SIST EN 1434-6:2016
(Main)Heat meters - Part 6: Installation, commissioning, operational monitoring and maintenance
Heat meters - Part 6: Installation, commissioning, operational monitoring and maintenance
This European Standard specifies installation, commissioning, operational monitoring and maintenance and applies to heat meters, that is to instruments intended for measuring the heat which, in a heat-exchange circuit, is absorbed (cooling) or given up (heating) by a liquid called the heat-conveying liquid. The heat meter indicates the quantity of heat in legal units. Electrical safety requirements are not covered by this European Standard. Pressure safety requirements are not covered by this European Standard. Surface mounted temperature sensors are not covered by this European Standard. This standard covers meters for closed systems only, where the differential pressure over the thermal load is limited.
Wärmezähler - Teil 6: Einbau, Inbetriebnahme, Überwachung und Wartung
Diese Europäische Norm legt die Inbetriebnahme, die Überwachung und die Wartung von Wärmezählern fest. Wärmezähler sind Geräte, die dazu dienen, die Energiemenge zu messen, die in einem Wärmetauscherkreislauf durch eine als Wärmeträgerflüssigkeit bezeichnete Flüssigkeit aufgenommen (Kühlen) oder abgegeben (Heizen) wird. Der Wärmezähler zeigt die Wärmemenge in gesetzlichen Einheiten an.
Elektrische Sicherheitsanforderungen werden in dieser Europäischen Norm nicht behandelt.
Den Druck betreffende Sicherheitsanforderungen werden in dieser Europäischen Norm nicht behandelt.
Oberflächenmontierte Temperaturfühler werden in dieser Europäischen Norm nicht behandelt.
Die vorliegende Norm behandelt ausschließlich Zähler für geschlossene Systeme, in denen der Differenz-druck am Wärmeüberträger begrenzt ist.
Compteurs d'énergie thermique - Partie 6 : Installation, mise en service, surveillance et maintenance
La présente Norme européenne spécifie l'installation, la mise en service, à la surveillance de fonctionnement et la maintenance et s'applique aux compteurs d'énergie thermique. Les compteurs d'énergie thermique sont des instruments destinés à mesurer l'énergie thermique qui, dans un circuit d'échange thermique, est absorbée (refroidissement) ou cédée (chauffage) par un liquide appelé « liquide caloporteur ». Le compteur d'énergie thermique fournit la quantité d'énergie thermique en unités de mesure légales.
La présente Norme européenne ne traite pas des prescriptions de sécurité électrique.
La présente Norme européenne ne traite pas des prescriptions de sécurité relative à la pression.
La présente Norme européenne ne traite pas des sondes de température montées en surface.
La présente norme couvre les compteurs pour les systèmes fermés uniquement, où la pression différentielle dans la charge thermique est limitée.
Merilniki toplote - 6. del: Vgradnja, zagon, nadzor in vzdrževanje
Ta evropski standard določa vgradnjo, zagon, nadzor in vzdrževanje ter se uporablja za toplotne števce, tj. instrumente, ki so namenjeni za merjenje toplote, ki jo v krogotoku toplotne izmenjave absorbira (hlajenje) ali oddaja (ogrevanje) tekočina, imenovana tekočina za prenos toplote. Toplotni števec podaja toploto v predpisanih enotah. Ta evropski standard ne zajema električnih varnostnih zahtev. Ta evropski standard ne zajema tlačnih varnostnih zahtev. Ta evropski standard ne zajema površinsko nameščenih senzorjev temperature. Ta standard zajema samo števce za zaprte sisteme, kjer je diferencialni tlak nad toplotno obremenitvijo omejen.
