Abstract

The requirements of this part of IEC 60364 apply to basic protection and other aspects in restricted access areas with switchgear and controlgear assemblies, including requirements for operating or maintenance gangways.

Status
Published
Publication Date
17-Nov-2009
Current Stage
6060 - National Implementation/Publication (Adopted Project)
Start Date
06-Oct-2009
Due Date
11-Dec-2009
Completion Date
18-Nov-2009

Buy Documents

Standardization document

SIST HD 60364-7-729:2009

English language (18 pages)
Preview
Preview
e-Library read for
×1 day

SIST HD 60364-7-729:2009 is the Slovenian adoption of the CENELEC Harmonization Document HD 60364-7-729:2009, based on IEC 60364-7-729:2007 and modified for European harmonization. It covers low-voltage electrical installations in restricted access areas with switchgear and controlgear assemblies, with a focus on operating and maintenance gangways. The document tells designers, installers and maintainers how to arrange access, evacuation paths and clearances around live parts and equipment.

What does SIST HD 60364-7-729:2009 specify?

SIST HD 60364-7-729:2009 specifies requirements for basic protection and related safety aspects in restricted access areas that contain switchgear and controlgear assemblies. It organizes those requirements into core clauses on scope, normative references, general characteristics, protection distances, and accessibility, plus annexes for evacuation, national conditions and country-specific deviations.

The main clauses are:

  • 729.1 Scope
  • 729.2 Normative references
  • 729.30 Assessment of general characteristics
  • 729.410.3.7 Basic protection by minimum distances
  • 729.513 Accessibility
AnnexWhat it covers
Annex AAdditional requirements for closed restricted access areas, especially evacuation and door arrangement
Annex BPointer to Annex ZA and Annex ZB
Annex CAdditional information on ventilation, conditioning, construction and lighting
Annex ZASpecial national conditions
Annex ZBA-deviations

What are the key requirements of SIST HD 60364-7-729:2009?

SIST HD 60364-7-729:2009 requires restricted access areas to be clearly marked, closed to unauthorised persons and fitted with doors that allow quick escape without a key or tool. In practice, access control and evacuation must be part of the physical design, not only of operating procedures.

Where basic protection against direct contact is not reasonably practicable, the standard uses minimum distances instead. It gives separate spacing rules for gangways with live parts on one side and on both sides, so the room layout must be checked against the actual arrangement of equipment.

Clause 729.513 requires gangways and access areas to be wide enough for work, operational access, emergency access, evacuation and equipment movement. Gangways must also allow equipment doors or hinged panels to open fully enough for normal operation and maintenance.

When barriers or enclosures are used as the protective measure, the standard gives its own clearance rules for gangways, panelling height and the position of live parts. When obstacles are used, the required widths and heights change again, so the protective method chosen in design directly affects the usable room layout.

Clause 729.513 also controls access to long gangways and closed restricted access areas. Long gangways must be reachable from both ends, and closed areas with greater length need doors at both ends, which reduces the risk of people becoming trapped and improves escape routes.

Annex A adds evacuation requirements for closed restricted access areas. Doors of equipment inside the area must open in the direction of evacuation, doors giving access to gangways must open outward, and the annex sets minimum clearances for passing during evacuation.

Annex C gives practical guidance on the room itself. Closed restricted access areas should be ventilated or air-conditioned, the aim being to control dust and temperature, and gangways should have a firm, even floor and adequate lighting.

What terms does SIST HD 60364-7-729:2009 define?

  • Restricted access areas - Areas with limited entry where switchgear and controlgear assemblies are installed and where access must be controlled for safety.
  • Basic protection - Protection against direct contact with live parts; the standard allows minimum distances where other measures are not reasonably practicable.
  • Gangway - The passage used for operating or maintaining equipment, and also for movement, access and evacuation.
  • Barriers or enclosures - Physical protective measures around live parts that affect the required widths and heights of gangways.
  • Obstacles - Another protective measure used to prevent accidental contact, with its own clearance rules.
  • Closed restricted access areas - Restricted access areas enclosed by doors, for which the standard adds evacuation, door and access requirements.

Who uses SIST HD 60364-7-729:2009?

SIST HD 60364-7-729:2009 is used by electrical designers, switchgear and controlgear specifiers, installation contractors, maintenance teams and inspectors. They use it to decide room layout, gangway width, door swing, evacuation paths and safe distances from live parts.

It is also relevant to buyers and facility managers when they need to check whether a proposed electrical room or switchroom can be operated and maintained safely. For practical projects, it helps answer questions such as where to place equipment, how to route access and how to verify that the room supports maintenance and emergency exit.

What changed in SIST HD 60364-7-729:2009 from the previous edition?

