Alarm systems - Intrusion and hold-up systems - Part 2-10: Intrusion detectors - Lock state contacts (magnetic)

This European Standard provides for security grades 1 to 4, (see EN 50131-1) specific or non-specific wired or wire-free lock state contacts, and includes the requirements for four environmental classes covering applications in internal and outdoor locations as specified in EN 50130-5.
Lock state contacts are installed in windows or doors and windows or doorframes to allow to monitor the lock/unlock status only or the lock/unlock status combined with the open/close status of a window/door simultaneously and are as such located in supervised premises. They provide the necessary range of signals or messages to be used by the rest of the intrusion alarm system.
A detector fulfils all the requirements of the specified grade.
Functions additional to the mandatory functions specified in this European Standard may be included in the detector, providing they do not influence the correct operation of the mandatory functions.
The combination of the two separate units of the lock state contact is referred to in the body of this European Standard as the detector.
This European Standard does not apply to system interconnections.

Alarmanlagen - Einbruch- und Überfallmeldeanlagen - Teil 2-10: Einbruchmelder - Verschluss- und Öffnungsüberwachungskontakte (magnetisch)

Systèmes d'alarme - Systèmes d'alarme contre l'intrusion et les hold-up - Partie 2-10: Détecteurs d'intrusion - Contact d'état de verrouillage (magnétique)

La présente Norme européenne fournit les grades de sécurité 1 à 4 (voir EN 50131-1), décrit les contacts d'état de verrouillage filaires spécifiques, filaires non spécifiques ou non filaires et inclut les exigences applicables aux classes d'environnement couvrant les applications dans des locaux situés à l'intérieur et à l'extérieur (voir EN 50130-5).
Les contacts d'état de verrouillage sont installés dans les fenêtres/portes et fenêtres/huisseries pour assurer le contrôle seul de l'état de verrouillage/déverrouillage ou le contrôle simultané de l'état de verrouillage/déverrouillage conjointement à l'état d'ouverture/de fermeture d'une fenêtre/porte et sont à ce titre situés dans des locaux surveillés. Ils fournissent la plage de signaux/messages nécessaire à l'utilisation par le reste du système d'alarme contre l'intrusion.
Un détecteur satisfait à l'ensemble des exigences du grade spécifié.
Des fonctions complémentaires aux fonctions obligatoires spécifiées dans la présente Norme européenne peuvent être incluses dans le détecteur, à condition qu'elles n'influencent pas le bon fonctionnement des fonctions obligatoires.
La combinaison des deux unités distinctes du contact d'état de verrouillage est désignée par le mot "détecteur" dans le corps de la présente Norme européenne.
La présente Norme européenne ne s'applique pas aux interconnexions du système.

Alarmni sistemi - Sistemi za javljanje vloma in ropa - 2-10. del: Javljalniki vloma - Magnetni kontakti

Ta evropski standard podaja varnostne razrede od 1 do 4 (glej EN 50131-1) za specifične ali nespecifične (ne)ožičene magnetne kontakte in zahteve za štiri okoljske razrede, ki zajemajo načine uporabe v notranjih prostorih in na prostem, kot je opredeljeno v standardu EN 50130-5.
Magnetni kontakti so nameščeni v oknih ali vratih in oknih ali vratnih okvirjih ter omogočajo spremljanje samo stanja zaklepa/odklepa ali stanja zaklepa/odklepa hkrati s stanjem odprtja/zaprtja okna/vrat in se kot takšni nahajajo v prostorih pod nadzorom. Posredujejo potrebno vrsto signalov ali sporočil, ki se uporabljajo v ostalih segmentih sistema za javljanje vloma.
Detektor izpolnjuje vse zahteve določenega razreda.
Poleg obveznih funkcij, ki so opredeljene v tem evropskem standardu, ima lahko javljalnik tudi dodatne funkcije, pri čemer te ne smejo vplivati na pravilno delovanje obveznih funkcij.
Kombinacija dveh ločenih enot magnetnega kontakta je v glavnem delu tega evropskega standarda navedena kot detektor.
Ta evropski standard se ne uporablja za medsebojne povezave sistemov.