General Information
Relations
Standards Content (Sample)
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.Merilniki toplote - 6. del: Vgradnja, zagon, nadzor in vzdrževanjeWärmezähler - Teil 6: Einbau, Inbetriebnahme, Überwachung und WartungCompteurs d'énergie thermique - Partie 6 : Installation, mise en service, surveillance et maintenanceHeat meters - Part 6: Installation, commissioning, operational monitoring and maintenance17.200.10Toplota. KalorimetrijaHeat. CalorimetryICS:Ta slovenski standard je istoveten z:EN 1434-6:2015SIST EN 1434-6:2016en,fr,de01-januar-2016SIST EN 1434-6:2016SLOVENSKI
STANDARDSIST EN 1434-6:20071DGRPHãþD
SIST EN 1434-6:2016
EUROPEAN STANDARD NORME EUROPÉENNE EUROPÄISCHE NORM
EN 1434-6
November
t r s w ICS
s yä t r rä s r Supersedes EN
s v u væ xã t r r yEnglish Version
Heat meters æ Part
xã Installationá commissioningá operational monitoring and maintenance Compteurs d 5énergie thermique æ Partie
xã Installationá mise en serviceá surveillance de fonctionnement et maintenance
Wärmezähler æ Teil
xã Einbauá Inbetriebnahmeá Überwachung und Wartung This European Standard was approved by CEN on
w September
t r s wä
egulations which stipulate the conditions for giving this European Standard the status of a national standard without any alterationä Upætoædate lists and bibliographical references concerning such national standards may be obtained on application to the CENæCENELEC Management Centre or to any CEN memberä
translation under the responsibility of a CEN member into its own language and notified to the CENæCENELEC Management Centre has the same status as the official versionsä
CEN members are the national standards bodies of Austriaá Belgiumá Bulgariaá Croatiaá Cyprusá Czech Republicá Denmarká Estoniaá Finlandá Former Yugoslav Republic of Macedoniaá Franceá Germanyá Greeceá Hungaryá Icelandá Irelandá Italyá Latviaá Lithuaniaá Luxembourgá Maltaá Netherlandsá Norwayá Polandá Portugalá Romaniaá Slovakiaá Sloveniaá Spainá Swedená Switzerlandá Turkey andUnited Kingdomä
EUROPEAN COMMITTEE FOR STANDARDIZATION COMITÉ EUROPÉEN DE NORMALISATION EUROPÄISCHES KOMITEE FÜR NORMUNG
CEN-CENELEC Management Centre:
Avenue Marnix 17,
B-1000 Brussels
9
t r s w CEN All rights of exploitation in any form and by any means reserved worldwide for CEN national Membersä Refä Noä EN
s v u væ xã t r s w ESIST EN 1434-6:2016
EN 1434-6:2015 (E) 2 Contents Page European foreword . 3 1 Scope . 5 2 Normative references . 5 3 Terms and definitions . 5 4 Requirements . 6 4.1 Design requirements . 6 4.2 Installation requirements . 7 4.3 Heat meter commissioning . 8 4.3.1 General . 8 4.3.2 Certification check . 8 4.3.3 Installation check . 8 4.3.4 Heat meter security . 8 Annex A (informative)
Heat meter installation . 9 Annex B (informative)
Heat meter operational monitoring and maintenance . 19 Annex C (informative)
Suggested gauge for checking the dimensions of installed temperature sensor pockets . 22 Annex ZA (informative)
Relationship between this European Standard and the Essential Requirements of EU Directive 2004/22/EC, MID . 23 Bibliography . 24
SIST EN 1434-6:2016
EN 1434-6:2015 (E) 3 European foreword This document (EN 1434-6:2015) has been prepared by Technical Committee CEN/TC 176 “Heat meters”, the secretariat of which is held by SIS. This European Standard shall be given the status of a national standard, either by publication of an identical text or by endorsement, at the latest by May 2016, and conflicting national standards shall be withdrawn at the latest by May 2016. Attention is drawn to the possibility that some of the elements of this document may be the subject of patent rights. CEN [and/or CENELEC] shall not be held responsible for identifying any or all such patent rights. This document supersedes EN 1434-6:2007. This document has been prepared under a mandate given to CEN by the European Commission and the European Free Trade Association, and supports essential requirements of EU Directive. For relationship with EU Directive, see informative Annex ZA, which is an integral part of this document. EN 1434, Heat meters consists of the following parts: — Part 1: General requirements — Part 2: Constructional requirements — Part 3: Data exchange and interfaces1) — Part 4: Pattern approval tests — Part 5: Initial verification tests — Part 6: Installation, commissioning, operational monitoring and maintenance In comparison to EN 1434-6:2007, the following changes have been made: — special cases for combined cooling and heating meters are added; — additional functionalities for smart metering applications are added; — installation requirements added for heat meters which are located next to cables like data communication cables and mains supply cables; — installation requirement changed for 4-wire connections; — cooling meters are added. According to the CEN/CENELEC Internal Regulations, the national standards organizations of the following countries are bound to implement this European Standard: Austria, Belgium, Bulgaria,
1) EN 1434-3 is maintained by CEN/TC 294.
