oSIST prEN 302 099 V2.3.0:2026
(Main)Environmental Engineering (EE) - Powering of equipment in access network
- Abstract
REN/EE-027017
- Status
- Not Published
- Public Enquiry End Date
- 30-Nov-2026
- Technical Committee
- SPN - Services and Protocols for Networks
- Current Stage
- 4020 - Public enquire (PE) (Adopted Project)
- Start Date
- 21-Sep-2026
- Due Date
- 08-Feb-2027
- Completion Date
- 26-Nov-2026
oSIST prEN 302 099 V2.3.0:2026 is the Slovenian adoption of ETSI EN 302 099 V2.3.0 (2026-09). It specifies how to power telecommunications equipment in access networks, including local powering, remote powering and reverse powering, and it ties those choices to safety, EMC, protection, environmental conditions and power-management data.
This standard is for access-network equipment in copper, fibre, hybrid and radio networks, whether the equipment is in telecom centres, local exchanges, street cabinets, buildings or customer premises. In practice, it helps operators, equipment suppliers and installers choose a powering architecture and interface that fits the network, the site and the service continuity target.
What does oSIST prEN 302 099 V2.3.0:2026 specify?
oSIST prEN 302 099 V2.3.0:2026 specifies the principles and requirements for powering Telecommunications Equipment (TE) in access networks. It covers the power-unit interfaces, power-protection recommendations, the management data needed for availability, and the organization of local and remote powering in modern access networks.
The scope includes traditional copper-based access and Next Generation Access (NGA) networks based on fibre or hybrid fibre/copper, as well as radio access. It also addresses equipment inside or outside telecommunications centres and local exchanges, and it explicitly considers customer-premises equipment and reverse powering from the customer side.
The document is organized into the following main parts and annexes.
| Part | What it covers |
|---|---|
| Clauses 5 to 8 | Powering configurations, technology impact, local powering and remote powering |
| Clause 9 | Power source interruption management |
| Clause 10 | Power management and alarms |
| Clause 11 | Safety, EMC, protection, earthing and wiring requirements |
| Clause 12 | Environmental conditions |
| Annex A | Public grid availability data and its relevance for access-network powering |
| Annex B | Battery sizing, back-up power, autonomy and battery tests |
| Annex C | Comparative reliability approach for remote powering versus local powering |
| Annex D | Bibliography |
| Annex E | Change history |
What are the key requirements of oSIST prEN 302 099 V2.3.0:2026?
oSIST prEN 302 099 V2.3.0:2026 sets out the main powering options for access-network TE and links each option to the appropriate interfaces, backup approach and safety constraints. The practical message is simple: the powering method must match the network topology, the equipment location and the expected service continuity.
Powering architecture has to follow the network layout
Clause 5 distinguishes centralized powering, cluster powering, local powering and reverse powering. It also shows how the same access network can be powered in different ways depending on whether the link to the telecom centre is metallic or non-metallic.
In practice, this means the reader has to decide where power is sourced, where backup is provided and whether power is distributed by the telecom centre, by a local power unit or by the customer. That decision affects cabling, maintenance, space, battery strategy and failure behavior.
Local powering uses defined interface families
Clause 7 covers TE with a local power plant or local power unit (LPU). The document uses the established interface families for -48 VDC, 230 VAC, 50 Hz and up to 400 VDC, and it notes that other DC voltages are outside the document’s coverage.
For equipment designers and buyers, this means the supply interface has to be checked early. A site can use an LPU for short-time protection and power conversion, or it can feed the TE directly from the mains if the installation is designed for that arrangement.
Remote powering is controlled at both the source and the receiver
Clause 8 defines the Remote Power Unit (RPU), the Remote Power Receiver (RPR), RFT-V and RFT-C operation, and the up to 400 VDC remote-powering case. It also sets the framework for input characteristics, output behavior, steady-state operation, transients and safe start-up.
In practice, this is the clause that a system integrator uses to verify that the source, line and receiver work as one system. It matters for line length, number of receivers on a line, fault handling, voltage drop, and whether the remote power line is used in voltage mode, current mode or up to 400 VDC mode.
Reverse powering has extra wiring and protection constraints
Clause 5.2.3 and clause 8.0 cover reverse powering from customer premises, and clause 5.2.3.2 focuses on wiring and electrical limitations on copper pairs. The standard ties reverse powering to the safety standards for the cable and the network interface, and it requires protection against additive power and return currents when more than one Power Sourcing Equipment is present on the wiring.
For a planner or installer, this means reverse powering is not just a functional choice - it is also an electrical and installation-design choice. The wiring, connectors, current limitation and fault protection all have to be considered together.
Interruption management and backup are treated as a system question
Clause 9 recognizes that many NGA installations rely on short filtering of dips and interruptions rather than long battery autonomy. Annex B then gives guidance for battery sizing, autonomy and battery state-of-health testing.
In practice, this helps operators decide whether backup should sit in the cabinet, the telecom centre, the remote power source or not be used at all. Annex A and Annex C support that decision with grid-availability and comparative-reliability information.
Power management, alarms and remote monitoring are part of the design
Clause 10 requires the operating status of the power and backup equipment to be known to the network operator. It also links centralized power, local power, cluster power and reverse powering to alarm reporting, local indication and management interfaces.
This matters because power failures are not just electrical events - they are operational events. The standard expects failure states such as input loss, module failure, protection-device opening, battery condition and reverse-power interruption to be visible to management systems.
Safety, EMC, earthing and environmental conditions must be respected
Clause 11 covers product safety, EMC, resistibility, earthing and bonding, and the wiring rules for remote power feeding up to 400 VDC. Clause 12 links the solution to the environmental class appropriate to the installation location.
For implementation, this means the power solution has to fit the installation site as well as the electronics. The standard points to the relevant earthing practice for central offices, customer premises and remote sites, and to the environmental classifications for indoor, outdoor and underground locations.
What terms does oSIST prEN 302 099 V2.3.0:2026 define?
- Access network - The part of the telecommunications network between the Network Termination/Access Gateway and the first switching unit.
- Local Power Unit (LPU) - A power supply unit located at the same site as the TE and used to supply that equipment.
- Remote Power Unit (RPU) - A unit that takes power from the grid or a DC power system and sends remote DC along power lines to distant TE or an RPR.
- Remote Power Receiver (RPR) - The unit that receives remote DC from an RPU and converts it to the input power interface of the TE or radio unit.
- Remote Powering (RP) - Power feeding of TE by a remote power circuit made up of an RPU, distribution wiring and fed receivers.
- RFT-V - An RFT circuit designed so that voltage is limited under normal and single-fault conditions, with a limited accessible contact area.
- RFT-C - An RFT circuit designed so that current is limited under normal and single-fault conditions.
Who uses oSIST prEN 302 099 V2.3.0:2026?
oSIST prEN 302 099 V2.3.0:2026 is used by telecom network operators, access-network designers, equipment manufacturers, installers and maintenance teams. It is also relevant for quality, safety and procurement staff who need to specify how access-network equipment is powered in FTTH, FTTC, FTTB, FTTdp, hybrid and radio deployments.