General Information

Status
Published
Publication Date
17-Oct-2018
Technical Committee
Current Stage
6060 - National Implementation/Publication (Adopted Project)
Start Date
05-Oct-2018
Due Date
10-Dec-2018
Completion Date
18-Oct-2018

Relations

Standard
SIST EN 50131-2-10:2018
English language
32 pages
sale 10% off
Preview
sale 10% off
Preview
e-Library read for
1 day

Standards Content (Sample)


SLOVENSKI STANDARD
01-november-2018
1DGRPHãþD
SIST-TS CLC/TS 50131-2-10:2014
Alarmni sistemi - Sistemi za javljanje vloma in ropa - 2-10. del: Javljalniki vloma -
Magnetni kontakti
Alarm systems - Intrusion and hold-up systems - Part 2-10: Intrusion detectors - Lock
state contacts (magnetic)
Alarmanlagen - Einbruch- und Überfallmeldeanlagen - Teil 2-10: Einbruchmelder -
Verschluss- und Öffnungsüberwachungskontakte (magnetisch)
Systèmes d'alarme - Systèmes d'alarme contre l'intrusion et les hold-up - Partie 2-10:
Détecteurs d'intrusion - Contact d'état de verrouillage (magnétique)
Ta slovenski standard je istoveten z: EN 50131-2-10:2018
ICS:
13.310 Varstvo pred kriminalom Protection against crime
13.320 Alarmni in opozorilni sistemi Alarm and warning systems
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.

EUROPEAN STANDARD EN 50131-2-10

NORME EUROPÉENNE
EUROPÄISCHE NORM
September 2018
ICS 13.320 Supersedes CLC/TS 50131-2-10:2014
English Version
Alarm systems - Intrusion and hold-up systems - Part 2-10:
Intrusion detectors - Lock state contacts (magnetic)
Systèmes d'alarme - Systèmes d'alarme contre l'intrusion et Alarmanlagen - Einbruch- und Überfallmeldeanlagen - Teil
les hold-up - Partie 2-10: Détecteurs d'intrusion - Contact 2-10: Einbruchmelder - Verschluss- und
d'état de verrouillage (magnétiques) Öffnungsüberwachungskontakte (magnetisch)
This European Standard was approved by CENELEC on 2018-05-10. CENELEC members are bound to comply with the CEN/CENELEC
Internal Regulations which stipulate the conditions for giving this European Standard the status of a national standard without any alteration.
Up-to-date lists and bibliographical references concerning such national standards may be obtained on application to the CEN-CENELEC
Management Centre or to any CENELEC member.
This European Standard exists in three official versions (English, French, German). A version in any other language made by translation
under the responsibility of a CENELEC member into its own language and notified to the CEN-CENELEC Management Centre has the
same status as the official versions.
CENELEC members are the national electrotechnical committees of Austria, Belgium, Bulgaria, Croatia, Cyprus, the Czech Republic,
Denmark, Estonia, Finland, Former Yugoslav Republic of Macedonia, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia,
Lithuania, Luxembourg, Malta, the Netherlands, Norway, Poland, Portugal, Romania, Serbia, Slovakia, Slovenia, Spain, Sweden,
Switzerland, Turkey and the United Kingdom.