SIST EN 1434-6:2016
EN 1434-6:2015 (E) 4 Croatia, Cyprus, Czech Republic, Denmark, Estonia, Finland, Former Yugoslav Republic of Macedonia, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia, Lithuania, Luxembourg, Malta, Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain, Sweden, Switzerland, Turkey and the United Kingdom. SIST EN 1434-6:2016
EN 1434-6:2015 (E) 5 1 Scope This European Standard specifies commissioning, operational monitoring and maintenance and applies to heat meters. Heat meters are instruments intended for measuring the energy which in a heat-exchange circuit is absorbed (cooling) or given up (heating) by a liquid called the heat-conveying liquid. The heat meter indicates the quantity of heat in legal units. Electrical safety requirements are not covered by this European Standard. Pressure safety requirements are not covered by this European Standard. Surface mounted temperature sensors are not covered by this European Standard. This standard covers meters for closed systems only, where the differential pressure over the thermal load is limited. 2 Normative references The following documents, in whole or in part, are normatively referenced in this document and are indispensable for its application. For dated references, only the edition cited applies. For undated references, the latest edition of the referenced document (including any amendments) applies. EN 1434-1:2015, Heat meters — Part 1: General requirements 3 Terms and definitions For the purposes of this document, the terms and definitions given in EN 1434-1:2015 and the following apply. 3.1 heating system heating installation of the dwelling or premises, including the exchange circuit, the heat meter, the associated fittings and the electrical equipment Note 1 to entry: The heating system typically commences and finishes at the two connections to the heat mains. 3.2 heat mains heat suppliers distribution pipes to which the consumer's installation is connected 3.3 inlet and outlet limbs pipes connecting the heating system to the heat mains 3.4 primary circuit circuit hydraulically connected to the heat mains 3.5 secondary circuit circuit hydraulically separated from the primary circuit 3.6 competent authority persons or organizations charged with the responsibility for the heat meter and/or its installation SIST EN 1434-6:2016
EN 1434-6:2015 (E) 6 4 Requirements 4.1 Design requirements 4.1.1 When designing the heating system, the heat meter manufacturer meter specification and installation instructions shall be followed. For DN 40 and smaller, it is possible to use short direct sensors. To achieve good temperature sensitivity, direct sensors should be installed without temperature pockets. Temperature pockets should only be used when required for safety reasons. 4.1.2 To avoid unnecessary systematic error the temperature sensors shall be placed directly before and after the thermal load. If the differential pressure between the sensors is too high this systematic error might be too large. For typical systematic negative error as a function of differential pressure and temperature difference, see Table 1. Table 1 — Typical systematic negative error as a function of differential pressure and temperature difference Diff in bar Temperature difference in K
3 5 10 20 30 40 50 60 0,5 0,2 0,2 0,1 0,1 0,1 0 0 0 1 0,5 0,4 0,3 0,2 0,1 0,1 0,1 0,1 2 0,9 0,7 0,5 0,3 0,2 0,2 0,1 0,1 3 1,4 1,1 0,8 0,5 0,3 0,2 0,2 0,2 4 1,8 1,5 1,0 0,6 0,4 0,3 0,3 0,2 5 2,3 1,9 1,3 0,8 0,5 0,4 0,3 0,3 6 2,7 2,2 1,5 0,9 0,6 0,5 0,4 0,3 7 3,2 2,6 1,9 1,1 0,7 0,6 0,5 0,4 8 3,6 3,0 2,0 1,2 0,9 0,7 0,5 0,4 9 4,1 3,3 2,3 1,4 1,0 0,7 0,6 0,5 10 4,5 4,0 2,5 1,5 1,1 0,8 0,7 0,5 The values are shown as fraction of the maximum permissible error for the calculator. The values below the marked line are higher than 1/3rd of the maximum permissible error for the heat calculator. If the resulting error is higher than 1/3rd of the maximum permissible error, it is recommended to change the installation to have smaller differential pressure. NOTE In cases where flows from two different loads with different temperatures (e.g. for space heating and domestic warm water) are merged together just before the temperature sensor, the optimum position for the sensor is after the flow sensor. 4.1.3 For bifunctional meters for change-over systems between heating and cooling additional requirements are necessary to ensure the correct switching over function between the heating and cooling register. These requirements are: — the lowest operating temperature in the inlet pipe at heating conditions shall be at least 3 °C higher than any specified optional switching over temperature hc, SIST EN 1434-6:2016
