Abstract

The present document applies to monitoring and control of AC UPS power systems for telecommunication equipment. The document defines :
The monitored and controlled AC UPS power system architectures.
The minimum set of exchanged information required at the interface, described in "natural language" in text tables.
The XML files with tags and variables corresponding to the data in the tables.

Status
Published
Publication Date
18-Jan-2010
Current Stage
6060 - National Implementation/Publication (Adopted Project)
Start Date
08-Dec-2009
Due Date
12-Feb-2010
Completion Date
19-Jan-2010

Buy Documents

Standard

ETSI ES 202 336-3 V1.1.1 (2009-08) - Environmental Engineering (EE); Monitoring and Control Interface for Infrastructure Equipment (Power, Cooling and Building Environment Systems used in Telecommunication Networks); Part 3: AC UPS power system control and monitoring information model

English language (31 pages)
sale 15% off
Preview
sale 15% off
Preview
Standard

ETSI ES 202 336-3 V1.1.1 (2009-10) - Environmental Engineering (EE); Monitoring and Control Interface for Infrastructure Equipment (Power, Cooling and Building Environment Systems used in Telecommunication Networks); Part 3: AC UPS power system control and monitoring information model

English language (31 pages)
sale 15% off
Preview
sale 15% off
Preview
Standardization document

SIST ES 202 336-3 V1.1.1:2010

English language (31 pages)
Preview
Preview
e-Library read for
×1 day

SIST ES 202 336-3 V1.1.1:2010 is the Slovenian standard for the monitoring and control interface of AC UPS power systems used in telecommunication networks. It specifies which AC UPS architectures are covered, which information is exchanged at the interface, and how that information is represented in XML for supervision and control.

What does SIST ES 202 336-3 V1.1.1:2010 specify?

SIST ES 202 336-3 V1.1.1:2010 applies to monitoring and control of AC UPS power systems for telecommunication equipment. It defines the monitored and controlled AC UPS architectures, the minimum exchanged information at the interface in text tables, and the XML files with tags and variables that match those tables.

The document also states that parallel operation of UPS systems is outside its scope. Its structure is practical: clauses 1 to 5 introduce the subject, references, definitions, AC UPS system descriptions, and the summary table of alarms, events, data, configuration and control. The normative annexes then break the requirements down by AC UPS type and XML structure.

AnnexWhat it covers
Annex AMandatory and non-mandatory monitoring and supervision information for On-line AC UPS and Modular On-line AC UPS
Annex BMandatory and non-mandatory monitoring and supervision information for Off-line AC UPS
Annex CMandatory and non-mandatory monitoring and supervision information for Line-interactive AC UPS
Annex DMandatory XML structure and specific XML elements for AC UPS power systems
Annex EBibliography

What are the key requirements of SIST ES 202 336-3 V1.1.1:2010?

AC UPS architectures and operating modes

SIST ES 202 336-3 V1.1.1:2010 covers on-line, modular on-line, off-line, and line-interactive AC UPS power systems. Clause 4 describes the main functional elements - rectifier, battery, protection and distribution, inverter, static bypass switch (SBS), external manual bypass, and system monitoring and control unit (XCU). In practice, this tells an integrator what kinds of UPS topologies and sub-units the interface model is meant to represent.

The document also links each architecture to the electrical context used in telecommunication sites, including single-phase and three-phase input and output combinations. That matters because the same monitoring model has to fit different site power arrangements.

Monitoring, data, configuration, and control

Clause 5 groups the interface content into alarms, events, data, data records, configuration, and control. It gives examples such as battery discharge, battery test failure, input and output voltage and current, frequency, power factor, temperature, battery autonomy, and control actions such as battery test on demand or device control. In practice, this is the core of the supervision model: it tells implementers what a management system should be able to read, log, and command.

Annexes A, B, and C then mark each item as mandatory (M) or non-mandatory (NM) for each UPS type. That distinction matters when deciding whether a device must support a given alarm, measurement, or command to conform to the document. The annex tables also show that some items apply only to particular configurations, such as modular on-line systems or three-phase arrangements.

Role of XCU, DGU, and RMA

Annexes A to C state that the information shall be provided by the Control Unit (XCU). If there is no XCU, the Data Gathering Unit (DGU) provides the data, and the DGU stores measurements and log files when connected through a field databus. The Remote Management Application (RMA) is the upper element that detects some communication failures.

In practice, this means the standard is not just about measurement points - it also defines where the data comes from and where it is stored in the management chain. That is important for alarm reporting, logging, and remote maintenance workflows.

XML structure and extensibility

Annex D defines the mandatory XML structure for AC UPS data. It shows the AC UPS system as an XML subtree inside a site-level document and lists the main child elements under <ac_ups_system>, including <rectifier>, <inverter>, <static_bypass_switch>, <battery>, and <protection_and_distribution>. For implementation, this is the part that maps the table-based model into machine-readable exchange data.

Annex D also allows manufacturers to add further sub-equipment elements when they need more detail. That matters when a system needs more granular reporting than the minimum model.

Measurements and thresholds that drive maintenance

The tables identify several values that are important in day-to-day operation, such as output voltage, battery voltage, battery current, output frequency, and temperature. They also include configuration thresholds like low DC shutdown voltage, output overload threshold, battery charging voltage, and maximum battery charging current. In practice, these values support alarm setting, battery protection, and service decisions.

Some items are explicitly used for detection or compensation, such as battery voltage precision for floating-voltage derating detection and temperature charge compensation. That tells the reader which measurements need enough accuracy to support real control actions, not just general status display.

What terms does SIST ES 202 336-3 V1.1.1:2010 define?

  • Alarm - information that signals an abnormal state, such as a fault or out-of-limit condition, and it always carries a severity indication.
  • Event - information that signals a state change that is not an alarm, such as a battery test or a change in charge state.
  • Control Unit (CU) - an integrated unit that monitors and controls equipment through sensors and actuators.
  • Data Gathering Unit (DGU) - a unit that collects serial, digital, and analog data and can forward it to management applications.
  • Uninterruptible Power Supply (UPS) - a device or system that continues supplying electrical power when commercial power falls below acceptable limits.
  • Static Bypass Switch (SBS) - the bypass device that monitors input and output voltage and can transfer supply to the load.
  • Low Voltage Disconnect (LVD) - the disconnect function used when battery voltage reaches the low-shutdown condition.

Who uses SIST ES 202 336-3 V1.1.1:2010?

SIST ES 202 336-3 V1.1.1:2010 is used by people who supervise and maintain AC UPS power systems in telecommunication networks. That includes operators, maintenance teams, system integrators, and manufacturers of infrastructure equipment.

It is especially relevant for telecommunication centres, access network locations, shelters, cabinets, and underground sites where power continuity matters. The standard gives these users a common interface model for alarms, measurements, logs, configuration, and remote control.

Which standards are used with SIST ES 202 336-3 V1.1.1:2010?

StandardContribution
ETSI ES 202 336-1Defines the generic monitoring and control interface and the type identifiers used in the tables
ETSI EN 300 132-3Gives the power supply interface context for AC and DC sources up to 400 V
ETSI ES 202 336-2Provides the DC power system control and monitoring information model in the same series
ETSI EN 300 132-2Gives the DC input power supply interface reference used in related definitions
ETSI EN 302 099Covers powering of equipment in access network locations
ETSI TR 102 121Gives guidance for power distribution to telecommunication and datacom equipment

What does the SIST ES 202 336-3 V1.1.1:2010 document contain?

The document contains a summary table of alarms, events, data, data records, configuration, and control items, with explanations and XML element names. It also contains figures showing the main AC UPS operating configurations: on-line, off-line, modular on-line, and line-interactive.

Annexes A, B, and C provide the type-specific mandatory and non-mandatory monitoring and supervision items. Annex D provides the XML document structure and the main child elements for AC UPS system data.

The tables are meant for implementation, testing, and integration work. They tell a supplier or integrator what to monitor, what to log, and what can be controlled remotely through the XCU or DGU.