European Committee for Electrotechnical Standardization
Comité Européen de Normalisation Electrotechnique
Europäisches Komitee für Elektrotechnische Normung
CEN-CENELEC Management Centre: Rue de la Science 23, B-1040 Brussels
© 2018 CENELEC All rights of exploitation in any form and by any means reserved worldwide for CENELEC Members.
Ref. No. EN 50131-2-10:2018 E
Contents Page
European foreword . 4
Introduction . 5
1 Scope . 6
2 Normative references . 6
3 Terms, definitions and abbreviations . 6
3.1 Terms and definitions . 6
3.2 Abbreviations . 8
4 Functional requirements. 8
4.1 Events . 8
4.2 Signals or messages . 9
4.3 Detection . 10
4.3.1 Detection performance . 10
4.3.2 Indication of detection . 11
4.4 Operational requirements . 11
4.4.1 Time interval between intrusion signals or messages . 11
4.4.2 Switch on delay . 11
4.4.3 Fault condition signals . 11
4.5 Tamper security . 11
4.5.1 Tamper security requirements . 11
4.5.2 Resistance to and detection of unauthorised access to the inside of the detector through
covers and existing holes . 12
4.5.3 Detection of removal from the mounting surface . 12
4.5.4 Magnetic or electromagnetic field interference . 12
4.5.5 Matched pairs, coding and encryption . 12
4.6 Electrical requirements . 13
4.6.1 Grade dependencies . 13
4.6.2 Detector current consumption . 13
4.6.3 Slow input voltage change and input voltage range limits . 13
4.6.4 Input voltage ripple . 13
4.6.5 Input voltage step change . 13
4.6.6 Total loss of external power . 13
4.6.7 Low supply voltage . 14
4.6.8 Interconnection Integrity . 14
4.7 Environmental classification and conditions . 14
4.7.1 Environmental classification . 14
4.7.2 Immunity to environmental conditions . 14
5 Marking, identification and documentation . 14
5.1 Marking and/or identification . 14
5.2 Documentation . 14
6 Testing . 15
6.1 Generalities . 15
6.2 General test conditions. 15
6.2.1 Standard laboratory conditions for testing . 15
6.2.2 General detection testing environment and procedures . 15
6.2.3 Testing procedures . 16
6.3 Basic test of detection capability . 16
6.4 Verification of detection performance . 16
6.4.1 Generalities . 16
6.4.2 Measurement of make / break distances . 16
6.5 Switch-on delay, time interval between signals, and indication of detection . 16
6.6 Tamper security . 16
6.6.1 Generalities . 16
6.6.2 Resistance to and detection of unauthorized access to the inside of the detector through
covers and existing holes . 17
6.6.3 Detection of removal from the mounting surface . 17
6.6.4 Resistance to magnetic field interference . 17
6.6.5 Matched pairs, coding and encryption . 18
6.7 Electrical tests . 18
6.7.1 Generalities . 18
6.7.2 Detector current consumption . 18
6.7.3 Slow input voltage change and input voltage range limits . 19
6.7.4 Input voltage ripple . 19
6.7.5 Input voltage step change . 19
6.7.6 Total loss of power supply . 19
6.7.7 Low power supply voltage . 20
6.7.8 Interconnection . 20
6.8 Environmental classification and conditions . 20
6.8.1 General . 20
6.8.2 Special conditions . 20
6.9 Marking, identification and documentation . 21
6.9.1 Marking and/or identification . 21
6.9.2 Documentation . 21
Annex A (normative) Dimensions and requirements of standardized interference test magnets . 22
A.1 Normative references . 22
A.2 Requirements . 22
Annex B (normative) General testing matrix. 25
Annex C (informative) List of small tools suitable for testing immunity of casing to unauthorised
access . 27
Annex D (normative) Axes of movement . 28
Annex E (normative) Test surfaces for ferromagnetic material . 29
Annex F (normative) Test faces for interference test units . 30
F.1 Surface mounted detector . 30
F.2 Flush mounted detector. 31
Bibliography . 32
European foreword
This document (EN 50131-2-10:2018) has been prepared by CLC/TC 79 “Alarm systems”.
The following dates are fixed:
• latest date by which this document has (dop) 2019-03-28
to be implemented at national level by
publication of an identical national
standard or by endorsement
• latest date by which the national (dow) 2021-09-28
standards conflicting with this document
have to be withdrawn
This document supersedes CLC/TS 50131-2-10:2014.
Attention is drawn to the possibility that some of the elements of this document may be the subject of patent
rights. CENELEC shall not be held responsible for identifying any or all such patent rights.
EN 50131-2 is currently composed of the following parts:
• EN 50131-2-2, Alarm systems — Intrusion and hold-up systems — Part 2-2: Intrusion detectors —
Passive infrared detectors;
• EN 50131-2-3, Alarm systems — Intrusion and hold-up systems — Part 2-3: Requirements for microwave
detectors;
• EN 50131-2-4, Alarm systems — Intrusion and hold-up systems — Part 2-4: Requirements for combined
passive infrared and microwave detectors;
• EN 50131-2-5, Alarm systems — Intrusion and hold-up systems — Part 2-5: Requirements for combined
passive infrared and ultrasonic detectors;
• EN 50131-2-6, Alarm systems — Intrusion and hold-up systems — Part 2-6: Opening contacts
(magnetic);
• CLC/TS 50131-2-8, Alarm systems — Intrusion and hold-up systems — Part 2-8: Intrusion detectors —
Shock detectors;