It is particularly useful when deciding between local powering, remote powering, cluster powering or reverse powering for street cabinets, central offices, local exchanges and customer-premises equipment.
What changed in oSIST prEN 302 099 V2.3.0:2026 from the previous edition?
Annex E states that this version removes the reference to ETSI EN 300 132-3-1 and replaces it with ETSI EN 300 132-3. It also says that general updates were made to align the document with current standards and technologies.
Which standards are used with oSIST prEN 302 099 V2.3.0:2026?
| Reference | What it contributes |
|---|---|
| ETSI EN 300 132-1 / -2 / -3 | Power interface requirements for AC, -48 VDC and up to 400 VDC equipment inputs |
| IEC 62368-3 / IEC EN 62368-3 | Safety aspects for DC power transfer through communication cables and ports; RFT-V and RFT-C behavior |
| EN 60038 | Nominal voltage framework for AC supply in Europe |
| EN 60664-1 | Insulation coordination and test principles for low-voltage systems |
| EN 50310 | Equipotential bonding and earthing in buildings with IT equipment |
| ETSI EN 300 253 | Earthing and bonding for ICT equipment powered by -48 VDC in telecom and data centres |
| ITU-T K.35 | Bonding configurations and earthing at remote electronic sites |
| ITU-T K.45 | Resistibility to overvoltages and overcurrents in access and trunk networks |
| ETSI ES 203 215 / EN 303 215 | Measurement methods and limits for power consumption in broadband telecommunication networks equipment |
| ETSI ES 202 336-1 / -8 / -11 | Monitoring, control and information models for infrastructure equipment and battery systems |
| ETSI TS 101 548-1 | Reverse powering requirements for remote access equipment over twisted pair networks |
| ETSI EN 301 605 | Earthing and bonding for 400 VDC ICT equipment and high-ohmic mid-point grounding |
| HD 60364 series / HD 60364-1 | Low-voltage electrical installations and fundamental principles for installation design |
| ETSI ES 203 408 | Colour and marking of DC cable and connecting devices |
| ETSI EN 302 999 | Safety requirements for the erection and operation of remote power feeding installations |
| ETSI EN 300 019-1-1 / -1-3 / -1-4 / -1-8 | Environmental condition classifications for storage and stationary use in protected, unprotected and underground locations |
What does the oSIST prEN 302 099 V2.3.0:2026 document contain?
The document contains configuration figures for centralized, cluster, local and reverse-powered access networks, plus tables for management alarms and example safety standards. It also includes battery-sizing guidance with worked examples, a comparative reliability approach using MTBF and MTTR concepts, and environmental-class examples for different installation locations.
For implementation work, the most useful parts are clause 5 for architecture selection, clause 8 for remote-power behavior, clause 10 for alarms and monitoring, clause 11 for safety and wiring, and Annex B and Annex C for backup and reliability decisions.
Get Certified
Connect with accredited certification bodies for this standard

ANCE
Mexican certification and testing association.

IMP NDT d.o.o.
Non-destructive testing services. Radiography, ultrasonic, magnetic particle, penetrant, visual inspection.

Inštitut za kovinske materiale in tehnologije
Institute of Metals and Technology. Materials testing, metallurgical analysis, NDT.
Sponsored listings
Frequently Asked Questions
oSIST prEN 302 099 V2.3.0:2026 is a standard published by the Slovenian Institute for Standardization (SIST). Its full title is "Environmental Engineering (EE) - Powering of equipment in access network". This standard covers: REN/EE-027017
REN/EE-027017
oSIST prEN 302 099 V2.3.0:2026 is classified under the following ICS (International Classification for Standards) categories: 19.040 - Environmental testing; 33.050.01 - Telecommunication terminal equipment in general. The ICS classification helps identify the subject area and facilitates finding related standards.
oSIST prEN 302 099 V2.3.0:2026 is available in PDF format for immediate download after purchase. The document can be added to your cart and obtained through the secure checkout process. Digital delivery ensures instant access to the complete standard document.
Standards Content (Sample)
Contents
- 1 Scope
- 2 References
- 2.1 Normative references
- 7 Draft ETSI EN 302 099 V2.3.0 (2026-09)
- 2.2 Informative references
- 8 Draft ETSI EN 302 099 V2.3.0 (2026-09)
- 9 Draft ETSI EN 302 099 V2.3.0 (2026-09)
- 3 Definition of terms, symbols and abbreviations
- 3.1 Terms
- 10 Draft ETSI EN 302 099 V2.3.0 (2026-09)
- 3.2 Symbols
- 11 Draft ETSI EN 302 099 V2.3.0 (2026-09)
- 3.3 Abbreviations
- 12 Draft ETSI EN 302 099 V2.3.0 (2026-09)
- 4 Introduction
- 4.1 General
- 5 Powering configurations
- 5.0 General
- 13 Draft ETSI EN 302 099 V2.3.0 (2026-09)
- 14 Draft ETSI EN 302 099 V2.3.0 (2026-09)
- 15 Draft ETSI EN 302 099 V2.3.0 (2026-09)
- 5.1 Remote powering architectures
- 16 Draft ETSI EN 302 099 V2.3.0 (2026-09)
- 17 Draft ETSI EN 302 099 V2.3.0 (2026-09)
- 18 Draft ETSI EN 302 099 V2.3.0 (2026-09)
- 19 Draft ETSI EN 302 099 V2.3.0 (2026-09)
- 5.2 Local powering architecture configurations
- 20 Draft ETSI EN 302 099 V2.3.0 (2026-09)
- 21 Draft ETSI EN 302 099 V2.3.0 (2026-09)
- 22 Draft ETSI EN 302 099 V2.3.0 (2026-09)
- 6 Effect of the technologies on the powering strategy
- 6.0 General
- 23 Draft ETSI EN 302 099 V2.3.0 (2026-09)
- 6.1 Powering strategy of family 1: metallic links
- 24 Draft ETSI EN 302 099 V2.3.0 (2026-09)
- 6.2 Powering strategy of family 2: non-metallic links
- 7 Requirements for local powering
- 7.1 TE including the power plant
- 7.2 TE powered by a DC voltage nominal -48 VDC or up to
- 25 Draft ETSI EN 302 099 V2.3.0 (2026-09)
- 7.3 TE powered by a LPU with a DC voltage other
- 7.4 TE powered by a nominal AC voltage of 230 VAC, 50 Hz
- 8 Requirements for remote powering
- 8.0 Remote powering solutions
- 8.1 Input of the Remote Power Unit (RPU)
- 26 Draft ETSI EN 302 099 V2.3.0 (2026-09)
- 8.2 Output characteristics of the Remote Powering system
- 27 Draft ETSI EN 302 099 V2.3.0 (2026-09)
- 28 Draft ETSI EN 302 099 V2.3.0 (2026-09)
- 8.3 Input characteristics of remote power receiver
- 29 Draft ETSI EN 302 099 V2.3.0 (2026-09)
- 9 Power source interruption management
- 10 Power management
- 30 Draft ETSI EN 302 099 V2.3.0 (2026-09)
- 31 Draft ETSI EN 302 099 V2.3.0 (2026-09)
- 32 Draft ETSI EN 302 099 V2.3.0 (2026-09)
- 11 Safety, EMC, protection
- 11.1 Product Safety
- 33 Draft ETSI EN 302 099 V2.3.0 (2026-09)
- 11.2 EMC
- 11.3 Protection/resistibility
- 11.4 Earthing and bonding of access network powering solutions
- 34 Draft ETSI EN 302 099 V2.3.0 (2026-09)
- 11.5 Wiring requirements of remote power feeding to TE through
- 35 Draft ETSI EN 302 099 V2.3.0 (2026-09)