Buy Documents

Standard

ETSI ES 202 336-3 V1.1.1 (2009-08) - Environmental Engineering (EE); Monitoring and Control Interface for Infrastructure Equipment (Power, Cooling and Building Environment Systems used in Telecommunication Networks); Part 3: AC UPS power system control and monitoring information model

English language (31 pages)
sale 15% off
Preview
sale 15% off
Preview
Standard

ETSI ES 202 336-3 V1.1.1 (2009-10) - Environmental Engineering (EE); Monitoring and Control Interface for Infrastructure Equipment (Power, Cooling and Building Environment Systems used in Telecommunication Networks); Part 3: AC UPS power system control and monitoring information model

English language (31 pages)
sale 15% off
Preview
sale 15% off
Preview
Standardization document

SIST ES 202 336-3 V1.1.1:2010

English language (31 pages)
Preview
Preview
e-Library read for
×1 day

Get Certified

Connect with accredited certification bodies for this standard

ANCE

Mexican certification and testing association.

EMA Mexico Verified

IMP NDT d.o.o.

Non-destructive testing services. Radiography, ultrasonic, magnetic particle, penetrant, visual inspection.

SA Slovenia Verified

Inštitut za kovinske materiale in tehnologije

Institute of Metals and Technology. Materials testing, metallurgical analysis, NDT.

SA Slovenia Verified

Sponsored listings

Frequently Asked Questions

SIST ES 202 336-3 V1.1.1:2010 is a standard published by the Slovenian Institute for Standardization (SIST). Its full title is "Environmental Engineering (EE) - Monitoring and Control Interface for Infrastructure Equipment (Power, Cooling and Building Environment Systems used in Telecommunication Networks) - Part 3: AC UPS power system control and monitoring information model". This standard covers: The present document applies to monitoring and control of AC UPS power systems for telecommunication equipment. The document defines : The monitored and controlled AC UPS power system architectures. The minimum set of exchanged information required at the interface, described in "natural language" in text tables. The XML files with tags and variables corresponding to the data in the tables.

The present document applies to monitoring and control of AC UPS power systems for telecommunication equipment. The document defines : The monitored and controlled AC UPS power system architectures. The minimum set of exchanged information required at the interface, described in "natural language" in text tables. The XML files with tags and variables corresponding to the data in the tables.

SIST ES 202 336-3 V1.1.1:2010 is classified under the following ICS (International Classification for Standards) categories: 19.040 - Environmental testing; 33.050.01 - Telecommunication terminal equipment in general. The ICS classification helps identify the subject area and facilitates finding related standards.

SIST ES 202 336-3 V1.1.1:2010 is available in PDF format for immediate download after purchase. The document can be added to your cart and obtained through the secure checkout process. Digital delivery ensures instant access to the complete standard document.

Standards Content (Sample)

Contents

  • 1 Scope
  • 2 References
  • 2.1 Normative references
  • 2.2 Informative references
  • 6 Final draft ETSI ES 202 336-3 V1.1.1 (2009-08)
  • 3 Definitions and abbreviations
  • 3.1 Definitions
  • 7 Final draft ETSI ES 202 336-3 V1.1.1 (2009-08)
  • 8 Final draft ETSI ES 202 336-3 V1.1.1 (2009-08)
  • 3.2 Abbreviations
  • 9 Final draft ETSI ES 202 336-3 V1.1.1 (2009-08)
  • 4 AC UPS power systems
  • 10 Final draft ETSI ES 202 336-3 V1.1.1 (2009-08)
  • 11 Final draft ETSI ES 202 336-3 V1.1.1 (2009-08)
  • 12 Final draft ETSI ES 202 336-3 V1.1.1 (2009-08)
  • 13 Final draft ETSI ES 202 336-3 V1.1.1 (2009-08)
  • 5 Summary of possible alarms, events, data, data
  • 14 Final draft ETSI ES 202 336-3 V1.1.1 (2009-08)
  • 15 Final draft ETSI ES 202 336-3 V1.1.1 (2009-08)
  • 16 Final draft ETSI ES 202 336-3 V1.1.1 (2009-08)
  • 17 Final draft ETSI ES 202 336-3 V1.1.1 (2009-08)
  • 18 Final draft ETSI ES 202 336-3 V1.1.1 (2009-08)
  • 19 Final draft ETSI ES 202 336-3 V1.1.1 (2009-08)
  • 20 Final draft ETSI ES 202 336-3 V1.1.1 (2009-08)
  • 21 Final draft ETSI ES 202 336-3 V1.1.1 (2009-08)
  • 22 Final draft ETSI ES 202 336-3 V1.1.1 (2009-08)
  • 23 Final draft ETSI ES 202 336-3 V1.1.1 (2009-08)
  • 24 Final draft ETSI ES 202 336-3 V1.1.1 (2009-08)
  • 25 Final draft ETSI ES 202 336-3 V1.1.1 (2009-08)
  • 26 Final draft ETSI ES 202 336-3 V1.1.1 (2009-08)
  • 27 Final draft ETSI ES 202 336-3 V1.1.1 (2009-08)
  • 28 Final draft ETSI ES 202 336-3 V1.1.1 (2009-08)
  • 29 Final draft ETSI ES 202 336-3 V1.1.1 (2009-08)
  • 30 Final draft ETSI ES 202 336-3 V1.1.1 (2009-08)
  • Bibliography
  • 31 Final draft ETSI ES 202 336-3 V1.1.1 (2009-08)

1 Scope

The present document applies to monitoring and control of AC UPS power systems for telecommunication equipment. The document defines :

  • The monitored and controlled AC UPS power system architectures.
  • The minimum set of exchanged information required at the interface, described in "natural language" in text tables.
  • The XML files with tags and variables corresponding to the data in the tables.

2 References

References are either specific (identified by date of publication and/or edition number or version number) or non-specific.

  • For a specific reference, subsequent revisions do not apply.
  • Non-specific reference may be made only to a complete document or a part thereof and only in the following cases:
  • if it is accepted that it will be possible to use all future changes of the referenced document for the purposes of the referring document;
  • for informative references.

Referenced documents which are not found to be publicly available in the expected location might be found at http://docbox.etsi.org/Reference.

NOTE: While any hyperlinks included in this clause were valid at the time of publication ETSI cannot guarantee their long term validity.

2.1 Normative references

The following referenced documents are indispensable for the application of the present document. For dated references, only the edition cited applies. For non-specific references, the latest edition of the referenced document (including any amendments) applies.

[1] ETSI ES 202 336-1: "Environmental Engineering (EE); Monitoring and Control Interface for Infrastructure Equipment (Power, Cooling and Building Environment Systems used in Telecommunication Networks) Part 1: Generic Interface".

[2] ETSI EN 300 132-3: "Environmental Engineering (EE); Power supply interface at the input to telecommunications equipment; Part 3: Operated by rectified current source, alternating current source or direct current source up to 400 V".

2.2 Informative references

The following referenced documents are not essential to the use of the present document but they assist the user with regard to a particular subject area. For non-specific references, the latest version of the referenced document (including any amendments) applies.

[i.1] IEEE 802.1 to 802.11: "IEEE Standard for Local & Metropolican Area Network". [i.2] ISO/IEC 10164: " Information technology -- Open Systems Interconnection -- Systems Management: Objects and attributes for access control".

ETSI

6 Final draft ETSI ES 202 336-3 V1.1.1 (2009-08)

[i.3] ISO/IEC 8879: " Information processing -- Text and office systems -- Standard Generalized Markup Language (SGML)".

[i.4] ETSI EN 300 132-2: "Environmental Engineering (EE); Power supply interface at the input to telecommunications equipment; Part 2: Operated by direct current (dc)". [i.5] ETSI EN 302 099: "Environmental Engineering (EE); Powering of equipment in access network". [i.6] ETSI TR 102 121: "Environmental Engineering (EE); Guidance for power distribution to telecommunication and datacom equipment".

[i.7] ETSI ES 202 336-2: " Environmental Engineering (EE); Monitoring and Control Interface for Infrastructure Equipment (Power, Cooling and Building Environment Systems used in Telecommunication Networks); Part 2: DC power system control and monitoring information model".

3 Definitions and abbreviations

3.1 Definitions

For the purposes of the present document, the following terms and definitions apply:

NOTE: Terms referring to energy interface, equipment and distribution are described in power distribution standards EN 300 132-2 [i.4], EN 300 132-3 [2] for ac and dc interface and EN 302 099 [i.5] for access network equipment powering.

alarm: any information signalling abnormal state, i.e. different to specified normal state of hardware, software, environment condition (temperature, humidity, etc.) NOTE: The alarm signal should be understood by itself by an operator and should always have at least one severity qualification or codification (colour, level, etc.).