• CLC/TS 50131-2-9, Alarm systems — Intrusion and hold-up systems — Part 2-9: Intrusion detectors —
Active infrared beam detectors;
• EN 50131-2-10, Alarm systems — Intrusion and hold-up systems — Part 2-10: Intrusion detectors —
Lock state contacts (magnetic) [the present document];
• EN 50131-2-7-1, Alarm systems — Intrusion and hold-up systems — Part 2-7-1: Intrusion detectors —
Glass break detectors (acoustic);
• EN 50131-2-7-2, Alarm systems — Intrusion and hold-up systems — Part 2-7-2: Intrusion detectors —
Glass break detectors (passive);
• EN 50131-2-7-3, Alarm systems — Intrusion and hold-up systems — Part 2-7-3: Intrusion detectors —
Glass break detectors (active).
Introduction
This European Standard applies to lock state contacts (magnetic) used as part of intrusion and hold-up alarm
systems (I&HAS) installed in buildings. It includes four security grades and four environmental classes.
The purpose of a lock state contact (magnetic) is to detect the lock/unlock state only or the lock/unlock state
combined with the opening status/displacement from the defined closed position of a window or door
simultaneously. The lock state contact comprises two separate contact-less units, the active connection
between these units is at least one magnetic or electromagnetic based field. Separating the two units disturbs
the connection and produces an intruder signal or message.
The scope for lock state contacts (magnetic) and the number and types of generated signals or messages will
be more comprehensive for systems that are specified at the higher grades.
This European Standard is only concerned with the requirements and tests for lock state contacts (magnetic).
Other types of detectors are covered by other documents identified as in the EN 50131-2 series.
1 Scope
This European Standard provides for security grades 1 to 4, (see EN 50131-1) specific or non-specific wired
or wire-free lock state contacts, and includes the requirements for four environmental classes covering
applications in internal and outdoor locations as specified in EN 50130-5.
Lock state contacts are installed in windows or doors and windows or doorframes to allow to monitor the
lock/unlock status only or the lock/unlock status combined with the open/close status of a window/door
simultaneously and are as such located in supervised premises. They provide the necessary range of signals
or messages to be used by the rest of the intrusion alarm system.
A detector fulfils all the requirements of the specified grade.
Functions additional to the mandatory functions specified in this European Standard may be included in the
detector, providing they do not influence the correct operation of the mandatory functions.
The combination of the two separate units of the lock state contact is referred to in the body of this European
Standard as the detector.
This European Standard does not apply to system interconnections.
2 Normative references
The following documents are referred to in the text in such a way that some or all of their content constitutes
requirements of this document. For dated references, only the edition cited applies. For undated references,
the latest edition of the referenced document (including any amendments) applies.
EN 10130, Cold rolled low carbon steel flat products for cold forming — Technical delivery conditions
EN 50130-4, Alarm systems — Part 4: Electromagnetic compatibility — Product family standard: Immunity
requirements for components of fire, intruder, hold up, CCTV, access control and social alarm systems
EN 50130-5, Alarm systems — Part 5: Environmental test methods
EN 50131-1, Alarm systems — Intrusion and hold-up systems — Part 1: System requirements
3 Terms, definitions and abbreviations
3.1 Terms and definitions
For the purposes of this document, the terms and definitions given in EN 50131-1 and the following apply.
ISO and IEC maintain terminological databases for use in standardization at the following addresses:
• IEC Electropedia: available at http://www.electropedia.org/
• ISO Online browsing platform: available at http://www.iso.org/obp
3.1.1
connecting field
one or more generated magnetic or electromagnetic field(s) (e.g. magnetic, inductive, RFID, NFC) connecting
actively the two units of the detector
Note 1 to entry: Separating the two units disturbs the connection and produces an intrusion signal or message.
3.1.2
prohibited area
mounting arrangement, as stated by the manufacturer, of the two units of the detector in which the detector no
longer meets the requirements of this European Standard
3.1.3
incorrect operation
physical condition that causes an inappropriate signal or message from a detector
3.1.4
wire free detector
detector connected to convey information to the control and indicating equipment without using wires, such as
radio frequency signals
3.1.5
approach distance/make distance
separation distance between the two units of a detector that are being brought together at which an intrusion
signal or message is reversed
3.1.6
removal distance/break distance
separation distance between the two units of a detector that are being moved apart at which an intrusion
signal or message is generated
3.1.7
corresponding unit