- 12 Environmental conditions
- 36 Draft ETSI EN 302 099 V2.3.0 (2026-09)
- 37 Draft ETSI EN 302 099 V2.3.0 (2026-09)
- 38 Draft ETSI EN 302 099 V2.3.0 (2026-09)
- 39 Draft ETSI EN 302 099 V2.3.0 (2026-09)
- 40 Draft ETSI EN 302 099 V2.3.0 (2026-09)
- 41 Draft ETSI EN 302 099 V2.3.0 (2026-09)
- 42 Draft ETSI EN 302 099 V2.3.0 (2026-09)
- 43 Draft ETSI EN 302 099 V2.3.0 (2026-09)
- 44 Draft ETSI EN 302 099 V2.3.0 (2026-09)
- 45 Draft ETSI EN 302 099 V2.3.0 (2026-09)
- Bibliography
- 46 Draft ETSI EN 302 099 V2.3.0 (2026-09)
- 47 Draft ETSI EN 302 099 V2.3.0 (2026-09)
1 Scope
The present document describes the principles for powering of Telecommunications Equipment (TE) in access networks (both traditional copper based and Next Generation fibre and/or hybrid based) and contains requirements for the powering systems, laying down:
- the characteristics of the input and output interfaces of the power units; the recommendations for TE power protection, also regarding network integrity and public services availability requirements;
- the management data, necessary to guarantee the required availability of the network and provided public services and to ensure the maintenance of the TE power units.
The present document takes into account the innovative characteristics of fibre-based access network equipment and considers the intrinsic limitations of local power plants and power distribution when ICT equipment is installed inside telecom centre, local exchanges, street cabinets or inside buildings: it goes from "complete integration of the power plant in the TE" to "remote power feeding from a distant power plant". The present document provides detailed information in annex A on the improved reliability of public electric power grid and on the improved reliability and availability of new fibre-based NGA network. It should be considered that, for street cabinet TE, the local power scenario is common, and, in that case, the main power supply availability characteristics are mainly based on electrical energy provider's performance.
The present document applies to the powering of all equipment of the access network (copper, fibre or radio networks) located inside or outside telecommunications centres or local exchanges, differentiating the applicable and sustainable power protection requirements. The access network is defined as the part of the telecommunications network, which comprises the network termination (passive or active) that is installed inside customer premises and the first exchange that can be also the broadband local exchange.
2 References
2.1 Normative references
References are either specific (identified by date of publication and/or edition number or version number) or non-specific. For specific references, only the cited version applies. For non-specific references, the latest version of the referenced document (including any amendments) applies.
Referenced documents which are not found to be publicly available in the expected location might be found in the ETSI docbox.
NOTE: While any hyperlinks included in this clause were valid at the time of publication, ETSI cannot guarantee their long-term validity.
The following referenced documents are necessary for the application of the present document. [1] ETSI EN 300 132-1: "Environmental Engineering (EE); Power supply interface at the input to Information and Communication Technology (ICT) equipment; Part 1: Alternating Current (AC)". [2] ETSI EN 300 132-2: "Environmental Engineering (EE); Power supply interface at the input of Information and Communication Technology (ICT) equipment; Part 2: -48 V Direct Current (DC)".
[3] IEC 62368-3: "Audio/video, information and communication technology equipment - Part 3:
Safety aspects for DC power transfer through communication cables and ports". [4] EN 60038: "CENELEC standard Voltages", (produced by CENELEC). [5] EN 60664-1: "Insulation coordination for equipment within low-voltage systems - Part 1:
Principles, requirements and tests", (produced by CENELEC).
[6] EN 50310: "Application of equipotential bonding and earthing in buildings with information technology equipment", (produced by CENELEC).
ETSI
7 Draft ETSI EN 302 099 V2.3.0 (2026-09)
[7] ETSI EN 300 253: "Environmental Engineering (EE); Earthing and bonding of ICT equipment powered by -48 VDC in telecom and data centres".
[8] Recommendation ITU-T K.35: "Bonding configurations and earthing at remote electronic sites". [9] Recommendation ITU-T K.45: "Resistibility of telecommunication equipment installed in the access and trunk networks to overvoltages and overcurrents".
[10] ETSI ES 203 215: "Environmental Engineering (EE); Measurement Methods and Limits for Power Consumption in Broadband Telecommunication Networks Equipment". [11] ETSI EN 300 132-3: "Environmental Engineering (EE); Power supply interface at the input of Information and Communication Technology (ICT) equipment; Part 3: Up to 400 V Direct Current (DC)".
[12] ETSI ES 202 336-1: "Environmental Engineering (EE); Monitoring and Control Interface for Infrastructure Equipment (Power, Cooling and Building Environment Systems used in Telecommunication Networks); Part 1: Generic Interface".
[13] ETSI TS 101 548-1: "Access, Terminals, Transmission and Multiplexing (ATTM); European Requirements for Reverse Powering of Remote Access Equipment; Part 1: Twisted pair networks".
[14] ETSI EN 301 605: "Environmental Engineering (EE); Earthing and bonding of 400 VDC data and telecom (ICT) equipment".
[15] Void.
[16] HD 60364 series: "Low Voltage electrical installations", produced by CENELEC. [17] ETSI ES 202 336-8: "Environmental Engineering (EE); Monitoring and Control Interface for Infrastructure Equipment (Power, Cooling and Building Environment Systems used in Telecommunication Networks); Part 8: Remote Power Feeding System control and monitoring information model".
[18] ETSI ES 203 408: "Environmental Engineering (EE); Colour and marking of DC cable and connecting devices".
2.2 Informative references
References are either specific (identified by date of publication and/or edition number or version number) or non-specific. For specific references, only the cited version applies. For non-specific references, the latest version of the referenced document (including any amendments) applies.
NOTE: While any hyperlinks included in this clause were valid at the time of publication, ETSI cannot guarantee their long-term validity.
The following referenced documents may be useful in implementing an ETSI deliverable or add to the reader's understanding, but are not required for conformance to the present document. [i.1] ETSI EN 300 019-1-1: "Environmental Engineering (EE); Environmental conditions and environmental tests for telecommunications equipment; Part 1-1: Classification of environmental conditions; Storage".