EXAMPLE: Rectifier failure, battery low volage, etc.

alarm loop: electrical loop which open or closed state correspond to alarm start (set) or end (clear) state alarm message: text parts of the alarm structure alarm structure: organized set of information fields in an alarm data frame (time stamp, set/clear, text, etc.) battery: complete arrangement of battery cells or blocks in one string or more in parallel battery cell: basic electrochemical element (e.g. a 2 V nominal cell for a high capacity lead acid battery) battery string: a number of serially interconnected battery blocks or cells client post: any device (laptop, PDA, console, etc.) connected to servers via the operation system networks to perform maintenance or supervision operations Control form Style Sheet (CSS): simple mechanism for adding style (e.g. fonts, colors, spacing) to Web documents. Tutorials, books, mailing lists for users, etc.

Control Unit (CU): integrated unit in an equipment to monitor and control this equipment through sensors and actuators ETSI

7 Final draft ETSI ES 202 336-3 V1.1.1 (2009-08)

Data Gathering Unit (DGU): functional unit used for several functions:

  • collect serial, digital, and analog data from several equipment;
  • option to send (output) serial or digital commands;
  • forward/receive information to/from the Local/Remote Management Application via agreed protocols;
  • mediation between interfaces and protocols.

NOTE: This function may be integrated as part of specific equipment. Dynamic Host Control Protocol (DHCP): protocol used for self configuration of TCP/IP parameters of a workstation assigning IP address and a subnetwork mask NOTE: DHCP may also configure DNS.

Dynamic Name Server (DNS): associates a single domain name to an IP address dynamic synoptic: dynamic display of geographical maps, networks, installations and equipment ethernet: LAN protocol NOTE: Equivalent to IEEE 802.1 to IEEE 802.11 [i.1].

event: any information signalling a change of state which is not an alarm: e.g. battery test, change of state of battery charge NOTE: The event signal should be understood by itself by an operator and should always have at least one severity qualification or codification (color, level, etc.). It should be transmitted in a formatted structure with text message and other fields like for alarm, e.g. an event can be coded as an alarm with severity "0". eXtensible Style sheet Language (XSL): language for expressing style sheets NOTE: It consists of two parts, a language for transforming XML documents, and an XML vocabulary for specifying formatting semantics. An XSL style sheet specifies the presentation of a class of XML documents by describing how an instance of the class is transformed into an XML document that uses the formatting vocabulary.

infrastructure equipment: power, cooling and building environment systems used in telecommunications centres and Access Networks locations EXAMPLE: Cabinets, shelters, underground locations, etc.

intranet: internal company network generally using Ethernet protocol and extended IP addresses logbook: chronological file that contains alarm and event messages may be paper or electronic Management Information Base (MIB): dynamic data base that gathers all objects and should evolve to include automatic and manual configuration tools with self coherence tests menu: list of possible input command choices that may be presented in different ways on a display NOTE: Selection is normally made by a keyboard, a pointing device, a mouse or directly by finger on a sensitive screen.

object: class description of items that accept a set of properties or functions NOTE: Generic objects can include more specific items and inherit from their properties. If correctly structured, object programming can allow the system to evolve, i.e. be more future-proof. The code should intrinsically be open and structured.

PHP: powerful tool for making dynamic and interactive Web pages pop-up: information or command screen that appears when a menu choice is selected NOTE: For example this may be a pop-up menu when the pointer is on a title button. ETSI

8 Final draft ETSI ES 202 336-3 V1.1.1 (2009-08)

REpresentational State Transfer (REST): way to build an application for distributed system as www Simple Object Access Protocol (SOAP): way to communicate between applications running on different operating systems, with different technologies and programming languages NOTE: SOAP communicates over HTTP, because HTTP is supported by all Internet browsers and servers, SOAP traffic is not blocked by firewalls and proxy servers (see W3C). Systems Management Function (SMF): object properties or classes with projection on CMIS application context communication NOTE: Set of ISO system management functions according to ISO/IEC 10164 [i.2]. Uninterruptible Power Supply (UPS): device or system that provides electrical power without interruption in the event that commercial power drops to un unacceptable voltage level warning: low severity alarm web: common name for the Internet or Intranet windows: virtual area on the display that corresponds to a specific application World Wide Web Consortium (W3C): consortium founded in October 1994 to develop common interoperable protocols and promote World Wide Web NOTE: See http://www.w3c.org.

XCU: CU enabled to communicate using XML interface as defined in the present document XHTML: stricter and cleaner version of HTML. XHTML consists of all the elements in HTML 4.01 combined with the syntax of XML. It can be read by all XML browser (see W3C) eXtensible Mark-up Language (XML): application profile or restricted form of SGML NOTE: By construction, XML documents are conforming SGML the Standard Generalized Markup Language (ISO/IEC 8879 [i.3]). documents.XML is designed to describe data and focus on what data is. XML should be discerned from the well known Hypertext Transfer Mark-up Language (HTML) which was designed to display data and to focus on how data looks.

XML Schema Definition (XSD): new more detailed XML description compared to the previous one, the DTD

3.2 Abbreviations

For the purposes of the present document, the following abbreviations apply:

AC Alternating Current CU Control Unit of an equipment CSS Control form Style Sheet DC Direct Current DGU Data Gathering Unit DHCP Dynamic Host Control Protocol DNS Dynamic Name Server HTML Hypertex Transfer Make-up Language HTTP HyperTex Transfer Protocol IP Internet Protocol LAN Local Array Network LVD Low Voltage Disconnection MIB Mnagement Information Base MN Management Network REST REpresentational State Transfer RMA Remote Management Application SBS Static Bypass Switch SMF Systems Management Function SOAP Simple Object Access Protocol ETSI

9 Final draft ETSI ES 202 336-3 V1.1.1 (2009-08)

TCP Transmission Control Protocol for IP UPS Uninterruptible Power Supply W3C World Wide Web Consortium XCU XML enabled CU XML eXtensible Mark-up Language (see W3C) XSD XML Schema Definition XSL eXtensible Style sheet Language

4 AC UPS power systems

The AC UPS power systems subset described in ES 202 336-1 [1] and TR 102 121 [i.6] provides electrical power without interruption in the event that commercial power drops to un unacceptable voltage level. The AC UPS power system provide uninterruptible 230V/400V; 50 Hz voltage according EN 300 132-3 [2], in period defined by capacity of installed back-up battery.

The AC UPS power systems addressed by the present document can be single phase input/single phase output, three phases input/single phase output and three phases input/three phases output. The following configurations of static AC UPS power system will be under the scope of the present document: On-line AC UPS, Modular On-line AC UPS, Off-line AC UPS and Line-interactive AC UPS, which are depicted in figures 1 to figure 4.

In the case of paralleled AC UPS systems there can be an aditional control unit (device) which controls parallel operation of the AC UPS systems. Parallel operation of UPS systems is outside the scope of the present document. Mandatory and non-mandatory monitoring/supervision information and functions for On-line AC UPS and Modular On-line AC UPS are given in annex A.

Mandatory and non-mandatory monitoring/supervision information and functions for Off-line AC UPS are given in annex B.

Mandatory and non-mandatory monitoring/supervision information and functions for Line-interactive AC UPS are given in annex C.

External X (Maintenance) Bypass UPS Module (with integrated SBS) SBS Contactor SBS Off SBS Input SBS Rectifier Inverter X Current using dc Link equipment Rectifier UPS X Input Output Denotes mechanical X Denotes manually interlock (no key) operated switch Denotes contact of Denotes mechanical X electromagnetic switching device interlock ( key trapped)

Figure 1: On-line AC UPS - normal operation ETSI

10 Final draft ETSI ES 202 336-3 V1.1.1 (2009-08)

External X (Maintenance) Bypass UPS Module (with integrated SBS) SBS Contactor SBS X Current using On equipment SBS UPS Input Output SBS Rectifier Inverter dc Link Rectifier Input X Denotes mechanical X Denotes manually interlock (no key) operated switch Denotes mechanical Denotes contact of X interlock ( key trapped) electromagnetic switching device

Figure 2: Off-line AC UPS - normal operation ETSI

11 Final draft ETSI ES 202 336-3 V1.1.1 (2009-08)

External (Maintenance)

Bypass UPS SBS Contactor SBS off SBS input SBS UPS Module 1 Rectifier Inverter

UPS Module 2 Rectifier Inverter

Current using equipment Rectifiers UPS input output UPS Module n Rectifier Inverter

Denotes manually x Denotes mechanical operated switch Interlock (no key) Denotes mechanical Denotes contact of

Interlock (key trapped) electromagnetic switching device

NOTE 1: Battery can be central, or each module can have own battery. NOTE 2: SBS can be central, or each module can have own SBS.