EN 1434-6:2015 (E) 7 — the highest operating temperature in the inlet pipe at cooling conditions shall be at least 3 °C lower than any specified optional switching over temperature hc, — the minimum temperature difference in heating and cooling application shall be more than 3 K. NOTE The above mentioned temperature range of at least 3 °C covers the maximum accepted uncertainty in absolute temperature and the cable resistance. A temperature sensor with smaller tolerances than 2 °C for measuring absolute temperature is recommended. 4.2 Installation requirements The heat meter shall be installed in accordance with the manufacturer's instructions. Before installation, the circuit into which the flow sensor is to be installed shall be thoroughly flushed to remove debris. The strainer, where fitted, shall be cleaned. The heat meter shall be protected from the risk of damage by shock and vibration induced by the surround-ings at the place of installation. The heat meter shall not be subjected to undue stresses caused by pipes and fittings. The pipe lines of the heating system up and downstream of the heat meter shall be adequately anchored. Heat meters designed to operate from an AC mains supply shall be wired in accordance with wiring regulations applicable. The AC mains power supply shall be secured against accidental interruption. However, circuit protection shall be incorporated according to the state of the art, to safely disconnect the device when electrical problems occur. Measurement signal leads shall not be laid directly alongside other leads such as mains supply cables, low voltage supply cables and data communication cables and shall be independently supported. The separation between those groups shall not be less than 50 mm. Unless the calculator under installation was type tested according to the latest version of EN 1434-4, it is recommended to install cables and calculators with a distance of at least 60 cm to strong electromagnetic fields, e.g. frequency controlled pumps and similar high energy mains cables. Mains and external signal cables longer than 10 m shall in areas where lightning is frequent be protected with an external lightning surge protection at the cable entrance to the building. Each signal lead between temperature sensors and calculator shall be one continuous length without joints except 4-wire connection solutions which are approved. Signal circuits between parts of a heat meter shall be so installed as to deter unauthorized interference and disconnection. Precautions shall be taken to prevent damage to the heat meter by unfavourable hydraulic conditions (cavitation, surging, water hammer). When the installation of the heat and cooling meters is complete, it shall be inspected and approved by representatives of the competent authority in accordance with established procedures and the inspection shall be documented. Installation shall be done according to national legislation on legal metrology. SIST EN 1434-6:2016
EN 1434-6:2015 (E) 8 4.3 Heat meter commissioning 4.3.1 General The responsibility for the carrying out of each of the inspection phases is not necessarily restricted to one person or one authority depending on the national legislation on legal metrology, but however arranged, the following points shall be addressed and responsibilities defined. 4.3.2 Certification check Before commissioning commences it shall be ascertained firstly, that the correct heat meter has been installed by comparing the heat meter manufacturer's type and size designation against the system specification. Secondly, it shall be checked that the heat meter, if a complete instrument, bears the correct pattern approval mark and, if a combined instrument, that each of the meters sub-assemblies bear the pattern approval marks stipulated in the pattern approval document for the heat meter installed. 4.3.3 Installation check At least the following points shall be checked: — Is the flow sensor mounted in the correct position and with the correct flow direction? — Does the temperature sensor fit correctly into the pocket (pockets shorter than 140 mm shall be marked "EN 1434" or dimensions checked)? — Are the temperature sensors correctly installed? — Is the heat meter installed at a safe distance from sources of electromagnetic interference (switchgear, electric motors, fluorescent lights)? — Where called for, has the heat meter been correctly earthed? — The specified protection class (IP) has to be ensured: Is every cable diameter within the minimum and maximum diameter as specified by the manufacturer? — Are the gaskets
...