SIST HD 60364-7-729:2009 is a modified adoption of IEC 60364-7-729:2007. The foreword states that the informative Annex B of IEC 60364-7-729:2007 is disregarded and replaced by normative Annex ZA and informative Annex ZB, both added by CENELEC.

Which standards are used with SIST HD 60364-7-729:2009?

  • HD 60364-1:2008 - Provides the fundamental principles, assessment of general characteristics and definitions used with this part.
  • HD 60364-4-41 - Provides the general protection against electric shock that this part supplements and modifies for restricted access areas.

What does the SIST HD 60364-7-729:2009 document contain?

SIST HD 60364-7-729:2009 contains dimensional layouts and clause text for gangways with live parts on one side or on both sides, and for gangways where barriers, enclosures or obstacles are the protective measure. It also includes evacuation figures for closed restricted access areas, showing door direction and passing space in escape situations.

Annex ZA lists special national conditions for several countries, where local practice changes the harmonized requirements. Annex ZB lists A-deviations tied to national regulations, including country-specific departures from the European requirements. Annex C gives practical guidance on ventilation, temperature control, floors and lighting for closed restricted access areas.

Relations

Effective Date
08-Apr-2026
Effective Date
09-Feb-2026
Effective Date
09-Feb-2026
Effective Date
09-Feb-2026
Effective Date
03-Feb-2026
Effective Date
03-Feb-2026
Effective Date
03-Feb-2026
Effective Date
03-Feb-2026
Effective Date
01-Oct-2017

Buy Documents

Standardization document

SIST HD 60364-7-729:2009

English language (18 pages)
Preview
Preview
e-Library read for
×1 day

Get Certified

Connect with accredited certification bodies for this standard

DIBt (Deutsches Institut für Bautechnik)

German Institute for Building Technology.

DAKKS Germany Verified

DIN CERTCO

DIN Group product certification.

DAKKS Germany Verified

Aboma Certification B.V.

Specialized in construction, metal, and transport sectors.

RVA Netherlands Verified

Sponsored listings

Frequently Asked Questions

SIST HD 60364-7-729:2009 is a standardization document published by the Slovenian Institute for Standardization (SIST). Its full title is "Low-voltage electrical installations -- Part 7-729: Requirements for special installations or locations - Operating or maintenance gangways". This standard covers: The requirements of this part of IEC 60364 apply to basic protection and other aspects in restricted access areas with switchgear and controlgear assemblies, including requirements for operating or maintenance gangways.

The requirements of this part of IEC 60364 apply to basic protection and other aspects in restricted access areas with switchgear and controlgear assemblies, including requirements for operating or maintenance gangways.

SIST HD 60364-7-729:2009 is classified under the following ICS (International Classification for Standards) categories: 91.140.50 - Electricity supply systems. The ICS classification helps identify the subject area and facilitates finding related standards.

SIST HD 60364-7-729:2009 has the following relationships with other standards: It is inter standard links to SIST EN 1647:2026, SIST EN 1647:2019+A1:2021, SIST EN 1647:2019, SIST EN 17928-1:2025, SIST HD 60364-7-753:2014, SIST HD 60364-7-721:2009, SIST HD 60364-7-708:2009, SIST EN IEC 63208:2025, SIST HD 60364-7-729:2009/A11:2017. Understanding these relationships helps ensure you are using the most current and applicable version of the standard.

SIST HD 60364-7-729:2009 is available in PDF format for immediate download after purchase. The document can be added to your cart and obtained through the secure checkout process. Digital delivery ensures instant access to the complete standard document.

Standards Content (Sample)


SLOVENSKI STANDARD
01-december-2009
1L]NRQDSHWRVWQHHOHNWULþQHLQãWDODFLMHGHO=DKWHYH]DSRVHEQHLQãWDODFLMH
DOLORNDFLMH'HORYQLDOLY]GUåHYDOQLSUHKRGL ,(&VSUHPHQMHQ
Low-voltage electrical installations -- Part 7-729: Requirements for special installations or
locations - Operating or maintenance gangways
Errichten von Niederspannungsanlagen - Anforderungen für Betriebsstätten, Räume und
Anlagen besonderer Art - Teil 7-729: Bedienungsgänge und Wartungsgänge
Installations électriques à basse tension -- Partie 7-729: Règles pour les installations et
emplacements spéciaux - Passages d'entretien ou de service
Ta slovenski standard je istoveten z: HD 60364-7-729:2009
ICS:
91.140.50 Sistemi za oskrbo z elektriko Electricity supply systems
2003-01.Slovenski inštitut za standardizacijo. Razmnoževanje celote ali delov tega standarda ni dovoljeno.