Figure 3: Modular On-line AC UPS - normal operation ETSI

12 Final draft ETSI ES 202 336-3 V1.1.1 (2009-08)

External X (Maintenance) Bypass UPS Module (with integrated SBS) SBS Contactor Voltage regulator and power conditioner SBS X Current using On equipment SBS UPS Input Output SBS Rectifier Inverter dc Link Rectifier Input X Denotes mechanical Denotes manually X interlock (no key) operated switch Denotes contact of Denotes mechanical X electromagnetic switching device interlock ( key trapped)

NOTE 1: Rectifier and inverter in operation. Inverter synchronized to mains supply but not carrying load current. NOTE 2: Bold lines indicate the load current path.

Figure 4: Line-interactive AC UPS - normal operation The main elements of AC UPS power systems are:

  • rectifier that converts AC voltage to DC voltage (i.e. 230 VAC/400VAC to DC voltage),
  • battery (one or more strings of cells) that stores energy and can power the loads when AC interrupts or rectifiers fail. There can be test and permanent battery monitoring systems to reduce the failure detection time and the MTTR,
  • protection and distribution (DC bus, breaker, etc.) to power different user loads and discriminate faults,
  • inverter that converts DC voltage to AC voltage (i.e. DC voltage to 230 VAC/400VAC),
  • Static Bypass Switch (SBS) monitors output and input voltage (mains AC voltage) of UPS, and synchronizes UPS output voltage to the input voltage, or transfers theinput voltage to the output to supply Current using equipment,
  • External (Manual) Bypass that transfers input voltage to the output to supply Current using equipment, in the case of UPS failure, UPS service, maintenance, etc.,
  • a system monitoring and control unit (XCU) to monitor voltage, current, power, temperature etc, extend alarms and provide system control functionality.

NOTE: In Modular On-line AC UPS power system, each module is consist of rectifier and inverter. Construction of the AC UPS module can be 1 phase input/1 phase output and 3 phases input/3 phases output. Modular On-line AC UPS power system can be 1 phase input/1 phase output, 3 phases input/1phases output and 3 phases input/3 phases output.

Several measurements are possible: UPS input parameters: voltages, current, frequency, power, power factor (PF) etc., UPS output parameters: voltages, current, frequency, power, power factor (PF) etc., battery parameters: voltage, current andtemperature, etc.

Several controls are possible: to adjust rectifier voltage and battery current, to start a battery test procedure, to adjust output UPS voltage and frequency, etc.

ETSI

13 Final draft ETSI ES 202 336-3 V1.1.1 (2009-08)

5 Summary of possible alarms, events, data, data

records, configuration and control with explanation for AC UPS power system In table 1 are given possible alarms, events, data, data records, configuration and control with explanation for AC UPS power system.

The "Explanation" column provided in the following data tables has been used where necessary to further explain the statements in the "Monitored information" column. The "Element type" column gives the assigned name used in XML coding and the "Monitored information" column provides details of the condition or state being monitored. The identifiers used in the Type column of the following tables are described in ES 202 336-1 [1]. NOTE: There can be others alarm, event, data, data record, configuration and control for an AC UPS power system, but they are not under the scope of the present document. Annex A standardizes alarms, events, data, data records, configuration and control for an On-line AC UPS. Table A.1 corresponds to mandatory and non-mandatory data that shall be provided for an On-line AC UPS and Modular On-line AC UPS in different configurations (1 phase input/1 phase output, 3 phases input/1 phase output and 3 phases input/3 phases output).

Annex B standardizes alarms, events, data, data records, configuration and control for a Off-line AC UPS. Table B.1 corresponds to mandatory and non-mandatory data that shall be provided for an Off-line AC UPS. Annex C standardizes alarms, events, data, data records, configuration and control for Line-interactive AC UPS. Table C.1 corresponds to mandatory and non-mandatory data that shall be provided for a Line-interactiveAC UPS. Tables A.1, B.1 and C.1 will have the necessary information for specific AC UPS systems, such as: On-line, Modular On-line, Off-line and Line-interactive.

Each table summarizes mandatory (normative) and non-mandatory (informative) monitoring/supervision information and functions of diferent AC UPS power systems.

...

Contents

  • 1 Scope
  • 2 References
  • 2.1 Normative references
  • 2.2 Informative references
  • 6 ETSI ES 202 336-3 V1.1.1 (2009-10)
  • 3 Definitions and abbreviations
  • 3.1 Definitions
  • 7 ETSI ES 202 336-3 V1.1.1 (2009-10)
  • 8 ETSI ES 202 336-3 V1.1.1 (2009-10)
  • 3.2 Abbreviations
  • 9 ETSI ES 202 336-3 V1.1.1 (2009-10)
  • 4 AC UPS power systems
  • 10 ETSI ES 202 336-3 V1.1.1 (2009-10)
  • 11 ETSI ES 202 336-3 V1.1.1 (2009-10)
  • 12 ETSI ES 202 336-3 V1.1.1 (2009-10)
  • 13 ETSI ES 202 336-3 V1.1.1 (2009-10)
  • 5 Summary of possible alarms, events, data, data
  • 14 ETSI ES 202 336-3 V1.1.1 (2009-10)
  • 15 ETSI ES 202 336-3 V1.1.1 (2009-10)
  • 16 ETSI ES 202 336-3 V1.1.1 (2009-10)
  • 17 ETSI ES 202 336-3 V1.1.1 (2009-10)
  • 18 ETSI ES 202 336-3 V1.1.1 (2009-10)
  • 19 ETSI ES 202 336-3 V1.1.1 (2009-10)
  • 20 ETSI ES 202 336-3 V1.1.1 (2009-10)
  • 21 ETSI ES 202 336-3 V1.1.1 (2009-10)
  • 22 ETSI ES 202 336-3 V1.1.1 (2009-10)
  • 23 ETSI ES 202 336-3 V1.1.1 (2009-10)
  • 24 ETSI ES 202 336-3 V1.1.1 (2009-10)
  • 25 ETSI ES 202 336-3 V1.1.1 (2009-10)
  • 26 ETSI ES 202 336-3 V1.1.1 (2009-10)
  • 27 ETSI ES 202 336-3 V1.1.1 (2009-10)
  • 28 ETSI ES 202 336-3 V1.1.1 (2009-10)
  • 29 ETSI ES 202 336-3 V1.1.1 (2009-10)
  • 30 ETSI ES 202 336-3 V1.1.1 (2009-10)
  • Bibliography
  • 31 ETSI ES 202 336-3 V1.1.1 (2009-10)

1 Scope

The present document applies to monitoring and control of AC UPS power systems for telecommunication equipment. The document defines :

  • The monitored and controlled AC UPS power system architectures.
  • The minimum set of exchanged information required at the interface, described in "natural language" in text tables.
  • The XML files with tags and variables corresponding to the data in the tables.

2 References

References are either specific (identified by date of publication and/or edition number or version number) or non-specific.

  • For a specific reference, subsequent revisions do not apply.
  • Non-specific reference may be made only to a complete document or a part thereof and only in the following cases:
  • if it is accepted that it will be possible to use all future changes of the referenced document for the purposes of the referring document;
  • for informative references.

Referenced documents which are not found to be publicly available in the expected location might be found at http://docbox.etsi.org/Reference.

NOTE: While any hyperlinks included in this clause were valid at the time of publication ETSI cannot guarantee their long term validity.

2.1 Normative references

The following referenced documents are indispensable for the application of the present document. For dated references, only the edition cited applies. For non-specific references, the latest edition of the referenced document (including any amendments) applies.

[1] ETSI ES 202 336-1: "Environmental Engineering (EE); Monitoring and Control Interface for Infrastructure Equipment (Power, Cooling and Building Environment Systems used in Telecommunication Networks) Part 1: Generic Interface".

[2] ETSI EN 300 132-3: "Environmental Engineering (EE); Power supply interface at the input to telecommunications equipment; Part 3: Operated by rectified current source, alternating current source or direct current source up to 400 V".

2.2 Informative references

The following referenced documents are not essential to the use of the present document but they assist the user with regard to a particular subject area. For non-specific references, the latest version of the referenced document (including any amendments) applies.