[i.2] ETSI EN 300 019-1-3: "Environmental Engineering (EE); Environmental conditions and environmental tests for telecommunications equipment; Part 1: Classification of environmental conditions; Sub-part 3: Stationary use at weatherprotected locations". [i.3] ETSI EN 300 019-1-4: "Environmental Engineering (EE); Environmental conditions and environmental tests for telecommunications equipment; Part 1: Classification of environmental conditions; Sub-part 4: Stationary use at non-weatherprotected locations". ETSI
8 Draft ETSI EN 302 099 V2.3.0 (2026-09)
[i.4] ETSI EN 300 019-1-8: "Environmental Engineering (EE); Environmental conditions and environmental tests for telecommunications equipment; Part 1-8: Classification of environmental conditions; Stationary use at underground locations".
[i.5] Void.
[i.6] Void.
[i.7] HD 60364-1: "Low-voltage electrical installations - Part 1: Fundamental principles, assessment of general characteristics, definitions", (produced by CENELEC).
[i.8] ETSI EN 302 999: "Safety; Remote Power Feeding Installations; Safety requirements for the erection and operation of information technology installations with remote power feeding". [i.9] ENISA: "Power Supply Dependencies in the Electronic Communications Sector Survey, analysis and recommendations for resilience against power supply failures", December 2013. TH [i.10] Council of European Energy Regulators (CEER): "7 CEER-ECRB Benchmarking report on the quality of electricity and gas supply", Ref: C22-EQS-103-03.
[i.11] ARERA Annual report.
[i.12] ETSI TS 103 553-1: "Environmental Engineering (EE); Innovative energy storage technology for stationary use; Part 1: Overview".
[i.13] Void.
[i.14] Void.
[i.15] IEC EN 62368-3: "Audio/video, information and communication technology equipment - Part 3: Safety aspects for DC power transfer through communication cables and ports". [i.16] Recommendation ITU-T L.1001: "External universal power adapter solutions for stationary information and communication technology devices".
[i.17] IEC EN 62368-1: "Audio/video, information and communication technology equipment - Part 1: Safety requirements".
[i.18] Directive (EU) 2022/2555 of the European Parliament and of the Council of 14 December 2022 on measures for a high common level of cybersecurity across the Union, amending Regulation (EU) No 910/2014 and Directive (EU) 2018/1972, and repealing Directive (EU) 2016/1148 (NIS 2 Directive).
[i.19] ETSI EN 303 215: "Environmental Engineering (EE); Measurement methods and limits for power consumption in broadband telecommunication networks equipment". [i.20] Void.
[i.21] TR 62102: "Electrical safety - Classification of interfaces for equipment to be connected to information and communications technology networks", (produced by CENELEC). [i.22] Void.
[i.23] Recommendation ITU-T L.1220 (2017-08): "Innovative energy storage technology for stationary use - Part 1: Overview of energy storage".
[i.24] Void.
[i.25] Recommendation ITU-T L.1202 (2015): "Methodologies for evaluating the performance of an up to 400 VDC power feeding system and its environmental impact". [i.26] Void.
[i.27] Broadband Forum oneM2M TR-301: "Architecture and Requirements for Fiber to the Distribution Point".
ETSI
9 Draft ETSI EN 302 099 V2.3.0 (2026-09)
[i.28] ETSI TS 103 553-2: "Environmental Engineering (EE); Innovative energy storage technology for stationary use; Part 2: Battery".
[i.29] ETSI TS 103 553-3: "Environmental Engineering (EE); Innovative energy storage technology for stationary use; Part 3: Supercapacitor".
[i.30] ETSI ES 202 336-11: "Environmental Engineering (EE); Monitoring and control interface for infrastructure equipment (Power, Cooling and environment systems used in telecommunication networks); Part 11: Battery system with integrated control and monitoring information model". [i.31] Recommendation ITU-T I.112: "Vocabulary of terms for ISDNs". [i.32] Recommendation ITU-T L.1221: "Innovative energy storage technology for stationary use - Part 2: Battery".
[i.33] Recommendation ITU-T L.1222: "Innovative energy storage technology for stationary use - Part 3: Supercapacitor technology".
[i.34] Recommendation ITU-T L.1200 (May 2012): "Direct current power feeding interface up to 400 V at the input to telecommunication and ICT equipment".
3 Definition of terms, symbols and abbreviations
3.1 Terms
For the purposes of the present document, the following terms apply:
access gateway: gateway that interworks a significant number of analogue lines to a packet network and is located at the operator's premises access network: part of a telecommunications network between the Network Termination/Access Gateway and the first switching unit backfeeding or reverse powering: powering architecture that can supply power to access network units from the customer through its final distribution access copper pair NOTE: Access network units may be ONU, ONT or remote DSL units. centralized powering: remote powering in which the remote feeding source is located in a telecommunications centre cluster powering: remote powering of a cluster of equipment (1 to n items of equipment), in which the remote feeding source is located outside a telecommunications centre electric energy provider: provider of electrical energy from the public grid (mains) ES1, ES2, ES3: See IEC EN 62368-1 [i.17].
interface A: -48 VDC power interface at input of Telecom/ICT equipment with voltage range and other electrical specifications defined in ETSI EN 300 132-2 [2] interface A1: up to 400 VAC rms power interface at input of Telecom/ICT equipment with voltage range and other electrical specifications defined in ETSI EN 300 132-1 [1] interface A3: up to 400 VDC power interface at input of Telecom/ICT equipment with voltage range, and other electrical specifications defined in ETSI EN 300 132-3 [11] Local Power Unit (LPU): power supply equipment whose function is to supply a telecommunication equipment situated at the same location NOTE: It is generally locally connected to the mains and provides DC or AC voltage output to feed telecommunication equipment.
ETSI
10 Draft ETSI EN 302 099 V2.3.0 (2026-09)
local powering: powering principle of a telecommunications equipment by a (dedicated) power unit implemented in the same location network termination: functional group on the network side of a user-network interface NOTE: Source: Recommendation ITU-T I.112 [i.31].
primary circuit: See IEC EN 62368-1 [i.17].
protective device selectivity: coordination of the operating characteristics of two or more protective devices to ensure faulty equipment is safely disconnected with no or limited impact on other parts of the system PS1, PS2, PS3: See IEC EN 62368-1 [i.17].
Remote Feeding Telecommunication (RFT) circuit: secondary circuit within the equipment, intended to supply or receive DC power via a telecommunication network at voltages equal to or exceeding the limits for TNV circuits, and on which overvoltages from telecommunication networks are possible Remote Power Receiver (RPR): unit receiving remote DC from RPU though power lines and converting it to input power interface of a TE or a radio unit NOTE: The RPR may be an external unit with an adapted power interface (e.g. -48 VDC) or an integrated function of a telecommunications equipment.