HARMONIZATION DOCUMENT
HD 60364-7-729
DOCUMENT D'HARMONISATION
August 2009
HARMONISIERUNGSDOKUMENT
ICS 91.140.50
English version
Low-voltage electrical installations -
Part 7-729: Requirements for special installations or locations -
Operating or maintenance gangways
(IEC 60364-7-729:2007, modified)

Installations électriques à basse tension - Errichten von Niederspannungsanlagen -
Partie 7-729: Règles pour les installations Teil 7-729: Anforderungen
et emplacements spéciaux - für Betriebsstätten, Räume
Passages d'entretien ou de service und Anlagen besonderer Art -
(CEI 60364-7-729:2007, modifiée) Bedienungsgänge und Wartungsgänge
(IEC 60364-7-729:2007, modifiziert)

This Harmonization Document was approved by CENELEC on 2009-04-22. CENELEC members are bound to
comply with the CEN/CENELEC Internal Regulations which stipulate the conditions for implementation of this
Harmonization Document at national level.

Up-to-date lists and bibliographical references concerning such national implementations may be obtained on
application to the Central Secretariat or to any CENELEC member.

This Harmonization Document exists in three official versions (English, French, German).

CENELEC members are the national electrotechnical committees of Austria, Belgium, Bulgaria, Cyprus, the
Czech Republic, Denmark, Estonia, Finland, France, Germany, Greece, Hungary, Iceland, Ireland, Italy, Latvia,
Lithuania, Luxembourg, Malta, the Netherlands, Norway, Poland, Portugal, Romania, Slovakia, Slovenia, Spain,
Sweden, Switzerland and the United Kingdom.

CENELEC
European Committee for Electrotechnical Standardization
Comité Européen de Normalisation Electrotechnique
Europäisches Komitee für Elektrotechnische Normung

Central Secretariat: Avenue Marnix 17, B - 1000 Brussels

© 2009 CENELEC - All rights of exploitation in any form and by any means reserved worldwide for CENELEC members.
Ref. No. HD 60364-7-729:2009 E

Foreword
The text of document 64/1595/FDIS, future edition 1 of IEC 60364-7-729, prepared by IEC TC 64,
Electrical installations and protection against electric shock, was submitted to the IEC-CENELEC parallel
vote.
A draft amendment, prepared by the former SC 64A, Protection against electric shock, of Technical
Committee CENELEC TC 64, Electrical installations and protection against electric shock, was submitted
to the formal vote.
The combined texts were approved by CENELEC as HD 60364-7-729 on 2009-04-22.
The following dates were fixed:
- latest date by which the existence of the HD (doa) 2009-11-01
has to be announced at national level
- latest date by which the HD has to be implemented (dop) 2010-05-01
at national level by publication of a harmonized
national standard or by endorsement
- latest date by which the national standards conflicting (dow) 2012-05-01
with the HD have to be withdrawn
In this document, the common modifications to the International Standard are indicated by a vertical line
in the left margin of the text.
For this Harmonization Document, the informative Annex B of IEC 60364-7-729:2007 shall be
disregarded and has been replaced by the normative Annex ZA, Special national conditions, and the
informative Annex ZB, A-deviations.
Annexes ZA and ZB have been added by CENELEC.

– 3 – HD 60364-7-729:2009
729 Introduction
The requirements of this part of HD 60364 supplement, modify or replace certain of the general
requirements of the other parts of HD 60364.
The clause numbering of Part 7-729 follows the pattern and corresponding references of HD 60364. The
numbers following the particular number of Part 7-729 are those of the corresponding parts or clauses of
HD 60364.
The absence of reference to a part, clause or subclause means that the corresponding general
requirements are applicable.
729.1 Scope
The requirements of this part of HD 60364 apply to basic protection and other aspects in restricted
access areas with switchgear and controlgear assemblies, including requirements for operating or
maintenance gangways.
729.2 Normative references
The following normative documents contain provisions which through reference in this text, constitute
provisions of this part of HD 60364. For dated references, subsequent amendments to, or revisions of any
of these publications do not apply.
HD 60364-1:2008, Low-voltage electrical installations – Part 1: Fundamental principles, assessment of
general characteristics, definitions (IEC 60364-1:2005, mod.)
HD 60364-4-41, Low-voltage electrical installations – Part 4-41: Protection for safety – Protection against
electric shock (IEC 60364-4-41, mod.)
729.30 Assessment of general characteristics
Add the following requirements:
For restricted access areas the following apply:
– restricted access areas shall be clearly and visibly marked by appropriate signs;
– unauthorised persons shall not have access to restricted access areas;
– door(s) provided for closed restricted access areas shall allow easy evacuation to the outside by
opening without the use of a key, tool or any other device which not part of the opening mechanism.
729.410.3.7
Replace the paragraph with the following requirements:
In restricted access areas where it is not reasonably practicable to provide protective measures for basic
protection (protection against direct contact) in accordance with HD 60364-4-41, minimum distances are
required.
NOTE 1  See HD 60364-1, Clause 30 for assessment of general characteristics when deciding to use this method of protection.
NOTE 2  In cases of protective device with high rating, such as large circuit-breakers, greater distances may be necessary for the
withdrawing of the device.
729.410.3.7.1
Where the gangway has unprotected live parts arranged on one side only (see Figure 729.1), the
minimum distances shall be:
a) width of gangway between the wall and live parts  900 mm;
b) free passage in front of controls (handles, etc.)  700 mm;
c) height of live parts above the floor 2 500 mm.