[i.1] IEEE 802.1 to 802.11: "IEEE Standard for Local & Metropolican Area Network". [i.2] ISO/IEC 10164: " Information technology -- Open Systems Interconnection -- Systems Management: Objects and attributes for access control".

ETSI

6 ETSI ES 202 336-3 V1.1.1 (2009-10)

[i.3] ISO/IEC 8879: " Information processing -- Text and office systems -- Standard Generalized Markup Language (SGML)".

[i.4] ETSI EN 300 132-2: "Environmental Engineering (EE); Power supply interface at the input to telecommunications equipment; Part 2: Operated by direct current (dc)". [i.5] ETSI EN 302 099: "Environmental Engineering (EE); Powering of equipment in access network". [i.6] ETSI TR 102 121: "Environmental Engineering (EE); Guidance for power distribution to telecommunication and datacom equipment".

[i.7] ETSI ES 202 336-2: " Environmental Engineering (EE); Monitoring and Control Interface for Infrastructure Equipment (Power, Cooling and Building Environment Systems used in Telecommunication Networks); Part 2: DC power system control and monitoring information model".

3 Definitions and abbreviations

3.1 Definitions

For the purposes of the present document, the following terms and definitions apply:

NOTE: Terms referring to energy interface, equipment and distribution are described in power distribution standards EN 300 132-2 [i.4], EN 300 132-3 [2] for ac and dc interface and EN 302 099 [i.5] for access network equipment powering.

alarm: any information signalling abnormal state, i.e. different to specified normal state of hardware, software, environment condition (temperature, humidity, etc.) NOTE: The alarm signal should be understood by itself by an operator and should always have at least one severity qualification or codification (colour, level, etc.).

EXAMPLE: Rectifier failure, battery low volage, etc.

alarm loop: electrical loop which open or closed state correspond to alarm start (set) or end (clear) state alarm message: text parts of the alarm structure alarm structure: organized set of information fields in an alarm data frame (time stamp, set/clear, text, etc.) battery: complete arrangement of battery cells or blocks in one string or more in parallel battery cell: basic electrochemical element (e.g. a 2 V nominal cell for a high capacity lead acid battery) battery string: a number of serially interconnected battery blocks or cells client post: any device (laptop, PDA, console, etc.) connected to servers via the operation system networks to perform maintenance or supervision operations Control form Style Sheet (CSS): simple mechanism for adding style (e.g. fonts, colors, spacing) to Web documents. Tutorials, books, mailing lists for users, etc.

Control Unit (CU): integrated unit in an equipment to monitor and control this equipment through sensors and actuators ETSI

7 ETSI ES 202 336-3 V1.1.1 (2009-10)

Data Gathering Unit (DGU): functional unit used for several functions:

  • collect serial, digital, and analog data from several equipment;
  • option to send (output) serial or digital commands;
  • forward/receive information to/from the Local/Remote Management Application via agreed protocols;
  • mediation between interfaces and protocols.

NOTE: This function may be integrated as part of specific equipment. Dynamic Host Control Protocol (DHCP): protocol used for self configuration of TCP/IP parameters of a workstation assigning IP address and a subnetwork mask NOTE: DHCP may also configure DNS.

Dynamic Name Server (DNS): associates a single domain name to an IP address dynamic synoptic: dynamic display of geographical maps, networks, installations and equipment ethernet: LAN protocol NOTE: Equivalent to IEEE 802.1 to IEEE 802.11 [i.1].

event: any information signalling a change of state which is not an alarm: e.g. battery test, change of state of battery charge NOTE: The event signal should be understood by itself by an operator and should always have at least one severity qualification or codification (color, level, etc.). It should be transmitted in a formatted structure with text message and other fields like for alarm, e.g. an event can be coded as an alarm with severity "0". eXtensible Style sheet Language (XSL): language for expressing style sheets NOTE: It consists of two parts, a language for transforming XML documents, and an XML vocabulary for specifying formatting semantics. An XSL style sheet specifies the presentation of a class of XML documents by describing how an instance of the class is transformed into an XML document that uses the formatting vocabulary.

infrastructure equipment: power, cooling and building environment systems used in telecommunications centres and Access Networks locations EXAMPLE: Cabinets, shelters, underground locations, etc.

intranet: internal company network generally using Ethernet protocol and extended IP addresses logbook: chronological file that contains alarm and event messages may be paper or electronic Management Information Base (MIB): dynamic data base that gathers all objects and should evolve to include automatic and manual configuration tools with self coherence tests menu: list of possible input command choices that may be presented in different ways on a display NOTE: Selection is normally made by a keyboard, a pointing device, a mouse or directly by finger on a sensitive screen.

object: class description of items that accept a set of properties or functions NOTE: Generic objects can include more specific items and inherit from their properties. If correctly structured, object programming can allow the system to evolve, i.e. be more future-proof. The code should intrinsically be open and structured.

PHP: powerful tool for making dynamic and interactive Web pages pop-up: information or command screen that appears when a menu choice is selected NOTE: For example this may be a pop-up menu when the pointer is on a title button. ETSI

8 ETSI ES 202 336-3 V1.1.1 (2009-10)

REpresentational State Transfer (REST): way to build an application for distributed system as www Simple Object Access Protocol (SOAP): way to communicate between applications running on different operating systems, with different technologies and programming languages NOTE: SOAP communicates over HTTP, because HTTP is supported by all Internet browsers and servers, SOAP traffic is not blocked by firewalls and proxy servers (see W3C). Systems Management Function (SMF): object properties or classes with projection on CMIS application context communication NOTE: Set of ISO system management functions according to ISO/IEC 10164 [i.2]. Uninterruptible Power Supply (UPS): device or system that provides electrical power without interruption in the event that commercial power drops to un unacceptable voltage level warning: low severity alarm web: common name for the Internet or Intranet windows: virtual area on the display that corresponds to a specific application World Wide Web Consortium (W3C): consortium founded in October 1994 to develop common interoperable protocols and promote World Wide Web NOTE: See http://www.w3c.org.

XCU: CU enabled to communicate using XML interface as defined in the present document XHTML: stricter and cleaner version of HTML. XHTML consists of all the elements in HTML 4.01 combined with the syntax of XML. It can be read by all XML browser (see W3C) eXtensible Mark-up Language (XML): application profile or restricted form of SGML NOTE: By construction, XML documents are conforming SGML the Standard Generalized Markup Language (ISO/IEC 8879 [i.3]). documents.XML is designed to describe data and focus on what data is. XML should be discerned from the well known Hypertext Transfer Mark-up Language (HTML) which was designed to display data and to focus on how data looks.

XML Schema Definition (XSD): new more detailed XML description compared to the previous one, the DTD

3.2 Abbreviations

For the purposes of the present document, the following abbreviations apply:

AC Alternating Current CU Control Unit of an equipment CSS Control form Style Sheet DC Direct Current DGU Data Gathering Unit DHCP Dynamic Host Control Protocol DNS Dynamic Name Server HTML Hypertex Transfer Make-up Language HTTP HyperTex Transfer Protocol IP Internet Protocol LAN Local Array Network LVD Low Voltage Disconnection MIB Mnagement Information Base MN Management Network REST REpresentational State Transfer RMA Remote Management Application SBS Static Bypass Switch SMF Systems Management Function SOAP Simple Object Access Protocol ETSI

9 ETSI ES 202 336-3 V1.1.1 (2009-10)

TCP Transmission Control Protocol for IP UPS Uninterruptible Power Supply W3C World Wide Web Consortium XCU XML enabled CU XML eXtensible Mark-up Language (see W3C) XSD XML Schema Definition XSL eXtensible Style sheet Language

4 AC UPS power systems

The AC UPS power systems subset described in ES 202 336-1 [1] and TR 102 121 [i.6] provides electrical power without interruption in the event that commercial power drops to un unacceptable voltage level. The AC UPS power system provide uninterruptible 230V/400V; 50 Hz voltage according EN 300 132-3 [2], in period defined by capacity of installed back-up battery.

The AC UPS power systems addressed by the present document can be single phase input/single phase output, three phases input/single phase output and three phases input/three phases output. The following configurations of static AC UPS power system will be under the scope of the present document: On-line AC UPS, Modular On-line AC UPS, Off-line AC UPS and Line-interactive AC UPS, which are depicted in figures 1 to figure 4.

