control Unit (CU): integrated unit in an equipment to monitor and control this equipment through sensors and actuators Control form Style Sheet (CSS): simple mechanism for adding style (e.g. fonts, colours, spacing) to Web documents. Tutorials, books, mailing lists for users, etc.

ETSI

SIST ES 202 336-2 V1.1.1:2009

8 ETSI ES 202 336-2 V1.1.1 (2009-03)

Data Gathering Unit (DGU): functional unit used for several functions:

  • collect serial, digital, and analog data from several equipment;
  • option to send (output) serial or digital commands;
  • forward/receive information to/from the Local/Remote Management Application via agreed protocols;
  • mediation between interfaces and protocols.

NOTE: This function may be integrated as part of specific equipment. Dynamic Host Control Protocol (DHCP): protocol used for self configuration of TCP/IP parameters of a workstation assigning IP address and a subnetwork mask NOTE: DHCP may also configure DNS.

Dynamic Name Server (DNS): associates a single domain name to an IP address dynamic synoptic: dynamic display of geographical maps, networks, installations and equipment Ethernet: LAN protocol NOTE: Equivalent to IEEE 802.1 to 11 [i.1].

event: any information signalling a change of state which is not an alarm: e.g. battery test, change of state of battery charge NOTE: The event signal should be understood by itself by an operator and should always have at least one severity qualification or codification (colour, level, etc.). It should be transmitted in a formatted structure with text message and other fields like for alarm, e.g. an event can be coded as an alarm with severity "0". infrastructure equipment: power, cooling and building environment systems used in telecommunications centres and Access Networks locations EXAMPLE: Cabinets, shelters, underground locations, etc.

intranet: internal company network generally using Ethernet protocol and extended IP addresses logbook: chronological file that contains alarm and event messages may be paper or electronic Management Information Base (MIB): dynamic data base that gathers all objects and should evolve to include automatic and manual configuration tools with self coherence tests menu: list of possible input command choices that may be presented in different ways on a display NOTE: Selection is normally made by a keyboard, a pointing device, a mouse or directly by finger on a sensitive screen.

object: class description of items that accept a set of properties or functions NOTE: Generic objects can include more specific items and inherit from their properties. If correctly structured, object programming can allow the system to evolve, i.e. be more future-proof. The code should intrinsically be open and structured.

PHP: powerful tool for making dynamic and interactive Web pages pop-up: information or command screen that appears when a menu choice is selected NOTE: For example this may be a pop-up menu when the pointer is on a title button. REpresentational State Transfer (REST): way to build an application for distributed system as www ETSI

SIST ES 202 336-2 V1.1.1:2009

9 ETSI ES 202 336-2 V1.1.1 (2009-03)

Simple Object Access Protocol (SOAP): way to communicate between applications running on different operating systems, with different technologies and programming languages NOTE: SOAP communicates over HTTP, because HTTP is supported by all Internet browsers and servers, SOAP traffic is not blocked by firewalls and proxy servers (see W3C). Systems Management Function (SMF): object properties or classes with projection on CMIS application context communication NOTE: Set of ISO system management functions according to ISO/IEC 10164 [i.2]. warning: low severity alarm World Wide Web Consortium (W3C): consortium founded in October 1994 to develop common interoperable protocols and promote World Wide Web NOTE: See http://www.w3c.org.

Windows: virtual area on the display that corresponds to a specific application web: common name for the Internet or Intranet XCU: CU enabled to communicate using XML interface as defined in the present document XHTML: stricter and cleaner version of HTML. XHTML consists of all the elements in HTML 4.01 combined with the syntax of XML. It can be read by all XML browser (see W3C) eXtensible Mark-up Language (XML): application profile or restricted form of SGML NOTE: By construction, XML documents are conforming SGML the Standard Generalized Markup Language (ISO/IEC 8879 [i.3]). documents.XML is designed to describe data and focus on what data is. XML should be discerned from the well known Hypertext Transfer Mark-up Language (HTML) which was designed to display data and to focus on how data looks.

XML Schema Definition (XSD): new more detailed XML description compared to the previous one, the DTD Extensible Style sheet Language (XSL): language for expressing style sheets NOTE: It consists of two parts, a language for transforming XML documents, and an XML vocabulary for specifying formatting semantics. An XSL style sheet specifies the presentation of a class of XML documents by describing how an instance of the class is transformed into an XML document that uses the formatting vocabulary.

3.2 Abbreviations

For the purposes of the present document, the following abbreviations apply:

CSS Control form Style Sheet CU Control Unit of an equipment DGU Data Gathering Unit DHCP Dynamic Host Control Protocol DNS Dynamic Name Server DTD Document Type Definition HTML Hypertext Transfer Make-up Language HTTP Hypertext Transfer Protocol I Average output load current (DC) Av I Total battery current (DC) Batt I Total output load current (DC) Load IP Internet Protocol I Total rectifier output current (DC) Rect LAN Local Array Network MIB Management Information Base MN Management network ETSI

SIST ES 202 336-2 V1.1.1:2009

10 ETSI ES 202 336-2 V1.1.1 (2009-03)

PHP Hypertext Preprocessor REST REpresentational State Transfer RMA Remote Management Application SMF Systems Management Function SOAP Simple Object Access Protocol TCP Transmission Control Protocol for IP W3C World Wide Web Consortium XCU XML enabled CU XML eXtensible Markup Language (see W3C) XSD XML Schema Definition XSL eXtensible Style sheet Language

4 DC power supply system

The DC system subset described in ES 202 336-1 [1] transforms AC interface from mains or AC back-up engine defined in EN 300 132-3 [3], in DC voltage on interface A defined in EN 300 132-2 [2] or EN 300 132-3 [3] for telecom centre or defined for local or remote power supply of access network equipment in EN 302 099 [4]. The DC power systems addressed by the present document are depicted in figures 1 and 2. One single control unit XCU can monitor and control several power cabinets through field bus. Field bus is outside the scope of the present document.

Mandatory monitoring/ supervision information and functions are given in annex A. Non-mandatory (optional) monitoring/ supervision information and functions are given in annex B.

Figure 1: Simple DC power supply system with no battery backup Rectifier Modules Output distribution IRect ILoad AC DC Bus (Vdc) IBatt AC AC Battery strings

Figure 2: Modular DC power supply system with battery backup ETSI

SIST ES 202 336-2 V1.1.1:2009

11 ETSI ES 202 336-2 V1.1.1 (2009-03)

The main elements of DC power supply systems are:

- Rectifier (one or more) that converts AC voltage to DC voltage (i.e. 230 VAC to DC voltage). NOTE: Other alternative energy sources may be used to provide DC power e.g. Photovoltaic, wind turbine, etc. - Battery (one or more strings of cells) that stores energy and can power the loads when AC interrupts or rectifiers fail. There can be test and permanent battery monitoring system to reduce the failure detection time and the MTTR.

  • Protection and distribution (DC bus, breaker, etc.) to power different user loads and discriminate faults
  • A system monitoring and control unit (XCU) to monitor voltage, current, power, temperature, etc., extend alarms and provide system control functionality.

Several measurements are possible: rectifier states, rectifier voltage and current, battery voltage, current and temperature, user load currents, etc.

...