Remote Power Unit (RPU): unit, powered by the grid or by a DC power system delivering -48 VDC or up to 400 VDC, which supplies remote DC on power lines to distant Telecommunication Equipment (TE) e.g. radio unit or RPR Remote Powering (RP): power feeding of a telecommunications equipment by a remote power circuit NOTE: Such a circuit consists of a remote power unit, distribution wiring, and fed receivers. RFT-C circuit: RFT circuit which is so designed and protected that under normal operating conditions and single fault conditions the currents in the circuit do not exceed defined values RFT-V circuit: RFT circuit which is so designed and protected that under normal operating conditions and single fault conditions the voltages are limited and the accessible area of contact is limited secondary circuit: See IEC EN 62368-1 [i.17].
SELV circuit: See IEC EN 62368-1 [i.17].
TN-C: See HD 60364-1 [i.7].
TN-S: See HD 60364-1 [i.7].
TNV circuit: See EN 62368-1 [i.24].
TT: See HD 60364-1 [i.7].
3.2 Symbols
For the purposes of the present document, the following symbols apply:
I , I I , I I , I , power interface 1 2 3 4 5 6 L- Power line of negative potential polarity L+ Power line of positive potential polarity S Signal S/P Filter separating signal S and power P filter ETSI
11 Draft ETSI EN 302 099 V2.3.0 (2026-09)
3.3 Abbreviations
For the purposes of the present document, the following abbreviations apply:
A Autonomy of a battery bat AC Alternating Current AN Access Node ANU Access Network Unit B Battery CB Circuit Breaker CO Central Office CPE Customer's Premises Equipment DC Direct Current DC/DC Direct Current/Direct Current NOTE: DC/DC are used in general in expression such as DC/DC converter or DC/DC conversion. DSL Digital Subscriber Line DSLAM Digital Subscriber Line Access Module Energy Capacity of a battery EC bat EMC ElectroMagnetic Compatibility FTTB Fibre To The Building FTTC Fibre To The Curb FTTCab Fibre To The Cabinet FTTdp Fibre To The distribution point FTTH Fibre To The Home HD Harmonization Document HTA Home Terminal Adaptor ICT Information & Communication Technology IEC International Electrical Committee ISDN Integrated Services Digital Network IT Information Technology ITU-T International Telecommunication Union - Telecommunication standardization sector LED Light Emitting Diode LPU Local Power Unit LV Low Voltage MDF Main Distribution Frame MP Mid-Point MTBF Mean Time Between Failure MTTR Mean Time To Repair NGA Next Generation Access ONT Optical Network Termination ONU Optical Network Unit P Power NOTE: Indices can be used associated with P as P in some clauses to clarify which power P is used in indice formula.
PD Powered Device PM Powering Method POTS Plain Old Telephone Service PSE Power Sourcing Equipment PSTN Public Switched Telephone Network PSU Power Supply Unit R Rectifier RFT Remote Feeding Telecommunication RFT-C Remote Feeding Telecommunication-Current RFT-V Remote Feeding Telecommunication-Voltage RP Remote Power RPR Remote Power Receiver RPU Remote Power Unit SAIDI System Average Interruption Duration Index ETSI
12 Draft ETSI EN 302 099 V2.3.0 (2026-09)
SAIFI System Average Interruption Frequency Index SELV Safety Extra Low Voltage TC Telecommunication Centre TE Telecom Equipment TLC TeLecommuniCation TNV Telecommunication Network Voltage UPS Uninterruptible Power Supply VRLA Valve Regulated Lead Acid
4 Introduction
4.1 General
Innovative fibre-based and hybrid-based NGA network TE has changed the traditional powering paradigm. The present document proposes the viable measures to comply with the integrity, availability and uninterrupted telephone/VoIP provision that the European Directive defines for public networks [i.18]. It describes different configurations of powering the TE and the impacts on networks and services continuity and reliability:
- Local power supply for TE (e.g. street cabinet, active network termination, etc.).
- Remote Feeding to TE from central office through copper access pair.
- Cluster Power supply feeding power for a cluster of TE.
- Remote power feeding to TE from centre or cluster power through a power cable.
- Back feeding or Reverse Powering architecture that can supply power to Access Network Units such as ONU or ONT or remote DSL unit from the customer premises through its final distribution access copper pair. The present document provides information on powering equipment, power strategy, local powering, remote powering, power management, safety. EMC and environmental requirements.
5 Powering configurations
5.0 General
Next Generation Access (NGA) networks induce changes in the powering model and in the need of local back-up, when compared to traditional access networks centre where the back-up is obtained by battery alone or with back-up generator source (Diesel, fuel cell).
Both fixed and mobile NGA networks, usually, require local powering of access network active equipment that are installed outside Central Offices and closer to the end user's premises, Typical NGA scenarios are fiber-based FTTH, hybrid FTTC/FTTCab, FTTdp and FTTB architectures.
The new local powering scenario of fibre-based or hybrid fibre/copper NGA networks of a public Telecom networks and services provider, shall include back-up measures in order to ensure to comply with continuity, availability and reliability requirements defined by European Directive [i.18]. But for FTTB, FTTC/FTTCab, FTTdp with the increasing deployment of a great number of distributed active small cabinets, that can be installed inside buildings (FTTB) or in the street (FTTC, FTTCab), the basic power supply backup autonomy has to be optimized, due to a large number of small active cabinets to be installed at optimized costs and dimensions. Only when it is required for some service offers, a long back-up autonomy is obtained by local battery extension or alternatively by remote powering solution proposed to avoid local energy storage.
ETSI
...