Live parts
2 500 mm
900 mm
700 mm
NOTE  The 2 500 mm height above the floor given as the minimum distance to live parts applies only in the gangway where it is
possible for persons to stand or walk.
Figure 729.1 – Gangways in installations with live parts on one side
729.410.3.7.2
Where the gangway has live parts on both sides (see Figure 729.2), the minimum distances shall be:
a) width of gangway between live parts 1 300 mm;
b) minimum distance between the front of the handle
and the live parts on the opposite side of the gangway 1 100 mm;
c) minimum free passage in front of controls (handles,
isolation position of circuit breakers, etc.)  900 mm;
d) height of live parts above the floor 2 500 mm.

– 5 – HD 60364-7-729:2009
Live parts
Circuit breaker
in the position
“isolation”
2500 mm
1300 mm
900 mm
1100 mm
1100 mm
NOTE  The 2 500 mm height above the floor given as the minimum distance to live parts applies only in the gangway where it is
possible for persons to stand or walk.
Figure 729.2 – Gangways in installations with live parts on both sides
729.513 Accessibility
Add the following paragraphs:
729.513.2 Requirements for operating and maintenance gangways
The width of gangways and access areas shall be adequate for work, operational access, emergency
access, emergency evacuation and for the movement of equipment.

Gangways shall permit equipment doors or hinged panels to be opened to at least 90° (see also Annex A,
Clause A.1).
729.513.2.1 Restricted access areas where the protective measure of barriers and enclosures
applies
Where the protective measure is provided by barriers or enclosures in accordance with HD 60364-4-41,
the following minimum distances apply (see Figure 729.3):
a) width of gangways with barriers or enclosures between
switch handles and circuit-breakers in position “isolation”
or switch handles and the wall  600 mm;
b) width of gangways between barriers or enclosures
and other barriers or enclosures, or barriers or enclosures
and the wall  700 mm;
c) height of panelling above the floor 2 000 mm;
d) height of live parts above the floor 2 500 mm.

NOTE 1  Where additional workspace is needed e.g. for special switchgear and controlgear assemblies, larger dimensions may be
required.
Live parts
Panelling Barriers or
enclosures
2500 mm
Circuit breaker
in the position
“isolation”
2000 mm
600 mm
600 mm
700 mm
700 mm
700 mm
Figure 729.3 – Gangways in installations where the protective measure of barriers
or enclosures applies
NOTE 2  The above dimensions apply after all parts of the panelling have been mounted and closed and to circuit breakers in the
position ”isolation”.
729.513.2.2  Restricted access areas where the protective measure of obstacles applies
Where the protective measure of obstacles applies in accordance with HD 60364-4-41, the following
minimum distances apply (see Figure 729.4):
a) width of gangway between obstacles and switch handles,
or obstacles and the wall, or switch handles and the wall  700 mm;
b) height of panelling above floor 2 000 mm;
c) height of live parts above the floor 2 500 mm.

– 7 – HD 60364-7-729:2009
Live parts
Panelling
Obstacles
Circuit breaker
in the position
“isolation”
2000 mm
2500 mm
700 mm
700 mm 700 mm
700 mm
Figure 729.4 – Gangways in installations where the protective measure of obstacles applies

NOTE  The above dimensions apply after all parts of the panelling have been mounted and closed and to circuit breakers in the
position ”isolation”.
729.513.2.3 Access of gangways
Gangways longer than 10 m shall be accessible from both ends.
NOTE 1  This may be accomplished by placement of the equipment a minimum of 700 mm from the end walls (see Figure 729.5) or
by providing an access door, if needed, on the opposite end wall.
Closed restricted access areas with a length exceeding 20 m shall be accessible by doors from both
ends.
NOTE 2  For closed restricted access areas with a length exceeding 6 m, accessibility from both ends is recommended.

Figure 729.5 – Examples of positioning of doors in long closed restricted access areas

– 9 – HD 60364-7-729:2009
Annex A
(normative)
Additional requirements
...