In the case of paralleled AC UPS systems there can be an aditional control unit (device) which controls parallel operation of the AC UPS systems. Parallel operation of UPS systems is outside the scope of the present document. Mandatory and non-mandatory monitoring/supervision information and functions for On-line AC UPS and Modular On-line AC UPS are given in annex A.

Mandatory and non-mandatory monitoring/supervision information and functions for Off-line AC UPS are given in annex B.

Mandatory and non-mandatory monitoring/supervision information and functions for Line-interactive AC UPS are given in annex C.

External X (Maintenance) Bypass UPS Module (with integrated SBS) SBS Contactor SBS Off SBS Input SBS Rectifier Inverter X Current using dc Link equipment Rectifier UPS X Input Output Denotes mechanical X Denotes manually interlock (no key) operated switch Denotes contact of Denotes mechanical X electromagnetic switching device interlock ( key trapped)

Figure 1: On-line AC UPS - normal operation ETSI

10 ETSI ES 202 336-3 V1.1.1 (2009-10)

External X (Maintenance) Bypass UPS Module (with integrated SBS) SBS Contactor SBS X Current using On equipment SBS UPS Input Output SBS Rectifier Inverter dc Link Rectifier Input X Denotes mechanical X Denotes manually interlock (no key) operated switch Denotes mechanical Denotes contact of X interlock ( key trapped) electromagnetic switching device

Figure 2: Off-line AC UPS - normal operation ETSI

11 ETSI ES 202 336-3 V1.1.1 (2009-10)

External (Maintenance)

Bypass UPS SBS Contactor SBS off SBS input SBS UPS Module 1 Rectifier Inverter

UPS Module 2 Rectifier Inverter

Current using equipment Rectifiers UPS input output UPS Module n Rectifier Inverter

Denotes manually x Denotes mechanical operated switch Interlock (no key) Denotes mechanical Denotes contact of

Interlock (key trapped) electromagnetic switching device

NOTE 1: Battery can be central, or each module can have own battery. NOTE 2: SBS can be central, or each module can have own SBS.

Figure 3: Modular On-line AC UPS - normal operation ETSI

12 ETSI ES 202 336-3 V1.1.1 (2009-10)

External X (Maintenance) Bypass UPS Module (with integrated SBS) SBS Contactor Voltage regulator and power conditioner SBS X Current using On equipment SBS UPS Input Output SBS Rectifier Inverter dc Link Rectifier Input X Denotes mechanical Denotes manually X interlock (no key) operated switch Denotes contact of Denotes mechanical X electromagnetic switching device interlock ( key trapped)

NOTE 1: Rectifier and inverter in operation. Inverter synchronized to mains supply but not carrying load current. NOTE 2: Bold lines indicate the load current path.

Figure 4: Line-interactive AC UPS - normal operation The main elements of AC UPS power systems are:

  • rectifier that converts AC voltage to DC voltage (i.e. 230 VAC/400VAC to DC voltage);
  • battery (one or more strings of cells) that stores energy and can power the loads when AC interrupts or rectifiers fail. There can be test and permanent battery monitoring systems to reduce the failure detection time and the MTTR;
  • protection and distribution (DC bus, breaker, etc.) to power different user loads and discriminate faults;
  • inverter that converts DC voltage to AC voltage (i.e. DC voltage to 230 VAC/400VAC);
  • Static Bypass Switch (SBS) monitors output and input voltage (mains AC voltage) of UPS, and synchronizes UPS output voltage to the input voltage, or transfers theinput voltage to the output to supply Current using equipment;
  • External (Manual) Bypass that transfers input voltage to the output to supply Current using equipment, in the case of UPS failure, UPS service, maintenance, etc.;
  • a system monitoring and control unit (XCU) to monitor voltage, current, power, temperature etc, extend alarms and provide system control functionality.

NOTE: In Modular On-line AC UPS power system, each module is consist of rectifier and inverter. Construction of the AC UPS module can be 1 phase input/1 phase output and 3 phases input/3 phases output. Modular On-line AC UPS power system can be 1 phase input/1 phase output, 3 phases input/1phases output and 3 phases input/3 phases output.

Several measurements are possible: UPS input parameters: voltages, current, frequency, power, Power Factor (PF), etc., UPS output parameters: voltages, current, frequency, power, Power Factor (PF), etc., battery parameters: voltage, current andtemperature, etc.

Several controls are possible: to adjust rectifier voltage and battery current, to start a battery test procedure, to adjust output UPS voltage and frequency, etc.

ETSI

13 ETSI ES 202 336-3 V1.1.1 (2009-10)

5 Summary of possible alarms, events, data, data

records, configuration and control with explanation for AC UPS power system In table 1 are given possible alarms, events, data, data records, configuration and control with explanation for AC UPS power system.

The "Explanation" column provided in the following data tables has been used where necessary to further explain the statements in the "Monitored information" column. The "Element type" column gives the assigned name used in XML coding and the "Monitored information" column provides details of the condition or state being monitored. The identifiers used in the Type column of the following tables are described in ES 202 336-1 [1]. NOTE: There can be others alarm, event, data, data record, configuration and control for an AC UPS power system, but they are not under the scope of the present document. Annex A standardizes alarms, events, data, data records, configuration and control for an On-line AC UPS. Table A.1 corresponds to mandatory and non-mandatory data that shall be provided for an On-line AC UPS and Modular On-line AC UPS in different configurations (1 phase input/1 phase output, 3 phases input/1 phase output and 3 phases input/3 phases output).

Annex B standardizes alarms, events, data, data records, configuration and control for a Off-line AC UPS. Table B.1 corresponds to mandatory and non-mandatory data that shall be provided for an Off-line AC UPS. Annex C standardizes alarms, events, data, data records, configuration and control for Line-interactive AC UPS. Table C.1 corresponds to mandatory and non-mandatory data that shall be provided for a Line-interactiveAC UPS. Tables A.1, B.1 and C.1 will have the necessary information for specific AC UPS systems, such as: On-line, Modular On-line, Off-line and Line-interactive.

Each table summarizes mandatory (normative) and non-mandatory (informative) monitoring/supervision information and functions of diferent AC UPS power systems.

...

Contents

  • 1 Scope
  • 2 References
  • 2.1 Normative references
  • 2.2 Informative references
  • 6 ETSI ES 202 336-3 V1.1.1 (2009-10)
  • 3 Definitions and abbreviations
  • 3.1 Definitions
  • 7 ETSI ES 202 336-3 V1.1.1 (2009-10)
  • 8 ETSI ES 202 336-3 V1.1.1 (2009-10)
  • 3.2 Abbreviations
  • 9 ETSI ES 202 336-3 V1.1.1 (2009-10)
  • 4 AC UPS power systems
  • 10 ETSI ES 202 336-3 V1.1.1 (2009-10)
  • 11 ETSI ES 202 336-3 V1.1.1 (2009-10)
  • 12 ETSI ES 202 336-3 V1.1.1 (2009-10)
  • 13 ETSI ES 202 336-3 V1.1.1 (2009-10)
  • 5 Summary of possible alarms, events, data, data
  • 14 ETSI ES 202 336-3 V1.1.1 (2009-10)
  • 15 ETSI ES 202 336-3 V1.1.1 (2009-10)
  • 16 ETSI ES 202 336-3 V1.1.1 (2009-10)
  • 17 ETSI ES 202 336-3 V1.1.1 (2009-10)
  • 18 ETSI ES 202 336-3 V1.1.1 (2009-10)
  • 19 ETSI ES 202 336-3 V1.1.1 (2009-10)
  • 20 ETSI ES 202 336-3 V1.1.1 (2009-10)
  • 21 ETSI ES 202 336-3 V1.1.1 (2009-10)
  • 22 ETSI ES 202 336-3 V1.1.1 (2009-10)
  • 23 ETSI ES 202 336-3 V1.1.1 (2009-10)
  • 24 ETSI ES 202 336-3 V1.1.1 (2009-10)
  • 25 ETSI ES 202 336-3 V1.1.1 (2009-10)
  • 26 ETSI ES 202 336-3 V1.1.1 (2009-10)
  • 27 ETSI ES 202 336-3 V1.1.1 (2009-10)
  • 28 ETSI ES 202 336-3 V1.1.1 (2009-10)
  • 29 ETSI ES 202 336-3 V1.1.1 (2009-10)
  • 30 ETSI ES 202 336-3 V1.1.1 (2009-10)
  • Bibliography
  • 31 ETSI ES 202 336-3 V1.1.1 (2009-10)

1 Scope

The present document applies to monitoring and control of AC UPS power systems for telecommunication equipment. The document defines :

  • The monitored and controlled AC UPS power system architectures.
  • The minimum set of exchanged information required at the interface, described in "natural language" in text tables.
  • The XML files with tags and variables corresponding to the data in the tables.