part of the detector, comprising one or more components, to act and/or react via one or more connecting
field(s) and is as such related to the process unit of the detector
3.1.8
process unit
part of the detector, comprising one or more components, analysing the connecting field(s) and/or their
content(s) towards the corresponding unit and which generates an appropriate signal or message
3.1.9
lock state contact
detector which consists usually out of two separate units, where each of the units (process unit and
corresponding unit) is mounted within one of the two parts of the monitored object (fixed and moving parts)
while allowing to monitor the lock state only or the lock and the open state simultaneously
Note 1 to entry: The active connection between the two units is at least one connecting field. Separating the two units
disturbs the connection and produces an intrusion signal or message.
3.1.10
sealed contact
type of detector construction, whereby there is no direct access to the internal components or connections,
e.g. a “potted” unit usually supplied with integral connecting cable
3.1.11
reverse signal
signal or message generated by a detector to indicate that there is no longer an intrusion event, e.g. change
of state or cancellation of an intrusion signal or message
3.1.12
intrusion event
abnormal condition indicating the presence of a hazard
3.1.13
low supply voltage
supply voltage level below which the operation of the detector can no longer be guaranteed
3.1.14
interference test unit
unit(s) (e.g. magnet(s), RFID tag(s)) - similar to the corresponding unit - used for verifying the behaviour of the
detector in the presence of external connecting field(s), at least one of which is identical to the corresponding
unit supplied with the detector, whereas technology depending internal different states are valid
3.1.15
external connecting field
deliberately induced connecting field generated by a source other than the corresponding or process unit
(e.g. sabotage magnet, RFID Tag)
3.1.16
immunity
characteristic of a detector such that only a limited change in its detection performance is permitted in the
presence of one of the interference test unit(s)
3.1.17
pure interference test magnet
unsealed magnetic field generating component (pure magnet) of the corresponding unit not mounted or build
into the corresponding unit housing which is used for mounting or installation
3.2 Abbreviations
For the purposes of this document, the abbreviations given in EN 50131-1:2006 and the following apply.
— AC Alternative Current;
— BTD Basic Test of Detection capability;
— DC Direct Current;
— EMC Electromagnetic Compatibility;
— RFID Radio Frequency Identification.
4 Functional requirements
4.1 Events
The detector shall respond to events in accordance with Table 1 and as defined in this Clause 4.
Table 1 — Events to be processed and main functions to be provided by grade
Event to be processed and Grade
functions to be provided
1 2 3 4
Break distance exceeded M M M M
Inside make distance M M M M
a
Remote enable of detection indication Op Op M M
Connecting field interference Op Op M M
b c c c
Prevention and detection of access to the Op M M M
inside of the detector
d
Removal from the mounting surface Op M M M
e
Low power supply voltage Op Op M M
f
Total loss of external power M M M M
g g
Matched pairs, coding and encryption Op Op M M
Key
M = Mandatory
Op = Optional
a
Only required if detection indicator present.
b
Generation of a tamper signal for opening by normal means is not required.
c
Not required for sealed lock state contacts according to 4.5.2.
d
Mandatory for wire-free at grades 2, 3 and 4; mandatory for all grade 4 types,
optional for wired grades 1, 2 and 3.
e
See 4.6.7.
f
See 4.6.6.
g
See 4.5.5.
4.2 Signals or messages
The response to the signals or messages generated by the detector is determined by the I&HAS. The detector
shall generate signals or messages in accordance with Table 2, based on the events listed in Table 1. The
response of a detector to events defined as optional in Table 1 shall be in accordance with Table 2.
Table 2 — Generation of signals or messages
Event Signals or messages
Intrusion Tamper Fault
Break distance exceeded M NP NP
Inside make distance NP NP NP
a
Magnetic interference grade 3 Op Op Op
b
Magnetic interference grade 4 M Op M
Detection of access to the inside of the NP M NP
detector
Removal from the mounting surface NP M NP
c
Low power supply voltage Op Op M
d
Total loss of external power M Op Op
Key
M = Mandatory
NP = Not Permitted
Op = Optional
a
Required only if the make and break distances are greater than twice the distances
specified by the manufacturer (see 6.6.4); at least one of these signals or messages
(Intrusion or/and Tamper or/and Fault) shall be generated or an independent signal or
message shall be generated.
b
Required only if the make and break distances are greater than twice the distances
specified by the manufacturer (see 6.6.4); either intrusion AND fault signals or messages,
OR an independent signal or message shall be generated.
c
See 4.6.7.
d
See 4.6.6.
4.3 Detection
4.3.1 Detection performance
4.3.1.1 Generalities
The operating parameters of the detector shall be verified as specified by the manufacturer for the axes of