Contents
- 1 Scope
- 2 References
- 2.1 Normative references
- 7 Draft ETSI EN 302 099 V2.3.0 (2026-09)
- 2.2 Informative references
- 8 Draft ETSI EN 302 099 V2.3.0 (2026-09)
- 9 Draft ETSI EN 302 099 V2.3.0 (2026-09)
- 3 Definition of terms, symbols and abbreviations
- 3.1 Terms
- 10 Draft ETSI EN 302 099 V2.3.0 (2026-09)
- 3.2 Symbols
- 11 Draft ETSI EN 302 099 V2.3.0 (2026-09)
- 3.3 Abbreviations
- 12 Draft ETSI EN 302 099 V2.3.0 (2026-09)
- 4 Introduction
- 4.1 General
- 5 Powering configurations
- 5.0 General
- 13 Draft ETSI EN 302 099 V2.3.0 (2026-09)
- 14 Draft ETSI EN 302 099 V2.3.0 (2026-09)
- 15 Draft ETSI EN 302 099 V2.3.0 (2026-09)
- 5.1 Remote powering architectures
- 16 Draft ETSI EN 302 099 V2.3.0 (2026-09)
- 17 Draft ETSI EN 302 099 V2.3.0 (2026-09)
- 18 Draft ETSI EN 302 099 V2.3.0 (2026-09)
- 19 Draft ETSI EN 302 099 V2.3.0 (2026-09)
- 5.2 Local powering architecture configurations
- 20 Draft ETSI EN 302 099 V2.3.0 (2026-09)
- 21 Draft ETSI EN 302 099 V2.3.0 (2026-09)
- 22 Draft ETSI EN 302 099 V2.3.0 (2026-09)
- 6 Effect of the technologies on the powering strategy
- 6.0 General
- 23 Draft ETSI EN 302 099 V2.3.0 (2026-09)
- 6.1 Powering strategy of family 1: metallic links
- 24 Draft ETSI EN 302 099 V2.3.0 (2026-09)
- 6.2 Powering strategy of family 2: non-metallic links
- 7 Requirements for local powering
- 7.1 TE including the power plant
- 7.2 TE powered by a DC voltage nominal -48 VDC or up to
- 25 Draft ETSI EN 302 099 V2.3.0 (2026-09)
- 7.3 TE powered by a LPU with a DC voltage other
- 7.4 TE powered by a nominal AC voltage of 230 VAC, 50 Hz
- 8 Requirements for remote powering
- 8.0 Remote powering solutions
- 8.1 Input of the Remote Power Unit (RPU)
- 26 Draft ETSI EN 302 099 V2.3.0 (2026-09)
- 8.2 Output characteristics of the Remote Powering system
- 27 Draft ETSI EN 302 099 V2.3.0 (2026-09)
- 28 Draft ETSI EN 302 099 V2.3.0 (2026-09)
- 8.3 Input characteristics of remote power receiver
- 29 Draft ETSI EN 302 099 V2.3.0 (2026-09)
- 9 Power source interruption management
- 10 Power management
- 30 Draft ETSI EN 302 099 V2.3.0 (2026-09)
- 31 Draft ETSI EN 302 099 V2.3.0 (2026-09)
- 32 Draft ETSI EN 302 099 V2.3.0 (2026-09)
- 11 Safety, EMC, protection
- 11.1 Product Safety
- 33 Draft ETSI EN 302 099 V2.3.0 (2026-09)
- 11.2 EMC
- 11.3 Protection/resistibility
- 11.4 Earthing and bonding of access network powering solutions
- 34 Draft ETSI EN 302 099 V2.3.0 (2026-09)
- 11.5 Wiring requirements of remote power feeding to TE through
- 35 Draft ETSI EN 302 099 V2.3.0 (2026-09)
- 12 Environmental conditions
- 36 Draft ETSI EN 302 099 V2.3.0 (2026-09)
- 37 Draft ETSI EN 302 099 V2.3.0 (2026-09)
- 38 Draft ETSI EN 302 099 V2.3.0 (2026-09)
- 39 Draft ETSI EN 302 099 V2.3.0 (2026-09)
- 40 Draft ETSI EN 302 099 V2.3.0 (2026-09)
- 41 Draft ETSI EN 302 099 V2.3.0 (2026-09)
- 42 Draft ETSI EN 302 099 V2.3.0 (2026-09)
- 43 Draft ETSI EN 302 099 V2.3.0 (2026-09)
- 44 Draft ETSI EN 302 099 V2.3.0 (2026-09)
- 45 Draft ETSI EN 302 099 V2.3.0 (2026-09)
- Bibliography
- 46 Draft ETSI EN 302 099 V2.3.0 (2026-09)
- 47 Draft ETSI EN 302 099 V2.3.0 (2026-09)
1 Scope
The present document describes the principles for powering of Telecommunications Equipment (TE) in access networks (both traditional copper based and Next Generation fibre and/or hybrid based) and contains requirements for the powering systems, laying down:
- the characteristics of the input and output interfaces of the power units; the recommendations for TE power protection, also regarding network integrity and public services availability requirements;
- the management data, necessary to guarantee the required availability of the network and provided public services and to ensure the maintenance of the TE power units.
The present document takes into account the innovative characteristics of fibre-based access network equipment and considers the intrinsic limitations of local power plants and power distribution when ICT equipment is installed inside telecom centre, local exchanges, street cabinets or inside buildings: it goes from "complete integration of the power plant in the TE" to "remote power feeding from a distant power plant". The present document provides detailed information in annex A on the improved reliability of public electric power grid and on the improved reliability and availability of new fibre-based NGA network. It should be considered that, for street cabinet TE, the local power scenario is common, and, in that case, the main power supply availability characteristics are mainly based on electrical energy provider's performance.
The present document applies to the powering of all equipment of the access network (copper, fibre or radio networks) located inside or outside telecommunications centres or local exchanges, differentiating the applicable and sustainable power protection requirements. The access network is defined as the part of the telecommunications network, which comprises the network termination (passive or active) that is installed inside customer premises and the first exchange that can be also the broadband local exchange.
2 References
2.1 Normative references
References are either specific (identified by date of publication and/or edition number or version number) or non-specific. For specific references, only the cited version applies. For non-specific references, the latest version of the referenced document (including any amendments) applies.
Referenced documents which are not found to be publicly available in the expected location might be found in the ETSI docbox.
NOTE: While any hyperlinks included in this clause were valid at the time of publication, ETSI cannot guarantee their long-term validity.
The following referenced documents are necessary for the application of the present document. [1] ETSI EN 300 132-1: "Environmental Engineering (EE); Power supply interface at the input to Information and Communication Technology (ICT) equipment; Part 1: Alternating Current (AC)". [2] ETSI EN 300 132-2: "Environmental Engineering (EE); Power supply interface at the input of Information and Communication Technology (ICT) equipment; Part 2: -48 V Direct Current (DC)".
[3] IEC 62368-3: "Audio/video, information and communication technology equipment - Part 3:
Safety aspects for DC power transfer through communication cables and ports". [4] EN 60038: "CENELEC standard Voltages", (produced by CENELEC). [5] EN 60664-1: "Insulation coordination for equipment within low-voltage systems - Part 1:
Principles, requirements and tests", (produced by CENELEC).
[6] EN 50310: "Application of equipotential bonding and earthing in buildings with information technology equipment", (produced by CENELEC).
ETSI
oSIST prEN 302 099 V2.3.0:2026
7 Draft ETSI EN 302 099 V2.3.0 (2026-09)
[7] ETSI EN 300 253: "Environmental Engineering (EE); Earthing and bonding of ICT equipment powered by -48 VDC in telecom and data centres".
[8] Recommendation ITU-T K.35: "Bonding configurations and earthing at remote electronic sites". [9] Recommendation ITU-T K.45: "Resistibility of telecommunication equipment installed in the access and trunk networks to overvoltages and overcurrents".
[10] ETSI ES 203 215: "Environmental Engineering (EE); Measurement Methods and Limits for Power Consumption in Broadband Telecommunication Networks Equipment". [11] ETSI EN 300 132-3: "Environmental Engineering (EE); Power supply interface at the input of Information and Communication Technology (ICT) equipment; Part 3: Up to 400 V Direct Current (DC)".
[12] ETSI ES 202 336-1: "Environmental Engineering (EE); Monitoring and Control Interface for Infrastructure Equipment (Power, Cooling and Building Environment Systems used in Telecommunication Networks); Part 1: Generic Interface".