2 References

References are either specific (identified by date of publication and/or edition number or version number) or non-specific.

  • For a specific reference, subsequent revisions do not apply.
  • Non-specific reference may be made only to a complete document or a part thereof and only in the following cases:
  • if it is accepted that it will be possible to use all future changes of the referenced document for the purposes of the referring document;
  • for informative references.

Referenced documents which are not found to be publicly available in the expected location might be found at http://docbox.etsi.org/Reference.

NOTE: While any hyperlinks included in this clause were valid at the time of publication ETSI cannot guarantee their long term validity.

2.1 Normative references

The following referenced documents are indispensable for the application of the present document. For dated references, only the edition cited applies. For non-specific references, the latest edition of the referenced document (including any amendments) applies.

[1] ETSI ES 202 336-1: "Environmental Engineering (EE); Monitoring and Control Interface for Infrastructure Equipment (Power, Cooling and Building Environment Systems used in Telecommunication Networks) Part 1: Generic Interface".

[2] ETSI EN 300 132-3: "Environmental Engineering (EE); Power supply interface at the input to telecommunications equipment; Part 3: Operated by rectified current source, alternating current source or direct current source up to 400 V".

2.2 Informative references

The following referenced documents are not essential to the use of the present document but they assist the user with regard to a particular subject area. For non-specific references, the latest version of the referenced document (including any amendments) applies.

[i.1] IEEE 802.1 to 802.11: "IEEE Standard for Local & Metropolican Area Network". [i.2] ISO/IEC 10164: " Information technology -- Open Systems Interconnection -- Systems Management: Objects and attributes for access control".

ETSI

SIST ES 202 336-3 V1.1.1:2010

6 ETSI ES 202 336-3 V1.1.1 (2009-10)

[i.3] ISO/IEC 8879: " Information processing -- Text and office systems -- Standard Generalized Markup Language (SGML)".

[i.4] ETSI EN 300 132-2: "Environmental Engineering (EE); Power supply interface at the input to telecommunications equipment; Part 2: Operated by direct current (dc)". [i.5] ETSI EN 302 099: "Environmental Engineering (EE); Powering of equipment in access network". [i.6] ETSI TR 102 121: "Environmental Engineering (EE); Guidance for power distribution to telecommunication and datacom equipment".

[i.7] ETSI ES 202 336-2: " Environmental Engineering (EE); Monitoring and Control Interface for Infrastructure Equipment (Power, Cooling and Building Environment Systems used in Telecommunication Networks); Part 2: DC power system control and monitoring information model".

3 Definitions and abbreviations

3.1 Definitions

For the purposes of the present document, the following terms and definitions apply:

NOTE: Terms referring to energy interface, equipment and distribution are described in power distribution standards EN 300 132-2 [i.4], EN 300 132-3 [2] for ac and dc interface and EN 302 099 [i.5] for access network equipment powering.

alarm: any information signalling abnormal state, i.e. different to specified normal state of hardware, software, environment condition (temperature, humidity, etc.) NOTE: The alarm signal should be understood by itself by an operator and should always have at least one severity qualification or codification (colour, level, etc.).

EXAMPLE: Rectifier failure, battery low volage, etc.

alarm loop: electrical loop which open or closed state correspond to alarm start (set) or end (clear) state alarm message: text parts of the alarm structure alarm structure: organized set of information fields in an alarm data frame (time stamp, set/clear, text, etc.) battery: complete arrangement of battery cells or blocks in one string or more in parallel battery cell: basic electrochemical element (e.g. a 2 V nominal cell for a high capacity lead acid battery) battery string: a number of serially interconnected battery blocks or cells client post: any device (laptop, PDA, console, etc.) connected to servers via the operation system networks to perform maintenance or supervision operations Control form Style Sheet (CSS): simple mechanism for adding style (e.g. fonts, colors, spacing) to Web documents. Tutorials, books, mailing lists for users, etc.

Control Unit (CU): integrated unit in an equipment to monitor and control this equipment through sensors and actuators ETSI

SIST ES 202 336-3 V1.1.1:2010

7 ETSI ES 202 336-3 V1.1.1 (2009-10)

Data Gathering Unit (DGU): functional unit used for several functions:

  • collect serial, digital, and analog data from several equipment;
  • option to send (output) serial or digital commands;
  • forward/receive information to/from the Local/Remote Management Application via agreed protocols;
  • mediation between interfaces and protocols.

NOTE: This function may be integrated as part of specific equipment. Dynamic Host Control Protocol (DHCP): protocol used for self configuration of TCP/IP parameters of a workstation assigning IP address and a subnetwork mask NOTE: DHCP may also configure DNS.

Dynamic Name Server (DNS): associates a single domain name to an IP address dynamic synoptic: dynamic display of geographical maps, networks, installations and equipment ethernet: LAN protocol NOTE: Equivalent to IEEE 802.1 to IEEE 802.11 [i.1].

event: any information signalling a change of state which is not an alarm: e.g. battery test, change of state of battery charge NOTE: The event signal should be understood by itself by an operator and should always have at least one severity qualification or codification (color, level, etc.). It should be transmitted in a formatted structure with text message and other fields like for alarm, e.g. an event can be coded as an alarm with severity "0". eXtensible Style sheet Language (XSL): language for expressing style sheets NOTE: It consists of two parts, a language for transforming XML documents, and an XML vocabulary for specifying formatting semantics. An XSL style sheet specifies the presentation of a class of XML documents by describing how an instance of the class is transformed into an XML document that uses the formatting vocabulary.

infrastructure equipment: power, cooling and building environment systems used in telecommunications centres and Access Networks locations EXAMPLE: Cabinets, shelters, underground locations, etc.

intranet: internal company network generally using Ethernet protocol and extended IP addresses logbook: chronological file that contains alarm and event messages may be paper or electronic Management Information Base (MIB): dynamic data base that gathers all objects and should evolve to include automatic and manual configuration tools with self coherence tests menu: list of possible input command choices that may be presented in different ways on a display NOTE: Selection is normally made by a keyboard, a pointing device, a mouse or directly by finger on a sensitive screen.

object: class description of items that accept a set of properties or functions NOTE: Generic objects can include more specific items and inherit from their properties. If correctly structured, object programming can allow the system to evolve, i.e. be more future-proof. The code should intrinsically be open and structured.

PHP: powerful tool for making dynamic and interactive Web pages pop-up: information or command screen that appears when a menu choice is selected NOTE: For example this may be a pop-up menu when the pointer is on a title button. ETSI

SIST ES 202 336-3 V1.1.1:2010

8 ETSI ES 202 336-3 V1.1.1 (2009-10)

REpresentational State Transfer (REST): way to build an application for distributed system as www Simple Object Access Protocol (SOAP): way to communicate between applications running on different operating systems, with different technologies and programming languages NOTE: SOAP communicates over HTTP, because HTTP is supported by all Internet browsers and servers, SOAP traffic is not blocked by firewalls and proxy servers (see W3C). Systems Management Function (SMF): object properties or classes with projection on CMIS application context communication NOTE: Set of ISO system management functions according to ISO/IEC 10164 [i.2]. Uninterruptible Power Supply (UPS): device or system that provides electrical power without interruption in the event that commercial power drops to un unacceptable voltage level warning: low severity alarm web: common name for the Internet or Intranet windows: virtual area on the display that corresponds to a specific application World Wide Web Consortium (W3C): consortium founded in October 1994 to develop common interoperable protocols and promote World Wide Web NOTE: See http://www.w3c.org.

XCU: CU enabled to communicate using XML interface as defined in the present document XHTML: stricter and cleaner version of HTML. XHTML consists of all the elements in HTML 4.01 combined with the syntax of XML. It can be read by all XML browser (see W3C) eXtensible Mark-up Language (XML): application profile or restricted form of SGML NOTE: By construction, XML documents are conforming SGML the Standard Generalized Markup Language (ISO/IEC 8879 [i.3]). documents.XML is designed to describe data and focus on what data is. XML should be discerned from the well known Hypertext Transfer Mark-up Language (HTML) which was designed to display data and to focus on how data looks.