movement shown in Annex D. The operating parameters shall be defined under the condition that a
successful locking position is ensured.
The manufacturer shall clearly state in the product documentation all removal/break and approach/make
distances including their tolerance range for each distance in order to specify all potential variances due to
product design and manufacturing.
Furthermore, the manufacturer shall clearly state as well in the product documentation any special limitation
concerning installation e.g. a prohibited area between a surface on the detector and the minimum make
distance.
4.3.1.2 Removal/break distance
The detector shall generate an intrusion signal or message at the removal/break distance specified by the
manufacturer. This distance shall be specified for all normal operating axes. If the detector is designed for
installation on ferromagnetic surfaces or in ferromagnetic material, the removal/break distance shall also be
specified for all normal operating axes when the detector is mounted using the material as specified in
Annex E.
4.3.1.3 Approach/make distance
The detector shall generate a reverse signal or message at the minimum separation distance(s) specified by
the manufacturer. This distance(s) shall be specified for all normal operating axes. If the detector is designed
for installation on ferromagnetic surfaces or in ferromagnetic material, the approach/make distance shall be
specified for all normal operating axes when the detector is mounted using the material as specified in
Annex E.
4.3.2 Indication of detection
When a detection indicator is provided to show when an intrusion signal or message is generated and in
normal operation visible (e.g. surface mounted contacts) when installed according to the manufacturer's
instructions, this indicator shall be capable of being enabled and disabled.
The adjustment to enable or disable this indication locally within the detector shall only be accessible when
the detector is opened by normal means, in case of opening is required.
A detector at grade 3 or grade 4 shall be capable of receiving indication enable and disable commands from
the CIE when such an indicator is present, according to clause one of this paragraph.
4.4 Operational requirements
4.4.1 Time interval between intrusion signals or messages
Detectors using wired interconnections shall be able to provide an intrusion signal or message not more than
15 s after the end of the preceding intrusion signal or message.
Detectors using wire free interconnections shall be able to provide an intrusion signal or message after the
end of the preceding intrusion signal or message within the following times:
–  Grade 1 300 s;
–  Grade 2 180 s;
–  Grade 3 30 s;
–  Grade 4 15 s.
4.4.2 Switch on delay
Where a detector requires an internal or external power supply in accordance with 4.6, the detector shall meet
all functional requirements within 180 s of the power supply reaching its nominal voltage.
4.4.3 Fault condition signals
A detector shall generate a fault signal or message in accordance with the manufacturer’s specification and
the provisions of Table 2 in the presence of a fault condition, according to Table 1, or as result of an internal
self-test, if this feature is provided.
4.5 Tamper security
4.5.1 Tamper security requirements
All terminals and means of mechanical and electronic adjustments shall be located within the detector’s
housings.
The tamper security requirements for each grade of detector are shown in Table 1.
4.5.2 Resistance to and detection of unauthorised access to the inside of the detector through
covers and existing holes
Access holes shall not allow interference with the operation of the detector by probing with commonly
available tools. Damage shall not be caused that would prevent normal operation.
If the detector can be opened, a tool shall be required to open the unit. For grades 2, 3 and 4 detectors all
covers giving access to components that could adversely affect the operation of the detector shall be fitted
with a tamper detection device that shall generate signals or messages in accordance with Table 2. It shall not
be possible to gain such access without generating a tamper signal or message or causing visible damage.
Sealed contacts do not require the means to detect access to the inside of the detector.
4.5.3 Detection of removal from the mounting surface
Means shall be provided which generate a tamper signal or message in accordance with Table 2 if the
detector is removed from the mounting surface. Operation of the tamper detection means shall not be
compromised by deliberate tamper actions before access can be gained to it and the means had been
activated.
4.5.4 Magnetic or electromagnetic field interference
When the detector is mounted in accordance with the manufacturer’s instructions in the target application
environment (e.g. window frame) and is subject to the presence of an external field, which is based on the
same physical principal as the connecting field (e.g. magnetic or electromagnetic) generated by:
• the interference test unit as specified in Annex A and one interference test unit which is identical to the