[13] ETSI TS 101 548-1: "Access, Terminals, Transmission and Multiplexing (ATTM); European Requirements for Reverse Powering of Remote Access Equipment; Part 1: Twisted pair networks".
[14] ETSI EN 301 605: "Environmental Engineering (EE); Earthing and bonding of 400 VDC data and telecom (ICT) equipment".
[15] Void.
[16] HD 60364 series: "Low Voltage electrical installations", produced by CENELEC. [17] ETSI ES 202 336-8: "Environmental Engineering (EE); Monitoring and Control Interface for Infrastructure Equipment (Power, Cooling and Building Environment Systems used in Telecommunication Networks); Part 8: Remote Power Feeding System control and monitoring information model".
[18] ETSI ES 203 408: "Environmental Engineering (EE); Colour and marking of DC cable and connecting devices".
2.2 Informative references
References are either specific (identified by date of publication and/or edition number or version number) or non-specific. For specific references, only the cited version applies. For non-specific references, the latest version of the referenced document (including any amendments) applies.
NOTE: While any hyperlinks included in this clause were valid at the time of publication, ETSI cannot guarantee their long-term validity.
The following referenced documents may be useful in implementing an ETSI deliverable or add to the reader's understanding, but are not required for conformance to the present document. [i.1] ETSI EN 300 019-1-1: "Environmental Engineering (EE); Environmental conditions and environmental tests for telecommunications equipment; Part 1-1: Classification of environmental conditions; Storage".
[i.2] ETSI EN 300 019-1-3: "Environmental Engineering (EE); Environmental conditions and environmental tests for telecommunications equipment; Part 1: Classification of environmental conditions; Sub-part 3: Stationary use at weatherprotected locations". [i.3] ETSI EN 300 019-1-4: "Environmental Engineering (EE); Environmental conditions and environmental tests for telecommunications equipment; Part 1: Classification of environmental conditions; Sub-part 4: Stationary use at non-weatherprotected locations". ETSI
oSIST prEN 302 099 V2.3.0:2026
8 Draft ETSI EN 302 099 V2.3.0 (2026-09)
[i.4] ETSI EN 300 019-1-8: "Environmental Engineering (EE); Environmental conditions and environmental tests for telecommunications equipment; Part 1-8: Classification of environmental conditions; Stationary use at underground locations".
[i.5] Void.
[i.6] Void.
[i.7] HD 60364-1: "Low-voltage electrical installations - Part 1: Fundamental principles, assessment of general characteristics, definitions", (produced by CENELEC).
[i.8] ETSI EN 302 999: "Safety; Remote Power Feeding Installations; Safety requirements for the erection and operation of information technology installations with remote power feeding". [i.9] ENISA: "Power Supply Dependencies in the Electronic Communications Sector Survey, analysis and recommendations for resilience against power supply failures", December 2013. TH [i.10] Council of European Energy Regulators (CEER): "7 CEER-ECRB Benchmarking report on the quality of electricity and gas supply", Ref: C22-EQS-103-03.
[i.11] ARERA Annual report.
[i.12] ETSI TS 103 553-1: "Environmental Engineering (EE); Innovative energy storage technology for stationary use; Part 1: Overview".
[i.13] Void.
[i.14] Void.
[i.15] IEC EN 62368-3: "Audio/video, information and communication technology equipment - Part 3: Safety aspects for DC power transfer through communication cables and ports". [i.16] Recommendation ITU-T L.1001: "External universal power adapter solutions for stationary information and communication technology devices".
[i.17] IEC EN 62368-1: "Audio/video, information and communication technology equipment - Part 1: Safety requirements".
[i.18] Directive (EU) 2022/2555 of the European Parliament and of the Council of 14 December 2022 on measures for a high common level of cybersecurity across the Union, amending Regulation (EU) No 910/2014 and Directive (EU) 2018/1972, and repealing Directive (EU) 2016/1148 (NIS 2 Directive).
[i.19] ETSI EN 303 215: "Environmental Engineering (EE); Measurement methods and limits for power consumption in broadband telecommunication networks equipment". [i.20] Void.
[i.21] TR 62102: "Electrical safety - Classification of interfaces for equipment to be connected to information and communications technology networks", (produced by CENELEC). [i.22] Void.
[i.23] Recommendation ITU-T L.1220 (2017-08): "Innovative energy storage technology for stationary use - Part 1: Overview of energy storage".
[i.24] Void.
[i.25] Recommendation ITU-T L.1202 (2015): "Methodologies for evaluating the performance of an up to 400 VDC power feeding system and its environmental impact". [i.26] Void.
[i.27] Broadband Forum oneM2M TR-301: "Architecture and Requirements for Fiber to the Distribution Point".
ETSI
oSIST prEN 302 099 V2.3.0:2026
9 Draft ETSI EN 302 099 V2.3.0 (2026-09)
[i.28] ETSI TS 103 553-2: "Environmental Engineering (EE); Innovative energy storage technology for stationary use; Part 2: Battery".
[i.29] ETSI TS 103 553-3: "Environmental Engineering (EE); Innovative energy storage technology for stationary use; Part 3: Supercapacitor".
[i.30] ETSI ES 202 336-11: "Environmental Engineering (EE); Monitoring and control interface for infrastructure equipment (Power, Cooling and environment systems used in telecommunication networks); Part 11: Battery system with integrated control and monitoring information model". [i.31] Recommendation ITU-T I.112: "Vocabulary of terms for ISDNs". [i.32] Recommendation ITU-T L.1221: "Innovative energy storage technology for stationary use - Part 2: Battery".
[i.33] Recommendation ITU-T L.1222: "Innovative energy storage technology for stationary use - Part 3: Supercapacitor technology".
[i.34] Recommendation ITU-T L.1200 (May 2012): "Direct current power feeding interface up to 400 V at the input to telecommunication and ICT equipment".
3 Definition of terms, symbols and abbreviations
3.1 Terms
For the purposes of the present document, the following terms apply:
access gateway: gateway that interworks a significant number of analogue lines to a packet network and is located at the operator's premises access network: part of a telecommunications network between the Network Termination/Access Gateway and the first switching unit backfeeding or reverse powering: powering architecture that can supply power to access network units from the customer through its final distribution access copper pair NOTE: Access network units may be ONU, ONT or remote DSL units. centralized powering: remote powering in which the remote feeding source is located in a telecommunications centre cluster powering: remote powering of a cluster of equipment (1 to n items of equipment), in which the remote feeding source is located outside a telecommunications centre electric energy provider: provider of electrical energy from the public grid (mains) ES1, ES2, ES3: See IEC EN 62368-1 [i.17].
interface A: -48 VDC power interface at input of Telecom/ICT equipment with voltage range and other electrical specifications defined in ETSI EN 300 132-2 [2] interface A1: up to 400 VAC rms power interface at input of Telecom/ICT equipment with voltage range and other electrical specifications defined in ETSI EN 300 132-1 [1] interface A3: up to 400 VDC power interface at input of Telecom/ICT equipment with voltage range, and other electrical specifications defined in ETSI EN 300 132-3 [11] Local Power Unit (LPU): power supply equipment whose function is to supply a telecommunication equipment situated at the same location NOTE: It is generally locally connected to the mains and provides DC or AC voltage output to feed telecommunication equipment.