XML Schema Definition (XSD): new more detailed XML description compared to the previous one, the DTD

3.2 Abbreviations

For the purposes of the present document, the following abbreviations apply:

AC Alternating Current CU Control Unit of an equipment CSS Control form Style Sheet DC Direct Current DGU Data Gathering Unit DHCP Dynamic Host Control Protocol DNS Dynamic Name Server HTML Hypertex Transfer Make-up Language HTTP HyperTex Transfer Protocol IP Internet Protocol LAN Local Array Network LVD Low Voltage Disconnection MIB Mnagement Information Base MN Management Network REST REpresentational State Transfer RMA Remote Management Application SBS Static Bypass Switch SMF Systems Management Function SOAP Simple Object Access Protocol ETSI

SIST ES 202 336-3 V1.1.1:2010

9 ETSI ES 202 336-3 V1.1.1 (2009-10)

TCP Transmission Control Protocol for IP UPS Uninterruptible Power Supply W3C World Wide Web Consortium XCU XML enabled CU XML eXtensible Mark-up Language (see W3C) XSD XML Schema Definition XSL eXtensible Style sheet Language

4 AC UPS power systems

The AC UPS power systems subset described in ES 202 336-1 [1] and TR 102 121 [i.6] provides electrical power without interruption in the event that commercial power drops to un unacceptable voltage level. The AC UPS power system provide uninterruptible 230V/400V; 50 Hz voltage according EN 300 132-3 [2], in period defined by capacity of installed back-up battery.

The AC UPS power systems addressed by the present document can be single phase input/single phase output, three phases input/single phase output and three phases input/three phases output. The following configurations of static AC UPS power system will be under the scope of the present document: On-line AC UPS, Modular On-line AC UPS, Off-line AC UPS and Line-interactive AC UPS, which are depicted in figures 1 to figure 4.

In the case of paralleled AC UPS systems there can be an aditional control unit (device) which controls parallel operation of the AC UPS systems. Parallel operation of UPS systems is outside the scope of the present document. Mandatory and non-mandatory monitoring/supervision information and functions for On-line AC UPS and Modular On-line AC UPS are given in annex A.

Mandatory and non-mandatory monitoring/supervision information and functions for Off-line AC UPS are given in annex B.

Mandatory and non-mandatory monitoring/supervision information and functions for Line-interactive AC UPS are given in annex C.

External X (Maintenance) Bypass UPS Module (with integrated SBS) SBS Contactor SBS Off SBS Input SBS Rectifier Inverter X Current using dc Link equipment Rectifier UPS X Input Output Denotes mechanical X Denotes manually interlock (no key) operated switch Denotes contact of Denotes mechanical X electromagnetic switching device interlock ( key trapped)

Figure 1: On-line AC UPS - normal operation ETSI

SIST ES 202 336-3 V1.1.1:2010

10 ETSI ES 202 336-3 V1.1.1 (2009-10)

External X (Maintenance) Bypass UPS Module (with integrated SBS) SBS Contactor SBS X Current using On equipment SBS UPS Input Output SBS Rectifier Inverter dc Link Rectifier Input X Denotes mechanical X Denotes manually interlock (no key) operated switch Denotes mechanical Denotes contact of X interlock ( key trapped) electromagnetic switching device

Figure 2: Off-line AC UPS - normal operation ETSI

SIST ES 202 336-3 V1.1.1:2010

11 ETSI ES 202 336-3 V1.1.1 (2009-10)

External (Maintenance)

Bypass UPS SBS Contactor SBS off SBS input SBS UPS Module 1 Rectifier Inverter

UPS Module 2 Rectifier Inverter

Current using equipment Rectifiers UPS input output UPS Module n Rectifier Inverter

Denotes manually x Denotes mechanical operated switch Interlock (no key) Denotes mechanical Denotes contact of

Interlock (key trapped) electromagnetic switching device

NOTE 1: Battery can be central, or each module can have own battery. NOTE 2: SBS can be central, or each module can have own SBS.

Figure 3: Modular On-line AC UPS - normal operation ETSI

SIST ES 202 336-3 V1.1.1:2010

12 ETSI ES 202 336-3 V1.1.1 (2009-10)

External X (Maintenance) Bypass UPS Module (with integrated SBS) SBS Contactor Voltage regulator and power conditioner SBS X Current using On equipment SBS UPS Input Output SBS Rectifier Inverter dc Link Rectifier Input X Denotes mechanical Denotes manually X interlock (no key) operated switch Denotes contact of Denotes mechanical X electromagnetic switching device interlock ( key trapped)

NOTE 1: Rectifier and inverter in operation. Inverter synchronized to mains supply but not carrying load current. NOTE 2: Bold lines indicate the load current path.

Figure 4: Line-interactive AC UPS - normal operation The main elements of AC UPS power systems are:

  • rectifier that converts AC voltage to DC voltage (i.e. 230 VAC/400VAC to DC voltage);
  • battery (one or more strings of cells) that stores energy and can power the loads when AC interrupts or rectifiers fail. There can be test and permanent battery monitoring systems to reduce the failure detection time and the MTTR;
  • protection and distribution (DC bus, breaker, etc.) to power different user loads and discriminate faults;
  • inverter that converts DC voltage to AC voltage (i.e. DC voltage to 230 VAC/400VAC);
  • Static Bypass Switch (SBS) monitors output and input voltage (mains AC voltage) of UPS, and synchronizes UPS output voltage to the input voltage, or transfers theinput voltage to the output to supply Current using equipment;
  • External (Manual) Bypass that transfers input voltage to the output to supply Current using equipment, in the case of UPS failure, UPS service, maintenance, etc.;
  • a system monitoring and control unit (XCU) to monitor voltage, current, power, temperature etc, extend alarms and provide system control functionality.

NOTE: In Modular On-line AC UPS power system, each module is consist of rectifier and inverter. Construction of the AC UPS module can be 1 phase input/1 phase output and 3 phases input/3 phases output. Modular On-line AC UPS power system can be 1 phase input/1 phase output, 3 phases input/1phases output and 3 phases input/3 phases output.

Several measurements are possible: UPS input parameters: voltages, current, frequency, power, Power Factor (PF), etc., UPS output parameters: voltages, current, frequency, power, Power Factor (PF), etc., battery parameters: voltage, current andtemperature, etc.

Several controls are possible: to adjust rectifier voltage and battery current, to start a battery test procedure, to adjust output UPS voltage and frequency, etc.

ETSI

SIST ES 202 336-3 V1.1.1:2010

13 ETSI ES 202 336-3 V1.1.1 (2009-10)

5 Summary of possible alarms, events, data, data

records, configuration and control with explanation for AC UPS power system In table 1 are given possible alarms, events, data, data records, configuration and control with explanation for AC UPS power system.

The "Explanation" column provided in the following data tables has been used where necessary to further explain the statements in the "Monitored information" column. The "Element type" column gives the assigned name used in XML coding and the "Monitored information" column provides details of the condition or state being monitored. The identifiers used in the Type column of the following tables are described in ES 202 336-1 [1]. NOTE: There can be others alarm, event, data, data record, configuration and control for an AC UPS power system, but they are not under the scope of the present document. Annex A standardizes alarms, events, data, data records, configuration and control for an On-line AC UPS. Table A.1 corresponds to mandatory and non-mandatory data that shall be provided for an On-line AC UPS and Modular On-line AC UPS in different configurations (1 phase input/1 phase output, 3 phases input/1 phase output and 3 phases input/3 phases output).

Annex B standardizes alarms, events, data, data records, configuration and control for a Off-line AC UPS. Table B.1 corresponds to mandatory and non-mandatory data that shall be provided for an Off-line AC UPS. Annex C standardizes alarms, events, data, data records, configuration and control for Line-interactive AC UPS. Table C.1 corresponds to mandatory and non-mandatory data that shall be provided for a Line-interactiveAC UPS. Tables A.1, B.1 and C.1 will have the necessary information for specific AC UPS systems, such as: On-line, Modular On-line, Off-line and Line-interactive.

Each table summarizes mandatory (normative) and non-mandatory (informative) monitoring/supervision information and functions of diferent AC UPS power systems.

Annex D standardizes XML coding structures for these data.

...