corresponding unit, each applied to the faces of the detector according to Annex F for purely magnetic
field based products (one after one) to generate an external connecting field;
• an interference test unit based on the same physical principal and digital identification means (e.g. tag
number provided by a RFID field, if encryption is not provided) applied to the faces of the detector
according to Annex F to generate an external connecting field;
the detector shall either:
a) be immune to any influence by each of the interference test units and continue to operate normally with
the make and break distances not exceeding twice those specified in accordance with 4.3.1, or
b) generate an intrusion, and/or tamper, and/or fault, and/or other independent signal or message in
accordance with Table 2 when the make or break distances exceed twice those specified in accordance
with 4.3.1; these signals or messages may be generated either on application of the interference test unit
or when the corresponding unit has returned to its original installed position.
NOTE The signals or messages generated by a grade 4 detector are intended to be used by the I&HAS to positively
identify an attempt to sabotage the detector through magnetic or electromagnetic field interference.
In case of purely magnetic field based products, a further interference test shall be performed to identify and
avoid specific critical points at the process unit where magnetic interference or manipulation could be possible
(e.g. to reduce the risk of manipulation which simulates that the window is in a closed and locked state of the
process unit of an open window). Therefore, the pure interference test magnet shall be applied at any selected
area or directly to each accessible surface of the process unit, while no other magnetic fields shall have
influence (e.g. corresponding unit or interference test unit). In that case, in accordance with Table 2, the
detector shall generate a tamper, and/or fault, and/or other independent signal or message; alternatively, for
Grade 3 products, the process unit shall stay in the state that represents an intrusion event.
4.5.5 Matched pairs, coding and encryption
This requirement applies to all grade 4 detectors and grade 3 detectors based on digital identification means
and do not apply to grade 3 detectors purely magnetic field based products.
If a grade 4 detector is a purely magnetic field based product, it shall consist of a matched pair of switch
component and corresponding unit or similar means. The means of matching shall have a minimum of
8 differs. It shall not be possible to determine the specific pair identity by visual inspection of the detector.
If the connection between the process and the corresponding unit relies purely on digital identification means
(e.g. tag number provided by a RFID field), it shall not be easily possible to simply read out the digital
identification information and to generate a copy of the unit that holds the digital identification information. This
applies to grade 3 and grade 4 digital identification means based products.
In such cases, encryption, rolling code or other protection mechanisms shall provide a certain level of security.
4.6 Electrical requirements
4.6.1 Grade dependencies
The requirements of 4.6.2 to 4.6.6 only apply to detectors having external power to operate the components of
the detector. The grade dependent application is given in Table 3.
Table 3 — Electrical requirements
Test Grade 1 Grade 2 Grade 3 Grade 4
Detector current consumption Required Required Required Required
Input voltage range Required Required Required Required
Slow input voltage rise Not required Required Required Required
Input voltage ripple Not required Required Required Required
Input voltage step change Not required Required Required Required
4.6.2 Detector current consumption
The detector's quiescent and maximum current consumption shall not exceed the figures claimed by the
manufacturer at the nominal input voltage by more than 20 % in either mode.
4.6.3 Slow input voltage change and input voltage range limits
The detector shall meet all functional requirements when the input voltage lies between ± 25 % of the nominal
value, or between the manufacturer's stated values if greater. When the supply voltage is raised slowly, the
detector shall function normally at the specified range limits.
4.6.4 Input voltage ripple
The detector shall meet all functional requirements during the modulation of the input voltage by a peak to
peak voltage of 10 % of the nominal value, at a frequency of 100 Hz.
4.6.5 Input voltage step change
No signals or messages shall be caused by a step in the input voltage between nominal and maximum and
between nominal and minimum.
4.6.6 Total loss of external power
This subclause does not apply to detectors with internal power supplies or detectors in bus systems.
This does not include any applied voltage to a purely mechanical (e.g. pure magnetic field / reed switch)
based detector. This test only applies to wired and wire free grade 4 detectors and wire free grade 3
detectors.
An intrusion signal or message shall be generated by the total loss of the supply voltage. No generation of a