ETSI
oSIST prEN 302 099 V2.3.0:2026
10 Draft ETSI EN 302 099 V2.3.0 (2026-09)
local powering: powering principle of a telecommunications equipment by a (dedicated) power unit implemented in the same location network termination: functional group on the network side of a user-network interface NOTE: Source: Recommendation ITU-T I.112 [i.31].
primary circuit: See IEC EN 62368-1 [i.17].
protective device selectivity: coordination of the operating characteristics of two or more protective devices to ensure faulty equipment is safely disconnected with no or limited impact on other parts of the system PS1, PS2, PS3: See IEC EN 62368-1 [i.17].
Remote Feeding Telecommunication (RFT) circuit: secondary circuit within the equipment, intended to supply or receive DC power via a telecommunication network at voltages equal to or exceeding the limits for TNV circuits, and on which overvoltages from telecommunication networks are possible Remote Power Receiver (RPR): unit receiving remote DC from RPU though power lines and converting it to input power interface of a TE or a radio unit NOTE: The RPR may be an external unit with an adapted power interface (e.g. -48 VDC) or an integrated function of a telecommunications equipment.
Remote Power Unit (RPU): unit, powered by the grid or by a DC power system delivering -48 VDC or up to 400 VDC, which supplies remote DC on power lines to distant Telecommunication Equipment (TE) e.g. radio unit or RPR Remote Powering (RP): power feeding of a telecommunications equipment by a remote power circuit NOTE: Such a circuit consists of a remote power unit, distribution wiring, and fed receivers. RFT-C circuit: RFT circuit which is so designed and protected that under normal operating conditions and single fault conditions the currents in the circuit do not exceed defined values RFT-V circuit: RFT circuit which is so designed and protected that under normal operating conditions and single fault conditions the voltages are limited and the accessible area of contact is limited secondary circuit: See IEC EN 62368-1 [i.17].
SELV circuit: See IEC EN 62368-1 [i.17].
TN-C: See HD 60364-1 [i.7].
TN-S: See HD 60364-1 [i.7].
TNV circuit: See EN 62368-1 [i.24].
TT: See HD 60364-1 [i.7].
3.2 Symbols
For the purposes of the present document, the following symbols apply:
I , I I , I I , I , power interface 1 2 3 4 5 6 L- Power line of negative potential polarity L+ Power line of positive potential polarity S Signal S/P Filter separating signal S and power P filter ETSI
oSIST prEN 302 099 V2.3.0:2026
11 Draft ETSI EN 302 099 V2.3.0 (2026-09)
3.3 Abbreviations
For the purposes of the present document, the following abbreviations apply:
A Autonomy of a battery bat AC Alternating Current AN Access Node ANU Access Network Unit B Battery CB Circuit Breaker CO Central Office CPE Customer's Premises Equipment DC Direct Current DC/DC Direct Current/Direct Current NOTE: DC/DC are used in general in expression such as DC/DC converter or DC/DC conversion. DSL Digital Subscriber Line DSLAM Digital Subscriber Line Access Module Energy Capacity of a battery EC bat EMC ElectroMagnetic Compatibility FTTB Fibre To The Building FTTC Fibre To The Curb FTTCab Fibre To The Cabinet FTTdp Fibre To The distribution point FTTH Fibre To The Home HD Harmonization Document HTA Home Terminal Adaptor ICT Information & Communication Technology IEC International Electrical Committee ISDN Integrated Services Digital Network IT Information Technology ITU-T International Telecommunication Union - Telecommunication standardization sector LED Light Emitting Diode LPU Local Power Unit LV Low Voltage MDF Main Distribution Frame MP Mid-Point MTBF Mean Time Between Failure MTTR Mean Time To Repair NGA Next Generation Access ONT Optical Network Termination ONU Optical Network Unit P Power NOTE: Indices can be used associated with P as P in some clauses to clarify which power P is used in indice formula.
PD Powered Device PM Powering Method POTS Plain Old Telephone Service PSE Power Sourcing Equipment PSTN Public Switched Telephone Network PSU Power Supply Unit R Rectifier RFT Remote Feeding Telecommunication RFT-C Remote Feeding Telecommunication-Current RFT-V Remote Feeding Telecommunication-Voltage RP Remote Power RPR Remote Power Receiver RPU Remote Power Unit SAIDI System Average Interruption Duration Index ETSI
oSIST prEN 302 099 V2.3.0:2026
12 Draft ETSI EN 302 099 V2.3.0 (2026-09)
SAIFI System Average Interruption Frequency Index SELV Safety Extra Low Voltage TC Telecommunication Centre TE Telecom Equipment TLC TeLecommuniCation TNV Telecommunication Network Voltage UPS Uninterruptible Power Supply VRLA Valve Regulated Lead Acid
4 Introduction
4.1 General
Innovative fibre-based and hybrid-based NGA network TE has changed the traditional powering paradigm. The present document proposes the viable measures to comply with the integrity, availability and uninterrupted telephone/VoIP provision that the European Directive defines for public networks [i.18]. It describes different configurations of powering the TE and the impacts on networks and services continuity and reliability:
- Local power supply for TE (e.g. street cabinet, active network termination, etc.).
- Remote Feeding to TE from central office through copper access pair.
- Cluster Power supply feeding power for a cluster of TE.
- Remote power feeding to TE from centre or cluster power through a power cable.
- Back feeding or Reverse Powering architecture that can supply power to Access Network Units such as ONU or ONT or remote DSL unit from the customer premises through its final distribution access copper pair. The present document provides information on powering equipment, power strategy, local powering, remote powering, power management, safety. EMC and environmental requirements.
5 Powering configurations
5.0 General
Next Generation Access (NGA) networks induce changes in the powering model and in the need of local back-up, when compared to traditional access networks centre where the back-up is obtained by battery alone or with back-up generator source (Diesel, fuel cell).
Both fixed and mobile NGA networks, usually, require local powering of access network active equipment that are installed outside Central Offices and closer to the end user's premises, Typical NGA scenarios are fiber-based FTTH, hybrid FTTC/FTTCab, FTTdp and FTTB architectures.
The new local powering scenario of fibre-based or hybrid fibre/copper NGA networks of a public Telecom networks and services provider, shall include back-up measures in order to ensure to comply with continuity, availability and reliability requirements defined by European Directive [i.18]. But for FTTB, FTTC/FTTCab, FTTdp with the increasing deployment of a great number of distributed active small cabinets, that can be installed inside buildings (FTTB) or in the street (FTTC, FTTCab), the basic power supply backup autonomy has to be optimized, due to a large number of small active cabinets to be installed at optimized costs and dimensions. Only when it is required for some service offers, a long back-up autonomy is obtained by local battery extension or alternatively by remote powering solution proposed to avoid local energy storage.
ETSI