message or signal is required when this total loss of external power condition is detected by the CIE due to
system design, e.g. bus based systems.
4.6.7 Low supply voltage
This subclause applies to detectors that require either internal or external power supplies.
This does not include any applied voltage to a purely mechanical (e.g. pure magnetic field/reed switch) based
detector. This test only applies to wired and wire free grade 4 detectors and wire free grade 3 detectors.
A fault signal or message shall be generated when the minimum level of voltage that is required for the
detector to operate reliably is compromised according to the specification of the manufacturer. No generation
of a message or signal is required when this low power condition is detected by the CIE due to system design,
e.g. bus based systems.
4.6.8 Interconnection Integrity
The detector shall provide means to enable the I&HAS to monitor the integrity of the interconnection. Where
the interconnecting cable or wire is provided with the detector, means shall be provided to permit the
monitoring of this interconnecting cable in accordance with EN 50131-1 (e.g. a tamper loop or end of line
resistor built into the body of the detector).
This requirement may be fulfilled either by the detector itself or by suitable system design.
4.7 Environmental classification and conditions
4.7.1 Environmental classification
The environmental classification is described in EN 50131-1 and shall be specified by the manufacturer.
4.7.2 Immunity to environmental conditions
Detectors shall meet the requirements of the relevant environmental tests described in EN 50130-5 and
EN 50130-4 at the severity levels defined in Table 4 and in Table 5.
For all grades, the detector shall not generate or be affected by the EMC conditions and severity levels
defined in EN 50130-4.
Unless specified otherwise for operational tests, the detector shall not generate unintentional intrusion,
tamper, fault or other signals or messages when subjected to the specified range of environmental conditions.
Impact tests shall not be carried out on delicate detector components such as LEDs.
For endurance tests, the detector shall continue to meet the requirements of this European Standard after
being subjected to the specified range of environmental conditions.
5 Marking, identification and documentation
5.1 Marking and/or identification
Marking and/or identification shall be applied to the product in accordance with the requirements of
EN 50131-1.
5.2 Documentation
The product shall be accompanied with clear and concise documentation in accordance with EN 50131-1. The
documentation shall additionally state for the corresponding grade dependent functions:
a) a list of all options, functions, inputs, indications, signals or messages and their relevant characteristics;
b) the recommended mounting configuration, details of suitable fixing methods, prohibited areas, mounting
location and siting requirements;
c) a statement of the operational approach/make and removal/break distances on ferromagnetic and non-
ferromagnetic mounting surfaces for all recommended configurations and operational axes including all
tolerances as described in 4.3.1.1;
d) the effect of any adjustable controls on the detector’s performance;
e) any disallowed field adjustable control settings or combinations of these;
f) the operating voltage range and/or nominal operating voltage and the maximum and quiescent detector
current consumption at this nominal voltage, if applicable;
g) the value of supply voltage below which a fault signal is generated, if applicable;
h) if the direct installation in or on ferromagnetic material is supported, this should be mentioned in the
product documentation, including all relevant potential material or/and changes to any product
characteristics due to that installation environment (e.g. make / break distances, tolerances, etc.);
i) information for the test facility only on what functions are being tested during a local or / and remote self-
test and what actions or alterations are required to simulate a self-test failure;
j) if the connection between the process and the corresponding unit relies purely on digital identification
means (e.g. tag number provided by a RFID field), the manufacturer shall describe the basic technology
used for pairing of the process and the corresponding unit and the fundamentals of the encryption of the
communication process between the paired components for the test facility only, including a potential test
method to verify the requirements of 4.5.4 and 4.5.5.
6 Testing
6.1 Generalities
The tests are intended to be primarily concerned with verifying the correct operation of the detector to the
specification provided by the manufacturer. All the test parameters specified shall carry a general tolerance
of ± 10 % unless otherwise stated. A list of tests appears as a general test matrix in Annex B.
6.2 General test conditions
6.2.1 Standard laboratory conditions for testing
The general atmospheric conditions in the measurement and
...

Questions, Comments and Discussion

Ask us and Technical Secretary will try to provide an answer. You can facilitate discussion about the standard in here.

Loading comments...